ML20094M999

From kanterella
Jump to navigation Jump to search
Rev 2 to Environ Qualification Master Equipment List
ML20094M999
Person / Time
Site: Vermont Yankee Entergy icon.png
Issue date: 08/10/1984
From:
VERMONT YANKEE NUCLEAR POWER CORP.
To:
Shared Package
ML20094M988 List:
References
NUDOCS 8408160056
Download: ML20094M999 (26)


Text

-

p.. -

.g~ 0 En21 curo (1)

VERMONT YANKEE NUCLEAR POWER CORPORATION ENVIRONMERITAL QUALIFICATIOM MASTER EQUIPMENT LIST Revision - 2 August 10, 1984 r

i 8408160056 840810 PDR ADOCK 05000271 p PDR

f I VERM0NT YANKEE NUCLEAR P0WER STATION PRODUCED 84/08/10. l ENVIR0 MENTAL QUALIFICATION OF ELECTRICAL EQUIPMENT

, MASTER EQUIPMENT LIST PACE 1

!  !  ! QUALIFICATION ! DEFICIENCY /  !

IDIUSER  ! MAIAJFACTURER ! MODEL Nul9ER ! STATUS  ! RESOLUTION !CONENTS CONTAINMENT ATMOSPHERIC DILUTION SYSTEM FS0-109-75A-1  ! TARGET ROCK  ! 82-0001  ! QUALIFIED  !  !

FS0-109-75A-2 ! TARGET ROCK  ! 82-U002  ! QUALIFIED  !  !

FS0-109-75A-3 ! TARGET ROCK  ! 75E002  ! QUALIFIED  !  !

l FS0-109-75A-4  ! TARGET ROCK  ! 75E002 -! QUALIFIED  !  !

i FS0-109-758-1  ! TARGET ROCK  ! 82-0001  ! QUALIFIED  !  !

FS0-109-728-2 ! TARGET ROCK  ! 82-U001  ! QUALIFIED  !  !

, FS0-109-75C-1  ! TARGET ROCK !82-U001  ! QUALIFIED  !  !

FS0-109-75C-2 ! TARGET ROCK  ! 82-0001  ! QUALIFIED-  !  !

FS0-109-75D-1  ! TARGET ROCK  ! 82-U001  ! QUALIFIED  !  !

FS0-109-75D-2 ! TARGET ROCK  ! 82-U001 .! QUALIFIED  !  !

FS0-109-76A  ! TARGET ROCK  ! 82-U001  ! QUALIFIED  !  ! CATEGORY D FS0-109-768  ! TARCET ROCK !82-U001  ! QUALIFIED  !  !

NG-11A  ! TARGET ROCK !75E001  ! QUALIFIED  !  ! CATEGORY D NO-11B  ! TARGET ROCK  ! 75E001  ! QUALIFIED  !  ! CATEGORY D

'NG-12A  ! TARGET ROCK  ! 75E001  ! QUALIFIED  !  ! CATEGORY D IJG-129  ! TARGET ROCK  ! 75E001  ! QUALIFIED  !  ! CATEGORY D NO-13A  ! TARGET ROCK !75E001  ! QUALIFIED  !  ! CATEGORY D

.NG-13B  ! TARGET ROCK  ! 75E001  ! QUALIFIED  !  ! CATEGORY D SAH-VG-5A  ! TELEDYE  ! 225C:%-2  ! QUALIFIED  !  !

SAH-YG-58  ! TELEDYNE  ! 225CMA-2  ! OVALIFIED  !  !

! VG-9A  ! TARGET ROCK  ! 75E002  ! QUALIFIED  !  ! CATEGORY D

, VG-9B  ! TMGET ROCK  ! 75E002  ! QUALIFIED  !  ! CATEGORY D VG-22A  ! LIMITORQtE  ! SP9-000  ! QUALIFIED  !  ! CATEGORY D VG-22B  ! LIMITORQlE  ! SMB-000  ! QUALIFIED  !  ! CATE0 CRY D VO-23  ! TARGET ROCK  ! 75E002  ! QUALIFIED  !  !

V0-24  ! TARGET ROCK  ! 75E002  ! QUALIFIED  !  !

VG-25  ! TARGET ROCK  ! 75E002  ! QUALIFIED  !  !

VG-26  ! TARGET ROCK  ! 75E002  ! QUALIFIED  !  ! CATEGORY D V0-33  ! TARGET ROCK  ! 75E002  ! QUALIFIED  !  !

VO-34  ! TARGET ROCK  ! 75E002  ! QUALIFIED  !  ! i EMERGENCY POWER SYSTEM A-ECCS BATT !C+D  ! KC-9  ! QUALIFIED  !  !

A-ECCS DP  ! ERCURY  !  ! QUALIFIED  !  !

B-ECCS BATT !C+D  ! KC-9  ! QUALIFIED  !  !

B-ECCS DP  ! ERCURY  !  ! QUALIFIED  !  !

DC-!A  ! ESTINGHOUSE  ! TYPE W  ! QUALIFIED  !  ! CATEGORY D DC-!B  ! WESTINGHOUSE ! TYPE W  ! QUALIFIED  !  ! CATEGORY D DC-2A  ! WESTINCH0USE ! TYPE W  ! QUALIFIED  !  !

DC-29  ! ESTIN0NOUSE  ! TYFT W  ! QUALIFIED  !  ! CATEGORY D

r-

~*!

VERM0NT YANKEE NUCLEAR P0WER STATION PRODUCED 8 84/08/10.

ENVIROMENTAL QUALIFICATION OF ELECTRICAL EQUIPENT MASTER EQUIPMENT LIST PAGE 2

'!  !  ! QUALIFICATION ! DEFICIENCY /  !

1D INSER  ! MANUFACTlRER ! MODEL ! USER ! STATUS  ! RESOLUTION !CONIENTS EMERGENCY P0WER SYSTEM (CONTINUED)

, MCC-8B  ! ESTINGHOUSE ! TYPE W  ! QUALIFIED  !  !

MCC-GE  ! ESTINGHOUSE ! TYPE W  ! QUALIFIED  !  !

MCC-98  ! ESTINGHOUSE ! TYPE W  ! QUALIFIED  !  !

MCC-90  ! ESTINGHOUSE ! TYPE W  ! QUALIFIED  !  !

MCC-894  ! ITE  ! 5600  ! QUALIFIED  !  !

NCC-89B  ! ITE  ! 5600  ! QUALIFIED  !  !

PP-89  ! ESTINGHOUSE !  ! QUALIFIED  !  ! PART OF MCC-9D LPS-14  ! EXIDE  !  ! QUALIFIED  !  ! CATEGORY D LFS-1B  ! EX1DE  !  ! QUALIFIED  !  ! CATEGORY D VAC-B  ! GEN ELECTRIC ! TYPE NAB  ! QUALIFIED  !  !

l HEATING & VENTILATION SYSTEM l

RRU-5  ! RELIANCE ELEC !  ! QUALIFIED  !  !

RRU-6  ! RELIANCE ELEC !  ! QUALIFIED  !  !

RRU-7  ! RELIANCE ELEC !  ! QUALIFIED  !  !

l- RRU-8  ! REllANCE ELEC !  ! QUALIFIED  !  !

j STANDBY GAS TREATMENT SYSTEM ElH-2 !C20MALOX9KW ! 106-114426-00l! QUALIFIED  !  !

ElH-4  ! C20MALOX 9KW ! 106-114426-00l! QUALIFIED  !  !

FS-1-125-1A  ! PEECO  ! IFS  ! QUALIFIED  !  !

FS-1-125-1B  ! PEECO  ! !PS  ! QUALIFIED  !  !

LS-SB-1A  ! MICROSWITCH  ! OPD-AR-6809  ! QUALIFIED  !  !

l LS-SB-1B !MICR0$ WITCH  ! OPD-AR-6809 ! QUALIFIED  !  !

LS-SB-2A  ! MICROSWITCH  ! OPD-AR-6809  ! QUALIFIED  !  !

i LS-SB-2B !MICR0 SWITCH  ! OPD-AR-6809 ! QUALIFIED  !  !

l LS-SB-36, '

! MICROSWITCH  ! OPD-AR-6809  ! QUALIFIED  !

LS-SB-38  ! MICROSWITCH  ! OPD-AR-6809  ! QUALIFIED  !  !

l LS-SB-4A  ! MICROSWITCH  ! OPD-AR-6809  ! QUALIFIED  !  !

LS-SB-4B  ! MICR03 WITCH !OPD-AR-6809 ! QUALIFIED  !  !

LS-SB-5  ! MICROSWITCH !OPD-AR-6809  ! QUALIFIED  !  !

REF-2A  ! RELIANCE ELEC ! 215T. TYPE B ' QUALIFIED  !  !

l REF-29  ! RTLIANCE ELEC ! 215T. TYPE B ' QUALIFIED  !  !

SB-1A  ! ASCO  ! 206-300-7F  ! QUALIFIED  !  !

SB-1B  ! ASCO  ! 206-300-7F  ! QUALIFIED  !  !

SB-2A  ! ASCO  ! 206-380-7F  ! QUALIFIED  !  !

58-2B  ! ASCO  ! 206-300-7F  ! QUALIFIED  !  ! .

D3A  ! ASCO !206-380-7F  ! QUALIFIED  !  !

18-38  ! ASCO  ! 206-380-7F  ! QUALIFIED  !  !

t

'fL

$ VERM0NT YANKEE NUCLEAR P0WER STATION PRODUCED 8 84/08/10.

t

. ENVIR010 ENTAL QUALIFICATION OF ELEC1RICAL EQUIPENT I MASTER EQUIPMENT LIST p PAGE 3

!  !  ! QUALIFICATION  ! DEFICIENCY /  !

ID IAJleER  ! MANUFACTURER ! MODEL NUMBER ! STATUS  ! RESOLifTION !C0ffENTS

~ STANDBY-0AS TREATMENT SYSTEM (CONTINUED) l SB-4A  ! ASCO  ! 206-300-7F  ! QUALIFIED  !  !

! SB-48  ! ASCO  ! 206-300-7F  ! QUALIFIED  !  !

l S8-5  ! ASCO  ! 206-380-7F  ! QUALIFIED  !  !

.TSH-1-125-15A ! C W)MALOX  ! 5-17108  ! QUALIFIED  ! !PART OF ELECTRIC EATER (EUH-2)

TSH-t-125-15B  ! CISOMALOX  ! 5-17100  ? QUALIFIED  ! !PART OF ELECTRIC EATER (EUH-4)

NUCLEAR BOILER SYSTEM A0V-2-80A  ! ASCO  ! IF8323A36V  ! QUALIFIED  !  !

A0V-2-80B  ! ASCO  ! F8323A36V  ! QUALIFIED  !  !

A0V-2-80C  ! ASCO !If8323A36V  ! QUALIFIED  !  !

l A0V-2-80D  ! ASCO  ! F8323A36V  ! QUALIFIED  !  !

A0V-2-86A  ! ASCO  ! If8323A36V  ! QUALIFIED  !  !

A0V-2-MB  ! ASCO  ! W 8323A36V  ! QUALIFIED  !  !

