ML20094D912

From kanterella
Jump to navigation Jump to search
Fifth Interim Deficiency Rept Re Environ Qualification of safety-related Electrical Components.Initially Reported on 811021.Caused by Util Failure to Develop Procedural Controls on Qualification Program.Next Rept Expected by 850621
ML20094D912
Person / Time
Site: Bellefonte  
Issue date: 07/20/1984
From: Mills L
TENNESSEE VALLEY AUTHORITY
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
IEB-79-01B, IEB-79-1B, NUDOCS 8408090033
Download: ML20094D912 (21)


Text

I TENNESSEE VALLEY AUTHORITY CH ATTANOOGA. TENNESSEE 374o1 400 Chestnut Street Tower II nn.

i, IJuly"20,'.198 4 BLRD-50-438/81-66 BLRD-50-439/81-65 U.S. Nuclear Regulatory Commission Region II Attn:

Mr. James P. O'Reilly, Regional Administrator 101 Marietta Street, NW, Suite 2900 Atlanta, Georgia 30323

Dear Mr. O'Reilly:

BELLEFONTE NUCLEAR PLANT UNITS 1 AND 2 - ENVIRONMENTAL QUALIFICATION OF SAFETY-RELATED ELECTRICAL COMPONENTS - BLRD-50-438/81-66, BLRD-50-439/81 FIFTH INTERIM REPORT The subject deficiency was initially reported to NRC-0IE Inspector R. V. Celenjak on October 21, 1981 in accordance with 10 CFR 50.55(e) as NCRs BLN NEB 8113 through BLN NEB 8118. This was followed by our first interim report dated November 16, 1981. Related NCRs BLN NEB 8119 R2, and 8205 and BLN NEB 8203 R2 were reported in our second interim report dated May 10, 1982; NCRs BLN NEB 8208, 8209, 8211, 8213, 8214, and 8215, and GEN QAB 8204 were reported in our third interim report dated August 16,1982; and related NCRs BLN NEB 8217 and 8218 and BLN EEB 8203 R2, 8303, 8304, 8310 8311, 8312 8313, 8314, and 8315 were reported in our fourth interim report dated August 3,1983 Since that time, related NCRs BLN NEB 8221, BLN NEB 8302, BLN EEB 8402, BLN EEB 8405, BLN EEB 8413, BLN BLP 8328, and BLN MEB 8302 R1 'have also been reported. Enclosed is our fifth interim report. We expect to submit our next report by June 21, 1985.

If you have any questions, please get in touch with R. H. Shell at FTS 858-2688.

Very truly yours, TENNESSEE VALLEY AUTHORITY DS W L. M. Mills, Manager Nuclear Licensing Enclosure cc:

Mr. Richard C. DeYoung, Director (Enclosure)

Office of Inspection and Enforcement U.S. Nuclear Regulatory Commission Washington, D.C.

20555 cc: Continued on page 2 (WFICIAL M}

8408090033 g40720 0500043s

~3 8 d

PDR ADOCK

/

l S

  1. ~"~

PDR jl

-m l-

,.. U.S. Nuclear Regulatory Commission July 20, 1984 H. B. Barkley, Manager (Enclosure) 205 Plant Project Services P.O. Box 1260 Lynchburg, Virginia 24505 Records Center (Enclosure)-

Institute of Nuclear Power Operations 1100 circle 75 Parkway, Suite 1500 Atlanta, Georgia 30339 l

4 i

r 4

f l

-,.,, ~.. _,

,i ENCLOSURE BELLEFON'E NUCLEAR PLANT UNITS 1 AND 2 ENVIRONMENTAL QUALIFICATION OF SAFETY-RELATED ELECTRICAL COMPONENTS.

