ML20094B182

From kanterella
Jump to navigation Jump to search
Rev 3 to Moderate Energy Line Break Study
ML20094B182
Person / Time
Site: Seabrook  
Issue date: 06/30/1984
From: Carl G, Rhoads D
UNITED ENGINEERS & CONSTRUCTORS, INC.
To:
Shared Package
ML20094B171 List:
References
TP-7, TP-7-R03, TP-7-R3, NUDOCS 8411070051
Download: ML20094B182 (63)


Text

i 9

SEABROOK STATION MODERATE ENERGY LINE BREAK STUDY PREPARED BY UNITED ENGINEERS & CONSTRUCTORS INC.

FOR PUBLIC SERVICE COMPANY OF NEW HAMPSHIRE MANCHESTER, NEW HAMPSHIRE l

O 4

JUNE 1984 K O O hk 3 f

D PDR

r

!K I

SEABROOK STATION MODERATE ENERGY LINE I

BREAK STUDY PREPARED BY l

UNITED ENGINEERS & CONSTRUCTORS INC.

FOR PUBLIC SERVICE COMPANY OF NEW HAMPSHIRE I

i t

I Prepared by:

Report TP-7 y

Rev. 3, June 15, 1984 Reviewed by:

g I

E I

t

I MODERATE ENERGY LINE BREAK STUDY TABLE OF CONTENTS

^

l.0 INTRODUCTION l

2.0 REFERENCES

I 3.0 DEFINITIONS f

4.0 ANALYSIS 4.1 RHR, Containment Spray, and Safety Injection l

Equipment Vaults 4.2 Primary Auxiliary Building l

4.3 Control Building 4.4 Diesel Generator Building l

4.5 Emergency Feedwater Pumphouse j

4.6 Service Water Pumphouse 1

4.7 Main Steam and Feedwater Pipe Chases f

4.8 Containment Enclosure Fan Room 4.9 Miscellaneous Areas l

l

5.0 CONCLUSION

S i

6.0 LIST OF TABLES I

Table No.

Title t

4.1 RHR, CBS, and SI Equipment Vaults Essential I

Components f

4.2 Primary Auxiliary Building Essential Components 4.3 Centrol Building Essential Components t

l 4.4 Diesel Cenerator Building Essential Component f

4.5 Emergency Feedwater Pumphouse Essential Components 4.6 Service Water Pumphouse Essential Components 4.7 Main Steam and Feedwater Pipe Tunnel Essential

,I Components l

4.8 Containment Enclosure Essential Components l

-i-1

TABLE OF CONTENTS (continued)

F 7.0 ILLUSTRATIONS k

Figure No.

Title 7

l 4.1 RHR, CBS and SI Equipment Vaults

(

4.2 Primary Auxiliary Building 4.3 Control Building 4.4 Diesel Generator Building 4.5 Emergency Feedwater Pumphouse 4.6 Service Water Pumphouse 4.7 Main Steam and Feedwater Pipe Tunnel 4.8 Containment Enclosure Fan Room i

I I

I l

l MODERATE ENERGY LINE BREAK STUDY l

1.0 INTRODUCTION

In accordance with the requirements of 10CFR50, Appendix A, General Design Criteria for Nuclear Power Plants (Reference A), structures, systems and components important to safety must be capable of performing their safety-related functions under environmental condi-tions resulting from normal operation, maintenance, testing and postu-lated accidents.

One type of postulated accident which could result in an abnormal or severe environmental condition, affecting essential systems or components, is a rupture or crack in a line carrying moderate energy fluid in close proximity to systems or components important to safety at locations outside containment. (Ref. B)

The purpose of this study is to evaluate the effects of such a moderate energy line break on those systems or components important to the safety of the Seabrook plant. Each of these systems or components has been compiled and included in Tables 4.1 through 4.8 of Section 6 and is also illustrated in Figures 4.1 through 4.8 of Section 8.

This study considered primarily the flooding and spray impingement effects resulting from the rupture of moderate energy lines.

Complete immersion in conductive fluids could render many electrical and some mechanical components inoperable due to degradation of insulation, bearing lubrication, etc.

The method chosen for the analysis was to consider each major building individually. In I

I evaluating the effects of flooding, all moderate energy lines in a given area were reviewed and the line whose failure would result in the most severe flooding rate was selected to be considered the

.g 5

subject of the limiting failure.

In accordance with the requirements of Reference R, the following criteria were used:

1.

Cracks were postulated in all moderate energy fluid system piping and branch runs exceeding a nominal pipe size of one inch. These cracks were postulated individually at locations that resulted in the most severe environmental consequences.

2.

Fluid flow from a crack was based on a circular opening of area equal to that of a rectrangle one half pipe diameter in length and one half pipe wall thickness in width.

3.

The flow from the crack was assumed to result in an environ-ment that wetted all unprotected components within the compartment, with consequent flooding in the compartment and

.lW communicating compartments. Flooding effects were generally determined on the basis of a conservatively estimated time period required to effect corrective action.

I Rupture of moderate energy lines containing gaseous fluids such as compressed air or nitrogen was not considered because the resultc of these breaks would not cause failure of systems important to safety.

I I

In evaluating the effects of liquid spray, unless the component is located away from all moderate energy lines, the component was assumed to be subjected to spray impingement, regardless of the 1

moderate energy line source.

It is concluded on a general basis that spray impingement from a MELB does not adversely affect the capability of components from performing their safety function because of the protective features specified when the components were purchased. These features include drip-proof motors, enclosures for electrical components which arc either water proof or water shedding, water proof or water shedding instrument and control components, water shedding HVAC fan and filter housings, and water proof and water shedding electrical junction and pull boxes - some with drip shields.

Spray impingement will not be discussed in greater detail in the building sub-sections unless particular measures have been taken to protect essential components from MELB sprays.

B In evaluating the capability of essential safe shutdown components to remain operable in the presence of a MELB, the following assump-tions were made:

Valve and pump bodies, piping, and pressure vessels cannot be a.

af fected by water or water spray or by immersion, since they are carbon steel or stainless steel forgings or castings which are designed to act as fluid pressure boundaries.

O,

I b.

All safety-related motors used in this plant, other than those supplied by the NSSS, must meet the requirements of UE4C Specification 9763-128-1, and are either drip-proof or totally enclosed. Drip proof motors are protected by housings from f alling water or falling objects, and cooling air intakes are protected by baffles to prevent ingestion of solid objects or water spray. Heavy spray, directed into the air intakes, could be drawn into the motor, and if permitted to remain for long periods of time, could eventually cause deterioration of the motor insulation and lubrication, thereby shortening motor life.

Short-term or immediate failure of the motor as a result of water spray is not a credible event. (Ref. C) l Complete immersion due to flooding is considered to render c.

motors inoperable because of degradation of insulation and bearing lubrication, and because of possible short circuiting I

of internal circut.;ry, d.

Pneumatic and hydraulic valve operators will not be rendered inoperable by direct moderate-energy water spray because their solenoid valves and position switches are covered by NEMA-12 enclosures, which are water-resistant. Pneumatic diaphragms and pistons are enclosed in water-tight housings, and hydraulic pistons are enclosed in closed hydraulic systems which are sealed against the entry of water.

1 [

?

e.

Complete immersion of pneumatic operators is considered to render them inoperable by covering the discharge vent and possibly filling the low pressure chamber with water.

f.

Solenoid valves are not affected by moderate energy spray or complete immersion because their coils are potted with epoxy or polyster resins which are impervious to water, and because they are enclosed in water-tight housinge.

(Ref. F) g.

Safety class limit switches used for Seabrook are enclosed in NEMA-12 housings, and their function will not be affected by moderate energy spray. Complete immersion in water is con-sidered to render them inoperable because the weatherproof housings are not designed to exclude water under pressure.

h.

Switches mounted on cabinets or panels with watershed design are not affected by moderate energy spray. Complete immersion is considered to render them inoperable.

(Ref. H, J)

I Water shed design means that a cap or cover is used to deflect falling water away from openings in the cabinet. If direct spray is a credibic event, it is considered in the design of the cover.

l I

I

i. Instrument racks are designed with NEMA-12 housings and are not susceptible to damage due to moderate energy spray. (Ref. E)

J.

Essential dampers, pneumatic operators, pilot valves, thermal switches and fans are enclosed in NEMA-12 housings and are not considered to be affected by moderate energy spray.

(Ref. D) k.

Cables enclosed in conduit or in cable trays are not considered to be affected by moderate energy spray or immersions because their waterproof insulation is unbroken by splices.

1.

Motor control centers, terminal boards and other devices which contain electrical terminations are not considered to be water-proof, and direct moderate energy spray or immersion are considered to render them inoperable due to short circuiting, unless special protection is provided.

I m.

Flooding of one RilR vault would not affeet the equipment in the other vault, since pipe penetrations between the vaults are sealed to prevent leaks into the other vault.

l l

l I

I I l

I I

2.0 REFERENCES

A.

10CFR Part 50, Appendix A, General Design Criterion 4,

" Environmental and Missile Design Bases."

8.

Branch Technical Position ASB3-1, Protection Against Postulated Piping Failures in F1.uid Systems outside Containment _(NUREG-0800).

C.

UE&C Specification 9763-128-1, Rev. 4, Alternating Current Induction Motors.

D.

UE&C Specification 9763-248-13, Rev. 6, Actuators for Dampers and Valves.

E.

UE6C Specification 9763-171-1, Rev. 4, Instrument Racks.

F.

UE&C Specification 9763-173-7, Rev. 1, Solenoid Valves.

G.

UE&C Specificatioa 9763-174-1, Rev. 9, Electronic Transducers.

II. UE&C Specification 9763-252-14, Rev. 3, Pressure Switches.

I.

IJE6C Specification 9763-252-16, Rev. 8, Differential Pressure Instrumentation.

J.

UE&C Specification 9763-252-17, Rev. 2, Temperature Switches.

K.

SD-1, Rev. 6, System Design Description for Condensate, Feedwater, ad Heater Drain System.

L.