A0V-2-86C  ! ASCO !IF8323A36V  ! QUALIFIED  !  !

A0V-2-860  ! ASCO  ! W 8323A36V  ! QUALIFIED  !  !

LS-A0V-2-80A  ! NAMCO  ! EA-740  ! QUALIFIED  ! ,!

LS-A0V-2-80B  ! NMCO  ! EA-740  ! QUALIFIED  !  !

! LS-A0V-2-80C  ! NAMCO  ! EA-740  ! QUALIFIED  !  ! r LS-A0V-2-80D  ! NAMCO  ! EA-740  ! QUALIFIED  !  !

LS-A0V-2-86A  ! NAMCO  ! EA-740  ! QUALIFIED  !  !

i LS-A0V-2-868  ! NAMCO  ! EA-740  ! QUALIFIED  !  !

LS-A0V-2-86C  ! NAMCO  ! EA-740  ! GUALIFIED  !  !

LS-A0V-2-86D  ! NAMCO  ! EA-740  ! QUALIFIED  !  !

FCV-2-39  ! ASCO  ! 206-823-3  ! QUALIFIED  !  !

FCV-2-40  ! ASCO  ! 80173  ! QUALIFIED  !  ! CATEGORY D FT-2-110A !GE/MAC  ! 555111BDAAA3 ! QUALIFIED  !  ! CATEGORY D FT-2-Il0B  ! OE/MAC  ! 555ttlBDAAA3 ! QUALIFIED  !  ! CATEGORY D FT-2-110C  ! GE/MAC  ! 5551tlBDAAA3 ! QUALIFIED  !  ! CATEGORY D FT-2-1100  ! GE/MAC  ! 555111BDAA43 ! QUALIFIED  !  ! CATEGORY D MOV-2-53A !LIMITORQUE !SMB-2  ! QUALIFIED  !  !

MOV-2-538 !LIMITORQUE  ! SMB-2  ! QUALIFIED  !  !

MOV-2-54A  ! LIMITORQUE !SMB-000  ! QUALIFIED  !  !

MOV-2-54B  ! LIMITORQUE  ! SMB-000  ! OVALIFIED  !  !

MOV-2-74 !LIMITORQUE !SMB-000  ! QUALIFIED  !  !

l MOV-2-77 !LIMITORQUE  !99-000  ! QUALIFIED  !  ! CATEGORY D PS-2-71-1A  ! SOR  ! 6TA-B3-NI-  ! QUAllFIED  !  !

l  !  ! CIA-JJTT16  !  !  !

l PS-2-71-1B !SOR  !6TA-B3-NI-  ! QUALIFIED  !  !

!  ! CIA-JJTTI6  !  !  !

y .- -

VERM0NT YANKEE NUCLEAR P0WER STATION PRODUCED 84/08/10. 1 EWIROWNTAL QUALIFICATION 0F ELECTRICAL EQUIP!ENT MASTER EQUIPMENT LIST PAGE 4

!  !  ! QUALIFICATION ! DEFICIENCY /  !

IDMlf8ER  ! MANUFACTURER ! MODEL NUf8ER ! STATUS  ! RESOLtfTION !C0 K MTS NUCLEAR B0iLER SYSTEM (CONTilAJED)

PS-2-71-lC  ! SOR  ! 6TA-93-NX-  ! QUALIFIED  !  !

!  ! CIA-WTTX6  !  !  !

.PS-2-71-lD  ! SOR  ! 6TA-B3-NX-  ! QUALIFIED  !  !

!  ! CIA-WTTX6  !  !  !

PS-2-71-2A !SOR  ! 6TA-B3-NX-  ! QUALIFIED  !  !

!  ! CIA- WTTX6  !  !  !

PS-2-71-2B  ! SOR  ! 6TA-83-NX-  ! QUAllFIED  !  !

!  ! CIA-WTTX6  !  !  !

PS-2-71-2C !SOR  ! 6TA-B3-NX-  ! QUALIFIED  !  !

!  ! CIA-WTTX6  !  !  !

PS-2-71-2D  ! SOR  !6TA-B3-NX-  ! QUALIFIED  !  !

!  ! CIA-WTTX6  !  !  !

PS-2-71-3A  ! SOR  ! 6TA-B3-NX-  ! QUALIFIED  !  !

!  ! CIA-WTTX6  !  !  !

PS-2-71-3B  ! SOR  ! 6TA-B3-NX-  ! QUALIFIED  !  !

! -! CIA-JJTTX6  !  !  !

PS-2-71-3C  ! SOR  ! 6TA-B3-NX-  ! QUALIFIED  !  !

!  ! CIA- WTTX6  !  !  !

PS-2-71-3D  ! S0R  ! 6TA-B3-NX-  ! QUALIFIED  !  !

!  ! CIA-JJTTX6  !  !  !

PS-2-128A  ! SOR  ! M -KK3-CIA-X2 ! QUALIFIED  !  ! CATEGORY P PS-2-128B  ! SOR  ! M -KK3-CIA-X2 ! QUALIFIED  !  ! CATEGORY D PS-2-134A  ! SOR  ! 9TA-B45-NX-  ! QUALIFIED  !  !

!  ! CIA- WTTX6  !  !  !

PS-2-1348  ! SOR  ! 9TA-B45-NX-  ! QUALIFIED  !  !

!  ! CIA-JJTTX6  !  !  !

PS-2-134C  ! SOR  ! 9TA-B4'rNX-  ! OVALIFIED  !  !

!  ! CIA-WTTX6  !  !  !

PS-2-1340  ! SOR  ! 9TA-B45-NX-  ! QUALIFIED  !  !

!  ! CIA-JJTTX6  !  !  !

RV-2-7tA  ! ASCO  ! 206-381-6F  ! QUALIFIED  !  !

RV-2-719  ! ASCO  ! 206-381-6F  ! QUALIFIED  !  !

RV-2-71C  ! ASCO  ! 206-381-6F  ! QUALIFIED  !  !

RV-2-71D  ! ASCO !206-381-6F  ! QUALIFIED  !  !

SRV MONITOR  ! CEN. ELECTRIC ! 21984061  ! QUALIFIED  !  !

P!(-112019430005 TS-2-121A !FENWAL  ! 010-170020-090! QUALIFIED  !  !

TS-2-1218  ! FDAIAL !010-170020-090!00AllFIED  !  !

TS-2-12tC  ! FENWAL  ! 010-170020-090! QUALIFIED  !  !

,_.______.-1

VERM0NT YANKEE NUCLEAR P0WER STATION Fil0DUCED 84/08/10.

i ENVIR010 ENTAL QUALIFICATION OF ELECTRICAL EQUIPtENT MASTER EQUIPMENT LIST FACE 5

!  !  ! QUALIFICATION ! DEFICIENCY /  !

ID INSER  ! MAfGJFACTURER ! MODEL IU SER ! STATUS  ! RESOLUTION !C019ENTS NUCLEAR B0ILER SY$ TEM (CONTINUED) i TS-2-121D  ! FDWAL  ! 010-170020-090! QUALIFIED  !  !

TS-2-122A  ! FDWAL !010-170020-090! QUALIFIED  !  !

TS-2-1228  ! FEWAL !010-170020-090! QUALIFIED  !  !

l TS-2-122C  ! FDWAL  ! 010-170020-090! QUALIFIED  !  !

l TS-2-122D  ! FDWAL !010-170020-090! QUALIFIED  !  !

TS-2-1234  ! FD WAL  ! 010-170020-090! QUALIFIED  !  !

! TS-2-1238  ! FDWAL  ! 010-170020-090! QUALIFIED  !  !

! TS-2-123C  ! FE M AL !010-170020-090! QUALIFIED  !  !

TS-2-123D  ! FDWAL  ! 010-170020-090! QUALIFIED  !  !

TS-2-1244  ! FDWAL  ! 010-170020-090! QUALIFIED  !  !

l TS-2-1248  ! FElWAL !010-170020-090! QUALIFIED  !  !

l TS-2-124C !FElWAL  ! 010-170020-090! QUALIFIED  !  !

TS-2-124D  ! FElWAL  ! 010-170020-090! QUALIFIED  !  !

ZE-2-1A  ! ENDEVC0  ! 2273AM20  ! QUALIFIED  !  !

l ZE-2-1B  ! DOEVC0  ! 2273AM20  ! QUALIFIED  !  ! r

, ZT-2-1A  ! TEC !504E  ! QUALIFIED  !  !

l ZT-2-!B  ! TEC  ! 504E  ! QUALIFIED  !  !

f NUCLEAR BOILER VESSEL INSTRUMENTATION SYSTEM l LT-2-3-57A ! ROSEM0lMT  ! !!52DP4  ! QUALIFIED  !  ! t l

LT-2-3-579 ! ROSEMOUNT !Il52DP4  ! QUALIFIED  !  !

LT-2-3-504 !ROSEMOUNT  ! Il52DP4  ! QUALIFIED  !  !

LT-2-3-588 ! ROSEMOUNT !Il52DP4  ! QUALIFIED  !  !

LT-2-3-72A !ROSEMOUNT  ! !!52DP4  ! QUALIFIED  !  !

l LT-2-3-729 ! ROSEM0 TNT  ! !!52DP4  ! QUALIFIED  !  !

! LT-2-3-72C !ROSDOMT  ! Il52DP4  ! QUALIFIED  !  !

LT-2-3-72D !ROSEMOUNT  ! Il52DP4  ! QUALIFIED  !  !

LT-2-3-73A ! ROSEMOUNT  !!!5308  ! QUALIFIED  !  !

LT-2-3-738 ! ROSEN00NT  ! 115300 tQUALIFIED  !  !

PT-2-3-52C ! ROSDENT !1153G89  ! QUALIFIED  !  !

PT-2-3-52D !ROSEMOUNT !1153099  ! QUALIFIED  !  !

PT-2-3-55A ! ROSEMOUNT !11520P9  ! QUALIFIED  !  !

PT-2-3-558 ! ROSDENT  ! 11520P9  ! QUALIFIED  !  !

PT-2-3-55C ! ROSEMOUNT !11520P9  ! QUALIFIED  !  !

PT-2-3-55D !ROSEM0 TNT  ! Il520P9  ! QUALIFIED  !  !

PI-2-3-56A ! ROSEMOUNT !1152099  ! QUALIFIED  !  !

! PT-2-3-568 ! ROSEMOUNT !il520P9  ! QUALIFIED  !  !

PT-2-3-56C !R00EM00NT !Il520P9 !QU$tlFIED  !  !

PT-2-3-56D ! ROSDRWT  ! il520P9  ! QUALIFIED  !  !

  • O VERM0NT YANKEE NUCLEAR P0WER STAT 1ON PR0[UCED t 84/08/10.

ENVIROMENTAL QUALIFICATION OF ELECTRICAL EQUlffENT MASTER EQUIPMENT LIST PACE 6

!  !  ! QLAIFICATION ! [EFICIENCY/  !

ID NMER  ! MANUFACTURER ! MODEL NUP9ER ! STATUS  ! RESCLUTION !C0reqENTS NUCLEAR B0ILER VESSEL INSTRUMENTATION SYSTEM (CONTINUED) 2-3-52CIM)  ! ROSEMOUNT  ! 71000  ? QUALIFIED  !  !