NCRs BLN NEB 8113, 8114, 8115, 8116, 8117R2, 8118, 8119 R2, 8205R1, 8208R1, 8209R1, 8211R2, 8213R2, 8214R1, 8215R1, 8217R2, 8218R1, 8221, BLN EEB 8203 R2, 8303R1, 8304R1, 8305R1, 8306R1, 8308R1, 8309, 8310, 8311R1 8312, 8313R1, 8314R1, 8315R1, 8402, 8405, 84134 BLN BLP 8328, BLN MEB 8302R1 AND GEN QAB 8204 BLRD-50-438/81-66, BLRD-50-439/81-65 10 CFR 50.55(e)

FOURTH INTERIM REPORT Description of Deficiency During TVA's NUREG-0588 environmental qualification program, the components listed in Table I - Parts A and B (attached) were identified as potentially deficient because of insufficient documentation to verify that the equipment is environmentally qualified. This equipment was procured before the issuance of NUREG-0588.

Interim Progress Since TVA's fourth interim report seven additional nonconformance reports have been issued to identify potentially unqualified equipment. Information on these NCRs is included in Table 1 along with the status of other previously reported NCRs.

Corrective actions for NCR GEN QAB 8204, which was issued to identify TVA's failure to develop procedural controls on a qualification program after the issuance of NUREG-0588 and IE Bulletin 79-01B, have been completed. These actions include the issuance of computer gmerated environmental drawings and revisicns of the Division of Engineering Design (EN DES) Engineering Procedure (EP) 3 01, " Design Criteria Documents - Preparation, Review, and Approval," and applicable design criteria to reference these drawings (in the case of EP 3.01 additional references were included to provide for the proper usage of the environmental data during the accomplishment of procurement activities per EP 5.01, " Purchase Requisitions.

. ).

I

TABLE 1 TVA B&W NCR UNID No.

Comp. No, Model Manu facturer Corrective Action / Resolution BLNNEB8113 NL-1UT-001B-B CF-LT3A2 N2BQ75221X Bailey Meter Co.

- TVA has received additional docu-

-001A-A CF-LT3A1 mentation which verifies that this

-002A-A CF-UT381 equipment is qualified.. As such,

-002B-B CF-LT3BW j

no actual deficiency existed and l

10CFR50.55(e) no longer applies to this item.

BLNNEB8114 NC-IPT-004B-A RC-PT-17-3 1152GP9A92PB Rosemount, Inc.

This NCR has been closed since the 1

(Pressure

-004A-B hC-PT-17-4 Transmitter) two pressure transmitters are also identified in NCR bLNNEB 8119R2. TVA will discontinue reporting on this equipment under NCR BLNNEB8114 BLNNEB8115 CF-IUT-916B-B SP-Ur9A2 N1Q74221 Bailey Meter Co.

TVA has determined that this (Differential

-916A-A SP-Ur9A3 equipment'is qualified for its Pressure

-925A-A SP-Ur9B3

]

Transmitters)

-929B-B SP-LT982 intended use and that 10CFR50.55(e) no longer applies.

BLNNEB8116 NL-IPT-001A-A CF-PT4A1 N2KS68221 Bailey Meter Co.

This NCR has been closed since (Differential

-001B-B CF-PT4A2 this equipment is idestified in Pressure

-002A-A CF-PT4B1 BLNNEB8119R2. TVA will discon-Transmitter)

-002B-B CF-PT4B2 tinue reporting on this equipment under NCR BLNNEB8116.

l-BLNNEB8117 NC-ITE-900A-A RC-TE3A1 177 HW Rosemount, Inc.

Actual test data qualified this R2

-902A-D RC-TE3A2 equipment to 3500F. The' current (Resistance

-900B-A RC-TE3A3 main steam line break (MSLB)

]

Temperature

-901A-F RC-TE3A4 temperature has a peak temperature Detec tor)

-919B-B RC-TE3B1 of 3700F which decays to below

-917A-E RC-TE3B2 3500F in slightly over two

-919A-B RC-TE3B3 minutes. TVA has completed a 3

-918A-G RC-TE3B4

" thermal lag" analysis which shows

-911B-B RC-TE4A3 i

that the actual temperature of the i

I i

m

b TABLE 1 TVA B&W NCR UNID No.

Comp. No.