SD-23, Rev. 4. System Design Dest tiption for the Primary Component Cooling Water System (CC).

.I M.

SD-24, Rev. 4, System Design Description for Station Service Water System.

N.

S0-52, Rev. 7, Fire Protection System.

O.

SD-57, Rev. 6, Plant Storn Drainage System.

P.

Letter SB-17677, dated January 19, 1982, MELB Study Equipment I

Requirements.

I r

I Q.

UE6C Specification 9763-006-249-7, Rev. 3, Wall and Floor l

l Penetration Sealant.

R.

Branch Technical Position MEB-3-1, Postulated Rupture Locations in Fluid System Piping Inside and Outside Containment (NUREG-0800).

S.

SD-10, Rev. 2, System Design Description for Diesel Generator -

3 Mechanical Systems 3.0 DEFINITIONS Essential systems / components - systems and components required to shutdown the reactor and mitigate the consequences of a postulated piping failure without offsite power.

Moderate energy line - a line that during normal plant condition is either in operation or maintained pressurized above atmospheric pressure under conditions where both of the following conditions are met:

A.

Maximum operating temperature is 200*F or less, and B.

Maximum operating pressure is 275 psig or less.

I I

I I

I I

I I

I 4.0 ANALYSIS 1

4.1 RHR, Containment Spray and Safety Injection Equipment Vaults (Refer to Table 4.1 and Figure 4.1)

There are two RilR, containment spray, and safety injection equip-ment vaults. They extend from a roof elevation of 25'6" to an elevation of (-)61' where the sumps are located. Each floor elevation in the vaults contains grating such that liquid from a line break or crack will fall through the grating and accumulate at the (-)61' elevation with little or no accumulation elsewhere.

I Separating the two vaults is a 30-inch coccrete wall with a total of fifteen penetrations.

All fifteen penetrations are above the maximum flood level resulting from the worst case moderate energy E

line break in either vault. Six of the penetrations carry pipes, all of which are scaled to sleeves embedded in the concrete wall.

The seals are designed to withstand a pressure differential of approximately 3 psi, and tested at 4.5 psid.

There are seven spare penetration sleeves which penetrate the same wall; these are scaled by means of a 1/4-inch thick carbon steel plate seal welded to each end of the sleeves.

The two remaining penetrations are passageways between the vaults at Elevations (-)31'10" and 3'2".

Each of these passageways is equipped with a door. Both doors are well above the maximum flood level resulting from the worst case moderate energy line break in I.

l either vault. Although not designed to be a watertight door, the l

spray and flooding effects due to a line break above the doors will not result in significant passage of water beycad the door because of the physical location of piping in relation to the doorway and because of the floor grating which will drain water to lower elevations in the building. Thus, a MELB in one vault will not result in flooding or spray impingement effects in the other vault.

The following drawings were used in evaluating the effects of moderate energy pipe breaks in the vault areas:

Piping Drawings Electrical Drawings Instrumentation Drawings 9763-F-805060, Rev. 10 9763-F-310761, Rev. 14 9763-F-500331, Rev. 07 805061, Rev. 13 310762, Rev. 14 805078, Rev. 06 310763, Rev. 23 Arrangement Drawings I

805200, Rev. 12 310781, Rev. 08 805201, Rev. 13 310782, Rev. 11 9763-F-805060, Rev. I1 i

805202, Rev. 12 805078, Rev.

7 I

805203, Rev. 10 805204, Rev. 12 805205, Rev. 13 805206, Rev. 11 5

805207, Rev. 09 805545, Rev. 03 805563, Rev. 14 I

805565, Rev. 07 Mechanical Services Drawings

, Structural Drawings 9763-F-604112, Rev. 05 9763-F-101510, Rev. 16 604121, Rev. 09 101530, Rev. 13 604122, Rev. 10 301534, Rev. 11 I

101547, Rev. 07 101558, Rev. 06 I I

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _______ _ _____ ____ ___ ___________________ _ ___ __j

l-B 4.1.1 Flooding l

The vault area contains moderate energy lines in the following systems:

Chemical and Volume Control Containment Spray Primary Component Cooling Residual Heat Removal I

Safety Injection Sample Vent Fire Protection Of the above systems, those with the highest potential leak rates are the Primary Component Cooling Water System and the I

Residual Heat Removal System.

The largest lines in the vault area are the 20-inch component cooling lines which operate under a head of 200 feet of water. The calculated crack area for these lines would result in a leak rate of 85 cubic feet per minute.

Since each vault contains grating at each floor elevation, any line break will result in water falling through the grating and accumulating at the (-)61 foot elevation. No credit is taken for the operation of the vault area non-Class IE sump pumps, thus the water level in the affected vault would rise at the rate of approximately 0.1 foot per I

minute. After about 1.4 minutes, the Component Cooling Water System head tank Class IE low-low level alarm would be activated by the loss l

of component cooling water.

Since the vault sump level alarm also

.is not Class IE, no credit can be taken for using it as a flood warning device in the Control Room. Allowing a reaction time of l

30 minutes for isolation of the leakage, the water in the affected vault would reach a height of 3-3/4 feet, which would result in a loss of function of the containment spray pump in that vault.

However, the containment spray is not required to mitigate this MELB. In addition, the redundant containment spray pump in the other vault would not be affected because the vaults are completely separated. The RHR pump motor is located above the (-)S5'-0" elevation, and would not be affected by flooding in this case.

Loss of inventory in one component cooling water train will not result in the loss of the ability to achieve and maintain cold shutdown because a redundant component cooling water train is available to take up the loads.

There is one RHR pump suction line in each vault. These lines are connected directly to the reactor coolant piping of Loops 1 and 4, with two interlocked motor-operated isolation valves in each line. These valves are opened by the operator during reactor cooldown for the establishment of RHR cooling. Flow in these lines is continuously monitored when they are in use.

Any change in RRR flow rate or' pressure, or pressurizer level would alert the operator that a leak existed.

L e

i The RHR lines are used during reactor heat-up and cooldown.

Since they operate as high energy lines during only short operational periods, and qualify as moderate energy lines for the major portion of the plant operational life, through-wall leakage cracks have been postulated to occur during start-up and shutdown, and have been included in this study. These lines are assumed to be in operation at the maximum MELB temperature of 200*F and a pressure of 275 psig when the line break occurs.

Ruptures of the 14-inch and 16-inch portions of the RHR suction line need not be postulated because stresses in these portions are less than 0.41(1.2Sh + S ) and are exempted from crack A

postulation by BTP MEB 3-1 of NUREG 0800.

The postulated crack in the 12" RHR line would result in a flow of 95 cfm of reactor coolant into the vault area. The Control Room operator would be notified of a problem by a lou level alarm in both the Pressurizer and the Reactor Vessel. Assuming 30 minutes for operator response, the water level in the affected vault would rise about 4'-2".

Since the RHR pump motors are located above the (-)S5'-0" elevation, they would not be flooded by this event. Reactor cooling would continue at a reduced rate, using the other RHR loop maintaining subcriticall*v in the core.

I Instrument racks IR-14, IR-15 and IR-23 are located on elevation 3'-2" in the stairwell area. The only equipment that is required for safe shutdown in these racks is RH-HY-606-1 mounted in rack i

IR-14 above elevation 5'-8".

This is a solenoid operated valve and will not be affected by a rupture of any of the small cold

~

water lines in the stairwell area. Flooding to this elevation is not a credible event.

l I

I I

I I

I I

I I

I I

I I

L

.i.

4.2 Primary Auxiliary Building (Refer to Table 4.2 and Figure 4.2)

The PAB has full or partial floor levels at the following elevations:

I

(-)26'-0:, (-)6'-0",

2'-0",

7'-0", 25'-0", 53'-0" and 81'-0".

See h

Fig. 4.2 for arrangement of this building. No single elevation is scaled off from any other since there are equipment hatches, piping and electrical chases, HVAC duct openings and floor drains generally located on all elevations. All of the approximately sixty floor drains drains in the building except three, drain to the single sump at El. (-)26'-0".

I The three exceptions are in the northwest corner of the building at El's 25'-0" and 53'-0" in the area of the Component Cooling Water Heat Exchangers. These three floor drains are connected to a single 3" pipe which penetrate the building exterior wall and terminates in a normally closed valve. Initial leakage in this area would be held up in a curbed area surrounding the PCCW heat exchangers. The contents will be sampled and examined. If radioactive, the contents will be directed to the radioactive liquid waste system. Otherwise it will be disposed of in the yard storm drainage system.

I I

I I

The following drawings were used in evaluating the effects of a moderate energy line break in the PAB.

Piping Drawings 9763-F-805136, Rev. 04 9763-F-805223, Rev. 11 9763-F-805242, Rev. 05 805138, Rev. 03 805224, Rev. 13 805243, Rev. 07 805210, Rev. 08 805227, Rev. 10 805244, Rev. 04 805211, Rev. 14 805228, Rev. 10 805246, Rev. 07 805213, Rev. 13 805229, Rev. 08 805215, Rev. 11 805230, Rev. 05 805231, Rev. 10 l

9753-F-805216, Rev. 08 9763-F-805232, Rev. 07 805217, Rev. 11 805235, P,ev. 09 805218, Rev. 09 805236, Rev. 09 l

805219, Rev. 08 805237, Rev. 05 805220, Rev. 08 805238, Rev. 07 I

805221, Rev. 11 805239, Rev. 09 805222, Rev. 13 805240, Rev. 07 l

805241, Rev. 08 815214, Rev. 11 Structural Drawings l

Arrangement Drawings 9763-F-101511, Rev. 12 101512, Rev. 13 I

9763-F-805061, Rev. 13 101513, Rev. 12 j

805062, Rev. 13 101535, Rev. 18 805063, Rev. 12 101536, Rev. 11 805064, Rev. 13 101549, Rev. 09 805065, Rev. 13 101550, Rev. 09 l