2-3-52C(X)  ! AGASTAT  ! E0PB001 !QUrtlFIED  !  !

2-3-52D(M)  ! ROSEMOUNT  ! 71000  ! OUALIFIED  !  !

2-3-52D(I)  ! A0ASTAT  ! E0P9001  ! QUALIFIED  !  !

2-3-55A(M)  ! ROSEMOUNT  ! 7100U  ! QLR IFIED  !  !

2-3-55A(X)  ! AGASTAT  ! EGPB001  ! OVALIFIED  !  !

2-3-55B(M)  ! POSEMOUNT  ! 71000  ! QUALIFIED  !  !

2-3-55B(Xi' ! A0ASTAT  ! E0PB001  ! OUfLIFIED  !  !

2-3-55C(M)  ! ROSEXfJNT  ! 7100U  ! QUALIFIED  !  !

2-3-55C(X)  ! AGASTAT  ! E0P9001  ! OVALIFIED  !  !

2-3-55D(M)  ! ROSEMOUNT  ! 7100U  ! OUALIFIED  !  !

2-3-55D(I)  ! FASTAT  ! E0FB001  ! QUALIFIED  !  !

2-346A(M)  ! ROSEM0thT  ! 71000  ! QUALIFIED  !  !

2-3-56A(SI) ! ROSEMOUNT  ! 7100U  ! OUALIFIED  !  !

2-3-56AIX)  ! AGASTAT !EGPB001  ! QUALIFIED  !  !

3-3-56A(XI) ! AGASTAT  ! E0PB001  ! O R IFIED  !  !

2-3-56B(M)  ! ROSEMOUNT  ! 71000  ! QUrtlFIED  !  !

3-3-56B(SI) ! ROSEM0lNT  ! 710CU  ! O A IFIED  !  !

2-3-56B(X)  ! AGASTAT !EGPB001  ! O A IFIED  !  !

2-3-56B(XI) ! FASTAT  ! EGF9001  ! 00ft!FIED  !  !

3-3-56C(M)  ! ROSEMOUNT  ! 71000  ! O A !FIED  !  !

3-346C(SI)  ! ROSEM0LNT !7100U  ! QUALIFIED  !  !

2-3-56C(X)  ! AGASTAT  ! E0F0001  ! QUALIFIED  !  !

2-3-56C(XI) ! #ASTAT  ! E0FB001  ! QUALIFIED  !  !

2-3-56D(M)  ! ROSDGNT  ! 7100U  ! QUALIFIED  !  !

3-3-56D($1) ! ROTMOUNT  ! 71000  ! QUtt!FIED  !  !

2-3-56D(X)  ! AGASTAT !E0P9001  ! QUALIFIED  !  !

3-3-56DIXI) ! A0ASTAT  ! E0PB001  ! O A IFIED  !  !

2-3-57A(M)  ! ROSOt)UNT  ! 71000  ! O A IFIED  !  !

2-3-57A(SI) ! ROSEMulNT  ! 71000  ! OUrtlFIED  !  !

8-3-57A($2) ! ROSEMOUNT  ! 710[0  ! OUrt!FIED  !  !

3-3-57AIX)  ! FASTAT !E0PB001  ! QUALIFIED  !  !

2-3-57AIXI) ! AGASTAT  ! E0FB001  ! O A !FIED  !  !

2-3-57AIX2) ! AGASTAT !E0PB001 !OVALIFIED  !  !

3-3-57B(M)  ! ROTMOUNT  ! 71000  ! ORIFIED  !  !

2-3-57B(SI) ! ROSEMOUNT  ! 71000  ! OuttlFIED  !  !

2-3-57B($2) !ROSEMOUNT  ! 71000  ! ORIFIED  !  !

2-3-57BIX)  ! FASTAT  ! EOFB001  ! O A IFIED  !  !

2-3-57D(XI) ! AGASTAT !E000001 !OUtilFIED  !  !

?* VERM0NT YANKEE NUCLEAR P0WER STATION PRODUCED 84C/10.

ENYlR010 ENTAL QUALIFICATION OF ELECTRICAL EQUIPfENT MASTER EQUIPMENT LIST l

PACE 7

!  !  ! QUALIFICATION ! DEFICIENCY /  !

10It#EER  ! IW SJFACTURER ! MODEL NUMBER ! STATUS  ! RESOLUTION !COPOENTS

!=  !- -!  !  !

NUCLEAR B0ILER VESSEL INSTRUMENTATION' SYSTEM (CONTINUED) 2-3-579(X2)  ! AGASTAT !E0P9001  ! OUALIFIED  !  !

2-3-504(M)  ! ROSEM0ttif !71000  ! QUALIFIED  !  !

2-3-584($1)  ! ROSEMOUNT !7100U  ! QUALIFIED  !  !

2-3-504($2)  ! ROSEMOUNT  ! 7100U  ! QUALIFIED  !  !

2-3-50AIX) !A0ASTAT  ! E0P9001  ! OUALIFIED  !  !

2-3-584(X1)  ! A04 STAT  ! E0P9001  ! QUALIFIED  !  !

2-3-584(X2)  ! AGASTAT !E0P9001  ! QUALIFIED  !  !

2-3-50B(M) !ROSOIOUNT !7100U  ! QUALIFIED  !  !

2-3-509($1)  ! ROSEMOLMT !71000  ! QUALIFIED  !  !

2-3-589($2)  ! ROSD100NT !7100U  ! QUALIFIED  !  !

2-3-509(X) !AGASTAT  ! E0P9n01  ! QUALIFIED  !  !

2-3-509(X1) !A04 STAT !E0P9001  ! QUALIFIED  !  !

2-3-509(X2) !AGASTAT  ! E0P9001 !OlHLIFIED  !  !

2-3-72A(M)  ! ROSEMOUNT !71000  ! QUALIFIED  !  !

2-3-72A(SI)  ! ROSEMOUNT  ! 7100U  ! QUALIFIED  !  !

2-3-72A($2) !ROSEMOUNT  ! 71000  ! QUALIFIED  !  !

2-3-72A($3) !ROSEMOUNT  ! 7100U  ! QUALIFIED  !  !

2-3-72AIS4) !ROSDI0lMT  ! 7t000  ! QUALIFIED  !  !

2-3-72AIS5)  ! ROSDIOLMT !7100U  ! QUALIFIED  !  !

2-3-72A(I) !AGA6 TAT !E0P9001  ! QUALIFIED  !  !

2-3-724(XI) !AGASTAT !ECP9001  ! QUALIFIED  !  !

2-3-72A(X2) !AGASTAT !ETR14930001  ! QUALIFIED  !  !

2-3-72AIX3)  ! AGASTAT !ECP9001  ! QUALIFIED  !  !

2-3-72AIX4) !AGASTAT !E0P9001  ! QUALIFIED  !  !

2-3-72AIX5)  ! AGASTAT !E0P9001  ! QUAllFIED  !  !

2-3-729(M)  ! ROSO10VNT !71000  ? QUALIFIED  !  !

2-3-729(SI)  ! ROSEMOUNT  ! 7100U  ! QUALIFIED  !  !

2-3-729($2)  ! ROSO90VNT !7100U  ! QUALIFIED  !  !

2-3-729($3) !ROSO900NT !71000  ! QUALIFIED  !  !

2-3-729fS4)  ! ROS010lMT !11000  ! QUALIFIED 8 2-3-729(S5)  ! A0$0tWWT !710(t) !OVALIFIED  !  !

2-3-729(X) !AGASTAT !E0P9001  ! QUALIFIED  ! -

2-372B(X1)  ! AGASTAT !E0P9001 !00ALIFIED  !  !

2-3-729(X2)  ! AGA6 TAT !ETR14630001  ! QUALIFIED  !  !

2-3-729(X3)  ! A04 STAT  ! E@9001  ! QUALIFIED  !  !

2-3-729(X4) !A0ASTAT !E@9001  ! QUALIFIED  !  !

2-3-729(X5) !AGASTAT !E0P9001 !QUAllFIED  !  !

2-3-72C(M)  ! ROSOE)UNT !71000  ! GJALIFIED  !  !

2-3-72CISL) !ROSUIOUNT !7100U  ! QUALIFIED  !  !

i r

i VERM0NT- YA'NKEE NUCLEAR' P0WER STATION PRODUCED 84/08/10.

ENVIR0lfENTAL QUALIFICATION OF ELECTRICAL EQUIP!ENT MASTER EQUIPMENT LIST PAGE- 8

-!  !  ! QUALIFICATION  ! DEFICIENCY / !

-IDIUSER  ! MAltJFACTURER ! MODEL Nif9ER ! STATUS  ! ' RESOLUTION. !C0lfENTS NUCLEAR.-B0ILER. VESSEL. INSTRUMENTATION-SYSTEM (CONTINUED) 3-72C(S2)  ! ROSEMOUNT  ! 710DU  ! QUALIFIED  !  !

2-3-72C(S3)'  ! ROSEMOUNT  ! 7100U-  ! QUALIFIED  !  !

c2-3-72C(X)'  ! AGASTAT  ! E0PB001  ! QUALIFIED-  !  !

3-72C(XI) !AGASTAT '! EGP9001  ! QUALIFIED  !  !

2-3-72C(X2)  ! AGASTAT  ! ETR14B39001  ! QUALIFIED  !  !

2-3-72C(X3)  ! AGASTAT  ! E0PB001  ! QUALIFIED  !  !

2-3-72D(M)  ! ROSEMOUNT  ! 71000  ! QUALIFIED  !  !

2-3-72D(SI)  ! ROSEM0lMT  ! 710D0  ! QUALIFIED  !  !

2-3-720(S2)  ! ROSEMOUNT  ! 7100U  ! QUALIFIED-  !  !

2-3-72D(S3)  ! ROSEM0lMT  ! 7100U  ! QUALIFIED  !  !

2-3-72D(X)  ! AGASTAT  ! EGPB001  ! QUALIFIED  !  !

2-3-72D(X1)  ! AGASTAT  ! EGPB001  ! QUALIFIED  !  !

2-3-72D(X2) 4  ! AGASTAT-  ! ETR14838001  ! QUALIFIED  !  !

2-3-72D(Z3)  ! AGASTAT  ! E0PB001  ! QUALIFIED  !  !

2-3-73A(M)  ! ROSEMOUNT  ! 7100U  ! QUALIFIED  !  !

2-3-73A(X)  ! AGASTAT  ! E0PB001  ! QUALIFIED  !  !

2-3-738(M)  ! ROSEM0lMT  ! 71000  ! QUALIFIED  !  !

2-3-73B(X)  ! AGASTAT !E0PB001  ! QUALIFIED  !  !

CONTROL' ROD. DRIVE SYSTEM

'LT-3-231A  ! ROSEMOUNT  !'1153DB4PG  ! QUALIFIED '  !

LT'3-231B  ! ROSEM0lMT  ! 1153DB4P0  ! QUALIFIED  !  !

. LT-3-231C .! ROSEMOUNT  ! 1153DB4PG  ! QUALIFIED  !  !

