Tech Spec Change Request NPF-38-118,changing TS Table 4.3-2, ESFAS Instrumentation Surveillance Requirements to Extend Surveillance Frequencies for Automated Actuation Logic for Safety Injection & Containment Spray
ML20094D616
Person / Time
Site: Waterford 
Issue date: 12/18/1991
From: Burski R
ENTERGY OPERATIONS, INC.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
Shared Package
ML20094D618 List:
References
W3F191-0823, W3F191-823, NUDOCS 9112230222
Download: ML20094D616 (3)


Text

- - _ _ _ _ _

b

=." ENTERGY IM """*"' '"*-

.s R4 U!!.

R.9.flurski 5

I W3F191-0823 M.05 QA December 18,1991 U.S. Nuclear llegulatory Commission ATTN: Document Control Desk Washington, D.C.

20555

Subject:

Waterford 3 SES Docket No, 50-382 License No. NPF-38 Technical Specification Change Roquest NPF-38-118 Additional Information Gentlemen:

On October 11, 1991, Entergy Jperations, Incorporated submitted the subject request to change Waterford 3 Technical Specification Table 4.3-2, Engineered Safety Features Actuation System Instrumentation Surveillance Requirements.

The requested changes extend the surveillance frequencies for the automated actuation logic for safety _ injection, containment spray, containment isolation, main steam line isolution, safety injection system recirculation and emergency

- feedwater frcm monthly to quartorly for the initiation relays and to semi-annually

- for the subgroup actuation relays. Changes are also requested for the footnotes to reflect these extended frequencies. In the interest of expediting the review of the request extending the surveillance period of the initiation relays, Entergy is requesting the NRC to review the subject submittal disregarding those changes associated with the subgroup relays and footnotes. These changes will be submitted for your review as a separate request.

As indicated in the original submittal, W3F1-91-0428, the extension of the 4

surveillance for each of two relay types is based on a Combustion Engineering Users' Group (CEOG) analysis specific to the relay. The change extending the surveillance period for the " initiation" relays is based on information provided in CEN-327~ "RPS/ESFAS Extended Test Interval Evaluation." This report has already been approved by the NRC., The report supporting the change for the other type of relays, CEN-403: "ESFAS Subgroup Test Interval Extension," is presently still under NRC review. As web, the review of this report is delaying the approval of a change request that, essentially, has already received approval 9112230222 911218

/

PDR ADOCK'03000382 hi P

PDR Il8

Technical Specification Change Reques' NPF-38-118 Additional Information W3F191-0823 Page 2 December IB, 1991 by the commission. In the interest of expediting such an amendment, Entergy is asking the NRC to disregard them changes in the subject submittal associated with the subgroup relays and the footnotes and only review the request to extend the surveillance period of the initintion relays. If approved, an amendment may then be issued regardless of the review status of the unrelated CEOG topical report.

For convenience, please find a sample marked-up specification representing the extension to the surveillance period of the initiation relays, only. Please direct any questions or comments to Tim Gaudet on (504) 739-GGG6.

Very truly yours,

)

(n)<-

Quap)'

RFB / DAR /ssf Attachment ec:

R.D. Martin, NRC Region IV D.L. Wigginton, NRC-NRR R.B. McGeheo N.S. Reynolds NRC Resident luspectora Office Administrator Radiation Protection Divielon (State of Louisiana)