805066, Rev. 12 101551, Rev. 17 8

805069, Rev. 8 101552, Rev. 13 101625 Rev. 10 l

102966, Rev. 01 102972, Rev. 00 I

Electrical Drawings Instrumentation Drawings 8

9763-F-310761, Rev. 14 9763-F-500175, Rev. 06 310762, Rev. 14 500176, Rev. 05 l

310763, Rev. 23 500177, Rev. 03 310764, Rev. 14 500179, Rev. 06 5

310765, Rev. 17 500183, Rev. 02 l

310766, Rev. 18 P& I Diagrams 9763-F-804959, Rev. 01 804992, Rev. 06 804993, Rev. 07 I

I I

Electrical Drawings Mechanical Services I

9763-F-310767, Rev. 14 9763-F-604109, Rev. 07 I

310768 Rev. 13 604110, Rev. 10 310781, Rev. 08 604111, Rev. 07 310784, Rev. 15 604118, Rev. 04 I

310785, Rev. 14 604119, Rev. 07 310786, Rev. 16 604120, Rev. 05 310787, Rev. 17 604121, Rev. 09 310788, Rev. 13 604122, Rev. 10 I

4.2.1 Flooding The Primary Auxiliary Building contains moderate energy piping in the following systems:

Chemical and Volume Control Containment Spray I

Demineralized Water Hydrogen Gas Mechanical Seal B

Nitrogen Gas Primary Component Cooling Reactor Make-up Water I

Resin Sluicing Service Air Service Water Spent Fuel Cooling and Clean-up I

Vent Waste Process - Gaseous Waste Process - Liquid Fire Protection Preliminary calculations were made to determine leak rates from a crack in the largest line in each of the above systems in the Primary Auxiliary Building. The two lines with the potential of highest Icak rates are the 24" Service Water line and the 24" Primary Compo-nent Cooling Water line.

5 s.

I Rupture of the 24-inch Primary Component Cooling Water line at an elevation of 46'-0" would result in a flow of 103 cubic feet per minnt. which would activate the CC head tank redundant Class IE low-low level alarms in about 1-1/4 minutes. Since there are approxi-mately 25 floor drains at E1. 25'-0", even if 50% of them were plugged, the floor drainage system is large enough to carry the 103 cfm to the sump at (-)26'-0" without backing up.

The water would reach the sump in seconds and take approximately 1-1/4 minutes to fill the sump and energize the Class IE redundant high level alarms. The water would then rise above the (-)26'-0"

~

level at a rate of approximately 0.1 ft./ min. At El.

(-) 26'-0",

the structural wall between the Primary Auxiliary Building and the mechanical penettation area outside the Containment Building consists of a metal partition with a door. This partition is designed to withstand a pressure differential of 0.5 psi or a l

head of approximately 1 ft. of water. Thus, if the operator l

did not recognize and isolate the failed pipe within minutes following the two level alarms, water would begin leaking through the partition into the mechanical penetration area. The water

'I would gravitate to a pit at E1. (-) 34'-6" where a floor drain would carry it to the sump in one of the two R.H.R. Equipment l

Vaults at El. (-) 61'-0".

Should the break not be isolated for 30 minutes (considered a l

reasonable maximum time) approximately 3100 f t.3 (23,000 gal.)

of PCC water would be deposited in the RHR Vault. This would be approximattrly 4'-6" deep at El. (-)61'-0".

This would cause I I t

r-lI

z the Containment Spray Pump of one of the two redundant loops.to be inoperable. However, since,it is not required to

~

mitigate this accident, there is no safety problem involved.

Should tlie floor drain at E1. (-)34'-6" in the mechanical penetra-tion area outside the Containment Building be plugged, the water

- I would reach a depth of 3'-7" feet in 30 minutes. No components essential to plant safety would be submerged at that level.

As the water leaked out of the PCCW System, th'e general level I

(elevation) of the water in the system would drop, reducing the available NPSH. When the required NPSH was reached and passed, the PCCW Pump would start to cavitate. Also, since the heat removal capability of the system decreased, system temperatures would rise as flows decreased, and would be so noted in the control room. The unit would have to be shut down while shifting major loads to the redundant PCCW loop.

A crack in a 24" Service Water line at El. 63'-1-5/8" would pro-I duce a flow of 88.4 CFM or approximately 660 gpm.

Initially, the flooding would be confined to the curbed area at the northwest corner of the PAB at El. 53'-0*.

Some water would flow down through the annoli in the floor around the two Component Cooling Ileat Exchangers to El. 25'-0".

In 5 to 7 minutes the water I

1 would owerflow the 6" curb surrounding this area. Floor drains would immediately carry the water to the sump at El. (-)26'-0".

Within two r.:inutes, one or both redundant Class 1E sump high level alarms would notify the operator of a problem. Should the flow through the crack continue for 30 minutes, flooding would.

.; c,.9:f,.g ff.aj @t c

.-c 1.;.,'

s q,:,..

l: -

..;.c.:-(i

. _,'..,&. < :;- - L:.c

.y-

,A

. y

_ c. g. h.., s,3..9...., m. m. n.....

,,p,q.,a,. ;.

, _, ~. s.

.;.j.,k,,

-w 3.

.,e c..,.4

.~m s

  1. . w,

c t

'. e.., g ;. y. v. ;*:.7, g r.;y

.) :.a

.c ; \\; ': ;y,.? ;.,3.-.. y... ' ; (;. q;. (.. [.:. y g

.c.

y.f l y i X.yg Q y '.:

-.y

^%.*

~.

g g

f.,.

"'1-s

{

s

[

be similar to that with Component Cooling Water; however, with a

' k.,.

slightly lower rate and less total water. This flooding cituation

.j

,w

.y :

would also not compromise the operating capahitity of any safety y,.

g
s.

( (J related components.

G...

.;.. y.

~_ '

y.,

7.. -

j

' ". '~

The loss of 660 gpm or 6% of the total Service Water flow would 3-.

(,

,c g,j ;

result in a drop in line pressure of about 12%. This drop in n%.

"a.

L pressure would not be great enough to cause a Tower Actuation c:.t

v O'

Q-f signal, since the TA signal is actuated at approximately 50% of

,.p

' y.f QJ pump full load discharge pressure.

Isolation of one loop would N T-g i

result in an extended cool-down time, but one service water loop x

h_-

ts capable of supplying 100% of the flow required for all acci-F.e.

.o..

}#

P.**

dent conditions.

p

.,2

!-g:

k. ;.

.r p

~,2 If the non-safety related sump pumps in the sumps in either or

o...,

,} u.

both sumps in the PAB or RHR Vault operate during either of the

,.... h 44

>W above flooding conditions, the PCC Water or Service Water would sm

. o..

M.~

/s: '

be pumped to the Floor Drain Tank (s) in the Waste Process Building.

&.x

, e a.

Should one or both of these fill and overflow, the excess would flow y

.i g e.

. >n g

f %a to one of the two sumps at El. 31-0" in the WPB through the floor ji s.,

.si 2-

..A

.p'N.

drainage system. No safety related components nor systems would be

@g L7"

'{m j

y/

affected.

, =

5 y

,i _

.,9 f.,.. A.

'.(.. '

.,,y f

3..

...s.,

$6 K:

M:

s,.

m'

(,,. ;.

, s.,:

,z,

,' [ +

b.,.

' w S.

.{.

j..

T. e.-

., J

'\\

s

,[

.[

.];

i :.

, ~.

g.w,e,w.;.:.

n,,3

s., 3...., y g,.y.x,,.,,..,,.

g..,

wug -

I 4.3 Control Building (Refer to Table 4.3 and Fig. 4.3)

The Control Building contains three floor elevations as follows:

Kl. 75'-0" - Control Room plus offices E1. 50'-0" - Cable spreading room plus HVAC equipment room El. 21'-6" - 480 Volt switchgear, sub-station and battery rooms l

Refer to Fig. 4.3 for arrangement of the Control Building.

The only moderate energy piping in the Control Building are the fire protection piping and the potable water piping. The fire protection piping provides water to the hose stations in the stairwells of the Control Building and Diesel Generator Building.

The potable water system supplies water to the washrooms and HVAC j

equipment room.

I The following drawings were used in evaluating the effects of moderate energy pipe breaks in the Control Building:

)

Structural Drawings Electrical Drawings 9763-F-LOl341, Rev. 02 9763-F-310431, Rev. 22 101346, Rev. 10 310442, Rev. 22 101351, Rev. 10 310443, Rev. 18 I

101352, Rev. 07 310444, Rev. 22 101610, Rev. 10 310451, Rev. 18 l

101611, Rev. 11 310452, Rev. 16 310455, Rev. 07 310456, Rev. 09 l

310457, Rev. 11 310458, Rev. 09 I

310459, Rev. 10 310460, Rev. 06 310461, Rev. 06 I

310462, Rev. 07 310463, Rev. 08 l

310464, Rev. 05 310471, Rev. 03 I I

y

yp Arrangement Drawings Mechanical Services 9763-F-500090, Rev. 15 9763-F-604091, Rev. 06 310452, Rev. 19 604092, Rev. 11 310451, Rev. 21 604093, Rev. 12 500091, Rev. 6 604094, Rev. 06 310431, Rev. 22 604095, Rev. 08 604099, Rev. 09 604166, Rev. 01 604100, Rev. 07 4.3.1 Flooding During normal plant operttion, the Control Room is continuously staffed, and any evidence of flooding from the potable water piping in the washrooms and HVAC equipment room would immediately be r.oticed and investigated and prompt corrective action taken.

Rnpture of the potable water lines in the Control Building wash-rooms would result in a flow of approximately 2.6 cubic feet per minute. There is one 2-1/2 inch floor drain in each washroom.

Assuming only one drain is functional, the maximum flood level in the washrooms, in the event of a rupture of the potable water line, is approximately one half of an inch. Water would drain to the yard storm drainage system.

The Control Room is capable of sustair.ing a flood water level of at least 4 incoes without damage to essential equipment. All sections of the Main Control Board have an inside base which is 4 inches high, effectively requiring all MCB components to be at least 4 inches above the floor. The component parts of all other panels and racks in the Control Room are likewise located above the floor level. _ _ _. _

l l

Drainage from the Control Room is available through the door of the l

Turbine Butiding, through the stairway leading out of the building, and by way of the floor drains in the washrooms.