' LT-3-2310  ! R0 GEM 0UNT  ! 1153DB4PG  ! QUALIFIED  !  !

1 LT-3-231E  ! ROSEliDUNT  ! 1153DB4PG  ! QUALIFIED  !  !

LT-3-231F  ! MSE!'OlMT  ! 1153DB4PG  ! QUALIFIED  !  !

LT-3-2310  ! ROSEMOUNT  ! 1153DB4PG  ! QUALIFIED  !  !

LT-3-231H  ! ROSEMOUNT  ! 1153DB4PG  ! QUALIFIED  !  !

SE-3-ARI-A  ! ASCO !IF8316E36E  ! QUALIFIED  !  !

SE-3-ARI-B -! ASCO !If8316E36E' ! QUALIFIED  !  !

SE-3-31A  ! ASCO  ! WA90-405-2A ! QUALIFIED  !  !

SE-3-31B  ! ASCO  ! WA90-405-2A ! QUALIFIED  !  !

S0-3-13-117  ! ASCO .  ! WA90-405-2A ! QUALIFIED  !  ! SCRAM SOLEN 01DS-89 TOTAL S0-3-13-118-  ! ASCO  ! WA90-405-2A ! QUALIFIED-  !  ! SCRAM S0LEN01DS-89 TOTAL 25-56A-Al  !-RIS  ! AN1178  ! QUALIFIED  !

! CATEGORY D

'25-56A-B1  ! RIS  ! AN!!78  ! QUALIFIED  !  ! CATEGORY D 25-568-A2-  ! RIS  ! AN1178  ! QUALIFIED  !  ! CATEGORY D 25-56B-B2'  ! RIS ~  ! AN1178  ! QUALIFIED  !  ! CATEGORY D 13-231A(M)  ! ROSEMOUNT  ! 51000  ! QUALIFIED  !  ! CATEGORY D

'i VERM0N1 Y'A N K E E NUCLEAR P0WER STATION' PRODUCED : 84/08/10.

ENVIR0lMNTAL QUALIFICATION OF ELECTRICAL EQUIFtENT MASTER EQUIPMENT LIST PAGE 9

-!  ! -! QUALIFICATION  ! DEFICIENCY /  !

IDIDEER  ! MANLFACTURER ! MODEL ltMBER ! STATUS  ! RESOLUTION !COMENTS C0NTR0L'R0D DRIVE SYSTEM (CONTINUED) 3-231AIS1)  ! ROSEM0LNT  ! 51000  ! QUALIFIED  !  ! CATEGORY D 3-231A(X)  ! AGASTAT  ! EGPB002  ! QUALIFIED  !  ! CATEGORY D

'3-231AIX1)*  ! AGASTAT  ! EGPB002 -! QUALIFIED  !  ! CATEGORY D 3-231B(M)  ! ROSEMOUNT  ! 510D0  ! QUALIFIED  !  ! CATEGORY D 3-231B(SI)  ! ROSEMOUNT  ! 5100U  ! QUALIFIED  !  ! CATEGORY D 3-231B(X)  ! AGASTAT  ! EGPB002  ! QUALIFIED  !  ! CATEGORY D 3-231B(X1)  ! AGA3 TAT  ! EGPB002  ! QUALIFIED  !  ! CATEGORY D 3-231C(M)  ! ROSEMOUNT  ! 5100U  ! QUALIFIED  !  ! CATEGORY D 3-231C(X)  ! AGASTAT-  ! EGPB002  ! QUALIFIED  !  ! CATEGORY D 3-231D(M)  ! ROSEM0lNT  ! 51000  ? QUALIFIED  !  ! CATEGORY D 3-231D(X)  ! AGASTAT  ! EGP9002  ! QUALIFIED  !  ! CATEGORY D l

3-231E(M)  ! ROSEMOUNT  ! 5100U  ! QUALIFIED  !  ! CATEGORY D 3-231E(X)  ! AGASTAT  ! EGP9002  ! QUALIFIED  !  ! CATEGORY D 3-231F(M)  ! ROSEMOUNT  ! 51000  ! QUALIFIED  !  ! CATEGORY D 3-231F(X)  ! AGASTAT  ! EGPB002  ! QUALIFIED  !  ! CATEGORY D 3-231GIM)  ! ROSEM0lNT  ! 51000  ! QUALIFIED  !  ! CATEGORY D 3-2310(S1)  ! ROSEMOUNT  ! 510DU  ! QUALIFIED  !  ! CATEGORY D 3-231G(X)  ! AGASTAT  ! EGPB002  ! QUALIFIED  !  ! CATEGORY D 3-231G(X1)  ! AGASTAT  ! EGPB002  ! QUALIFIED  !  ! CATEGORY D 3-231H(M)  ! ROSEMOUNT  ! 51000  ! QUALIFIED  !  ! CATEGORY D 3-231H(SI)  ! ROSEMOUNT  ! 5100U  ! QUALIFIED  ! ' CATEGORY D 3-231H(X)  ! AGASTAT  ! EGPB002  ! QUALIFIED  !  ! CATEGORY D 3-231H(11)  ! AGASTAT  ! EGPB002  ! QUALIFIED '  ! CATEGORY D CRDM POS IND  ! GEN ELECTRIC !  ! JC0-29  ! NO DOC /QDR  ! (NOTE 3)

-REACTOR PROTECTION SYSTEM PtL5-7A  ! GEN ELECTRIC !  ! QUALIFIED  !  ! CATEGORY D PIL5-7B  ! GEN ELECTRIC !  ! QUALIFIED  !  ! CATEGORY D P!L5-7C '! 0EN ELECTRIC  !  ! QUALIFIED '  !  ! CATEGORY D PM.5-7D  ! GEN ELECTRIC  !  ! QUALIFIED  !  ! CATEGORY D PIL5-7E  ! GEN ELECTRIC  !  ! QUALIFIED  !  ! CATEGORY D PIL5-7F  ! GEN ELECTRIC !  ! QUALIFIED  !  ! CATEGORY D PfL5-70  ! 0EN ELECTRIC !  ! QUALIFIED  !  ! CATEGORY D PIL5-7H  ! GEN ELECTRIC '!  ! QUALIFIED  !  ! CATEGORY D PS-5-14A  ! SOR  ! STA-B45-NX- ! QUALIFIED  !  !

!  ! CIA-JJTTX6  !  !  !

PS-5-14B  ! SOR  ! STA-B45-NX-  ! QUALIFIED  !  !

!  ! CIA-JJTTX6  !  !  !

PS-5-14C  ! SOR  ! STA-B45-NX-  ! QUALIFIED  !  !

u

VERM0NT YANKEE NUCLEAR P0WER STATION PRODUCED : 84/08/10.

ENVIR010 ENTAL QUALIFICATION OF ELECTRICAL EQUIPENT MASTER EQUIPMENT L-I S T PACE 10

!-  !  ! QUALIFICATION ! DEFICIENCY /  !

ID MlMBER  ! MAltFACTURER !.MODEL NUMBER ! STATUS  ! RESOLUTION !C0ltENTS

/

' REACT 0R PR0TECTION SYSTEM (CONT!!CED)

!  ! CIA-JJTTX6  !  !  !

PS-5-140  ! SOR  ! STA-B45-NX- ! QUALIFIED  !  !

!  ! CIA-JJTTX6  !  !  !

PS-37  ! SOR  ! 5N6-BB45-NX- ! QUALIFIED  !  !

!-  ! CIA-JJTTX7  !  !  !

PS-38  ! SOR  ! 5N6-BB45-NX- ! QUALIFIED  !  !

!  ! CIA-JJTTX7  !  !  !

.PS-39  ! SOR  ! SN6-BB45-NX- ! QUALIFIED  !  !

!  ! CIA-JJTTX7  !  !  !

PS-40  ! SOR  ! SN6-BB45-NX- ! QUALIFIED  !  !

!  ! CIA-JJTTX7  !  !  !

PT-5-12A  ! ROSEM0lNT  ! 11520P4N22PB ! QUALIFIED  !  !

PT-5-12B  ! ROSEMOUNT  ! 11520P4N22PB ! QUALIFIED  !  !

'PT-5-12C  ! ROSEMOUNT  ! 11520P4N22PB ! QUALIFIED  !  !

PT-5-12D  ! ROSEMOUNT  ! 11520P4N22PB ! QUALIFIED  !  !

SVOS-1  ! NAMC0  ! EA-74000100 ? QUALIFIED  !  !

SYOS-2  ! NAMCO -! EA-74000100 ! QUALIFIED  !  !

SVOS-3  ! NAMCO  ! EA-74000100 ! QUALIFIED  !  !

SV0S-4  ! NAMCO  ! EA-74000100 ! QUALIFIED  !  !

5-12A(M)  ! ROSEMOUNT  ! 710DUOTT36005 ! QUALIFIED  !  !

5-12AIX)  ! A0ASTAT  ! E0PB001  ! QUALIFIED  !  !

5-12B(M)  ! ROSEM0lMT  ! 710DUOTT36005 ! QUALIFIED  !  !

.5-12B(X)  ! AGASTAT  ! E0PB001  ! QUALIFIED  !  !

'5-12C(M)  ! ROSEMOUNT  ! 7100UOTT35005 ! QUALIFIED  !  !

5-12C(X)  ! AGASTAT  ! ECPB001  ! QUALIFIED  !  !

5-12D(M)  ! ROSEM0lNT  ! 710000TT36005 ! QUALIFIED  !  !

5-12D(X)  ! AGASTAT  ! E0PB001  ! QUALIFIED  !  !

25-5A-(A1)  ! ELMA  ! 164C5261P002 ! QUALIFIED  !  !

25-5A-(B1)  ! ELMA  ! 16405261P002 ! QUALIFIED  !  !

25-6A-(A2)  ! ELMA  ! 164C5261P002 ! QUALIFIED  !  !

25-6A-(B2)  ! ELMA  ! 164C5261P002 ! QUALIFIED  !  !

NEUTRON MONITORING SYSTEM TIP SEAR VALVES!  !  ! QUALIFIED  !  ! CATEGORY D TIP BALL VALVES !  ! ' QUALIFIED  !  ! CATEGORY D LPRMS  ! GEN ELECTRIC ! 129836200026 ! JC0-39  ! NO DOC /QDR  ! (NOTE 3)

TIP DR  !  !  ! QUALIFIED  !  ! CATEGORY D RESIDUAL HEAT REMOVAL SYSTEM l

I VERM0NT' YANKEE NUCLEAR P0WER STATION PRODUCED 84/08/10.

ENVIR0l# ENTAL QUALIFICATION OF ELECTRICAL EQUIPfENT MASTER EQUIPMENT LIST PAGE- 11

~!  !  ! QUALIFICATION ! DEFICIENCY /  !

ID MIMBER  ! MAIGJFACTlRER ! MODEL NUMBER ! STATUS  ! RESOLUTION !C0ffENTS RESIDUAL HEAT REM 0 VAL SYSTEM (CONTINUED)

CP-82-2  ! PERCURY  !  ! QUALIFIED  !  !

DPT-10-71A -! ROSEMOUNT  ! 1153DB7PA  ! QUALIFIED  !  !

