ML20083F949

From kanterella
Jump to navigation Jump to search
Responds to Generic Ltr 83-41 Re Fast Cold Starts of Diesel Generators.Emergency Diesel Generators Provided W/Prelubrication & Warmup Capabilities & Have Never Been Subj to Fast Cold Start
ML20083F949
Person / Time
Site: Fort Calhoun 
Issue date: 01/06/1984
From: William Jones
OMAHA PUBLIC POWER DISTRICT
To: Eisenhut D
Office of Nuclear Reactor Regulation
References
GL-83-41, LIC-84-002, LIC-84-2, NUDOCS 8401100426
Download: ML20083F949 (1)


Text

.

1 Omaha Public Power District 1623 Harney Omaha, Nebraska 68102 402/536-4000 January 6, 1984 LIC-84-002 Mr. Darrell G.

Eisenhut, Director U.

S.

Nuclear Regulatory Commission Of fice of Nuclear Reactor Regulation Division of Licensing Washington, D.C.

20555

Reference:

Docket No. 50-285

Dear Mr. Eisenhut:

Fast Cold Starts of Diesel Generators Generic Letter 83-41 The Commission's letter dated December 16, 1983 requested in-formation concerning fast cold starts of diesel generators (i.e.,

starts with rapid acceleration and loading without prelubrication and wa rmup).

The emergency diesel generators at the Port Calhoun Station are provided with prelubrication and warmup capabilities.

Therefore, the diesels have never been subjected to a fast cold start.

The diesels are kept warm and ready for starting by a jacket water immersion heater.

In addition, a lube oil pump circu-lates oil when the diesel is not operating.

This oil is j

warmed by flowing through the lube oil heat exchanger.

Based on this, the concerns expressed regarding fast cold starts of diesel generators affecting reliability and avail-ability are not viewed as being applicable to the Fort Calhoun Station.

Si'ncerbly,

\\

8401100426 840106 l (([L 7>K/ps DR ADOCK 05000 W.

C..Jbnes Divisio'n Manager Production Operations WCJ/DJM:jmm cc:

LeBoeuf, Lamb, Leiby & MacRae 1333 New Hampshire Avenue, N.W.

Washington, D.C.

20036 Mr.

E.

G.

Tourigny, Project Manager 8f Mr.

L.

A.

Yandell, Senior Resident Inspector l !p 45.5124 Employment with Equal Opportunity Male / female

._ -