Flooding of the Control Room from the Turbine Building has a very low probability for the following reason:

the passageway to the Turbine Building consists of a double door airlock leading to a fifty foot long corridor and office complex. Beyond that is an open stairwell, with no piping in the area for a distance of approxi-mately fifty feet.

Flooding from the Control Room to the Cable Spreading Room directly below is not possible because all openings are sealed against a maximum pressure difference of 3 psi. The Cable Spreading room (El. 50'-0") has a normally dry water deluge system for fire protec-tion, therefore, flooding from a pipe break is not considered in that area.

The IWAC Equipment Room on El. 50'-0" of the Control Building has a 2" potable water line which supplies water to humidifiers and a 6" fire protection header which supplies water to the fire protection system in the adjacent Diesel Cenerator Building. A crack in the latter line would produce a leak of approximately 24 CFM or approximately 180 gpm.

I There are three - 3" floor drains in this area which drain through 1

a common 3" line to the storm sewer system.

If this common line were 100% plugged, the water would flow out of the equipment room, even if the door were closed, across the floor of the cable spreading room to two 6" floor drains on the cast side of the room. Either.. -....

I I

one or both of these drains would carry the 180 gpm of water away without significant build-up on the floor of the cable spreading room.

One of the 6" drains drops straight down and empties onto the floor of the train "A" electrical tunnel at El. O'-0".

lI The other 6" drain drops straight down and empties onto the floor of the train "B" electrical tunnel at El. (-) 20'-0".

The scenario would now be the same as that in Section 4.5.

All the water in both tunnels would gravitate to the sump in the "B" train electrical tunnel. A Class IE level alarm would notify the operator of a problem. Should the leak continue for 30 minutes, the level of water in the "B" train electrical tunnel f

would reach approximately 3".

This would not cause failure of any components required for safe shut down.

All other floor openings in the cable spreading room and HVAC equipment room are sealed so the water cannot escape to the electrical equipment room below.

On loss of water from the 6" fire protection supply line, one or both fire protection jockey pumps would start automatically. These, however, would not maintain system pressure (130 psig). Should the main fire pump (motor driven) start automatically at 100 psig, a non-Class IE alarm on the Main Control Board should also alert the operator.

I I I

i Flooding from the Heater Bay through the doorway in the North wall of the Cable Spreading Room is impossible since the floor of the Heater l

Bay in the area of the door consists of grating.

I The A and B Switchgear and Battery Rooms at El. 21'-6" contain no moderate energy lines. Flooding of this area through the doorway I

from the adjacent Heater Bay of the Turbine Building is virtually impossible 1,ecause the nearest piping is approximately 65 feet away.,

closer to the door is a battery room and a 480 volt substation. In addition, there are two 4" flow drains within 50 feet'of the doorway.

I t

I I

i I

I I

l I

I I

lI I

l I L

m I-4.4 Diesel Generator Building (Refer to Table 4.4 and Figure 4.4)

The Diesel Generator Building, adjacent to the Control Building has thyee floor levels. The Fuel Oil Storage Tanks are located at

(-) 16'-0" elevation. The engines and generators are at the 21'-6" level, and the day tanks, exhaust silencers, expansion tanks, and HVAC equipment are at the 51'-6" elevation (See Figure 4.4).

The off-engine moderate energy lines in the D.C. Building are de-mineralized water, potable water, fire mains, and engine jacket cooling water.

On-engine moderate energy lines are lube oil, fuel oil, and cooling water.

Each diesel generator system has four separate dry-type deluge fire protection systems associated with it.

Since the diesels and their auxiliaries are housed in separate concrete rooms, a moderate energy line break in one unit would not impair the start-up and operation of its redundant twin.

Drawings used in this evaluation are as follows:

Hechanical Drawings Electrical Drawings 9763-F-202264, Rev. 08 9763-F-310524, Rev. 18 202265, Rev. 11 310525, Rev. 09 202266, Rev. 09 310534, Rev. 07 202268, Rev. 03 310535, Rev. 06 202269, Rev. 07 310536, Rev. 03 202270, Rev. 06 310537, Rev. 10 l

l Mechanical Drawings Electrical Drawings l

9763-F-202271, Rev. 09 9763-F-310358, Rev. 08 202272, Rev. 07 310359, Rev. 07 l

202273, Rev. 07 202274, Rev. 04 Structural Drawings 202275, Rev. 06-l 9763-F-101382, Rev. 14 Mechanical Services Arrangement Drawings

(

9763-F-604102, Rev. 07 9763-F-202068, Rev.

7 604104, Rev. 11 202069, Rev. 10 604105, Rev. 07 202070, Rev. 10 l

604107, Rev. 07 604146, Rev. 05 l

4.4.1 Flooding The largest moderate energy line associated with the diesels is the l

10" diesel component cooling water line. This line enters the building I

below grade and below the operating rioor at El. 21'-6".

It reduces to i

8" in diameter and rises through the operating floor to the nozzle o'n the engine skid. Should a crack occur in the 10" portion, the leakage would be approximately 32 CFM or 240 gpm. Since the expansion tank on 1

this closed cooling loop and the sump at El. (-) 16'-0" have level alarms which are not Class IE, it is assumed that the operator would not be alerted immediately. The volume of the closed cooling loop is approximately 400 ft.3 or 3000 gal. Should the loop drain completely, in approximately 12.5 minutes, the floor at El. (-) 16'-0" would be l

covered by approximately 3" of water.

I l

I 1

I l

\\

I l

Should the break occur in the 8" portion of the loop above the operating floor at El. 21'-6", the leakage would be approximately 22.5 CFM or 168 gpm.

If the single 4" floor drain is open, the leaking water will fill the sump at El. (-) 16'-0" and overflow on the floor.

Should the leak continue, the loop would be empty in 18 minutes and there would be approximately 3" of water on the ficor.

l If the floor drain at El. 21'-6" were plugged, the water would l

not quite fill the trench system at El. 21'-6".

Existing six inch I

high curbs around the doorways would prevent this water from enter-l ing the adjacent compartment housing the redundant diesel generator.

8 On loss of cooling water several low pressure alarms would register at the appropriate diesel engine control board. In addition, non-t l

Class IE trouble alarm would register on the Main Control Board.

Following procedures, the redundant diesel would be placed in l

service. Should the alarm not function, or if the operator took l

no action, the diesel engine could possibly overheat and fail; in any case, the redundant unit would be available.

While each diesel and its auxiliaries are covered by dry delulge fire protection systems, a 6" fire main enters each half of the diesel building at El. 14'-6", below grade, in the fuel storage k

ta tk compartment. The deluge valves are located on a platform at El. (-) 8'-6" in the southwest and northwest corners of the building, I

'"""c"-

I

'I

r-L If one of the 6" fire mains should have a crack, the leakage flow would be approximately 26 ft.3/ min. or 195 gpm.

Should this go undetected for eight hours, 12,480 ft.3 of water would collect in the fuel oil storage tank room at El. (-)

16'-0".

This would cause failure of the Fuel Oil Transfer Pump. If the pump were running when the pipe break took place, the operator would be notifled of the problem by low level alarm in Day Tank and no flow in F.O. Transfer Pump discharge to Day Tank, and could take appropriate action to start the other diesel.

Following the latter pipe break and loss of fire protection water, one or both fire protection jockey pumps would start automatically with a drop in fire main pressure. What follows is similar to that in the Control Bt.11 ding with break in the 6" fire main at

~

El. 50'-0".

If the main motor driven fire pump starts automatic-ally, a non-Class IE alarm would notify the operator. Otherwise, the flow could continue for eight hours, and the 12,480 ft.3 og water at El. (-) 16'-0" would reach a level of approximately 8'.

Regarding the on-engine moderate energy lines, the cooling water loss has been discussed above. A break in a fuel oil or lobe oil pipe would produce a limited amount of liquid at the (-) 16'-0" level, but would not prevent the start-up and operation of the redundant diesel. The capacity of the Fuel Oil Day Tank is 1500 gallons while the total lube oil system holds approximately 2500 gallons. A variety of instrumentation would notify the operator in case of a rupture in either system. The resultant fuel oil or H

lube oil would be held up in either the sump at El. 16'-0" or on the floor at El. 21'-6".

The 6" curbs around the critical doors in each redundant compartment at E1. 21'-6" would prevent the oil from getting to the other compartment. Any liquid in the sump at El. (-) 16'-0" would eventually be pumped to an underground oil-water separator vault.

I I

I I

I I

I I

I D

I 4.5 Emergency Feedwater Pump House (Refer to Table 4.5 and Figure 4.5)

The Emergency Feedwater Pump flouse is a one story structure whose concrete floor elevation is 27'-0".

It is located directly to the north of the Containment and Containment Enclosure Buildings.

It l

houses the two Emergency Feedwater Pumps, associated piping and j

valves and HVAC equipment.

The moderate energy lines in this building are the 8" E.F. Pump suction lines, a 4" fire protection line which feeds the F.P.

standpipe in the adjoining stairtower and the 4", 6" and 8" E.F.

1 Pump discharge lines. Although high energy during operation, the l

latter are considered moderate energy at 275 PSI because of the pumps' short operating times.

l The following drawings were used to evaluate this area:

{

Mechanical Drawings Structural Drawings 9763-F-202296, Rev. 05 9763-F-101660, Rev. 09 l

202297, Rev. 05 101661, Rev. 04 202298, Rev. 05 101611, Rev. I1 202265, Rev. 05 101627, Rev. 11 202076, Rev. 03 101632, Rev. 08 604142, Rev. 03 101650, Rev.10 I

604100, Rev. 07 101652, Rev. 06 101653, Rev. 08 I

Arrangement Drawings 101662, Rev. 02 101664, Rev. 05 9763-F-202065 Rev. 03 101665, Rev. 05 l

4.5.1 Flooding The line which would cause the greatest amount of leakage, should a crack occur, would be the 8" discharge header at 275 psi. The l

leakage would be 93 cfm or approximately 696 gpm. The Emergency Feedwater Pump House has three 4" floor drains, two 4" hub drains i

and two 2-1/2" hub drains, all of which drain to an oil-water separ-II ator vault which is outside the building below grade. The inlet to 1

the oil-water separator has a device which limits the inlet flow to 75 gpm, therefore, 621 gpm remain to flood the area.