Model Manufacturer Corrective Action / Resolution BLNNEB8117R2

-911A-B RC-TE4A4 temperature-sensitive material in (Continued)

-908A-D RC-TE4A5 the components is raised to only '

-926A-F RC-TE4A7 approximately 2960F during this

-910A-E RC-TE4A9 transient period. NUREG-0588,

-912A-G RC-TE4A11 category II requirement allows the

-924B-A RC-TE4B3 use or analysis with partial type

-924A-A RC-TE4B4 test data "b3 qualify equipment.

-922A-D RC-TE4B5 Based on this, TVA has determined

-920A-F RC-TE4B7 that these components are

-925 A-E RC-TE4B9 qualified and, as such,

-923A-G RC-TE4B11 10CFR50.55(e) no longer applies to

-901B-F RC-TE3A6 this item.

-902B-D RC-TE3A5

-917B-E RC-TE3B5

-918B-G RC-TE386

-908B-D RC-TE4A6 1774W Rosemount, Inc.

-910B-E RC-TE4A10

-912B-G RC-TE4A12

-920 B-F RC-TE4B8

-922B-D RC-TE4B6

-923B-G RC-TE4B12

-925B-E RC-TE4B10

-926B-F RC-TE4A8

-909A-N RC-TE4A1

-9093-N RC-TE4A2

-921A-N RC-TE4B1

-921B-N RC-TE4B2

{

BLNNEB8118 N C-IFT-907 E-D RC-FT1 A1 N1BQ86221 Bailey Meter Co.

TVA has determined that these (Differential

-907F-F RC-FT1A2 differential pressure trans-Pre ssure

-907A-E RC-FT1 A3 mitters are not necessary for Transmitter)

-907B-G RC-FT1 A4 the mitigation of design basis

-913E-D RC-FT1B1 accidents and that they meet i

TABLE 1 TVA B&W NCR UNID No.

Comp. No.

Model Manufacturer Corrective Action / Resolution BLNNEB8118

-913F-F RC-FT1B2 the requirements of NUREG-0588, (Continued)

-9134-E RC-FT1B3 Appendix E, category C.

As such,

-913B-G RC-FT1B4 10CF50.55(e) no longer applies.

(Pre ssure NC-IPT-903D RC-PT2A1 N1KS69221 Bailey Meter Co.

Becatise thase pressure trans-Transmitter)

-904F RC-PT2A2 mitters are currently identified

-906 D RC-PT2A3 in NCR BLNNEB8119R2, TVA will

-905F RC-PT2A4 discontinue reporting on this

-914 G RC-PT2B1 equipment under NCR BLNNEB8118.

-915E RC-PT2B2

-916G RC-PT2B3 BLNNEB8119 NC-IFT-906-D RC-PT2A3 N1KS69221 Bailey Meter Co.

TVA is the process of relocating R2

-905-F RC-PT2A4 this equiment to a less harsh

-916-G RC-PT2B3 environment per engineering change

-903-D RC-PT2A1 notice (ECN) 3022.

-904-F RC-PT2A2

-914-G RC-PT2B1

-915-E RC-PT2B2

-004A-B RC-PT17-4 1152GP Rosemount

-004B-A RC-PT17-3

-0040-B RC-PT17-1 N3KS69221 Bailey Meter Co.

-004 D-B RC-PT17-2 NL-IPT-001A-A CF-PT4A1 N2KS68221 Bailey Meter Co.

-001B-B CF-PT4A2

-002A-A CF-PT4B1

-002B-B CF-PT4B2 KD-ILT-003A-A Not Available Not available Bailey Meter Co.

TVA has determined that this

-0038-B at this time at this time equipment will be in a mild NV-ILT-004 A-A environment upon completion of 1NB-ILT-027-A ECN 1579 which concerns 2NB-ILT-026-A relocating the startup and TABLE 1 TVA B&W NCR UNID No.

Comp. No.

Model Manufacturer Corrective Action / Resolution BLNNEB8119R2 KE-IFT-962B-A meirculation system.

