Text
,i 1
VIRGINIA POWER. COMPANY i
NORTH ANNA POWER STATION MONTHLY OPERATING REPORT MONTH:
June YEAR:
1995 1
Approved:
O Station Manager 9507200035 950713 PDR ADOCK 05000338 PDR R
OPERATING DATA REPORT l
l.
DOCKET NO.:
50-338 DATE: July 5, 1995 CONTACT: J. A. Stall l
PHONE: (703) 894 2101 OPERATING STATUS i
i 1.
Unit Name:................................ North Anna 1 2,
Reporting Period:........................ June 1995 3.
Licensed Thermal Power (MWt):.............
2,893 4.
Nameplate Rating (Gross MWe):.............
994 5.
01 sign Electrical Rating (Net MWe):.......
907
(
6.
Mrximum Dependable Capacity (Gross MWe):..
948 7.
MIximum Dependable Capacity (Net MWe):....
900 1
1 S.
If changes occur in Capacity Ratings (Items No. 3 thru 7) since last report, give reasons: _N/A 9.
Power level to which restricted, if any (Net MWe): _ N/A
- 10. R2asons for restrictions, if any:
N/A This Month Y-t-D Cumulative
- 11. Hours in Reporting Period.........................
720.0 4,343.0 149,219.0
- 12. hanber of Hours Reac t or was Cr i t i cal......................
720.0 4,321.6 112,769.4
- 13. Reac tor Reserve Shutdown Hours..............
0.0 20.9 6,951.4
- 14. Hours Generator On-Line........
720.0 4,316.8 109,770.5
- 15. Unit Reserve Shutdown Hours........
0.0 0.0 0.0 j
- 16. Gross Thermal Energy Generated (MWH)...................... 2,082,164.1 12,421,268.6 292,606,848.5
- 17. Gross E lec t ri cal Energy Generated (MWH)...................
684,018.0 4,086,277.0 96,161,897.0
- 18. Net Electrical Energy Generated (MWH)..................
650,019.0 3,887,458.0 91,089,744.0
- 19. Unit Service Factor.......................................
100.0%
99.4%
73.6%
- 20. Unit Availability Factor..................................
100.0%
99.4%
73.6%
- 21. Unit Capacity Factor (using MDC Net)......................
100.3%
99.5%
68.3%
i
- 22. Unit Capacity Factor (using DER Net)......................
99.5%
98.7%
67.3%
- 23. Forced Outage Rate........................................
0.0%
0.6%
9.6%
- 24. Shutdowns Scheduled Over Next 6 Months (Type, Date, and Duration of Each):_N/A
- 25. If Shutdown at end of Report Period, estimated time of Startup:_N/A
- 26. Units in Test Status (Prior to Consnercial Operation):
Forecast Achieved INITIAL CRITICALITY INITIAL ELECTRICITY COMMERCIAL OPERATION
i
?
AVERAGE DAILY UNIT POWER LEVEL i
Docket No.:
50-338 Unit:
NA-1
}
Date:
Julv 5, 1995 J
Contact:
J. A.
Stall Phone:
(703) 894-2101 MONTH: June 1995 DAY AVERAGE DAILY POWER DAY AVERAGE DAILY POWER LEVEL (MWe-Net, LEVEL (MWe-Net) 1 904 17 303 2
904 18 903 3
904 19 902 4
904 20 902 5
904 21 903 6
904 22 902 7
904 23 894 8
904 24 903 9
904 25 902 b
10 904 26 902 11 903 27 902 12 903 28 903 13 903 29 903 14 903 30 902 15 903 16 903 Instructions:
On this format, list the average daily unit power level in MWe-Net for each day in the reporting month.
Compute to the nearest whole megawatt.
's
NORTH ANNA POWER STATION 1
UNIT NO.:
1 MONTH:
June
SUMMARY
OF OPERATING EXPERIENCE Page 1 of 1 Listed below in chronological sequence is a
summary of operating experiences for this month which required load reductions or resulted in significant non-load related incidents.
Date Time Data June 01, 1995 0000 Began month with unit at 100% power, 952 MWe.
June 23, 1995 0939 Commenced ramping unit from 100% power, 950 MWe for performance of Turbine Valve Freedom Test (TVFT).
1030 Unit stable at 90% power, 865 MWe.
1148 Turbine Valve Freedom Test completed satisfactory.
1200 Commenced ramping unit from 90% power, 861 MWe following TVFT.
1331 Unit stable at 100% power, 950 MWe.
June 30, 1995 2400 Ended month with unit at 100% power, 938 MWe.
1
e Page 1
of 1
UNIT SHUTDOWN AND POWER REDUCTIONS Explanation Sheet Docket No.:
50-338 Report Month June Unit Name:
NA-1 Year:
1995 Date: Julv 5.
1995
Contact:
J.