With little or no build-up at El. 27'-0", the water will enter floor openings in the southwest and southeast corners of the building.

Below the opening in the southwest corner is an isolated room at El. O'-0".

As soon as the break occurred, the operator would be alerted by the Class IE low feedwater flow alarms in the lines to the steam generator (s) being fed by the failed header. Allowing thirty minutes to isolate the break, and assuming all the water entered this area, the water would rise in the room to an olevation of approximately 11'-8".

The lowest opening in that room is a pipe tunnel connected to the west Main Steam and Feedwater Pipe Chase.

Its bottom elevation is 12'-0".

Allowing for a higher flow or longer time to isolate, water would enter the pipe tunnel at El. 12'-0" and collect in the bottom of the Main Steam and Feedwater Pipe Chase at El.

3'-0".

A water tight door to a room at the south end of the chase would prevent the water from causing failure of safety related equipment in that area.

In the major portion of the chase, there are no components required for plant shutdown.

Should the water enter the floor opening at the southwest corner of the room at El. 27'-0", it would fall to a compartment below with a floor at El. 8 '-2".

If the water level rose to El. 10'-0", it would pass through a doorway to the adjacent Pre-Action Valve Building, which houses the deluge valves for the fire protection of the train "A" and "B" electrical tunnels.

From here the water would gravitate to a compartment at the north end of the east Main Steam and Feedwater Pipe Chase. A single floor drain leads to the sump in the adjacent main portion of the MS and FW Pipe Chase.

If this W

drain were plugged, the water would rise harmlessly in the afore-mentioned compartment, to an elevation of 7'-3".

The lowest opening in this room is at El.

8'-0".

If the drain were open to the sump, the water level would rise only a few inches in this main portion of the pipe chase, where there are no components requi red for shutdown.

The 8" E.F. Pump suction lines are exempt from pipe break or crack considerations in accordance with NUREG 0800, BTP MEB 3-1, Section B.2.C.(1) for both lines, 0.4 (1.2Sh +S ) = 16,622 PSI.

A For line 4081 ASi4E III Sect. ND Eq. (9 + 10) = 8319 PSI.

For line 4082 ASME III Sect. ND Eq. ( 9 + 10) = 6954 PSI.

For each line, the summation is at the most highly stressed mode.

I I

I I

I lI k

4.6 Service Water Pumphouse (Refer to Table 4.6 and Figure 4.6)

The Service Water Pumphouse is adjacent to the Circulating Water Pumphouse and houses the Service Water Pumps, the Service Water Screen Wash Pumps, the Travelling Screens and the hot water unit heaters. The moderate energy lines are the 24" Service Water lines, the 6" Screen Wash lines, the service air and instrument eir lines, and a 3/4" potable water line. Note that the electrical switchgear room and the HVAC fan room are not affected by moderate energy line breaks.

The following drawings were used in evaluating this area:

Mechanical Drawings Mechanical Services 9763-F-202507, Rev. 01 9763-F-202418, Rev. 03 I

202508, Rev. 01 202419, Rev. 04 202419, Rev. 02 604459, Rev. 11 202576, Rev. 04 202499, Rev. 07 General Arrangements 9763-F-202476, Rev. 04 202477, Rev. 02 202478, Rev. 04 4.6.1 Flooding The moderate energy line which would produce the highest leak rate on failure is the 24" service water line. Rupture of this line would produce a leak rate of 92 cfm or approximately 685 gpm. The S.W. Pumphouse has eight 4" floor drains at El. 21'-0" operating floor and four 4" floor drains in the pit at E1. 4'-0" running north and south along the west side of the pumphouse.

In addition, there is one 4" drain in the trench which runs the length of the pit.

Since most of the service water piping is in the pit on the west side of the building, a break in a service water pipe would cause

I,

i~

flooding in the pit, assuming two of the four drains were plugged.

Since there are no safety related components in this pit, flooding would be no problem.

Should the pit overflow to the operating floor at El. 21'-0", half of the 8 hub drains and half of the 10 floor drains would limit the water depth to 2" or less. No safety related components would be affected.

The loss of 685 gpm from one service water loop would not activate the Tower Acteation signal since the line pressure would drop approx-imately 12%, which is far less than the 50% required for a TA signal.

Should the operator not note the drop in pressure and/or rise in temperature of the Primary Component Cooling Heat Exchanger service water discharge, the leak could continue for eight hours before isolation.

I I

I I

l lI

' 'I

I 4.7 Main Steam anl Feedwater Pipe Chases (Refer to Table 4.7 and Figure 4.7)

These two chases, one on the East and the other on the West side of the Containment and Containment Enclosure structures each basically contain the Safety and Code Class 2 portions of two main steam and two main feedwater lines outside the Containment Building. The East chase also contains portions of the following moderate energy lines:

Emergency Feedwater Instrument Air Service Air The West chase contains portions of the following moderate energy lines:

Emergency Feedwater Instrument Air Service Air Demineralized Water As stated previously, failure of instrument air or service air lines is not considered to cause a failure of safety related structures, systems, or components in the area.

~

I I

l,

The following drawings were used in evaluating this area:

Structural Drawings Mechanical Drawings 9763-F-101624, Rev. 05 9763-F-202236, Rev. 05 1

101625, Rev. 10 202237, Rev. 04 101626, Rev. 13 202238, Rev. 03 101627, Rev. 12 202239, Rev. 05 101628, Rev. 08 202240, Rev. 05 101629, Rev. 06 202241, Rev. 03 101630, Rev. 08 202242, Rev. 06 101631, Rev. 07 202243, Rev. 06 I

101632, Rev. 07 202244, Rev. 05 101633, Rev. 04 202245, Rev. 04 101634, Rev. 08 202246, Rev. 05 101657, Rev. 09 202:47, Rev. 04 I

101658, Rev. 09 202248, Rev. 03 101659, Rev. 01 202249, Rev. 07 102071, Rev. 03 202250, Rev. 07 I

101650, Rev. 10 202251, Rev. 06 202252, Rev. 05 General Arrangements 202253, Rev. 04 202254, Rev. 04 9763-F-202063, Rev. 05 202255, Rev. 07 202064, Rev. 05 202256, Rev. 04 604165, Rev. 07 4.7.1 Flooding A break in the 4" Emergency Feedwater pump discharge pipe would produce a flow of 27 cfm or approximately 203 gpm, calculated at 275 psig. The operator who would be monitoring the operation of the EFW pumps at this time would see the following indications of the problem: EFW pump low discharge pressure and low flow to steam generator (s). Allowing 30 minutes for operator action and break isolation, 6090 gallons would flood El. 3'-0" of the West chase (the smaller of the two chases) to a depth of 9-3/8" I

3,_

The corresponding elevation of water in the East MS and FW pipe chase would be 8".

Water-tight doors to compartments at the south end of each of the two chases at El.

3'-0" would prevent the sater from causing failure of safety related electrical equipment in those areas. There are no components required for plant shutdown in either pipe chase which would bc rendered inoperable following this event.

Each chase has a sump containing two non-Class IE sump pumps.

Normally, these would carry away any water present to the storm drainage system.

I I

l I

I I

llI l! l

h 4.8 Containment Enclosure Ventilation Fan Room See Figure 4.8, Sketch of this area and Table 4.8, list of essential components.

I The Containment Enclosure Ventilation Fan Room is at El. 21'-6" southwest of the Containment Building between the Primary Auxili-ary Building and the Fuel Storage Building. It houses redundant Containment Enclosure Fan Cooling Units, redundant Containment Enclosure Return Fans and redundant Containment Enclosure Emergency Exhaust Filter Units. The moderate energy lines in this area are the two redundant 10" Primary Component Coolant Water supply and return lines to and from the Fuel Storage Build-ing, the redundant 4" PCCW lines to and from the Fan Cooler Units and a 3/4" demineralized water line.

I The following drawings were used in evaluating this area:

Nuclear Drawings Structural Drawings Mechanical Service Dwgs.

9763-F-805270, Rev. 07 9763-F-101619, Rev. 09 9763-F-604110, Rev.10 I

805271, Rev. 07 604115, Rev. 05 805372, Rev. 07 General Arrangement 805053, Rev. 08 9763-F-805053, Rev. 09 I

4.8.1 Flooding A through-wall crack in the 10" PCCW line would produce a flow of 43 CFM (323 gpm). Six floor and hub drains would carry the water to the sump at E1. (-)26'-0" in the Primary Auxiliary Building. The first alarm in the Control Room would be the low level alarm from the PCCW head tank in approximately 2-1/2 minutes following the break.

The low-low 1cvel alarm would be activated about 20 seconds later.

I At about the same time, 3 minutes following the break, the Class IE high level alarm in the PAB sump would be indicated.

Allowing 30 minutes for isolation, a total of 1290 f t.3 would be released. Should all the water be drained to PAB El. (-)26'-0",

i l

It would be approximately I' 1-1/2" deep. It would not all drain to the PAB sump since some water would overflow into the Containment Purge System isolation valve pit at the northeast corner of the l

building. From here it wo.ild drain to El. (-)30'-0" in the annulus between the containment structure and the Containment Enclosure wall.

In either case, the flooding would not jeopardize the I

operation of systems or components necessary for plant shut-down.

j.

I Some of the flood water at El. (-)26'-0" of the PAB probably would leak through the metal partition separating the PAB from the Contain-iI ment mechanical penetration area. As in Section 4.2, this water would gravitate to El. (-)34'-6" in the Containment mechanical pene-tration area and then drain to the sump at El. (-)61'-0" in train A RHR Vault.

It's maximum depth would be approximately l'-8-1/2".

This would make the Containment Spray Pump in Train A inoperable

,I but would not prevent the plant from attaining a safe shutdown.