(Continued)

-965B-B

-968B-B KC-ILT-004-A

-005-B

-006-A

-007-B NV-IPT-004-A

-IFT-841-A

-842-B

-848-A

-849-B

-844-A

-845-A

-846-B

-847-B NS-ILT-003A-A

-003B-B

-IFT-900-A

-901-B ND-IFT-902-B

-907-A CF-ILT-916A-A This equipment was listed in the

-916B-B original NCR to document a

-925A-A potential radiation qualification

-925B-B deficiency. However, TVA has NC-ILT-004 A-D determined that no such deficiency

-004B-E exists, and 10CFR50.55(e) no

-0040-F longer applies to these. items.

-004 D-G 4

-004E-A

-004F-B

-951-B l 4

2%

IABLE 1

~ ~.

TVA B&W NCR UNID No.

Comp. No.

Model Manufact'arer Corrective Action / Resolution BLNNEB8119R2

-952-B (Continuu-)

-953-A

-954-B

-001A-A

-001B-B

-002A-A

-002B-B NS-IPT-904-D

-905-F

-906-G NC-IFT-907 A-E N1BQ86221 Bailey Meter Co.

TVA has determined that this

-907B-G equipment is not required for: the

-907 E-D mitigation of a design basis

-907F-F accident and that they meet the

-913A-E requirements of NUREG-0588,

-913B-G Appendix E, Category C.

As such,

-913E-D 10CFR50.55(e) no longer applies.

-913F-F SM-IPT-901A-B

-9018-A

-902A-B

-902B-A SM-IPT-903D This equipment was originally

-904G reported on under NCR BLNNEB8119,-

-905F but because they are also

-910D identified in NCR BLNNEB8214, TVA

-9110 is deleting these items from 8119

-912F and will report on them under 8214.

TABLE 1 TVA B&W NCR UNID No.

Comp. No.

Model Manufacturer Corrective Action / Resolution BLNNEB8119R2 NC-IEB-004 A-A TVA will delete this item. This (Continued) item was erroneously listed. No component with this UNID number exists.

BLNNEB8205R1 NS-EMOT-001-A N/A 500 HP Siemans-Allis This equipment has been qualified

-002-B by S-A test report NQ-8-90396-1, RO.

As such, 10CFR50.55(e) no longer applies to these motors.

ND-EMOT-001-A N/A 700 HP Westinghouse TVA is still seeking vendor

-002-B confirmation of the qualification NV-EMOT-001-A 900 HP on these motors.

-002-A

-003-B KC-EMOT-001-A N/A This equipment will be in a mild

-002-B environment what the startup and

-003-A recirculation system is moved in accordance with ECN 1579.

ND-EMOT-216-A N/A TVA has determined that this

-221-B equipment is not required for the NV-EMOT-838-B mitigation of design basis

-856-A accidets and meets the

-858-A requimments of NUREG-0588,

-860-A Appendix E, Category C.

As such, 10CFR50.55(e) no longer applies to these motors.

BLNNEB8208R1 VJ-EMOT-034-B N/A 150/75 HP Reliance TVA has determined that this

-035-A equipment is environmentally

-03C-B qualified and 10CFR50.55(e) no longer applies to these motors.

'b TABLE 9 TVA B&W g

UNID No.

Comp. No.

Model Manufacturer Corrective Action / Resolution BLNNEB8209R2 ND-IFCV-192-B DH-HV-9B SB-005-15 Limitorque This equipment will be in a mild NV-IFCV-077-A MU-HV-49A SB-00-25 environment for which it is

-419-B

-47B qualified upon completion of ECN

-450-A

-47A Unknown 1579. This ECN deals with the relocation of the startup and moirculation system.

KC-IFCV-147-A CC-HV-22 SMB-00-5 Limitorque TVA has determined that this

-212-A CC-HV2 equipment is environmentally ND-IFCV-010-A DH-HV-7A SMS-005-15 qualified and that 10CFR50.55(e)

-104-B

-7B no longer applies to these valve NV-IFCV-101-A HU-HV-51A SMB-00-7.5 operators.

-113-A

-51B

-213-B

-51C

-225-B

-51D

-411-B

-49B SMB-00-25 KD-IFCV-045-B Because these two operators are i

KD-IFCV-054-A not NSSS supplied they have been deleted from NCR BLNNEB8209R2.

