OFFICE OF SECRE TARY 00CKLTING S EERVICE sen.oe vee Piem BHANLH wucies,ooveons ELV-01729 0470 June 29, 1990 Docket No. 50-424 U. S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, D. C.

20555-Gentlemen:

V0GTLE ELECTRIC GENERATING PLANT LICENSEE EVENT REPORT LOSS OF 0FFSITE POWER LEADS TO SITE AREA EMERGENCY In accordance with 10 CFR 50.73, Georgia power Company (GPC) hereby submits the 20, 1990.

enclosed revised report related to an event which occurred on March This revision is necessary to clarify the information related to the number of successful diesel generator starts as discussed in the GPC letter dated April 9, 19, 1990 and to update the. status of corrective 1990 and the LER dated April actions in the LER.

If the criteria for the completion of the test program is understood to be the first successful test in accordance with Vogtle Electric 14980-1 " Diesel Generator Operability Test,"

Generating Plant (VEGP) procedure then there were 10 successful starts of Diesel Generator IA an end of April 19, 1990, the date the LER 50-424/1990-06 was submitted to the NRC.

The number of successful starts included in the original LER included some of The difference is attributed to the starts that were part of the test program.

diesel start record keeping practices and the definition of-the end of the test program.

In order to correct the LER and to provide more useful and up to date information the LER has been revised to state the number of valid diesel generator tests in accordance with Regulatory Guide 1.108 rather than the number The number of valid tests was established of successful starts since the event.

by reviewing diesel generator testing data from March 21 through June 7,1990.

Sincerely, g),),hL Y Y e

W. G. Hairston, 111 WGH,lll/HWM/gm

Enclosure:

LER 50-424/1990-006-01 9505230135 950417 PDR ADOCK 05000424 Q

PDR

F.

t s

a p

1 i

j l

1 NUCLEAR REG lA.ATORY COMMISSION So.1kN*eLA 3 IN I$

Docket No * *'ilf-** 4 4 OfficialExh, No.

lu the miW.cr cf V-s el e U4.+4

(+ 't u

Staff

___fDifRIFIED RECEIVED App!rcant REJECTED

- Intervenar Contg Offr o 'l - I 7 M T Contractor CATE Other M, ness A,l e_ C o y

3. A!IlaikI Hep 0fter

Georf,ia Poner d U. S. Nuclear Regulatory Commission ELV-01729 sc: Georaia Power Comoany Mr. C. K. McCoy Mr. G. Bockhold, Jr.

Mr. R. M. Odom Mr. P. D. Rushton NORMS U. S. Nuclear Raoulatory Commission Mr. S. D. Ebneter, Regional Administrator Mr. T. A. Reed, Licensing Project Manager, NRR Mr. B. R. Bonser, Senior Resident Inspector, Yogtle 6

l

l

\\

r u.. m., -

UCENSEE EVENT REPORT (LERI En.',*d""d!!'#,"o*'a7a'o".'s,wT*.A'.".'.".3%

i TEXT CONTINUATION E "a'e'.E U  % E.**"," M c*Tl 2 W E E f2 W".i.t.,.'.T'4.T, T&#'A..v'.'.".M'." F",.m,a j

es*=.' ao=* " =>

ua numesa e ema av, m

vtan se pt mp,.6,.4vy VEGP - UNIT 1 o ls lo j e j e 1 l ?j 4 9] 0 0 l 0g 6 0;I O 2 0 ;9 4

g o,

va, n-

.= w me.nm l

A.

REQUIREMENT FOR REPORT This event is reportable per: a) 10 CFR 50.73 (a)(2)(iv), because an unplanned Engineered Safety Feature (ESF) actuation occurred when the ESF f

Actuation System Sequencer started, and b) Technical Specification 4.8.1.1.3, because a valid diesel generator failure occurred. Additionally,

)

this report serves as a sussnary of the Site Area Emergency event.

8.