B At the north end of the Containment Enclosure Ventilation Fan Room, a door leads to a stairwell which decends to the electrical and I&C gg equipment room at the south end of the east Main Steam and Feedwater Pipe Chase.

A 6" curb around the door at El. 21'-6" prevents water f rom entering the stairwell.

I I -

I All the floor and hub drains at E1. 21'-6" are connected to the PAB sump through a common 4" line. Should this be plugged, all

)

I the water would enter the aforementioned Containment Purge iso-lation valve pit at the northeast corner of the building where it would not cause problems.

I At the south end of the building is a door which leads to two addi-tional doors. One leads to the exterior of the building and the other to the interior of the Fuel Storage Building. Leakage past any of all of these doors would cause no problems.

B I

I I

I I

I I

I I -

I 4.9 Miscellaneous Areas 4.9.1 Fuel Storage Building, Waste Process Building, and Tank Farm -

I While these buildings contain no systems or components required for plant shutdown they are in someway connected to buildings that do.

The Fuel Storage Building is connected to the Containment Enclosure Ventilation Fan Room indirectly through two doors, nor-mally closed, at El. 21'-6".

The FSB has moderate energy lines at El. 21'-6", however, in case of a break in one of them, there could be no water build-up because of 2 floor drains and grating which would carry any leakage to lower elevations in the FSB.

The Waste Process Building is separated from the PAB by the Tank Farm. Piping tunnels and the personnel tunnel connect the WPB and Tank Farm to the PAB.

The tunnels have individual sumps with non-class IE pumps. However, should there be a pipe break in a tunnel and no alarm, the water would either gravitate to the WPB I

where it could do no harm or to the PAB at El's.

15'-0", 5'-0" or

(-) 6'-0".

From any of these elevations it would flow through floor drains or floor openings to El. (-) 26'-0" and the sump with redundant Class IE level alarms.

Each tank in the tank farm, including Safety Class and Non-Safety Class tanks, is surrounded by a Seismic Category i dike, sized to I

contain the contents of the tank should it fail.

I i

I I

4.9.2 Circulating Water System NRCstaffRequestforInformationNo.J20.23requesteddiscussion of the effects of the failure of the non-safety related circulating water piping and non-safety related portion of the station service water system on the safety related station service water system or other safety related systems or components. The project respanse indi-cated that the Circulating Water pipe does not run in the vicinity of any station service water pipe. However, certain nonsafety related service water piping does run adjacent to Safety Class 3 SW pipe above and below ground. Since they have the same configuration as the non-safety related pipe, they will experience the same stress levels in the event of an SSE.

In addition, analysis indicates that water jets from a postulated crack in the non-seismic Category I piping would not cause sufficient erosion to compromise the support of adjacent safety related piping.

Flow from the Service Water discharge atmospheric vent has essenti-ally an unrectricted path to the open areas outside the PAB which dump into the storm drainage system.

I I

I I

I

-4 3-I

r I

4.9.3 Stairwells The following buildings have stairwells containing moderate energy fire protection standpipes with strategically located hose reels:

Diesel Generator Building - Each of the two stairwells C I

and D has a standpipe with a 6" supply.

Each stairwell serves the diesel fuel oil tank room, therefore a leak in the supply pipe or standpipe would spill on the floor at E1. (-) 16'-0".

This MELB is discussed in Section 4.4 on Diesel Generator Building.

Emergency Feedwater Pump Room - Stairwell "A" serving this building and the electrical tunnels below has a standpipe with a 4" supply.

Should a crack in this line occur, the leak would be approximately 15 cfm or 110 gpm. The water would gravitate to the "B" train electrical tunnel at El.

(-) 26'-0" and the sump at the base of the stairwell. The I

flooding scenario which would follow is similar to that described in Section 4.5.1, with approximately 1/5 t!.e water leakage rate.

RilR Equipment Vault - The stairwell in each vault has a tandpipe with a 4" supply line.

Should a through-wall crack appear in one of these lines, the leakage would be approxi ately 15 cfm or 110 gpm.

Should the sump pump and level alarm not function (non-Class IE) the water level would rise about 1/4" per hour.

l Since just one of the two redundant vaults involved and since the problem would be discovered before any safety related components ar-involved, no safety problem eFists.

l Primary Auxiliary Building - Both stairwells (#1 and #2) in the PAB have fire protection standpipes.

No. I stairwell is founded at El. (-) 26'-0" with the lowest portion of the standpipe being at (-)

6'-0".

A leak in the 4" standpipe or supply line would amount to 15 cfm or 110 gpm. The water would f all through the stairwell structure to the base mat at El. (-) 26'-0" and the sump 3 would collect with redundant Class 1E level alarms. Only 450 ft I

in the first half hour and this would not cause any safety problem.

I Stairwell No. 2 is founded at the 7'-0" elevation.

It also has a 4" standpipe and 4" supply line. A 15 cfm leak would flow across the floor at El. 7'-0" and enter 1 or more of the 17 floor drains at the level. These lead to the sump at El. (-) 26'-0" and the redundant Class lE level alarms. Thus this tailure would cause no safety problem.

Control Building - The stairwell serving the Control Building has a fire protection standpipe fed by a 6" line.

Leakage would be t

approximately 26 cfm or 200 gpm. The water would fall to the base of the stairwell at El. 21'-6".

At this point there are two doors

- one to the exterior of the building and one to electrical equip-ment room which is the first floor of the Control Building. Since these doorr, are not water-tight, leakage will occur under and around them.

"As-built" clearances below the doors are not known --

I at this time. However, if the clearance at the bottom of each door is 1/2", approximately 100 gpm will pass below each door with a head or build-up of about 1 1/2 inches of water on the floor.

Water entering the train "A" electrical equipment room (maximum depth 1/2") will be carried away by a 4" floor drain to the storm sewer. Should the floor drain be partially or completely blocked, the water would run by the two doors to the train "B" room and another 4" floor drain.

Conceivably, the water could also leave the train "B" roo.n by two more doorways, one to the Turbine Building Heater bay I

'/

/ (and more floor drains) and the second to the non-essential switchgear room. From here it would pass below double doors to the exterior of the building. Nowhere in any of the three electrical equipment rooms would the water become deep enough to make any shut-down components inoperable.

I I

I I

I I

I I

I

5.0 CONCLUSION

S there is,n_o pipeline of 5.1 In general, the study revealed that o

moderate energy in the Seabrook plant whose failure by a through-wall crack and resulting spraying and ficoding would prevent the plant from achieving a safe shutdown.

5.2 The major redundant systems and components required to shut the plant down are located in the RHR, Containment Spray and Safety Injection Vaults. A major flood in either redundant vault will not prevent the systems and components in the other vault from bringing the plant to a safe shutdown. A single failure of any moderate energy line cannot cause flooding of both vaults.

5.3 The Primary Auxiliary Building has many large and small moderate energy lines with the 24" Service Water and 24" s

Primary Component Cooling Water lines predominating. Water from a crack in either of these two systems will not cause flooding at any elevation except the lowest in the building (-)26'-0".

One or both Class 1E level alarms in the sump at this elevation will warn the operator of a I

potential flooding condition. Should a flooding condition start, the water would leak through the metal partition separating the PAB from the Containment piping penetration area. From here, the water would enter a floor drain at E1. (-)34'-6" and drain to the sump in Train "A" RHR vault. While it may cause some flooding here, Train "B" systems are available for plant shut-down.

I I

I.

5.4 The Control Building complex has a very low probability for flood-ing conditions to exist. The only moderate energy line in the Control Room itself is a small potable water line which is located in the area of two floor drains. The Cable Spreading Room has no moderate energy lines but it has two 6" floor drains to carry away the water in the unlikely event of the fire protection deluge system activation. n e electrical equipment room at grade has no moderate energy lines, but could possibly be exposed to water coming in under the outside door from the fire protection piping in the adjoining stairwell. Bis would be removed by a floor drain in each train area.

5.5 The Diesel Generator Building has several on and off-engine moderate energy lines. As with the RhR vaults, the flooding of one diesel generator area will not result in flooding its redundant twin. Thus, while one side of the building could be flooded with up to 10' of water at El. (-)l6'-0", with the Fuel Oil Transfer Pump inoperable, I

the other diesel train is intact and available for plant shut-down.

5.6 The Emergency Feedwater Pumphouse is not subj ect to flooding and subsequent component or system failure by any conceivaM.e failure of a moderate energy line in that area.

5.7 Likewise the Service Water Pumps and other safety related components in the Service Water Pumphouse are not subj ect to failure due to flooding resulting from a service water or any other moderate energy line break.

I B -

E

/

5.8 A watertight door at the south end of each Main Steam and Feed-

~

water Pipe Chase would prevent Class IE electrical components from being inundated and subsequently failing if the Emergency Feedwater Pump discharge line f ailed in either chase.

Minor flooding of the order of one foot from this break would not cause failure of any safety related components in the area.

I 5.9 In the Containment Enclosure Ventilation Fan Room, flooding is prevented following a leak in a PCCW line through the floor drains and/or the gravitation of the water to El. (-)30'-0" in the annulus between the Containment Building and the Containment Enclocure Building.

5.10 Failure of moderate energy lines in buildings which do not contain systems or components required for safe shut-down cannot cause fail-ure of systems or components required for safe shut-down and which are located in adjacent buildings.

I 5.11 Several stairwells in the various buildings of the plant contain fire protection stand pipes and hose reels.

In no case would a crack in one of these moderate energy lines cause a failure of I

safe shut-down equipment within that or adjoining building.

I I

I I

I I

--.-s----

B 6.0 LIST OF TABLES I

Table No. 4.1 RHR CONTAINMENT SPRAY & SAFETY INJECTION EQUIPMENT VAULTS Essential Components I

El. (-)61'-0", (-)50'-0", (-)31'-10", (-)9'-0",

3'-2" Equipment I.D.