They am now identified under NCR BLNMEB8302R1.

BLNNEB8211R2 CA-IZS-052A-B None EA170-100 Namco Upon completion of the relocation

-052B-B of the startup and meirculation

-053A-A system (ECN 1579) this equipment

-053B-A will be in a mild environment.

WL-IZS-067A-A

-067B-A NV-IZS-119A-A Namco TVA has determined that this 119B-A equipment is not required to l

l i

i TABLE 1 TVA B&W NCR UNID No.

Comp. No.

Model Manufacturer Corrective Action / Resolution BLNNEB8211R2 CA-IZS-062A-B mitigate a'ny design basis (Continued)

-062B-B accidet and meets the

-063A-A requirements of NUREG-0588,

-063B-A Appendix E, Category C.

As such, ND-IZS-064A-A 10CFR50,.55(e) no longer applies

-064B-A to these zone switches.

-158A-B

-158B-B

-04 0A-A

-04 0B-B

-134A-B

-134B-B KC-IZS-230A-A

-230B-A

-235A-B WL-IZS-091A-A

-091B-A

-121 B-A NF-IZS-036A-A

-036B-A NL-IZS-076-A This zone switch is not a safety-related switch and has been downgraded frca its class 1E status. 10CFR50.55(e) no longer applies to this switch.

BLNNEB8213R1 NC-IFCV-010-A RC-HV2 SMB-00-10 Limitorque TVA has determined that this

-062-B CF-HVSA equipment, which is located inside

-064-A CF-HV5B containment, has sufficient NV-IFCV-062-B MU-HV37A SMB-00-5 documentation to verify its

-065-B

-HV37B operability in a postaccident

-068-B

-HV37C environment. However, an

-071-3

-HV37D interface problem with the Solid State Control System (SSCS)

TABLE 1 TVA B&W NCR UNID No.

Comp. No.

Model Manufacturer Corrective Action / Resolution BLNNEB8213R1

-022-B MU-HV1C SMB-00-10 (Continued)

-026-B

-HV2A must be evaluated to determine if

-029-B

-HV1D these actuators are affected. TVA

-033-B

-HV2B will discontinue reporting under -

KC-IFCV-148-B CC-HV24 SMB-000-05 this NCR and will provide

-211-B CC-HV1 information on the interface problem under NCR BLNBLP8328.

KC-IFCV-053-B Limitorque TVA has determined that this' NC-IFCV-057-A equipment is not part of the NSSS NL-IFCV-076-A package and to facilitate NL-IFCV-079-B disposition, this equipment is now WL-IFCV-068-B identified in NCR BLNhEB8302R1.

WL-IFCV-090-B TVA will report on this equip:nent WG-IFCV-011-B under that NCR number.

NC-IFCV-012-A TVA has been notified by B&W that this valve operator is no longer incorporated in the plant design, and will not be installed.

BLNNEB8214R1 fKC-IFT-006A CC-FT21A N2BQ74221' Bailey Meter Co.

This equipment will be in a mild KE-IFT-962B-A RBC-FT1A2 environment upon relocation of the

.NV-ILT-004A-A MU-LT 16-2 startup and recirculation system.

x I' KD-ILT-003A-A CC-LT 11-1 N2BQ73221 NV-IFT-844A.

MU-FT30A N2BQ85221 c

-845A MU-FT30B

-846B MU-FT30C.

-847B MU-JT30D.

NS-ILT.-003B-B RSS-LT11-2 N2BQ75221 0 NV-IFT-841A MU-FT50A N2BQ36221

-8:;8A MU-FT50C

~

-IPT-004A MU-PT21 TABLE 1 i

TVA B&W

^

NCR UNID No.

Comp. No.

Model Manufacturer Corrective' Action / Resolution

-BLNNEB8214R1 SM-IPT-901A-B SP-PT12A1 N2KS69221 Bailey Meter Co.

TVA has determined that this (Continued)

-901B-A 2

equipment is not necessary for the

-902A-B B1 mitigation of any design basis

-902B-A 2

accident and meets the requirements of NUREG-0588, Appendix E, Category C.