DPT-10-913  ! ROSEM0lNT  ! 1153DB7PA  ! QUALIFIED  !  !

FS-10-140A  ! BARTON  ! 289A-2553  ! QUALIFIED  !  !

FS-10-1488 -! BARTON  ! 289A-2554  ! QUALIFIED  !  !

MOV-10-13A  ! LIMITORQlE -! SMB-2  ! QUALIFIED  !  !

MOV-10-13B  ! LIMITORQUE  ! SMB-2  ! JCO-68  ! DOC PROBLEMS  ! (NOTE 3)

MOV-10-13C  ! LIMITORQlE  ! SMB-2  ! QUALIFIED  !  !

MOV-10-130  ! LIMITORQUE  ! SMB-2  ! QUALIFIED  !  !

MOV-10-15A  ! LIMITORQUE  ! SMB-2  ! QUALIFIED  !  !

MOV-10-15B  ! LIMITORQlE  ! SMB-2  ! QUALIFIED  !  !

MOV-10-15C  ! LIMITORQlE  ! SMB-2  ! QUALIFIED  !  !

MOV-10-15D  ! LIMITORQUE  ! SMB-2  ! QUALIFIED  !  !

MOV-10-16A  ! LIMITORQUE  ! SMB  ! QUALIFIED  !  !

MOV-10-16B  ! LIMITORQlE  ! SMB  ! QUALIFIED  !  !

MOV-10-17  ! LIMITORQlE  ! SMB-4  ! QUALIFIED  !  ! CATEGORY D MOV-10-18  ! LIMITORQUE  ! SMB-2  ! QUALIFIED  !  !

MOV-10-25A  ! LIMITORQUE  ! SB-3  ! QUALIFIED  !  !

POV-10-25B  ! LIMITORQUE  ! SB-3  ! QUALIFIED  !  !

MOV-10-26A  ! LIMITORQUE  ! SMB-00  ! QUALIFIED  !  !

MOV-10-26B  ! LIMITORQlE  ! SMB-00  ! QUALIFIED  !  !

t0V-10-27A  ! LIMITORQlE  ! SMB-4T  ! QUALIFIED  !  !

MOV-10-27B  ! LIMITORQUE  ! SMB-4T  ! QUALIFIED  !  !

MOV-10-31A  ! LIMITORQUE  ! SMB-0  ! QUALIFIED  !  !

MOV-10-31B  ! LIMITORQUE  ! SMB-0  ! QUALIFIED  !  !

MOV-10-32  ! LIMITORQUE  ! SMB-00  ! JCO-43  ! PEND LICENSINO ACTION ! (NOTE 4)

MOV-10-33  ! LIMITORQUE  ! SMB-001  ! QUALIFIED  !  ! CATEGORY D MOV-10-24A  ! LIMIT 0kQUE  ! SMB-002  ! QUALIFIED  !  !

N0V-10-348  ! LIMITORQUE  ! SMB-002  ! QUALIFIED  !  !

MON-10-38A  ! LIMITORQUE  ! SMB-00  ! QUALIFIED  !  !

MOV-10-38B  ! LIMITORQlE  ! SMB-00  ? QUALIFIED  !  !

MOV-10-39A  ! LIMITORQlE  ! SMB-0  ! JC0-69  ! DOC PROBLEMS  ! (NOTE 3) 70V-10-39B  ! LIMITORQlE  ! SMB-0  ! QUALIFIED'  !  !

MOV-10-57  ! LIMITORQUE  ! SMB-00  ! QUALIFIED  !  ! CATEGORY D MOV-10-65A  ! LIMITORQUE  ! SMB-4  ! QUALIFIED  !  !

MOV-10-65B  ! LIMITORQUE  ! SMB-4  ! QUALIFIED  !  !

.MOV-10-66  ! LIMITORQlE  ! SMB-000  ! QUALIFIED  !  ! CATEGORY D MOV-10-89A-  ! LIMITORQUE  ! SMB-2  ! QUALIFIED  !  !

MOV-10-899  ! LIMITORQlE  ! SMB-2  ! QUALIFIED  !  ! l l

1 l

l J

T

  • VERM0NT' YANKEE NUCLEAR P0WER STAT!ON PRODUCED 84/08/10.

ENVIROM1 ENTAL QUALIFICATION OF ELECTRICAL EQUIPMENT MASTER EQUIPMENT LIST PAGE 12

!  !  ! QUALIFICATION  ! DEFICIENCY /  !

ID NtMBER  ! MANUFACTlRER ! MO[EL NJMBER ! STATUS  ! RESOLUTION !COMENTS RESIDUAL HEAT REM 0 VAL SYSTEM (CONTINUED)

P-8-1A  ! ESTINGHOUSE  ! CSP-USS-PP  ! QUALIFIED  !  !

P-8-1B  ! E STINGHOUSE  ! CSP-USS-PP  ! QUALIFIED  !  !

P-8-1C  ! ESTINGHOUSE ! CSP-USS-PP  ! QUALIFIED  !  !

P-0-1D  ! ESTINGHOUSE ! CSP-USS-FP ' QUALIFIED  !  !

P-10-1A  ! 0EN ELECTRIC .! BE F212003  ! QUALIFIED  !  !

P-10-1B  ! OEN ELECTRIC ! bee 219002  ! QUALIFIED  !  !

P-10-1C  ! OEN ELECTRIC  ! bee 219003  ! QUALIFIED  !  !

P-10-1D  ! GEN ELECTRIC ! BEF205002  ! QUALIFIED  !  !

POT-10-89A  ! HELIPOT  ! 5311  ! QUALIFIED  !  !

P0T-10-89B  ! ELIPOT  ! 5311  ! QUALIFIED  !  !

PS-10-105A  ! SOR  ! SN-AA3-X4  ! QUALIFIED  !  ! CATEGORY D PS-10-105B  ! SOR  ! 5N-AA3-X4  ! QUALIFIED  !  ! CATEGORY D PS-10-105C  ! SOR  ! 5N-AA3-X4  ! QUALIFIED  !  ! CATEGORY D PS-10-105D  ! SOR  ! 5N-AA3-X4  ! QUALIFIED  !  ! CATEGORY D PS-10-105E  ! SOR 8 5N-AA3-X4  ! QUALIFIED  !  ! CATEGORY D PS-10-105F  ! SOR  ! 5N-AA3-X4  ! QUALIFIED  !  ! CATEGORY D PS-10-1050  ! S0R  ! SN-AA3-X4  ! QUALIFIED  !  ! CATEGORY D PS-10-105H  ! SOR  ! SN-AA3-X4  ! QUALIFIED  ! ' CATEGORY D PT-10-101A  ! ROSEMOUNT  ! 11520P4N22PB ! QUALIFIED  !  !

PT-10-101B  ! ROSEM0 TNT  ! 11520P4N22PB ! QUALIFIED  !  !

PT-10-101C  ! ROSEMOUNT  ! 11520P4N22FB ! QUALIFIED  !  !

PT-10-101D  ! ROSEMOUNT  ! 11520P4N22PB ! QUALIFIED  !  !

10-101A(M)  ! ROSEMOUNT  ! 710000TT36005 ! QUALIFIED  !  !

10-101AIS1)  ! ROSEMOUNT  ! 710DUOTS  ! QUALIFIED  !  !

10-101A(X)  ! AGASTAT  ! EGPB001  ! QUALIFIED  !  !

10-101A(XI)  ! AGASTAT  ! EGPB001  ! QUALIFIED  !  !

10-101B(M)  ! ROSEMOUNT  ! 710DUOTT36005 ! QUALIFIED  !  !

10-101B(S1)  ! ROSEM0lNT  ! 710DUOTS  ! QUALIFIED  !  !

10-101B(X)  ! AGASTAT  ! EGPB001  ! QUALIFIED  !  !

10-101B(X1)  ! AGASTAT  ! E0PB001  ! QUALIFIED  !  !

10-101C(M)  ! ROSEMOUNT  ! 710DVOTT36005 ! QUALIFIED  !  !

10-101C(SI)  ! ROSEMOUNT  ! 710DUOTS  ! QUALIFIED  !  !

10-101C(X)  ! AGASTAT  ! EGPB001  ! QUALIFIED  !  !

10-101C(X1)-  ! AGASTAT  ! EGPB001  ! QUALIFIED  ! '

10-101D(M)  ! ROSEM0lNT  ! 710DUOTT36005 ! QLVLIFIED  !  !

10-101D(S1) '! ROSEMOUNT  ! 710DUOTS  ! QUALIFIED  ! '

10-1010(X)  ! AGASTAT  ! E0PB001  ! QUALIFIED  !  !

10-101D(X1)  ! AGASTAT  ! EGPB001  ! QUALIFIED  !  !

RE' ACTOR WATER CLEANUP SYSTEM 1

Y' VERMONT YANKEE- NUCLEAR POWER STAT 10N PRODUCED 84/08/10.

EWIR0lfENTAL QUALIFICATION OF ELECTRICAL EQUIPENT MASTER EQUIPMENT LIST PAGE 13

!  !  ! QUALIFICATION  ! DEFICIENCY /  !

IDIUSER  ! MANlfACTlRER ! MODEL WMBER ! STATUS  ! RESOLUTION !C0ffENTS REACT 0R' WATER CLEANUP. SYSTEM (CONTIMED)

FT-12-!A  ! ROSEM0LNT  ! 1153DB4  ! QUALIFIED  !  ! CATEGORY D FT-12-1B  ! ROSEMOUNT  ! 1153DB4  ! QUALIFIED  !  ! CATEGORY D MOV-12-15  ! LIMITORQUE  ! SMB-000  ! QUALIFIED  !  !

MOV-12-18  ! LIMITm0VE  ! $19-000  ! QUALIFIED  !  !

MOV-12-68  ! LIMITORQlE  ! SMB-00  ! QUALIFIED  !  ! CATEGORY D TS-12-101A  ! FEWAL  ! 01-17023(H)90 ! QUALIFIED  !  !

TS-12-101B !FENWAL  ! 01-170230-090 ? QUALIFIED  !  !

TS-12-102A  ! FE W AL  ! 01-170230-090 ! QLW.IFIED  !  !

TS-12-102B  ! FEWAL  ! 01-170230-090 ! QUALIFIED  !  !

TS-12-103A  ! FENWAL  ! 01-170230-090 ! QUALIFIED  !  !

TS-12-1038  ! FEWAL  ! 01-17023(H)90 ! QUALIFIED  !  !

TS-12-106A  ! FENWAL  ! 01-170230-090 ! QUALIFIED  !  !

TS-12-106B  ! FEWAL  ! 01-170230-090 ! QUALIFIED  !  !

TS-12-107A  ! FENWAL  ! 01-170230-090 ! QUALIFIED  ! '

TS-12-107B  ! FENWAL  ! 01-170230-090 ! QUALIFIED  !  !

TS-12-108A  ! FENWAL  ! 01-170230-090 ! QUALIFIED  !  !

TS-12-1083  ! FENWAL  ! 01-170230-090 ! QUALIFIED  !  !

TS-12-109A  ! FEWAL  ! 01-170230-090 ! QUALIFIED  !  !