Description Elevation Ril-P-8A Pump Motor El. (-)S5'-0" Ril-P-8 B Pump Motor El. (-)SS'-0" Ril-FCV-618 Flow Control Valve El. (-)37'-8" Ril-RCV-619 Flow Control Valve El. (-)37'-8" Ril-7.S-618 Position Switches El. (-)37'-8" Ril-ZS-619 Position Switches El. (-)37'-8" Ril-FY-618-1 Solenoid Pilot Valve El. (-)37'-8" Ril-FY-619-1 Solenoid Pilot Valve El. (-)37'-8" RH-IIY-606-1 Solenoid Pilot Valve El. (-)24'-9" Ril-IIY-607-1 Solenoid Pilot Valve El. (-)24'-9" Ril-ZS-606 Position Switch El. (-)24'-9" Ril-ZS-607 Position Switch El. (-)24'-9" B

Ril-HCV-606 Flow Control Valve El. (-)24'-9" Ril-IICV-607 Flow Control Valve El. (-)24'-9" CBS-V2 Motorized Valve El. (-)15'-0" I

C BS-V'i Motorized Valve El. (-)15'-0" CC-V-145 Motorized Valve El. 6'-0" CC-V-272 Motorized Valve El. 6'-0" CC-ZS-145 Position Switch El. 6'-0" CC-7.S-2 7 2 Position Switch El. 6'-0" 8

I I l

.~...$.5%Af5]Y k l..(Y-khh'4 $.? h & JD E.Y ; "l l OL ?-d'iiS $7 iL Table No. 4.2 PRIMARY AUXILIARY BUILDING ESSENTIAL COMPONENTS

'- [

El. (-)26'-0",

(-)6'-0",

7'-0",

25'-0", 42'-0",

53'-0"

(

a Equipment I.D.

Description Elevation CS-P-2A Pump El. 10'-6" CS-P-2B Pump El. 10'-6" CC-P-llA Pump El. 28'-0" CC-P-llB Pump El. 28'-0" CC-P-llc Pump El. 28'-0" CC-P-ilD Pump El. 28'-0" 4

CS-P-3A Pump El. 26'-4" CS-P-3B Pump El. 26'-4" CS-V-426 Valve El. 27'-0" CS-ZS-426 Position Switch E1. 27'-0" PAH-FN-42A Fan El. 42'-0" PAH-FN-42B Fan E1. 4 2 ' -0" 7

PAH-DP-43A Damper El. 42'-0" PAH-DP-43B Damper El. 42'-0*

PAH-FY-43A Solenoid Pilot Valve El. 42'-0" i

PAH-FY-43B Solenoid Pilot Valve E1. 4 2 '-0" PAH-ZS-43A Solenoid Pilot Valve El. 42'-0" PAH-ZS-43B Solenoid Pilot Valve El. 4 2 '-0" CC-TV-2171-1 Valve El. 41'-0"

~

CC-TV-2171-2 Valve E1. 41'-0" CC TY-2171-1 Solenoid Pilot Valve El. 41'-0" CC-TY-2171-2 Solenoid Pilot Valve El. 41'-0" l

CC-TY-2172-1 Solenoid Pilot Valve El. 41'-0" j]l CC-TY-2172-2 Solenoid Pilot Valve El. 41'-0" CC-ZS-2171-1 Solenoid Pilot Valve E1. 41'-0" CC-ZS-2171-2 Solenoid Pilot Valve El. 41'-0" l

CC-ZS-2172-1 Solenoid Pilot Valve El. 41'-0" CC-ZS-2172-2 Solenoid Pilot Valve El. 41'-0" CS-LCV-112B Valve El. 53'-0" CS-LCV-ll2C Valve El. 53'-0" CC-E-17A Heat Exchanger El. 53'-0" CC-E-17B Heat Exchanger E1. 53'-0" CC-TV-2271-1 Valve El. 41'-0" CC-TV-2271-2 Valve El. 41'-0" CC-TY-2271-1 Solenoid Pilot Valve El. 41'-0" CC-TY-2271-2 Solenoid Pilot Valve El. 41'-0" CC-TY-2272-1 Solenoid Pilot Valve El. 41'-0" z

i CC-TY-2272-2 Solenoid Pilot Valve El. 41'-0" g

CC-ZS-2271-1 Solenoid Pilot Valve E1. 41 '-0" N

CC-ZS-2271-2 Solenoid Pilot Valve El 41'-0" h

CC-ZS-2272-1 Solenoid Pilot Valve El. 41 '-0" CC-ZS-2272-2 Solenoid Pilot Valve E1. 41 '-0" CS-LT-7446 Level Transmitter El. 25'-0" CS-LT-7464 Level Transmitter El. 25'-0" " ~: h:. 7: p... :

w _' ' L..

J'

' n ;&.[.

.% ' W ' '..; r.., _ ~ _. x;i7 ' - [.:. V.. r ".. ',; f.. ? ~ ' '.1 ;.

Teble No. 4.2 (cont.)

El. (-)26'-0",

(-)6'-0",

7'-0",

25'-0, 42'-0, 53'-0" Equipment I.D.

Description Elevation SW-V-16 Valve El. 53'-0" SW-V-18 Valve El 53'-0" DE-E-42A Heat Exchanger El. 53'-0" DG-E-42B Heat Exchanger E1. 53'-0" CC-TK-19A CC Head Tank E1. 65'-9" CC-TK-19B CC Head Tank E1. 65'-9" CS-V-142 Valve El. (-)17'-9" (Pipe Tunnel)

CS-V-112D Valve El. 20'-0" (Tank Farm)

CS-V-112E Valve El. 20'-0" (Tank Farm)

CS-V-847 Valve El. (-)17'-9" (Radioactive Tunnel)

CS-V-846 Valve El. (-)17'-9" (Radioactive Tunnel)

SI-V-138 Valve E1. (-)17'-9" (Radioactive Tunnel)

SI-V-139 Valve El. (-)17'-9" Radioac.tive Tunnel to be Deleted CC-LT-2172-1 Level Transmitter El. 53'-0" CC-LT-2172-2 Level Transmitter EL. 53'-0" CC-LT-2172-3 Level Transmitter El. 53'-0" CC-LT-2192-1 Level Transmitter El. 53'-0" CC-LT-2192-2 Level Transmitter El. 53'-0" CC-LT-2192-3 Level Transmitter El. 53'-0" CC-LT-2272-1 Level Transmitter El. 53'-0" CC-LT-2272-2 Level Transmitter El. 53'-0" CC-LT-2272-3 Level Transmitter El. 53'-0" CC-LT-2292-1 Level Transmitter El. 53'-0" CC-LT-2292-2 Level Transmitter E1. 53'-0" CC-LT-2292-3 Level Transmitter El. 53'-0" WLD-LS-6269 Level Switch El. (-)26'-0" PAH-DP-357 Damper E1. 25'-0" PAH-DP-358 Damper El. 25'-0" I. - -.

Table No. 4.3 CONTROL BUILDING ESSENTIAL COMPONENTS El. 21'-6",

50'-0",

75'-0" Equipment I.D.

_ Description Elevation CBA-FN-19 Supply Air Fan Motor El. 51'-6" CBA-FN-20 Ret. Air Fan Motor El. 51'-6" CBA-FN-21A Exh. Fan Motor E1. 51'-6" CBA-FN-21B Exh. Fan Motor E1. 51'-6" CBA-FN-32 Supply Air Fan Motor E1. 51'-6" CBA-FN-33 Supply Air Fan Motor El. 51'-6' CBA-DP-24A Damper El. 58'-0" CBA-ZY-24A Sol. Valve E1. 58'-0" CBA-DP-24F Damper El. 58'-0" CBA-ZY-24F Sol. Valve El. 58'-0" CBA-DP-24B Damper El. 66'-2" CBA-ZY-24B Sol. Valve El 66'-2" CBA-DP-24E Damper El. 66'-2" CBA-ZY-24E Sol. Valve E1. 66'-2" CBA-DP-24C Damper El. 69'-10" CBA-ZY-24C Sol. Valve E1. 69'-10" CBA-DP-24D Damper El. 69'-10" CBA-ZY-24D Sol. Valve El. 69'-0" E-5 Elect. Bus E1. 21'-b" E-6 Elect. Bus E1. 21'-6" IIV-4 Battery El. 21'-6" HV-5 Battery El. 21'-6" IIV-6 Bnt te ry El. 21'-6" HV-7 Battery El. 21'-6" DC Bus 11A DC Switchgear El. 21 '-6" DC Bus 11B DC Switchgear El. 21'-6" DC Bus 11C DC Switchgear E1. 21'-6" DC Bus llD DC Switchgear El. 21'-6" MMCP-12 SSPS Train A E1. 21'-6" I

MMCP-13 SSPS Train B El. 21'-6" I - -

TABLE NO. 4.4 DIESEL GENERATOR BUILDING ESSENTIAL COMPONENTS El.

(-)l6'-0", 21'-6",

51'-6" I

Equipment I.D.

Description Elevation DAH-bP-16A Damper E1. 53'-0" DAH-DP-16B Damper El. 53 '-0" I

DAH-ZS-16A Position Switch El. 53'-0" DAH-ZS-16B Position Switch E1. 53'-0" DAH-FY-16A Solenoid Pilot Valve El. 53'-0" DAH-FY-16B Solenoid Pilot Valve El. 53'-0" DAH-FN-26A Exhaust Fan E1. 53'-0" DAH-FN-26B Exhaust Fan E1. 53'-0" DAH-FN-25A Supply Fan E1. 53'-0" DAH-FN-25B Supply Fan E1. 53'-0" DAll-FY-15A Solenoid Pilot Valve El. 53'-0" DAH-FY-15B Solenoid Pilot Valve E1. 53'-0" DAH-ZS-ISA Positions Switch E1. 53'-0" DAH-ZS-ISB Positions Switch El. 53'-0" DAll-DP-15A Damper E1. 53'-0" DAH-DP-15B Damper El. 53'-0" DG-1A Diesel Generator El. 21'-6" DG-1B Diesel Generator E1. 21'-6" I

TK-45A D.G. Starting Air Receiver El. 21'-6" TK-45B D.G. Starting Air Receiver E1. 21'-6" TK-45C D.G. Starting Air Receiver El 21'-6" TK-45D D.G. Starting Air Receiver El. 21'-6" TK-26A D.G. Fuel Oil Storage Tank El. (-)l6'-0" TK-26B D.G. Fuel Oil Storage Tank El. (-)l6'-0" P-38A D.C. Fuel Oil Transfer Pump El. (-)l6'-0" P-38B D.G. Fuel Oil Transfer Pump El. (-)l6'-0" TK-78A D.G. Fuel Oil Day Tank E1. 55'-6" TK-78B D.G. Fuel Oil Day Tank E1. 55'-6" TK-46A D.G. PCCW Expansion Tank El. 67'-6" TK-46B D.G. PCCW Expansion Tank El. 67'-6" I

l I <

G a

,r,-

I TABLE No. 4.5 EMERGENCY FEEDWATER PUMP HOUSE ESSENTIAL COMPONENTS El. 27'-0" Equipment I.D.