A.
Stall No entry this month.
UNIT SHUTDOWNS AND POWER REDUCTIONS DOCKET NO.:
50-338 UNIT NAME:
NA-1 DATE: July 5, 1995 REPORT MONTH: June 1995 CONTACT: J. A. Stall PHONE: (703) 894-2101.
1 2
3 4
5 No.
Date Type Duration Reason Method of Licensee System Component Cause & Corrective (hrs)
Shutting Event Code Code Action to Down Reactor Report #
Prevent Recurrence No Entry This Month O
4 1: Type 2: Reason 3: Method 4:
F= Forced A= Equipment Failure (explain) 1= Manual Exhibit F - Instructions S= Scheduled B= Maintenance or Test 2= Manual Scram for preparation of Data C= Refueling 3= Automatic Scram Entry Sheets for Licensee-D= Regulatory Restriction 4= Continuations Event Report (LER) File E= Operator Training & License Examination 5= Load Reduction (NUREG-0161)
F= Administrative 9=Other G= Operational Error 5:
H-Other (explain)
Exhibit H - Same Source
OPERATING DATA REPCRT DOCKET NO.:
50-339 DATE: July 5, 1995 CONTACT:
J. A. Stall PHONE: (703) 894-2101 OPERATING STATUS 1.
Unit Names................................ North Anna 2 2.
Rrporting Period:......................... June 1995 3.
Li censed Therma l Power (MWt ):.............
2893 4.
Nameplate Rating (Gross MWe):.............
979 5.
Dzsign Electrical Rating (N2t MWe).......
907 6.
Mixinum Dependable capacity (Gross MWe):..
935 7.
nsximum Dependable Capacity (Net MWe):....
887 8.
If changes occur in Capacity Ratings (!tems No. 3 thru 7) since last report, give reasons: _ N/A 9 Power level to which restricted, if any (Net MWe):
N/A
- 10. Reasons for restrictions, if any:
N/A This Month YtD Cumulative
- 11. Hv 7 in Reporting Period.................................
720.0 4,343.0 127,487.0
- 12. NLam r of Hours Reac t or has Cr i t i cal......................
720.0 2,732.7 105,666.2
- 13. Reac tor iteserve Shutdown Hours...........................
0.0 1.3 6,510.2
- 14. Hours Generator On-Line..........
707.4 2,700.9 104,536.6 1
- 15. Unit Reserve Shutdown Hours...............................
0.0 0.0 0.0
)
I
- 16. Gross Thermal Energy Genera t ed (MWH )..................... 1,849,601.9 6,724,738.1 283,340,702.1
- 17. Gross E l ect r i cal Energy Generat ed (MWH)...................
605,837.0 2,193,537.0 92,670,394.0
- 18. Net Elec t rical Energy Generat ed (MWH).....................
573,605.0 2,074,464.0 88,614,432.0
]
- 19. Unit Service factor...........................
98.2%
62.2%
82.0%
- 20. Unit Availability Factor.................................
98.2%
62.2%
82.0%
- 21. Unit Capacity Factor (using MDC Net)......................
89.8%
53.9%
77.3%
- 22. Uni t capac i ty F ac t or (usi ng DE R Net )......................
87.8%
52.7%
76.6%
- 23. Forced Outage Rate........................................
0.0%
0.0%
5.0%
- 24. Shutdowns Scheduled Over Next 6 Months (Type, Date, and Duration of Each):
N/A
- 25. If Shutdown at end of Report Period, estimated time of Startup:
N/A
- 26. Units in Test Status (Prior to Commercial Operation):
Forecast Achleyed IN!11AL CRITICALITY INITIAL ELECTRICITY COMMERCIAL OPERATION r
=.
4:
1 AVERAGE DAILY UNIT POWER LEVEL l
'l Docket No.:
50-339 Unit:
NA-2 Date:
Julv 5, 1995
Contact:
J.
A.
Stall Phone:
(703) 894-2101 j
f 9
MONTH: June 1995 i
i DAY AVERAGE DAILY POWER DAY AVERAGE DAILY POWER LEVEL (MWe-Net)
LEVEL (MWe-Net) 1 84 17 910 2
184 18 909 3
299 19 908 4
586 20 908 5
728 21 907 6
799 22 907 7
733 23 908 8
733 24 909 l
9 759 25 908 l
10 908 26 904 11 909 27 820 12 909 28 910
-l 13 910 29 911 14 910 30 909 15 911 16 910 q
t I
Instructions:
On this format, list the average daily unit power level in MWe-Net for each day in the reporting month.
Compute to the nearest-whole megawatt, u
1 1
NORTH ANNA POWER STATION UNIT NO.:
2 MONTH:
June
SUMMARY
OF OPERATING EXPERIENCE Page 1 of 2 Listed below in chronological sequence is a summary of operating experiences for this month which required load reductions or resulted in significant non-load related incidents.