As such, 10CFR50.55(e) no longer applies.

+

SM-IPT-903-D SP-PT12A3 N2KS69221 Bailey Meter Co.

TVA has initiated ECN 1603 to

-904-G 4

relocate this equipment to a

-905-F 5

milder environment.

-910-D B3 1

-911-G 4

1

-912-F 5

BLNNEB8215R1 IP-IXE-005-D NI-5-NT WL-24 061 Westinghouse TVA has determined that this (Neutron

-006-E NI-6-NT equipment is not necessary for the 2

Detec tors)

-007-F NI-7-NT mitigation of any design basis

-008-G NI-8-NT accident and meets tha raquirements of NUREG-0588, Appendix Category C.

As such, 10CFR50.55(e) no longer applies to these detectors.

BLNNEB8217R2 CA-ILM-052B-B SP-FY19B 546 Fisher TVA has determined that this i

(Elec tromatic

-053B-A SP-FY19A equipment will be in a mild Transducers)

-062B-B SP-FY18A environment upon relocaton of the KC-IPM-230-A CC-FY28A startup and recirculation system.

4

-235-B CC-FY28B ND-IFM-04 0B-A AH-FY14A

-064B-A AH-FY3A

-134B-B AH-FY14B

-158B-B AH-FY3B

NEB - July 19, 1984

b TABLE 1 TVA B&W NCR UNID No.

Comp. No.

Model Manufacturer Corrective Action / Resolution BLNNEB8217R2 NV-IFM-143B-A MV-FY30A2 (Continued)

-155B-A MV-FY30B2

-167B-B MV-FY30C2

-179B-B MV-FY30D2 CA-ILM-063B-A 546 Fisher TVA has determined that this NV-IFM-050B-A equipment is not necessary for the SM-IPM-039-B mitigation of any design basis.

-052-A accident and this equipment meets the requirements of NUREG-0588, Appendix E, Category C.

As such, 10CFR50.55(e) no longer applies.

BLNNEB8218R1 NS-EMOT-001-A NA Siemen-Allis

-002-B ND-EMOT-216A SK143FL1';35 General Electric TVA has determined that these

-221B motors are already idattified NV-EMOT-838-B in NCR BLNNEB8205R1 and will

-858-A discontinue reporting on the 1

-860-B motors under this NCR.

KC-EMOT-001-A NA Allis-Chalmers

-003-A BLNNEB8221 NV-IFCV-065-B MU-HV379 SMB-000 Limitorque TVA has determined that this

-071-B equipment is not qualified for

-068-B submergence and has issued ECN 2863 to move these valves above the maximum LOCA flood level.

BLNEEB8203R2 IX-ILPR-001-D NA Type EF York Electro-TVA has determined that for this J

-002-A Flexible Panel Control type conduit the threshold of

-003-F Conduit failure is 5.5 x 105 rads TID,

-004-E-ard has identified the fact that

m TABLE 1 TVA B&W NCR UNID No.

_ Comp. No.

Model Manufacturer Corrective Action / Resolution BLNEEB8203R2

-005-B (Continued)

-006-0 the threshold of failure would be exceeded only during a LOCA, and only affect conduit. sections.

inside containment. These sections will be replaced by qualified stainless steel conduit per ECN 1596.

BLNEEB8303R1 ND-ILE-908C-A NA XM36495 Delaval TVA is the process of replacing (Level

-908D-A these devices.

Sensors)

-908E-A

-909A-B

-909B-B

-9090-B

-909D-B

-909E-B

-908A-A

-908B-A BLNEEB8304R1 WE-ILE-965-A NA XM36495 Delaval (Level

-967-B TVA is in the process of replacing Sensors) these devices.

(Level WE-ILT-965-A 36400 series Transmitters)

-967-B TVA is in the process of replacing i

these devices.

BLNEEB8305R1 VB-IFS-001-A NA LT-80 Fluid Components, TVA has determined that this and

-002-B Inc.

BLNEEB8306R1

-009-A equipment is not necessary for the 2

(Level

-010-B mitigation of any design basis Transmitters) accident and that they meet the and requirements of NUREG-0588, Appendix E, Category C.