UNIT STATUS AT TIME OF EVENT Unit I was in Mode 6 (Refueling) at 0% rated thermal power. The reactor had been shut down since 2-23-90 for a 45 day scheduled refueling outage. The

~

reactor core reload had been completed, the initial tensioning of the reactor vessel head studs was complete, and the outage team was awaiting permission from the control room to begin the final tensioning. Reactor level was being maintained at mid-loop with the Train A Coolant System (RCS)l (RHR) pump in service for decay heat removal.

Residual Heat Remova The temperature of the RCS was being maintained at approximately 90 degrees F.

Due to the refueling outage maintenance activities in progress, some equipment was out of service and several systems were in abnormal configurations. The Train B Diesel Generator (DG18) was out of service for a required 36 month maintenance inspection. The Train B Reserve Auxiliary Transfomer (RAT 1B) had been removed from service for an oil change. The Train B Class 1E 4160 Volt switchgear,1BA03, was being powered from the Train A RAT 1A through its alternate supply breaker. All non-1E switchgear was being powered from the Unit Auxiliary Transfomers (UAT) by backfeeding from the switchyard. All Steam Generator (S/G) nozzle dans had been removed, but only 5/G's 1 and 4 had their primary manways secured.

Maintenance personnel were in the process of restoring the primary manways on S/G's 2 and 3.

RCS level was being maintained at mid-loop for valve repairs and the S/G manway restorations. In addition, the pressurizer manway was removed to provide an RCS vent path.

C.

DESCRIPTION 0F EVENT On March 20, 1990, at approximately 0817 CST, a truck driver with a security escort entered the protected area in a fuel truck. Although not a member of the plant operating staff, the driver was a Georgia power Company employee belonging to a service group used to perform various plant services. The driver caecked the welding machine that was in the area and found that it did not need fuel. He returned to the fuel truck and was in the process of backing out of the area when he hit a support holding the phase 'C' insulator for RAT 1A. The insulator and line fell causing a phase to ground fault, and the transformer breakers tripped.

..... u r. -

g,,..

UCENSEE EVENT REPORT (LER)

%"1'.'.'?.#".'.M,l%" Nd%.T".,*J',";",'O TEXT CONTINUATION Q.gl'gg*T!'."dF,J'll27#.",SN O'.J.'. '.M"J "'?.2',MNM J

a te,*

m ;;

.+

0l1 0 l3 or 0 l9 0 0l6 VEGP - UNIT 1 o ls to lo le 1 l2 1 4 9; O 4

1 At 0820 CST, both Unit 1 RAT 1A and the Unit 2 RAT 28 High Side and low Side breakers tripped causing a loss of offsite power condition [LOSP) to the Unit 1 Train A Class 1E 4160 volt bus IAA02, the Unit 2 Tra4n B Class IE bus 2BA03, and the 480 volt busses supplied by 1AA02 and 28A03. The Unit 1 Train B Class 1E 4160 volt bus 1BA03 also lost power since RAT IA was feeding both Trains of Class IE 4160 volt busses. The loss of power caused the associated ESF Actuation System Sequencers to send a start signal to one Unit I and one Unit 2 Diesel Generator. DG1A and DG2B started and sequenced the loads to their respective busses. Further description of the Unit 2 response to this event is provided in LER 50-425/1990-002.

{

One minute and twenty seconds after DGIA started and sequenced the loads to the Class IE bus, the engine tripped. This again caused an undervoltage (UV) condition to class 1E bus 1AA02. The UV signal is a maintained signal at the sequencer. However, since DGIA was coasting down from the trip, the shutdown logic did not allow the DG fuel racks or starting air solenoids to open and start the engine. This properly caused the engine starting logic to lock up, a condition that existed until the UV signal was reset. For this reason, DGIA did not automatically re-start after it tripped.

After the trip, operators were dispatched to the engine control panel to investigate the cause of the trip.

