ML20084D205

From kanterella
Jump to navigation Jump to search
AO 50-219/74/31:on 740519,one Bergen-Paterson Hydraulic Shock & Sway Arrestor on South Core Spray Sys Found Inoperable.Caused by Loss of Hydraulic Fluid.Seven Units Replaced W/Units Equipped W/Ep Seals
ML20084D205
Person / Time
Site: Oyster Creek
Issue date: 05/20/1974
From: Carroll J
JERSEY CENTRAL POWER & LIGHT CO.
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
References
AO-50-219-74-31, NUDOCS 8304080495
Download: ML20084D205 (6)


Text

b'J

. -, v.,

4 49 a P

To:

J ar;e u P. O'1:ei1ly y

lii rect ora t e of lacy,u l t.t ory Operat l on:.

P.el:i on 1 631 Pa rl. Aventie 1:ing of Pro:.si a, l'cini::y l van i a 1910f>

l' rou :

Jersey Cent ral Po.se r r, l i p,h t Co: p,iny Oyst er C r ee?.';ncl ea r Gene ra t i nr. :; t at i on, th)cl,et 50-219 l' oil.et! I:i ve r, lleiv Je rsey O M7.il S.li.i ce t :

N>no rma l Occu rrt nce Ib' port.-! o. 50-219/71/31

  • i l a follu.ior. i:. a pieliminom y s epon inei nr. subui t 1 c. fi. 2.

Prelininary Approva1:

)-

/

_3

. n-.f-s.~

.....,,..,,. f < :--

T,/20/7:

' J. T. Car ro ll, J r.

u/*/

/

/

l) ate cc.

lir. A. Gi v.busso f

i' l

i

,,/

p'.

\\, J l, ' (

(,

\\

8304080495 740520 PDR ADUCK 05000219 S

PDR

  • p,

,.t,? /.;

con sur IWG10N

/

Initial TcIcphone Date of l

I:e, sort Dat c:

_5/20/74 U

OccurrencO

{

5/19/74

)

Jrii t i a l-1lri t t en Time of Reydrt Date:

5/IO/74 Occurren c.e :

1530 i

,i OYSTER CitEEK !;UC1. EAR GENERATING STATIO:1 FORKED RIVER, N1N JERSEY 08731 i

Abnornal occurrence Report No. 50-219/74/ R j

i IDENTIFICATION Violation of the Technical Specifications, paragraph N/ A _,

OF OCCURRESCE:

Inoperability of one I:crgen-Paterson !!ydraulie Shock and Sway l

Arrestor located on the South Core Spray Systen in the Reactor 11uildi ng.

'ihis event ir, considered to be an abnor:aal occurrence as de-i fined in the Technical Specifications, paragraph 1.15D CONDITIONS PRIOR TO OCCURDESCli:

Steady State Power Routine Shutdown llot Standby Operation Cold Shutdoun 1.oad Changes During X_ Refueling Shutdown Routine Power Operation Rout ine Start u1)

Ot her (Sneci f.v)

I Opcration i

?

I l

DiiSCRW1103 An 11.spection of the Reactor fluilding snubbers, Bergen-OF OCCul:lUINCll:

1 Paterson Type llSSA-10, located two inoperable units and five j

leaking units.

They are as follows:

t

(

l i

i t

i

+

T l

Abdurnal Occurrence i

P.eport No. 50-219/74/31 Page 2 l

l l

1 i

Unit System Condition Elevation 477287 Containuent Spray Fai1ed

-19' 469873 Containment Spray 1, cal i ng 23'

469903, Shut du.-;n Cooli ng 1,caling 51' 4698%

Core Spiay 1,cahing 75' 469855 Core Spray Failed 75' 4878 5 11 linergency Cond.

Leaking 75' 477170 A. Energency Cond.

I.enLing 75' APPARENT CAUSli X

Design Procedure OF OCCllRRiiNCE:

Manu f act u re linusual Service Condition Installation /

Inc. Envir onment al Const ruct i on Con:ponent Failure Operator

_ Other (Specify)

The cause of failure of the Core Spray System snubber was a loss of the hydraulic fluid.

This snubber has not been rebuilt since April 1973 and probably has never been rebuilt. The type of seal material in this unit is of the millabic r,un 1)olyure-thane or cast polyurethane type.

