7 PHILADELPHIA ELECTRIC COMPANY jj O:.

2301 MARKET STREET

,~f 3

Qj L,e>

PHILADELPHI A. PA.19101 j

>7g

\\ i,g 1215)841 40o0

%s-[

3,D December 28, I974

Y Mr. A. Giambusso Deputy Director of Reactor Projects I

United States Atomic Energy Commission Directorate of Licensing Washington, DC 20545

Dear Mr. Giambusso:

Subject:

Abnormal Occurrence The following occurrence was reported to Mr. Walt Baunack, A.E.C. Region 1 Regulatory Operations Office on December 19, 1974.

Written notification was made to Mr. James P. O'Reilly, Region 1 Regulatory Operations Office on December 19, 1974.

In accordance with Section 6.7.2.A of the Technical Specifications, Appendix A of DPR-56 for Unit 3 Peach Bottom Atomic Power Station, the following report is being submitted to the Directorate of Licensing as an Abnormal Occurrence.

Reference:

License Number DPR-56 Technical Specification Reference 3 5.G Report No.:

50-278-74-38 Report Date:

December 28. 1974 I

Occurrence Date:

December 18, 1974 Facility:

Peach Bottom Atomic Power Station R.D. 1, Delta, Pennsylvania 17314 Identification of Occurrence:

Manual isolation valve from the "B" Core Spray Discharge Header to the " Stay Full system accumulator was found ' closed; this valve should be open.

Conditions Prior to Occurrence:

~

i Unit 3 at approximately 73X power.-

I Description of Occurrence:

~

1 While conducting ST 1.5 the "B" Core ' Spray' Logic System Func-tional Surveillance Test, it was not possible to pressurize between MOV-3-14-118 and MOV-3-14-128 to stroke the later valvo.

Inve stig at ion determined that the stay full system. vent solenoid, SV-5224, which opens -

on-low level,.was open. Further investigation found that the " Stay Full"

. IO hvpnp' {

?

j: A} h. d5 :-

/ z;:

,.8401230200 741228-

  • )

PDR ADOCK 05000278 8

PDR ~

C(FY SENf glONf h

Mr. A. Giambusso Occcmber 28, 1974 Page 2 accumulator was valved out of service. The " Core Spray Line Vent Accumulator Low Level" alarm was also found to be inoperabic.

Designation of Apparent Cause of Orcurrence:

The last checkoff list shows that the val ve was open, and the last calibration on this accumuis ter was prior to the checkof f list.

The reason for the valve being closed was investigated, but was not determined.

Analysis of Occurrence:

The fact that this valve was closed has very littic safety implication because the system is pressurized continuously by the con-densate transfer system. When the system was returned to service it was judged that the piping system was full except for the accumulator.

Corrective Action:

The Unit 3 Core Spray System Valve Check-Of f List was redone; no other valves were found to be "off-normal".

The " Stay Full" system valving on both Unit 2 and Unit 3 RHR and Core Spray systems were veri-ficd to be alioned properly.

The icvel annunciator microswitch which failed to alarm the low level was repaired.

Failure Data:

Nonc previous on the " Stay Full" system.

Very truly yours,

/

M. J. Cooney Ass' t Gen ' l Super intendent Generation Division 1

l cc:

Mr. J. P. O'Reilly l

Director, Reqion 1 U. S. Atomic Energy Commissio'n 631 Park Avenue King of Prussia, PA 19406

?