Date Time Data June 01, 1995 0000 Began month with unit stable at 4.7% Reactor power in Mode 2, waiting for chemistry hold to clear to increase power and go on line following 1995 Refueling / Steam Generator Replacement outage.
June 01, 1995 0931 Unit entered Mode 1.
1239 Unit placed on-line.
Commenced ramp-up to 30%
power.
1323 Unit stable at 30% power, 231 MWe.
June 03, 1995 0940 Commenced unit ramp-up following release from Chemistry hold.
Unit at 30% power, 231 MWe.
1445 Unit stable at 50% power. Suspended unit ramp-up due to high sulfate concentrations in Steam Generators.
June 1,
1995 0339 Chemistry hold cleared.
Commenced unit ramp-up.
1010 Unit stable at 74.5%
- power, 707 MWe for Chemistry hold.
June 05, 1995 1048 Cleared Chemistry hold.
Commenced unit ramp-up.
Unit at 75% power, 718 MWe, 1228 Suspended unit ramp-up due to Chemistry Action Level I
on sodium in "A"
and "C"
Unit at 81.5% power, 779 MWe.
1343 Cleared Action Level for Steam Generator chemistry.
Commenced unit ramp-up.
1601 Unit stable at 88%
power (nuclear instrumentation) and 100%
power (delta temperature).
June 06, 1995 0155 Commenced unit ramp-up following nuclear instrumentation calibration and adjustment.
Unit at 88.3% power, 843 MWe.
I
~
SUMMARY
OF OPERATING EXPERIENCE Page 2 of 2 June 06, 1995 0410 Secured unit ramp-up to allow power level verification.
Unit at 96% power (nuclear instrumentation) and 95% power (calorimetric),
900 MWe.
1435 Commenced unit ramp-down due to decreasing Main Condenser vacuum.
1512 Unit stable at 84 % ' power, 782 MWe.
Main Condenser vacuum returning to normal.
1800 Chemistry hold cleared.
All secondary-parameters within specifications.
Commence condenser waterbox leakage testing.
June 09, 1995 1645 Commence power increase after waterbox maintenance.
June 10, 1995 0023 Unit stable at 100% power, 948 MWe.
June 27, 1995 1228 Commenced ramping unit off-line due to failure of "B" Solid State Protection PT (action of T.
S.
3.3.1.1 and 3.3.2.1).
1 1413 Unit ramp-down secured at 33% power, 266 MWe, 1416 "B"
Train of Solid State Protection declared operable.
1438 Commenced unit ramp-up to 100% power.
Unit at 34.5% power, 270 MWe.
1743 Stopped unit ramp-up for calorimetric calibration of nuclear instrumentation.
Unit at 90% power, 857 MWe.
1750 Commenced unit ramp-up to 100% power.
1835 Unit stable at 100% power, 951 MWe.
June 30, 1995 2400 Ended month with unit stable at 100% power, 950 i
Mwe.
Page 1
of 1
UNIT SHUTDOWN AND POWER REDUCTIONS Explanation Sheet Docket No.:
50-339 f
Report Month June Unit Name:
NA-2 Year:
1995 Date: July 5, 1995
Contact:
J.
A.
Stall
- 95-02 Power reduction initiated from 100% power due to failure of "B"
Solid State Protection Testing on June 27, 1995 at 1228 hours0.0142 days <br />0.341 hours <br />0.00203 weeks <br />4.67254e-4 months <br />.
Ramp terminated at 33% power June 27, 1995 at 1413
- hours, i
l
DOCKET NO.:
50-339 UNIT NAME:
NA-2 DATE: July 5, 1995 REPORT MONTH: June 1995 CONTACT:
J.
A.
Stall PHONE: (703) 894-2101 1
2 3
4 5
3 No.
Date Type Duration Reason P-athod of Licensee System Component Cause & Corrective (hrs)
Shutting Event Code code Action to y
Down Reactor Report #
Prevent Recurrence 6
95-02 950627 F
0 B/A 5
N/A N/A N/A N/A g
y i
En G
1: Type 2: Reason 3: Method 4:
3 F= Forced A= Equipment Failure (explain) 1= Manual Exhibit F-Instructions S= Scheduled B= Maintenance or Test 2= Manual Scram for preparatict' tta f
C= Refueling 3= Automatic Scram Entry Sheets
-_ __censee M
D= Regulatory Restriction 4= Continuations Event Report (LER) File y
E= Operator Training & License Examination 5= Load Reduction (NUREG-0161)
.it F= Administrative 9=Other gy G= Operational Error 5:
N h-H=Other (explain)
Exhibit H - Same Source M
'9 y
e i
l 1
i Corrected Page May 1995 North Anna Monthly Operating Report i