Text
_ _ _ _ - _ _. _
O Cp&L.
O soant I
~
Carolina Power &' Light Company June 22, 1973 i
t FILE: 5213 NG-73-llE I
i m-Mr. John F. O' Leary, Director I-
Directorate of Licensing
's
'?
}
U. S. Atomic EnerCy Commission g'
j
?
Washington, D. C.
20545 N/
2>
I-h
-]
i.,
. s.,
Dear Mr. O' Leary:
['~"
\\}
/s t
,.O H. B. ROBINSON UNIT NO. 2
,h
}
LICENSE DPR-23 t
PRESSURIZER SAFETY VALVE N0ZZLES
\\
d
.. /
I i
In our letter of July 6,1971, to Dr. Peter A. Morris we stated that we would perform a liquid penetrant inspection of the l
pressurizer safety valve nozzles during our first refueling outage.
l This inspection was to check for possible sensitization of the type i
316 stainless steel nozzle due to the hard surfacing operation during manufacture. Visual and liquid penetrant inspections were performed
{
during our recent first refueling outage. No indication of sensitization was found, and the valves were returned to service. Normal inservice i
inspection vill continue to be performed on these valves in accordance I
with ASME-Section XI, Inservice Inspection of Nuclear Reactor Coolant Systems.
Very truly yours,
[
/
l s-W //fk:
{
E.
. Iltley 1
j Vice-President t
Bulk Power Supply
{
k KEB/DBW/lw g-t ec:
Mr. C. D. Barham f
Mr. N. B. Bessac Mr. B. J. Furr h
[
Mr. D. V. Menscer
[*d Mr. D. B. Waters l
I )'
Y, f
2-0-4-a l
(
8307200327 730622 PDR ADOCK 05000261 G