Description Elevation FW-FT-4214-2 Flow Transmitter M1. 27'-0" FW-FT-4214-4 Flow Transmitter El. 27'-0" FW-FT-4214-5 Flow Transmitter E1. 27'-0" FW-FT-4424-2 Flow Transmitter El. 27'-0" FW-FT-4424-4 Flow Transmitter El. 27'-0" FW-FT-4424-5 Flow Transmitter El. 27'-0" FW-FT-4234-2 Flow Transmitter El. 27'-0" FW-FT-4234-4 Flow Transmitter El. 27'-0" FW-FT-4234-5 Flow Transmitter E1. 27'-0" FW-FT-4244-2 Flow Transmitter El. 27'-0" FW-FT-4244-4 Flow Transmitter E1. 27'-0" FW-FT-4244-5 Flow Transmitter El. 27'-0" FW-FV-4214B SG. A Emerg. FW. Cont. Valve E1. 28' '"

FW-FV-4224B SG. B Emerg. FW. Cont. Valve E1. 16 '-3" FW-FV-4234B SG. C Emerg. FW. Cont. Valve Bl. 28'-3" FW-FV-4244B SG. D Emerg. FW. Cont. VaD;e E1. 28'-3" FW-FV-4214A SG. A Emerg. FW. Coct. Valve El. 31'-3" FW-FV-4224A SG. B Emerg. FW. Cont. Valve El. 31'-3" FW-FV-4234A SG. C Emerg. TcW. Cont. Valve E1. 31'-3" FW-FV-4244A SG. D Emerg. FW. Cont. Valve El. 31'-3" EPA-TSH-5430 Temperature Switch El. 32'-0" EPA-TSH-5431 Temperature Switch E1. 32'-0" FW-P-37B Emerg. FW. Pump El. 30'-6" FW-P-37A Emerg. FW. Pump El 30'-6"

' EPA-FN-47A Fan El. 40'-0" EPA-FN-47B Fan El. 40 '-0" FW-PI-4209 Pressure Indicator El. 27'-0" FW-PI-4208 Pressure Indicator El. 27'-0" lI,I

TABLE NO. 4.6 SERVICE WATER PUMP HOUSE ESSENTIAL COMPONENTS E1. 21'-0" Equipment I.D.

Description Elevation I

SW-P-41A Pump El. 21'-0" I

SW-P-41B Pump El. 21'-0" SW-P-41C Pump El. 21'-0" SW-P-41D Pump El. 21'-0" SWA-FN-40A Fan El. 22'-0" SWA-FN-40B Fan El. 22'-0" I

SWA-TSil-5614-1 Temp Switch El. 22'-0" SWA-TSH-5614-2 Temp Switch El. 22'-0"

~

SWA-TSil-5615-1 Temp Switch E1. 22'-0" SWA-TSH-5515-2 Temp Switch El. 22'-0" SW-V2 Valve El. 23'-6" SW-V22 Valve E1. 23'-6" SW-V29 Valve El. 23'-6" SW-V31 Valve E1. 23'-6" SW-V4 Valve El. 70'-5" (Tank Farm) l SW-V5 Valve E1. 70'-5" (Tank Farm)

I

[lI lI 1 i

L

TABLE No. 4.7 MAIN STEAM & FEEDWATER PIPE CHASES ESSENTIAL COMPONENTS El. 3'-0".

12'-0",

20'-0",

26'-6", 42'-0" Equipment I.D.

Description Elevaticn MS-V-86 M.S. Isolation Valve El. 28'-0" MS-ZS-86A Position Switch El. 28'-0" MS-ZS-86B Position Switch El 28 '-0" MS-ZS-204 Position Switch El. 28'-0" MS-V-204 Bypass Valve E1. 28'-0" MS-FY-89A-1 Solenoid Pilot Valve El 28'-0" MS-FY-89B-1 Solenoid Pilot Valve El. 28'-0" MS-FY-102A-1 Solenoid Pilot Valve El. 28'-0" I

MS-FY-102B-1 Solenoid Pilot Valve E1. 28'-0" MS-FY-il7A-1 Solenoid Pilot Valve E1. 28'-0" MS-FY-ll7B-1 Solenoid Pilot Valve El. 28'-0" MS-V-88 M.S. Isolation Valve E1. 28'-0" MS-ZS-88A Position Switch El. 28'-0" MS-ZS-88B Position Switch El. 28'-0" MS-ZS-205 Position Switch El. 28'-0" MS-V-205 Bypass Valve El. 28'-O" MS-FY-89A-2 Solenoid Pilot Valve El. 28 '-0" MS-FY-89A-2 Solenoid Pilot Valve El. 28'-0" MS-FY-102A-2 Solenoid Pilot Valve El. 28'-0" MS-FY-102B-2 Solenoid Pilot Valve El. 28'-0" MS-FY-117A-2 Solenoid Pilot Valve El. 28'-0" MS-FY-ll7B-2 Solenoid Pilot Valve El. 28'-0" MS-V-90 M.S. Isolation Valve El. 28'-0" MS-FY-89A-3 Solenoid Pilot Valve El. 28'-0" MS-FY-89B-3 Solenoid Pilot Valve El. 28'-0" MS-FY-102A-3 Solenoid Pilot Valve El. 28'-0" I

MS-FY-102B-3 Solenoid Pilot Valve El. 28'-0" MS-FY-l l 7 A-3 Solenoid Pilot Valve El. 28'-0" MS-FY-117B-3 Solenoid Pilot Valve E1. 28'-0" MS-ZS-90A Position Switch El. 28'-0" MS-ZS-90B Position Switch El. 28'-0" MS-ZS-206 Position Switch El. 28'-0" MS-ZS-206 Bypass Valve El. 28'-0" MS-V-92 M.S. Isolation Valve E1, 28'-0" MS-FY-89A-4 Solenoid Pilot Valve El. 28'-0" MS-FY-89B-4 Solenoid Pilot Valve El. 28'-0" I

MS-FY-102A-4 Solenoid Pilot Valve El. 28'-0" MS-FY-102B-4 Solenoid Pilot Valve E1. 28'-0" MS-FY-ll7A-4 Solenoid Pilot Valve el. 28'-0" l L.

TABLE NO. 4.7 (Cont'd.)

MAIN STEAM & FEEDWATER PIPE CHASES ESSENfIAL COMPONENTS I

El.

3'-0",

12'-0",

20'-0",

26'-6", 42'-0" Equipment I.D.

Description Elevation MS-FY-ll7B-4 Solenoid Pilot Valve El. 28'-0" MS-ZS-92A Position Switch El. 28'-0" MS-ZS-92B Position Switch El. 28'-0" MS-PT-3178 Pressure Trans.

El. 28'-0" MS-PT-3174 Pressure Trans.

El. 28'-0" SB-V-9 Valve El.

3'-0" SB-V-10 Valve El.

3'-0" SB-V-Il Valve El 3'-0" SB-V-12 Valve El.

3'-0" s

SS-FY-1900A Solenoid Valve El.

3'-0" SB-FY-1900B Solenoid Valve E1.

3'-0" SB-FY-1901A Solenoid Valve E1.

3'-0" SB-FY-1901B Solenoid Valve E1.

3'-0" SB-FY-1902A Solenoid Valve E1.

3'-0" SB-FY-1902B Solenoid Valve El.

3'-0" SB-FY-1903A Solenoid Valve El.

3'-0" SB-FY-1903B Solenoid Valve El.

3'-0" MS-PT-3173 Pressure Trans.

El. 28'-0" MS-PT-3179 Pressure Trans.

El. 28'-0" MS-V-127 Valve El. 28'-0" MS-V-128 Valve El. 28'-0" MS-PV-3001 Valve El. 28'-0" MS-PV-3002 Valve El. 28'-0" MS-PV-3003 Valve E1. 28'-0" MS-PV-3004 Valve El. 28'-0" l

r F

l lll

TABLE NO. 4.8 CONTAINMENT ENCLOSURE ESSENTIAL COMPONENTS I

El. 21'-6" Equipment I.D.

Description Elevation t

I EAH-FN-5A Fan El. 21'-6" EAH-FN-5B Fan El. 21 '-6" EAH-AC-2A Air Cooler El. 21'-6" EAH-AC-2B Air Cooler El. 21'-6" EAH-ZS-3A Position Switch El. 21'-6" EAH-ZS-3B Position Switch El. 21'-6" EAll-DP-3A Damper El. 21'-6" EAH-DP-3B Damper El. 21'-6" EAH-ZS-37B Position Switch El. 36'-0" EAH-FY-37B Solenoid Pilot Valve El. 36'-0" EAll-DP-37B Damper El. 36'-0" EAH-ZS-37A Position Switch El. 37'-8" EAH-FY-37A Solenoid Pilot Valve El. 37'-8" EAH-DP-37A Damper El. 37'-8" EAH-ZS-25A Position Switch El. 44'-3" EAH-ZS-25B Position Switch El. 44'-3" EAll-DP-25A Damper El. 44'-3" EAH-DP-258 Damper El. 44'-3" EAll-FN-31 A Fan El. 44'-3" KAH-FN-llR.

F:m El. 44'-1" - - _,

a.

- /