As such, (Differential VB-IDT-001-A NA Veltron Air Monitor 10CFR50.55(e) no longer applies Pressure

-002-B Series to this equipment.

Transmitters) 2000 I

TABLE 1 TVA B&W NCR UNID No.

Comp. No.

Model Manufacturer Corrective Action / Resolution BLNEEB8308R1 CF-IFSV-068-A NA V70900-36 Valcor TVA is in the process of deter-(Solenoid

-070-A Valves)

Engineering mining the corrective action Corporation needed for this equipment (corrective action is depedent (Limit CF-IZS-068A-A' NA EA740 Namco Switches)

-068B-A on resolution of NCR BLNEEB8307

-070A-A which is being separately repor ted ).

-073B-A

~

BLNEEB8309 VA-IDH-008B-A 445-B1 Robertshaw The postulated accident dose this (I/P

-009B-A Transducers)

-014B-A equipment is expected to see is

-015B-A currently 2.5 x 103 rads and

-028B-B TVA is myiewing equipment

-129B-B qualification documentation

-130B-B to determine the suitability of

-131B-B this equipment.

BLNEEB8310 VX-IDH-011-A 445-B1 Robertshaw 1

(I/P

-012-B These transducers are located Transducers) inside the reactor building where the maximum gamma radiation ' dose is expected to be 3.6 x 103 rads, and the beta do expected to be 3 x 10ge is rads.

TVA is determining if the equipment will be qualified to this dose or if it will have to be relocated.

BLNEEB8311R1 CF-IFSV-069A-A NA WJHVA-206-Automatic TVA is in the process of deter-3 (Solenoid

-069B-B 380-5F-M0 Switch Co.

mining the corrective actions Valves)

-071A-A

-071B-A required to msolve BLNEEB8311 and 8312 (these actions am i

,3-

?

TABLE 1 TVA B&W NCR UNID No.

Como. No.

Model Manufacturer Corrective Action / Resolution-

~

-BLNEEB8311R1 KE-IFSV-100-B dependent on the resolution of (Continued)

-107-B NCR BLNBLP8324 which is being

~195-A separately mported).

-202-A (Limit CF-IZS-069E-A EA-740 Namco Switches)

-071E-A

-069A-A

-0698-A

-071B-A

-071E-A BLNEEB8312 RI-IFSV-361-A WJHVA-206-Automatic (Solenoid

-369-B 380-5F-M0 Switch Co.

Valves)

(Limit

-IZS-361A-A EA-740-20100 Namco Switches)

-361B-A

-369A-B

-369B-B BLNEEB8313R1 CF-EJBS-1-B NA Not Available Not Available TVA has issued ECN 2868 to replace (Devices SM-EJBX-1-A or eliminate the terminal blocks that have A classified as NUREG-0588, Appendix i

TVA Terminal B E, Category B devices.

1 Blocks) B B A B A CF-EJBX-2-B CF-EJB-2-A i l i

l

TABLE 1 TVA B&W NCR UNID No.

Comp. No.

Model Manufacturer Corrective Action / Resolution BLNEEB8314R1 CF-IHS-081B-B NA Not Available Not Available TVA has issued ECN 1868 to replace (Handswitches)

-080B-B or eliminate the handswitches classified as NUREG-0588, Appendix E, Category B devices.

BLNEEB8315R1 GS-IFSV-162-A NA 77D-006 Target Rock TVA has determined that these (Solenoid IR-IFSV-110-B Valves)

IR-IFSV-13C-A valves are qualified for their IR-IFSV-147-B environment and that IR-IFSV-14 8-B 10CFR50.55(e) no longer applies.

IR-IFSV-157-A IR-IFSV-500-A IR-IFSV-501-A IR-IFSV-502-B IR-IFSV-503-B NC-IFSV-015-A NC-IFSV-058-B 82F-001 NC-IFSV-960A-A 77BD-039 NC-IFSV-960B-A NC-IFSV-961A-A NC-IFSV-961B-A NC-IFSV-962A-B TVA has determined that these NC-IFSV-962B-B devices are qualified for their NC-IFSV-963A-A environment and that 10CFR50.55(e)

NC-IFSV-963B-A no longer applies.