ANALYSIS OF The safety significance of this occurrence was a partial loss OCCllRRiiNCE :

of the seismic rest raining ability for the affected system.

Ilad the plant suffered a design basis earthquake, the probability t h at this system would have suffered structural damage was in-creased.

G)!ml CrlVE The scven units were replaced with units equipped with EP seals Acr10N:

and pressure tested to 4000 psi.

FAILURl! DATA:

Manufacturer:

lle rgen-Pate rs on Type:

ilSSA-10 l

l

\\

C

.-. t.,, dC, aso,'

Date:

5/20/74 Prepared by:

s,'

%,L O

O

~

To:

James P. O'P.e!Ily Directorate of Regulatory Operations Region I 631 Park Avenue King of Prussin, Pennsylvanin 19406 From:

. Jersey Central Power 6 Light Cot-pany

- Oyster Crook Nucicar Gonorating Station, Docket #50419 Forked Itiver, New Jersey 08751

Subject:

Abnomal Occurrence Report No. 50-219/74/31 1

The following is a. preliminary rsport being submitted in compliance with the Technical Specifications l

. paragraph 6.6.2.

c j

Prolin:inary Approval:

4 4

l g

h A.,.a/t?/] 5/20/74

[J. T. Carroll, Jr. M Date cc: Mr. A. Giambusso 9

.h I

Occurrenco:

1530 Report Date:

5/20/74_

0YSTER CREEK NUCLEAR GENERATING STATION FORKED RIVER, NEW JERSEY 08731 Abnornal Occurrence Report No. 50-219/74/ 31 IDFXfIFICATION Violation of the Technical Specifications, paragraph N/A OF OCCURRENCE:

Inoperability of one Bergen-Paterson Hydraulic Shock and Sway Arrestor locate'd'on tho South Core Spray System in the Reactor Building.

'Ihis event is considered to be an abnormal occurrence as de-fined in the Technical Specifications, paragraph 1.15D CONDITIONS PRIOR TO OCCURRENCE:

_ Steady State Power Routine Shutdown

_ Ilot Standby Operation

_ Cold Shutdown Load Changes During X

Refueling shutdown Routine Power Operation

_ Routine Startup Other (Specify)

Operation u

DESCRIPTION An inspection of the Reactor Building snubbers, Borgon-0F OCCURRENCE:

Paterson Type itSSA-10, located two inoperable units and five

~

leaking units. 'Ihey are as follows:

e 9

e

Systen.

Cond!t n EIevation Unit'o

~.

477287 Containment Spray Falle

-19' 4698.73 Containment Spray thakina 23' 469903 Shutdown Cooling Leaking 51' 469846 Core Spray.

!Aaking 75' 469855 Core Spray Failed' 75' 487465 B. Ernorgency Cond.

Leaking 75' 477170 A. Emergency. Cond.

Leeking 75' APPAREITT CAUSn 1 Design Procedure OP' OCCURRENG:

Manufacturo thusual Service Condition Installation /

~~ Inc. Environr., ental Construction Component Failure Operator

-Other (Specify)

The cause of failure of the Core Spray System snubber was. a-loss of the hydraulic fluid. This snubber has not boon'robuilt since Apri1.1973'and probably has-never born rebuiIt. The type

- of scal material in this unit is of the millable. gum polyure-

. thane or cast polyurethane type.

ANALYSIS OF Tho. safety significance of this occurrence was n partini loss GCCURRENW:

.of the seismic restraining ability for the affected system. Had~

the pInat suffered a design basis earthquake, the probability that this syste.s3woul'.d"havo sufferedistructural'dsmage'.was in-e 5J'.;# A;.s

.--4

.,a.,

3 4

,5, creased..

(XIPJtECTIVB

  • Ihe seven units were replaced with units equipped with EP seals ACTION:

r and ' pressure tested to 4000 psi.

V 4.-

., (

FAILURiiDATN:

Manufacturcri' BergenuPaterson Type; HSSA-10 f

ll,

,)

)s

?

g

?

/

,f g

i 4 %. d f%_cs.u_-J Date:

Prepared by&:

.. o

_ 5/20/74

.m qg

,. + -

9 g_, *;~

.o a:-

's

_