According to the operator, several annunciators were lit. The operator briefly reviewed several instrument read-outs and detected no imediate problem. In order to restore emergency power, the operator reset the annunciators without delaying to evaluate or record the annunciators that were present. During this time, a Shift Supervisor (SS) and a Plant Equipment Operator (PE0) went to the sequencer The SS panel to determine if any problems were present on the 1A sequencer.

pushed the UV reset button, then reset the sequencer by deenergizing and energizing the power supply to the sequencer. This caused the DG air start solenoid to energize for another 5 seconds which caused the engine to start.

This happened 19 minutes after the DG tripped the first time. The engine started and the sequencer sequenced the available loads as designed. After 1 minute and 10 seconds, the breaker and the engine tripped a second time.

It did not automatically re-start due to the starting logic being blocked as described above.

By this time, operators, a maintenance foreman and the diesel generator vendor representative were in the DG room. The initial report was that the jacket water pressure trip was the cause of the trip.

This report was discounted because the maintenance foreman and vendor representative observed that the jacket water pressure at the gauge was about 12-13 PSIG. The trip set >oint is 6 PSIG and the alarm setpoint is 8 PSIG. Also, the control room osserved a lube oil sensor salfunction alare.

. ea...-

g,.

Ejnl.Y.c'**8E'.H" "'!E'., 'f"th' 5'.".'"'j UCENSEE EVENT REPORT (LER)

TEXT CONTINUATION y.'.Ye'."4*ff.'U.N'*/'.".Ec.'WE W "k'**fj M tt.,.'.T'.1.T7'.2'.a,".,.M'en..# T.. m.a u,

u..,

,..o, vs.a 888W8_*T,86

- QQ VEGP - UNIT 1 olstolole[41214 910 01016 0l1014 or 0 l9 var n e = m.w m Fifteen minutes after the second DGIA trip, DGIA was started from the engine The engine control panel using the emergency start breakglass button.

started and loads were manually loaded. When the DG is started in the However, all alarms emergency mode, all the trips except four are bypassed.During the will be annunciated.

room or at the engine control panel.

by the personnel either at the contro The only alarms noted by the control room operator assigned for DG operation were lube oil pressure sensor malfunction and fuel oil level high/ low alarm, neither of which would have tripped the diesel.

At 1040 CST, RAT 18 was energized to supply power to 4160 volt bus 3BA03.

DGIA supplied power to 4160 volt bus 1AA02 until 1157 CST, at which time bus IAA02 was tied to RAT 18.

A Site Area E6ergency was declared at 0840 CST, due to a loss of all offsite The Emergency Director signed and onsite AC power for more thr.n 15 minutes.

the notification form used to inform offsite government agencies of the The shift clerk attempted to initiate offsite emergency at 0848 CST. notification utilizing the primary ENN in the control roo The shift clerk then went to the back-up inoperable due to loss of power.

ENN and initiated notification after roll call on this system at 0857 CST.

Due to the loss of power, which rendered the primary Emergency Notification Network (ENN) inoperable, and some mis-comunication, the initial 1

notification was not received by all agencies untti 0935 CST.

The Emergency Director instructed personnel to complete various tasks for restoring containment and RCS integrity. All work was accomplished and maintenance personnel exited containment by 1050 CST.

The SAE was downgraded to an Alert Emergency at 0915 CST after restoration of core cooling and one train of electrical power. By 1200 CST, plant conditions had stabilized with both trains of electrical power being After discussions with the NRC supplied from an offsite source (RAT 18).

and local government agencies, the emergency was terminated at 1247 CST and all agencies were notified by 1256 r?L D.

CAUSE OF EVENT Direct Cause:

The direct cause of the loss of offsite Class IE AC power was the fuel 1.

truck hitting a pole supporting a 230kV line for RAT 1A. This was a There were cognitive personnel error on the part of the truck driver.

no unusual characteristics of the work location that directly contributed to this personnel error.