TS-12-109B  ! FE W AL  ! 01-170230-090 ! QUALIFIED  !  !

TS-12-110A  ! FEWAL  ! 01-170230-090 ? QUALIFIED  ! '

TS-12-110B  ! FEWAL  ! 01-170230-090 ! QUALIFIED  !  !

TS-12-111A  ! FENWAL  ! 01-170230-090 ! QUALIFIED  !  !

TS-12-111B  ! FEWAL  ! 01-170230-090 ! QUALIFIED  !  !

TS-12-112A  ! FEWAL  ! 01-170230-090 ! QUALIFIED  !  !

TS-12-112P  ! FE W AL  ! 01-17023(H)90 ! QUALIFIED  !  !

12-1A(M)  ! ROSEMOUNT  ! 710000TT16025 ! QUALIFIED  !  !

12-1AIX)  ! AGASTAT  ! E0PB001  ! QUALIFIED  !  ! CATEGORY D 12-1B(M)  ! ROSEMOUNT  ! 710DUOTT16025 ! QUALIFIED  !  !

12-1B(X)  ! AGASTAT  ! E0PB001  ! QUALIFIED  !  ! CATEGORY D 12-101A(17) ! AGASTAT  ! E0PB002  ! QUALIFIED  !  !

12-101B(X7) ! AGASTAT  ! E0PB002  ! QUALIFIED  !  !

REACTOR CORE ISOLATION C00 LINO SYSTEM CP-82-3  ! ERCURY  !  ! QUALIFIED  !  !

MOV-13-15  ! LIMITORQUE  ! SMB-000  ! JCO-46  ! DOC PROBLEMS  ! (NOTE 3)

MOV-13-16  ! LIMITORQlE  ! SMB-000  ! QUALIFIED  !  !

MTS-13-2  ! WESTINGHOUSE  ! MTSSM20225EX ! QUALIFIED  !  !

TS-13-79A  ! FE W AL !01-170230-090 ! QUALIFIED  !  !

TS-13-798  ! FENWAL !01-17023(H)90 ! QUALIFIED  !  !

VERM0NT YANKEE NUCLEAR P0WER STATION PRODJCED 84/08/10.

ENVIR0! MENTAL QUALIFICATION OF ELECTRICAL EQUIPENT MASTER EQUIPMENT LIST PAGE 14

!  !  ! QUALIFICATION  ! DEFICIENCY /  !

ID !AJMBER  ! MA!E ACTLRER ! MODEL NLMBER ! STATUS  ! RESOLUTION !COMENTS REACT 0R C0RE IS0LATI0N C00LIN0 SYSTEN (CONTINUED)

TS-13-79C  ! FENWAL !01-170230-090 ! QUALIFIED  !  !

TS-13-79D  ! FENWAL !01-170230-090 ! QUALIFIED  !  !

TS-13-80A  ! FENWAL !01-170230-090 ! QUALIFIED  !  !

TS-13-90B  ! FENWAL !01-170230-090 ? QUALIFIED  !  !

TS-13-80C  ! FEMML !01-170230-090 ! QUALIFIED  !  !

TS-13-80D  ! FENWAL !01-170230-090 ! QUALIFIED  !  !

TS-13-81A  ! FENWAL !01-170230-090 ? QUALIFIED  !  !

TS-13-81B  ! FENWAL !01-170230-090 ! QUALIFIED  !  !

TS-13-81C  ! FENWAL !01-170230-090 ! QUALIFIED  !  ! ,

TS-13-81D  ! FENWAL !01-170230-090 ! QUALIFIED  !  !

TS-13-82A  ! FENWAL !01-170230-090 ! QUALIFIED  !  !

TS-13-82B  ! FENW(L !01-170230-090 ! QUALIFIED  !  !

TS-13-82C  ! FENWAL !01-170230-090 ! QUALIFIED  !  !

TS-13-82D  ! FENWAL !01-170230-090 ! QUALIFIED  ! '

V-13-16  ! WESTINCH)USE ! TYPE W  ! QUALIFIED  !  ! LOCAL STARTER CORE SPRAY SYSTEM FS-14-45A ' BARTON  ! 289A-2456  ! QUALIFIED  !  !

FS-14-45B  ! BARTON ' 289A-8122  ! QUALIFIED  !  !

MOV-14-5A  ! LIMITORQUE  ! SMB-000  ! OUALIFIED  !  !

MOV-14-5B  ! LIMlllHQUE ' SMB-000  ! QUALIFIED ' '

MOV-14-7A  ! LIMITOROUE  ! SMB-00  ! QUALIFIED  !  !

MOV-14-7B  ! LIMITORQlE  ! SMB-00  ! QUALIFIED  ! '

MOV-14-11A ' LIMITORQUE  ! SMB-2 ' QUALIFIED  !  !

NOV-14-11B  ! LIMITORQlE  ! SMB-2  ! QUALIFIED  !  !

MOV-14-12A  ! LIMITORQUE  ! SMB-2  ! QUALIFIED  ! '

NOV-14-12B ' LIMITORQ'JE  ! SMB-2  ! QUALIFIED  !  !

MOV-14-26A  ! LIMITORQUE  ! SMB-1  ! QUALIFIED  !  ! CATEGORY D MOV-14-26B  ! LIMITORQUE ' SMB-1  ! QL%LIFIED  !  ! CATEGORY D P-44-1A  ! GEN ELECTRIC  ! FEJ604010  ? QUALIFIED  !  !

P-46-1B  ! GEN ELECTRIC ! FEJ604011 ' QUALIFIED  !  !

PS-14-44A  ! SOR  ! 5N-AA3  ! QUALIFIED '  ! CATEGORY D PS-14-449  ! SOR  ! 5N-AA3  ! QUALIFIED  ! CATE006Y D PS-14-44C  ! SOR  ! SPH43  ? QUALIFIED  !  ! CATEGORY D PS-14-44D  ! SOR  ! SN-AA3  ! QUALIFIED '  ! CATEGORY D PRIMARY CONTAINMENT ATMOSPHERIC CONTROL SYSTEM IPS-16-19-32A ! BARTON  ! 288A-6648  ! QUALIFIED  !  !

DPS-16-19-32B ! BARTON  ! 288A-6649  ! QUALIFIED  !  !

k VERM0NT YANKEE NUCLEAR P0WER STATION PRODUCED 84/08/10.

ENVIRONMENTAL QUALIFICATION OF ELECTRICAL EQUIPMENT MASTER EQUIPMENT LIST PAGE 15 1

!  !  ! QUALIFICATION  ! DEFICIDJCY/ !

ID NUMBER  ! ttANUFACTURER ! MODEL NUMBER ! STATUS  ! RESOLUTION  ! COMMENTS PRIMARY CONTAINMENT ATMOSPHERIC CONTROL SYSTEM l CONTINUED)

LT-16-19-10A ' ROSEMOUNT  ! 1153085  ! Q'JALIFIED  !  !

LT-16-19-10B  ! ROSEMOUNT  ! 1153DB5  ! QUALIFIED  !  !

PT-16-19-29A  ! ROSEMOUNT  ! 1153AB7  ! QUALIFIED  !  !

PT-16-19-293  ! ROSEMOUNT  ! 1153AB7  ! QUALIFIED '  !

RD-16-19-1A  ! VICT0REEN  ! 877  ! QUALIFIED  !  !

RD-16-19-1B  ! VICT0REEN  ! 877  ! QUALIFIED  !  !

SB-16-19-6  ! ASCO ' 206-380-7F  ! QUALIFIED  !  ! CATEGORY D SB-16-19-6A  ! ASCO  ! 206-380-7F  ! OVALIFIED  !  ! CATEGORY D SB-16-19-6B  ! ASCO ' 206-330-7F  ! QUALIFIED  !  ! CATEGORY D SB-16-19-7  ! ASCO  ! 206-380-7F  ! QUALIFIED  !  ! CATEGORY D SB-16-19-7A  ! ASCO  ! NP831654E  ! QUfLIFIED  !  ! CATEGORY D SB-16-19-7B  ! ASCO  ! H 31654E  ! QUALIFIED  !  ! CATEGORY D SB-16-19-8  ! ASCO ' NP831654E  ! QUALIFIED '  ! CATEGORY D SB-16-19-9  ! ASCO  ! W831654E  ! QUALIFIED  !  ! CATEGORY D SD-16-19-10  ! ASCO  ! NP831654E  ! QUALIFIED  !  ! CATEGORY D SB-16-19-11A  ! ASCO ' W831654E  ! QUALIFIED  ! '

LS-SB-16-19-11A ' MICROSWITW ' EXD-AR7001  ! QUALIFIED  ! '

SB-16-19-11B ' ASCO ' NPC31654E  ! QUALIFIED  ! '

LS-SB-16-19-11B ! MICR05MITCH  ! EXD-AR6809  ! QUALIFIED  ! '

SB-16-19-23 ' ASCO  ! NP8321A6  ! QUALIFIED  !  ! CATEGORY D TE-1-149-1 ' CONAX  ! 7952-10000-04 ' QUALIFIED  ! '

TE-1-149-2 ' CONAX  ! 7952-10000-04 ! QUALIFIED  !  !

TE-1-149-3 ' CONAX  ! 7952-10000-04 ! QUfLIFIED  !  !

TE-1-149-4  ! CONAX  ! 7952-10000-04 ! QUALIFIED  ! '

TE-1-149-5  ! COMX  ! 7952-10000-04 ! QUALIFIED  !  !

TE-1-140-6  ! CONAX ' 7952-10000-04 ! QUALIFIED  !  !

TE-1-149-7  ! CONAX ' 7952-10000-04 ! QUALIFIED  ! '

TE-1-149-8  ! C0tMX  ! 7952-10000-04 ! OUALIFIED  !  !

TE-1-149-9  ! CCfMX  ! 7952-10000-03 ! QUALIFIED  ! '

TE-1-149-10  ! CONAX  ! 7952-10000-03 ! QUALIFIED ' ' I TE-1-149-11  ! CONAX  ! 7952-10000-03 ' QUtLIFIED  !  !

TE-1-149-12 ' CONAX  ! 7952-10000-03 ' QUALIFIED  ! '

TE-16-19-30 ' CONAX  ! 7952-10000-01 ! QUALIFIED  !  !

TE-16-19-33A  ! CONAX  ! 7952-10000-02 ! QUALIFIED  !  !

TE-16-19-33C  ! CONAX  ! 7952-10000-02 ! QUALIFIED '  !

TE-16-19-34 ' CONAX  ! 7952-10000-01 ' QUALIFIED  !  !

V16-20-20  ! TARGET R0m  ! 82-U-001  ! QUALIFIED  !  ! CATEGORY D V16-20-22A  ! TARGET ROCK  ! 82-U-001  ! QUALIFIED  !  ! CATEG M Y D V16-20-22B  ! TARGET ROCK  ! 82-0-001  ! QUALIFIED '  ! CATEGORY D RADIATION MONITORING SYSTEM l

&c

R-  %

  • 'VERM0NT ' YANKEE NUCLEAR P0WER STATION PRODUCED 8 84/08/10.