NC-IFSV-964B-B NC-IFSV-964 A-B NC-IFSV-965A-B NC-IFSV-965B-B NC-IFSV-966A-A NC-IFSV-966B-A NC-IFSV-967A-B NC-IFSV-967B-B NC-IFSV-968A-A 1

_. _ _ _ _ _ _ _ _ _ _ - - - - - - - - - - - - - - ~

b TABLE 1 TVA B&W NCR

_UNID No.

_ Comp. No.

Model Manufacturer Corrective Action / Resolution BLNEEB8315R1 NC-IFSV-968B-A (Continued)

NC-IFSV-969 A-B NC-IFSV-969B-B NC-IFSV-970A-A NC-IFSV-970B-A NC-IFSV-971A-B NC-IFSV-971B-B NK-IFSV-126-A 77DD-038 Target Rock NK-IFSV-127-B NK-IFSV-129-A NK-IFSV-130-B NK-IFSV-131-G NK-IFSV-132-A i,

NK-IFSV-133-B NK-IFSV-135-A

)

NK-IFSV-136-B NK-IFSV-137-F 77DD-039 NL-IFSV-904A-A NL-IFSV-904B-A NL-IFSV-905A-B i

NL-IFSV-905B-B NL-IFSV-906A-A NL-IFSV-906 B-A NL-IFSV-907A-B NL-IFSV-907B-B 77DD-035 NO-IFSV-010-A NO-IFSV-011-B 77DD-039 NS-IFSV-902-A i

NS-IFSV-903-B NS-IFSV-904-A NS-IFSV-905-F NS-IFSV-906-B NV-IFSV-586 VH-IFSV-901-A TABLE 1 9

TVA B&W

~~

NCR UNID No.

Comp. No.

Model Manufacturer Corrective Action / Resolution BLNEEB8315R1 VH-IFSV-902-B (Continued)

YQ-IFSV-520-B Unknown YQ-IFSV-530-B BLNEEB8402 SA-IFT-901A-A NA E13DM Foxboro These transmitters are located in (Flow

-901B-B the auxiliary building, zone 46A, Transmitters)

-914A-A and are not qualified to the

-914 B-B postulated maximum accident temperature of 2480F. TVA is in the process of replacing these transmitters.

BLNEEB8405 Unknown at NA Unknown Unknown TVA has determined that electrical this time cables in the east steam valve vault do not have documentation which verifies their qualificatien to meet the current high energy line break (HELB) environment.

TVA'is currently determining the corrective actions necessary to resolve this deficiency.

BLNEEB8413 VA-ECMS-305-F NA P21 Gould Because these starters lack (Magnetic VA-ECMS-312-G qualification documentation, TVA Starters) is proceeding to relocate this equipment to a mild environment.

BLNMEB8302R1 KD-IFCV-045-B NA Limitorque TVA is in the process of

-053-B determining whether documentation

-054-A verifying environmental NC-IFCV-057-A qualification is obtainable.

NL-IFCV-076-A

-079-B WG-IFCV-011-B TABLE 1 TVA B&W Ng UNID No.

Comp. No.

Model Manufacturer Corrective Action / Resolution BLNMEB8302R1 WL-IFCV-068-B (Continued)

.-090-B BLNBLP8328 Unknown at i

Limitorque This NCR identifies an interface this time proble:n between the control leads of the Limitorque valve actuators inside containment and the resistance requirements of TVA's SSCS. The Limitorque test mport on qualification to a LOCA environment listed the varying resistance of its control leads with respect to time. At various tirees (from 4.2 hrs to 95.5 hrs into the test) the resistances of the majority of the control leads decreased from 400K ohms to 2K ohns. If the insulation value of the loads fall below 20K ohms, the SSCS could interpret this decrease I

as a closed contact even though the contact itself was still open.

TVA is investigating this matter to determine which actuators could be adversely affected and will I

provide additional information in our next mport.

I 4,

9,


d