The direct cause of the loss of onsite Class IE AC power was the failure 2.

of the operable DG, DG1A, to start and load the LOSP loads on bus IAA02.

r,,-

y - - - * - - - -,,

--r

--,w-

~

v

.---4---

--mm 1-m

u m u..... -

.g.,.

a.,==

UCENSEE EVENT REPORT (LER) 53'.?f *.". ".*.'".R" ",T."ev"us'*e."*de' ".'.".'.O E".'e7AU'.I?.S."="f'.ll!!.'c""'! L* "l'.".053 TEXT CONTINUATION f.'.t".,"'.*.*.7.1.Tt".#'.4,'.,*'.a'n".,." ": af.;;

n 1-caa1 aw.ms. s' 6a. anne.a m am

.et v ass m mer;

. nm,.s c

i 0l9-VEGP - UNIT 1 o ls lo le le l4 l 2l4 910 01016 011 0l5 o'

)

The direct cause of the failure of the primary ENN system in the i

3.

control room was the loss of electrical power to Unit 1.

The primary ENN in the control room is powered from Unit 1 Class IE AC power.

l Therefore, when Unit 1 lost Class IE AC electrical power, tse primary ENN in the control room did not work.

Root Cause:

The truck driver met all current site training and qualification 1.

requirements, including holding a Class 2 Georgia driver's license.

However, site safety rules, which require a flagman for backing vehicles when viewing is impaired, were violated.

2.

The root cause for the failure of DGIA has not been conclusively There is no record of the trips that were annunciated determined.

after the first trip because the annunciators were reset before the condition was fully evaluated. Therefore, the cause of the first trip can only be postulated, but it was most likely the same as that which i'

caused the second trip. The second trip occurred at the end of the timed sequence of the group 2 block logic. This logic allows the DG to achieve operating conditions before the trips become active. The block logic timed out and the trip occurred at about 70 seconds. The annunciators observed at the second trip included jacket water high temperature along with other trips. In conducting an investigation, the trip conditions that were observed on the second DG trip on 3-20-90 could be duplicated by venting 2 out of 3 jacket water temperature sensors, simulating a tripped condition. The simulation dupilcated both the annunciators and the 70 sec. trip time. The most likely cause of the DG trips was intermittent actuation of the jacket water temperature switches.

i Following the 3-20-90 event, all three jacket water temperature switches, which all have a design setpoint of 2000F, were bench tested.

Switch TS-19110 was found to have a setpoint of 197 degrees F, which Switch was approximately 6 degrees below its previous setting.

TS-19111 was found to have a setpoint of 199 degrees F, which was Switch TS-19112 was l

approximately the same as the original setting.

I l

found to have a setpoint of 186 degrees F, which was approximately 17 Switch degrees F below the previous setting and was re-adjusted.

l TS-19112 also had a small leak which was judged to be acceHable to support diagnostic engine tests and was reinstalled. The switches were recalibrated with the manufacturer's assistance to ensure a consistent I

calibration technique.

m u.... ~,... -.

g,,c ES!?

  • o!!!'#t"."'.'.T,,, T'2.',".'l.1"4 uCENSEE EVENT REPORT ILER) fn"!.".EM*.t"?.3..'.f*J'.".!E""'!2 0'."'O'n TEXT CONTINUATION m.!.?'.'.T'.o.t.r. ??. A. "'.'.:.m:,#.,Mt.'a

?

u u.

i m

.u a m pa6

-.m t

9 0 0 l0l6 0l1 016 or 0 l9 VEGP - UNIT 1 o Is le lo le l l2 l 4 4

1 v.x, u e - an.mm t

i During the subsequent test run of the DG on 3-30-90, one of the tr Qped and would not reset. This appeared to be switches (TS-19111) lure because it subsequently mechanically reset.

an intermittent fai This switch and the leaking switch (TS-19112) were replaced with new switches. All subsequent testing was conducted with no additional j

problems.

A test of the jacket water system temperature transient during engine starts was conducted. The purpose of this test was to determine the actual jacket water temperature at the switch locations with the engine in a normal standby lineup, and then followed by a series of starts The without air rolling the engine to replicate the starts of 3-20-90.

test showed that jacket water temperature at the switch location decreased from a standby temperature of 163 degrees F to approximately 156 degrees F and remained steady, Numerous sensor calibrations (including jacket water temperatures),

special pneumatic leak testing, and multiple engine starts and runs After the 3-20-90 event, the were performed under various conditions.

control systems of both engines were subjected to a comprehensive test Additionally, the jacket water high temperature switches were program.

sent to an independent laboratory, which found the switches set at temperatures ranging from 162 degrees F to 195 degrees F rather than the 200 degree F setting that was required. The calibration technique was changed and switches were re-calibrated and installed on DGlB on 5-23-90. However, another failure occurred on DGl8 (See Technical These switches were also sent Specification Special Report 1-90-4.)found the settings to be from 164 to the independent laboratory, which Subsequent to this testing, the onsite degrees F to 169 degrees F.

calibration procedure was again revised to provide a technique that is consistent with the actual operating conditions that the switches Switches were calibrated using this new technique, experience.

Since installed and found to operate within the expected parameters.

the event of 3-20-90 through 6-7-90, DG1B had received 12 valid tests with the one failure mentioned above, and DGIA had received 16 valid 4

tests with no failures.

Based on the above facts, it is concluded that the jacket water high l

temperature switches were the most probable cause of both trips on 3-20-90.

The investigation and testing following the 3-20-90 event revealed that pressure sensors in the diesel generator lube oil system had not been replaced in accordance with a 10 CFR 21 notification from the The 10 CFR 21 notification was confusing manufacturer dated 5-12-88.

relative to the requirements for their replacement.

It was subsequently revised in an addendum dated 6-6-90.

The pressure trip

1 a.....

_,,,,,,,,,,. =

.. umm Egl?,*,,t,*.* ec5",#.TO',," "".,'A',T.",,M l

d UCENSEE EVENT REPORT (LERI T."4"/M'Mm*"#" i.!!,'c"','M L7,",Sf2 TEXT CONTINUATION "J,,t",'*l.*iotlM'.,*e3'.a,',L,a'g*n.?,s? *, C,n 0 aan aesesset,as 8sueset u ia te.,oc as,e3 90 Cat, e,wasta es ggggggg g p,,,,

J1Y.aa,6 He Tsaa

,esevaar., g 0l1 0l7 or 0l9 0l 4 6 e l5 le lo j e 14 l214 9l0 vrAP. IfNTT 1 nx, a-

,a a.c - auu nn sensors have been modified in accordance with the manufacturer's instructions. GPC does not believe that these sensors contributed to the diesel generator trip on 3-20-90.

E.

ANALYSIS OF EVENT The loss of offsite power to Class IE bus 18A03 and the fallwe of DGIA to start and operate successfully, coupled with DG18 and RAT 18 being out of service for maintenance, resulted in Unit I being without AC power to both Class IE busses. With both Class IE busses deenergized, the (HR System could not perform its required safety function. Based on a noted rate of rise in the RCS temperature of 46 degrees F in 36 minutues, the RCS water would not have been expected to begin boiling until approximately I hour and 36 minutes after the beginning of the event. Using more conservative assumptions and methods, but the same actual time of the event, the calculated worst case time to boiling was found to be approximately 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and 11 minutes, and time to core uncovering was found to be approximately 11 hours1.273148e-4 days <br />0.00306 hours <br />1.818783e-5 weeks <br />4.1855e-6 months <br /> and 5 minutes. This assumed no gravity feed from the RWST.

Restoration of RHR and closure of the containment equipment hatch were completed well within the estimated I hour and 36 minutes for the projected A review of information obtained from the onset of boiling in the RCS.

Process and Effluent Radiation Monitoring System (PERMS) and grab sample analysis indicated all normal values. As a result of this event, no increase in radioactive releases to either the containment or the environment occurred.

Additional systems were either available or could have been made available to ensure the continued safe operation of the plant:

1.

The maintenance on RAT 18 was completed and the RAT was returned to service approximately 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> into the event.

Offsite power was available to non-lE equipment through the generator 2.

step-up transformers which were being used to 'back-feed' the Unit and supply the non-!E busses. Provided Auxiliary Transformers (UAT)lt was cleared, Class IE busses IAA02 and that the phase to ground fau IBA03 could have been powered by feeding through non-lE bus INA01.

The Refueling Water Storage Tank could have been used to manually 3.

establish gravity feed to tlie RCS to maintain a supply of cooling water to the reactor.

Consequently, neither plant safety nor the health and safety of the public was adversely affected by this event.

c

. = ou... m -.

g UCENSEE EVENT REPORT ILER)

E!llU.',*4*.8'ff,'J'5'.7.',/'.?l7# T#.?4' 35"E.'A7 tun.*"eN"elllfc70E UI' Ec'ITN TEXT CONTlWUATION f't.",W#. ' !.r. 7"#t.a..v'.i. tam # :".2 c..f.'a

.ecas,s.u.ss.a el 648 s.u.s. c.I p

as ks?y a a m

.amy

.;,m, VEGP - UNIT 1 o is Id lo ]e l 4l2 l 4 910 0 l 0l6 011 0 18 o' O l9
r F.

CORRECTIVE ACTIONS 1.

A management policy on control and operation of vehicles has been established.

2.

Tem >orary barricades have been erected with signs which direct autiorization for control of switchyard traffic to the SS.

j The Loss of Offsite Power (LOSP) diesel start and trip logic has been 3.

l modified on both Unit I and Unit 2 so that an automatic ' emergency" start will occur upon LOSP. Therefore, non-essential diesel engine trips are blocked upon LOSP. Additionally, high jacket water temperature has been deleted as a trip signal in the emergency start mode.

1 The DGIA test frequency was increased to three times per week until 4-20-90 when the test frequency was chanp'ed to once every 7 days in l

4.

accordance with Technical Specification able 4.8-1.

This frequency will be continued untti 7 consecutive valid tests are completed with no more than one valid failure in the last 20 valid tests. Up to and including the two valid failures of the 3-20-90 event, there were a total if four valid failures in 69 valid tests of DGIA.

The jacket water temperature switches for each DG were replaced or 5.

re-calibrated using a more appropriate technique prior to their installation.

A back-up ENN system powered from the AT&T system, which previously 6.

existed and was operational for South Carolina agencies, has been extended to include Georgia local and state agencies. Instructions have been given to Emergency Directors and Communicators concerning use of the emergency consnunication systems.

I G.

ADDITIONAL INFORMATION 1.

Failed Components:

Jacket Water High Temperature Switches manufactured by California Controls Company.

Model #A-3500-W3 2.

Previous Similar Events:

None

' h,h.2,

.u...,2, UCENSEE EVENT REPORT (LER)

EW?? til$n'.M",o!'.1El',v" 7,,,h'," ?a'i p,'

"J g*

TEXT CONTINUATION w m a = wea J "ev'e E,= m m..e n,

n.

ymr; m.

amme ol1 og g op ojg ojo y VEGP - UNIT 1 o is jo go te j 4l 2l4 gl 0 runsn ca m.wim 3.

Energy Industry Identification System Code:

Reactor Coolant System - AB l

Residual Heat Removal System - BP Diesel Generator Lube 011 System - LA Diesel Generator Starting Air System - LC Diesel Generator Cooling Water System - L8 Diesel Generator Power Supply System - EK Safety Injection System - BQ 13.8 kV Power System - EA 4160 volt non-1E power system - EA 4160 volt Class IE power system - E8 Chemical and Volume Control System - C8 Containment Building - NH 480 volt Class IE Power System - ED Engineered Safety Features Actuation System - JE Radiation Monitoring System - IL

)

\\

- -..