ENVIR0 MENTAL QUALIFICATION OF ELECTRICAL EQUIPfENT 1

MASTER _ EQUIPMENT LIST PAGE 16

!-  !-  ! QUALIFICATION ! DEF1CIENCY/  !

IDIMEER  ! MANUFACTIRER ! MODEL Nut 9ER ! STATUS  ! RESOLUTION !COMENTS RADIATION M0 NIT 0RIN0 SYSTEM (CONTINUED)-

'RM-17-4304 -! GEN ELECTRIC ! 194X927012  ! QUALIFIED '!  ! CATEGORY D RM-17-4308  ! GEN ELECTRIC ! 194X927012  ! QUALIFIED  !  ! CATEGORY D RM-17-431A  ! GEN ELECTRIC ! 194X927013  !. QUALIFIED  !  ! CATEGORY D RM-17-431B  ! GEN ELECTRIC ! 194X927013  ! QUALIFIED  !  ! CATEGORY D FUEL POOL COOLING SYSTEM LD-19-60A  ! FCI  ! 8-66 PFS  ! QUALIFIED  !  !

LD-19-60B  ! FCI  ! 8-66 PFS  ! QUALIFIED  !  !

P-9-1A  ! ESTINGHOUSE ! 40 W-286TS  ! QUALIFIED  !-  !

P-9-1B  ! ESTINGHOUSE ! 40W-286TS  ! QUALIFIED  !  !

PS-19-68A  ! SOR  !!2TA-B45-NX- ! QUALIFIED  !  !

!  ! CIA-JJTTX6  !  !  !

PS-19-68B  ! SOR  !!2TA-B45-NX- ! QUALIFIED  !  !

!  ! CIA-JJTTX6-  !  !  !

SW-9-1A  ! ELECTROSWITCH ! SERIES 20P '! QUALIFIED  !  !

'SW-9-1B  ! ELECTROSWITCH ! SERIES 20P  ! QUAllH ED  !  !

R4DWASTE SYSTEM A0V-20-82  ! ASCO  ! W8316A74E  ! QUALIFIED  !  ! CATE0(RY D A0V-20-83  ! ASCO  ! IF8316A74E  ! QUALIFIED  !  ! CATEClRY D

-A0V-20-94  ! ASCO !IF8316A74E  ! QUALIFIED  !  ! CATEGORY D A0V-20-95 ' ASCO  ! NP8316A74E ' QUALIFIED '  ! CATEGORY D HIGH PRESSURE COOLANT INJECTION SYSTEM NOV-23-15  ! LIMITORQUE .  ! Ste-O  ! QUALIFIED '

.MOV-23-16  ! LIMITORQUE  ! SMB-1 -! QUALIFIED  !  !

TS-23-101A  ! FEMiAL  ! 01-170230-090 ! QUALIFIED  !  !

TS-23-101B  ! FEMiAL  ! 01-170230-090 ? QUALIFIED  !  !

TS-23-101C  ! FEMiAL  ! 01-170230-090 ! QUALIFIED  !  !

TS-23-101D  ! FEmiAL  ! 01-170230-090 ! QUALIFIED  !  !

TS-23-102A  ! FEMIAL  ! 01-170230-090 ! QUALIFIED  !  !

TS-23-102B  ! FEMiAL  ! 01-170230-090 ! QUALIFIED  !  !

'TS-23-102C  ! FEmiAL  ! 01-170230-090 ! QUALIFIED  !  !

TS-23-102D  ! FEMiAL  ! 01-170230-090 ? QUALIFIED  !  !

TS-23-103A  ! FEMiAL  ! 01-170230-090 ! QUALIFIED  !  !

T3-23-1038  ! FENWAL '! 01-170230-090 ! QUALIFIED  !  !

.TS-23-103C  ! FENWAL  ! 01-170230-090 ! QUALIFIED  !  !

TS-23-103D  ! FEmiAL  ! 01-170230-090 ! QUALIFIED  !  !

TS-23-104A  ! FEMIAL  ! 01-170230-090 ! QUALIFIED  !  !

m 4 VERM0NT YANKEE NUCLEAR P0WER STATION PRODUCED 84/08/10.

ENVIR0 MENTAL QUALIFICATION OF ELECTRICAL EQUIPENT MASTER EQUIPMENT LIST PAGE 17

!  !  ! QUALIFICATION  ! DEFICIENCY /  !

IDIMEER  ! MANUFACTURER  !. MODEL NUPEER ~ ! STATUS  ! RESOLUTION !CONENTS HIOH PRESSURE C00LANT INJECTION S Y S T E li - (CONTDtJED)

TS-23-1048  ! FEleiAL  ! 01-170230-090 ? QUALIFIED  !  !

TS-23-104C  ! FElelAL  ! 01-170230-090 ! QUALIFIED  !  !

TS-23-104D. ! FEMIAL  ! 01-170230-090 t QUALIFIED  !  !

V-23-16  ! WESTINGHOUSE ! TYPE W  ! QUALIFIED  !  ! LOCAL STARTER SERVICE AND C00 LINO WATER SYSTEM

-LS-104-69A  ! ASCO !SC21BR/TA20A32R! QUALIFIED  !  !

LS-104-69B  ! ASCO !SC21BR/TA20A32R! QUALIFIED  !  !

MOV-70-19A  ! LIMITORQUE  ! SMB-1  ! QUALIFIED  !  !

MOV-70-19B  ! LIMITORQlE  ! SMB-1  ! QUALIFIED  !  ! ,

NOV-70-20  ! LIMITORQUE  ! SMS-1  ! QUALIFIED  !  !

P-59-1A  ! WESTINGHOUSE ! LIFELIE T  ! QUALIFIED  !  !

P-59-1B  ! ESTINGHOUSE  ! LIFELIE T

  • QUALIFIED  !  !

PS-104-57-1 ! AS G 0FT  ! 615-6480  ! QUALIFIED  !  ! CATE00RY D DS-104-57-2 ! ASHCROFT  ! 615-6480  ! QUALIFIED  !  ! CATEGORY D SE-70-4A  ! AGC0  ! WX8211C13  ! JCO-66  ! NO TEST DATA  ! (NOTE 3)

SE-7 H B  ! ASCO  ! W X8211C13 ' JCO-66  ! NO TEST DATA  ! (NOTE 3)

SE-70-40  ! ASCO  ! WX8211013  ! JCO-66  ! NO TEST DATA  ! (NOTE 3)

SE-70-4D  ! ASCO  ! W X8211C13  ! JCO-66  ! 10 TEST DATA  ! (NOTE 3s i

POST ACCIDENT SAMPLINO SYSTEM 71-r-1 ' ASCO  ! 206-380-2F  ! QUALIFIED 8 71-P-1  ! ASCO  ! 206-330-2F  ! QUALIFIED  !

71-S-1  ! ASCO  ! 206-380-2F  ! QUALIFIED  !  !

71-S-2  ! ASCO  ! 206-380-2F  ! Q@LIFIED  !  !

SERVICE AND INSTRUMENT AIR SYSTEM A0V-72-T.8A ! ASCO  ! 206-380-7F  ! QUALIFIED  !  ! CATE00RY D A0V-72-38B  ! ASCO  ! 206-380-7F  ! QUALIFIED  !  ! CATEGORY D CONDENSATE + DW TRANSFER SYSTEM

-107-12A(M)  ! ROSEMOUNT !510tAmCM014! QUALIFIED  !  ! l 107-12B(M)  ! ROSEMOUNT !510DU216026#n4! GLIFIED  !  ! l MISCELLANEOUS ELECTRICAL EQUIPMENT ELEC-3  ! LEWIS  ! SR/SR ' QUALIFIED  !  ! TERM 0 COUPLE CABLE ELEC-4  ! R0E  ! XLP/PVC  ! QUALIFIED  !  ! POWER CABLE ELEC-5  ! GEN ELECTRIC  ! NS02/NS03/NSO4! QUALIFIED  !  ! PEETRATION ELEC-6  ! R0E -  ! XLP/PVC  ! QUALIFIED  !  ! POER CABLE i

l l

VERM0NT YANKEE NUCLEAR P0WER STATI0N PROWCED 84/08/10.

ENVIRCNENTAL QUALIFICATION OF ELECTRICAL EQUIPtENT MASTER EQUIPMENT LIST PAGE 18

!  !  ! QUALIFICATION  ! DEFICIENCY /  !

ID NUMBER  ! MMUFACTURER ! MODEL NUMBER ! STATUS  ! RESOLUTION  ! COMMENTS MISCELLANEOUS ELECTRICAL EOU1PMENT (CONTINlED)

ELEC-7  ! BUCHANHN  ! 0222 ' QUALIFIED  !  ! TERMINAL ROCKS ELEC-8 ' ROME  ! XLP/PVC  ! QUALIFIED  !  ! POWER CABLE ELEC-9 ' KERITE  ! HTK/FR  ! QUALIFIED  !  ! POWER CABLE ELEC-10  ! APeiACONDA  ! UNISHIELD EP ! QUALIFIED  !  ! POWER CARE ELEC-11  ! ROME  ! XLP/PVC/PVC  ! QUALIFIED  !  ! CONTROL CABLE ELEC-12  ! ROME  ! XLP/PVC/PVC ! QUALIFIED  !  ! CONTROL CABLE ELEC-13 ' ROME  ! XLP/PVC/PVC  ! QUALIFIED  !  ! CONTROL CABLE ELEC-14  ! STATES  ! NT  ! QUALIFIED  ! ' TERMINAL BLOCK ELEC-15  ! STATES  ! NT  ! QUALIFIED  !  ! TERMINAL BLOCK ELEC-16  ! ROCKBESTOS  ! FIREWALL SR  ! QUALIFIED  !  ! CONTROL CABLE ELEC-17  ! ROCKBESTOS ' FIREWALL SR  ! QUALIFIED  !  ! CONTROL CABLE ELEC-18  ! GEN ELECTRIC ! VARIOUS  ! QUALIFIED  !  ! TERMINAL BLOCK ELEC-19  ! BlW  ! XLP/E0PENE  ! QUALIFIED  !  ! CONTROL CABLE ELEC-21  ! CINCH JOES  !  ! QUALIFIED  !  ! TERMINAL BLOCK ELEC-22  ! CERR0 ' FIREWALL EP  ! QUALIFIED  !  ! POWER CABLE ELEC-23 ' LEWIS  ! FE/PVC/SRD ! QUALIFIED  !  ! CONTROL CABLE ELEC-25  ! BUCHANAN  !  ! QUALIFirD  !  ! TERMINAL BLOCK ELEC-28  ! STATES  ! Ni  ! GUALIFIED  !  ! TEFJilNAL BLOCK ELEC-29 8 LEWIS  ! PE/PVC  ! QUALIFIED  !  ! T!ERM0COLFLE CARE ELEC-30  ! LEWIS  ! PE/PVC ' QURIFIED  !  ! TEFMCOURE CARE ELEC-31  ! ROCKDESTOS  ! FIREWALL III ! QUALIFIED  !  ! CONTROL CABLE ELEC-34  ! LEWIS  ! R0-95(H.T.)  ! JCO-39  ! NO DOC /Q m  ! 00-AXI#. CARE, FART CF LPRMS ELEC-35  ! GEN ELECTRIC ! 8 Jr0-39 ' N3 DOC /0DR  ! ELEC C0fth PART OF LPRtt3 ELEC-36  ! ENDcVC0  ! 3075M6  ! @ALIFIEC  !  ! CO-AXI(L CADLE ELEC-38  ! ROC /BES10S  ! FIREWa.L III ! QUALIFIED '

