Submits Status Rept Re Control Rod Drive Problem Originating from 691014 Filter Plugging Problem.Shutdown of Unit on 700418 Declared to Investigate Cause of Degradation of Drive Performance
ML20084H260
Person / Time
Site: Oyster Creek, 05000000
Issue date: 04/21/1970
From: Kelcec G
JERSEY CENTRAL POWER & LIGHT CO.
To: Morris P
US ATOMIC ENERGY COMMISSION (AEC)
Shared Package
ML20084H225 List:
References
01371, 1371, NUDOCS 8305020596
Download: ML20084H260 (2)


Text

k g., =.. -

_ _M.... -

+

e,m.g f.m f,

~ ; q-f 1

3 l:, ng x4

'7 l

'2 1 9

,..I Jersey Central PoIwM % Light Company

A y

M ADISoN AVENUE AT PUNCH BOWL Ro AD e MoRRISToWN, N.J. 07960 e 539 6111

'/

April 21, 1970 g

'/5Cc.

s

@ Nh h Dr. P,eter A. Morris, Director

b,).

/

Division of Reactor Licensing

\\/

United States Atomic Energy Commission

'M

.gs9 Nashington, D.C.

205h5 N

Ma

SUBJECT:

OYSTER CREEK UNIT NO. 1 CONTROL ROD DRIVES L

Dear Dr. Morris:

In consideration of the pontinued interest in the performance of c

the control rod drives at Oyster Creek that originated with the filter plugging problem reported to you on October 14, 1969, and the subsequent conclusions resulting from operating experience during the start-up test program, letter of March 6, 1970, it has been determined that a pre'sent status report be submitted regarding this subject.

t

'To date, all of the monitored drives have scrammed within the time limits specified, and none have exceeded the 90 percent insertion time of 3.6 seconds as referred to in your letter of November 6,1969

However,

~

from a maintenance standpoint, there is evidence of seal leakage as exhibited by drive performance monitoring during the normal withdraw cycle of the drives. This has been detemined by increased stall flows and the increase of drive water pressure required to start the drive in its withdraw motion.

The most recent experience as observed on a scram which occurred on April 7, 1970, was that upon completion of the scram, three drives, 14-35, 18-35 and 42-27, settled at notch "02" position, six inches short of full insertion, instead of the "00" position. Prior to the scram, two of these drives had been fully withdrawn from the core, and the other was partially withdrawn.

Unfortunately, none of these three drives were included in the twenty-six monitored drives (the two fully withdrawn have since been included in the monitored group). Each of the above three drives.vas inserted to the "00" position with the normal insert signal, then withdrawn to-the full out posi-tion and scrammed.

In each case, the 90 percent insertion time was kithin limits; however, each drive again settled in the "02" position. Byhhefact that each drive moved to the "00" position and remained there when 191serted by the operator it was evident that there was no~ physical restriction which would limit thh, ability of the drive to move to the full.in position.

This problem was reviewed with the General _ Electric Company; and as a result of their experience, we have been advised that t s phenomenon is attributed COPY StNT REGION _h o seal leakage.

T g/g 8305020596 700421

'[

gDRADOCK 05000219

'.01371 P.DR

pg N.r

_ =. -

.m

.g.

- S 2

~., l. L

~j g

Dr. Peter A. Morris April 21, 1970 Monitoring of stall flows and drive pressures continued with an increased nunber of drives exhibiting greater stall flows.

On April 14, 1970, another scram occurred, and all monitored scram times were within accepted limits, including drive Hos. 18-35 and 42-27 However, only one drive, Ho. 18-35, stopped in the "02" position; all others were at

^~

~7 "00 " Prior to restart, the above three questionable drives were retested with the result that all three again stopped in the "02" notch position.

1- - m _~

During start-up, drive no. 42-19 exhibited difficulty in the withdrav direction. It was inserted to the "00" position and declared inoperable.

As a ' result of the above observations and the apparent continued increase in operational problems with the control rod drives, it was decided to shut the unit down on the weekend of April 18, 1970, to inves-tigate the cause of this degradation of drive performance.

Very truly yours, C

d<-

G. Kelcee

  • Manager Generating Stations TJM;ja CC: