_

Thomas J. Martin Public Service Electric and Gas Company 80 Park Plaza Newark, N.J. 07101 201/4304316 Vice Presid(:nt Engineering and Construction May 25, 1984 Dr. Thomas E.

Murley, Administrator U. S. Nuclear Regulatory Commission Office of Inspection and Enforcement Region I 631 Park Avenue King of Prussia, Pennsylvania 19406

Dear Dr. Murley:

POTENTIAL CONSTRUCTION DEFICIENCY DEFECTS IN LUBE OIL PUMP DISCHARGE NOZZLES HOPE CREEK GENERATING STATION On April 25, 1984, a verbal report was made to Region I, Office of Inspection and Enforcement rerresentative, Mr.

E.

C.

iMcCabe, advising of a potentia]'

ricant construction deficiency regarding cracked '

our diesel generator lube oil pump discharge no7-

_.e following interim report is provided in ac with 10CFR50.55 (e).

Colt Industries submittet art 21 Report to Region III concerning a broken boss on a lube oil pump discharge nozzle discovered during factory testing of a diesel generator set.

A second lube oil pump was examined and the boss area was found to be cracked.

Colt reported that the noted conditions significantly reduce the sealing area between the pump and the threaded adapter.

.4 Our Architect / Engineer and Constructor, Bechtel, inspected the identical components on our diesel generator setc and.,

found cracks and casting discrepancies at the boss connections.

Bechtel has issued Nonconformance Report No. 3826 to document and control the hardware.

t m

)

t 8406120456 8405e3 PDR ADOCK 05000354 S

PDR 80 g,

, c,,

A, Dr. T. E. Murley 2

5/25/84 m

e A~ report conveying the requisite safety analysis and full details concerning our corrective actions will be submitted to.yourtoffice by July 13, 1984.

?

y A

Very truly yours, 4 ~;

g f

f s

/

s C Office of Inspection and Enforcement Division of Reactor Construction Inspection x,

Washington, D.~C.

20555 NRC' Resident' Inspector - Hope Creek P. O. Box 241 Hancocks. Bridge, NJ 08038 Records Center Institute of Nuclear Power Operations 1100 Circle'75 Parkway, Suite 1500