! SIS WIRE ElEC-40 ' ROCKBESTOS  ! FIRcWALL III ! QUiLIFIED  ! $ INSTRUMENT CARE ELEC-42  ! ROCKEESTOS ' FIREWALL III ! QUAllFIED  !  ! CO-AXIAL CABLE ELEC-43  ! RAYCHEM  ! VARIOUS  ! QUALIFIED  !  ! CABLE SPLICE KIT ELEC-44  ! ROCKBESTOS  ! FIREWALL III ! QUALIFIED  !  ! CD-AXIAL CABLE ELEC-45  ! LEWIS  ! RC-95  ! JC0-39  ! NO DOC /QDR  ! CO-AXIAL CABLE, PART OF LFfotS ELEC-46  ! OEN ELECTRIC ! 175A9132P008 ! QUALIFIED  !  ! FUSE HOLIER ELEC-47  ! CEN ELECTRIC  !  ! QUALIFIED  !  ! SIS WIRE ELEC-48  ! OEN ELECTRIC ! 167A2452P003 ! QUALIFIED  !  ! FUSE ELEC-49 8 ROCKBESTOS  ! FIREWALL Ill ! QUALIFIED  !  ! THERM 0 COUPLE CARE ELEC-50  !  ! 600V-PEPS  ! JC0-29 ' NO DOC /QM  ! SIONAL CABLE, PART OF CP.DM !ON ELEC-51  ! GEN ELECTRIC  ! 600V-VlLKEE ! JCO-29  ! NO DOC /QDR  ! SIONAL CABLE, PART OF CRDM MON ELEC-52  ! COLLYER  ! XLP ' QUALIFIED  !  ! POWER CABLE ELEC-53  ! WEIDMELLLER  ! SAK-6N  ! QUALIFIED ' ' TERMINAL BLOCK ELEC-54  ! ROCKBESTOS  ! FIREWLL III ! QUALIFIED '  ! CONTRCL CARE

4

.*i 'V E R M 0 N T .Y A'N K E E ' N U C L E A R P0WER STATION PRODUCED 84/08/10.

ENVIR010 ENTAL QUALIFICATION OF ELECTRICAL EQUIPENT MASTER EQUIPMENT LIST' PA0E 19

!  !  ! QUALIFICATION -! DEFICIENCY /  !

~ IDIUEER  ! MAltFACTlRER ! MODEL IU EER ! STATUS  ! RESOLUTION !C0lfENTS MISCELLANEOUS ELECTRICAL' EQUIPMENT (CONTINUED)

~ ELEC-55  ! 3M  !  ! QUALIFIED  !  ! TAPE SPLIE KIT ELEC-56  ! OEN ELECTRIC ! ETAL OXIDE ! QUALIFIED  ! ' CATECORY D

!  ! VARISTOR  !  !  !

ELEC-57  ! CONAX -! VARIOUS  ! QUALIFIED  !  ! CONDUIT SEAL ELEC-58  ! CONAX  ! VARIOUS  ! QUALIFIED  !  ! C0pBUIT SEAL e

3

.+-,,------m -.,-ww e ~ - *,-

v s w e - - , , , , , - w , -..w.-,-rv.--+. ,- y w- -.-e,,,i----ye,.-, ,

ENCLOSURE (1) NOTES VERMONT YANKEE ,

ENVIRONNENTAL QUALIFICATION MASTER EQUIPMENT LIST NOTES

1. The Master Equipment List consists only of electrical components located in a harsh environment for the design basis accident (s) in whichuit is relied upon to function (or not fail). These are Categories A, B, and D components listed in the EQ Matrix Report.
2. Components designated as " Category D" in the comment column are those components that function prior to the onset of a harsh environment and whose subsequent failure will not adversely affect any safety functions.

The technical basis for components in this category is provided in the

" Vermont Yankee Electrical Component Matrix Report".

3. Schedular Relief was approved by the NRC by letter dated August 2, 1984 (NVY 84-179).
4. Schedular Relief was appecved by the NRC by letter dated August 2, 1984 (NVY 84-179). The basis for schedular relief is the NRC's pending review and approval of the Vermont Yankee Primary Containment Leak Rate Testing Program (10CFR50, Appendix J Program). This program was submitted to the NRC by letter dated June 26, 1984, Proposed Change No. 121 to Facility Operating License No. DPR-28.

~ -

[.

e, * .* . _ -

'Enclecure (2) l1 l

VERMONT YANKEE NUCLE _AR POWER CORPORATION LIST OF CHANGES TO THE ENVIRONMENTAL QUALIFICATION MASTER EQUIPMENT LIST AND BASIS FOR CHANGE August 10, 1984 t

i 1

J 6

9 9

?. "' ' ADDITIONS TO THE MASTER EQUIPMENT LIST p

COMPONENT COMPONENT

-ID NO. TYPE 1 SERVICE REASON FOR ADDITION I

ELEC-56 . Surge Control Rod See Note 1. '

Suppression Drive Scram Diode Solenoids -

Associated Components LD-19-60A Level Detector Fuel Pool Level New design change to LD-19-60B provide qualified redundant Fuel Pool level indications.

LS-104-69A Pressure Switch RBCCW Surge Tank- New design change to LS-104-69B level provide qualified redundant RBCCW surge

, tank level indications.

1 TS-12-101A Temperature Reactor Water New design change to TS-12-101B Switch Clean-Up enhance line break TS-12-102A System Line detection capability.

TS-12-102B Break Sensor TS-12-103A TS-12-103B TS-12-106A TS-12-106B TS-12-107A -

TS-12-107B TS-12-108A TS-12-108B TS-12-109A TS-12-109B TS-12-110A TS-12-110B TS-12-111A ,

TS-12-111B l TS-12-112A l TS-12-112B l LT-2-3-73A Level Transmitter Reactor Vessel Design Change LT-2-3-73B Level Transmitter Water Level - to replace LITS-2-3-73A j LT-2-3-73A(M) Haster Trip Unit ECCS Permissive & B. 1 LT-2-3-73B(M) Master Trip Unit LT-2-3-73A(I) Auxiliary Relay LT-2-3-73B(I) Auxiliary Relay 1

. - ,_ . . . . - ~ . , , - - . . _ - ,_--- - ... .- . - - - - . - - . - - _ . - - . - - . . - - - - . - - - . . - - _ . -

e, * *. O ADDITIONS (continued) i COMPONENT COMPONENT ID 50. TYPE SERVICE REASON FOR ADDITION PT-2-3-52C Pressure Trans. Reactor Design Change PT-2-3-52D Pressure Trans. Pressure - to replace PT-2-3-52C(M) Master Trip Unit ECCS Permissive PS-2-3-52C & D.

PT-2-3-52D(M) Master Trip Unit PT-2-3-52C(X) Auxiliary Relay PT-2-3-52D(X) Auxiliary Relay ELEC-52 Collyer 600V Fuel Pool Cooling New items found during Power Cable HPCI Valve' field verification ELEC-54 Rockbestos 600V Controls walkdowns.

Control Cable 4

ELEC-10 Annaconda Power RHR, Core Spray, Qualified cable Cable RHR SW Pump replacing an unqualified cable.

ELEC-53 Weidmeuller Fuel Pool Cooling Design Change Terininal Block ELEC-55 3M Tape Splice Motor Termination Assures qualification of raotor termination ELEC-57 Conax seal MSIV Li.ait Design Change Switches ELEC-56 Conax ?oal MSIV Limit Design Change Switches i

l f

. , - . - . . . ~ . - _ _ . _ . --. - - , _ .- -- --.

l c; ??. 4 DELETIONS TO THE MASTER EQUIPMENT LIST l

COMPONENT COMPONENT' )

ID 50. TYPE SERVICE REASON FOR DELETION l NOV-2-66A Notor-Operated Reactor See Note 2.

NOV-2-66B Valve Recirculation System SN-3-140A Solenold-Operated Back-up Scram See Note 3.

SM-3-140B Valve Solenoid Valves A-ECCS-BC Battery Charger 24 Volt Relocated to a mild B-ECCS-BC Instrumentation environment.

System Local Indicating -- Fuel Pool Removed from Lights cooling System associated circuit.

LSH-19-60 Level Switch Fuel Pool Level Design Change (Replaced LSL-19-60 by LD-19-60A & B).

PS-2-3-52C Pressure Switch Reactor Pressure Design Change PS-2-3-52D ECCS Permissive (Replaced by PT-2-3-52C

& D).

LITS-2-3-73A Level Indicating Peacter Vessel Replaced by LT-2-3-73A LIIS-2-3-73B Transmitter Switch Water Level - & B.

ECCS Permissive ELEC-39 Okontte Pcwer RHR, Core Spray, Quallfled but replaced Cable RHR SW Pump during design change in accordance with an engineering improvement (Replaced by ELEC-10).

i l

l ELEC-10 Collyer RHR, Core Spray, Unqualified cable Power Cable RHR SW Pump replaced.

l j

1; . s I

ENCLOSURE (2) NOTRS l l

1.. These components were identified during our field verification walkdowns )

of the scram solenoid valves circuits. 1 Failure of these components due to a High Energy Line Break.(HELB) environment could result in de-energizing the scram solenoids and thereby

? cause a reactor scram.

Although a reactor scram is a " fail-safe condition", an inadvertent scram due to non-environmentally qualified components following a Reactor Water Clean-Up System HELB before the line break isolation valves are fully closed could impact our design basis assumptions. The environment postulated following an NWCU HELB is based upon normal closing times for  ;

the isolation valves. If we take the RWCU outboard DC isolation valve as ,

the single failure, and assume that a loss of offsite power occurs (due l to the inadvertant reactor scram) prior to the RWCU inboard AC isolation l valve closure, then our postulated design basis environment could be non-conservative since it will take the AC isolation valve an additional l 13 seconds to close due to the emergency diesel start-up time. Although the failure of these components could result in de-energizing the scram solenoids, we have determined that these components operate in a mild environment for the first 25 seconds following an RWCU HELB, thereby eliminating this concern. l

2. NOV-2-66A & B are Reactor Recirculation System cross-tie bypass valves.

These valves are aligned such that one valve is normally open and one is normally closed. Both valves automatically close on an accident signal.

The motors were originally intended to be replaced with environmentally qualified motors but installation was not possible due to physical interference. The motor leads to the normally closed bypass valve have been disconnected to prevent any single f ailure from opening this valve.

This changs eliminated the need to environmentally qualify these valves.

3. The back-up scram solenoid valvos are not specifically required for any safety function. The intended function is to back up the Hydraulic Control Unit's (FCU) scram solencid valves. Since the plant design .

accounts for one stuck rod; the back-up scram solencida are not depended upon even for a single failure of an HCU scram solenoid.

I l

i l I

,