ML20083A188

From kanterella
Jump to navigation Jump to search
Final Deficiency Rept,Item 125 Re Welding Defects in Reliance Electric Co Class IE Auxiliary Control Panel. Initially Reported on 830401.Welds Repaired.Vendor Instructed to Follow QA Manual for Unit 2 Equipment
ML20083A188
Person / Time
Site: Harris 
Issue date: 12/13/1983
From: Parsons R
CAROLINA POWER & LIGHT CO.
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
CON-NRC-153 10CFR-050.55E, 10CFR-50.55E, 125, NUDOCS 8312200205
Download: ML20083A188 (4)


Text

.. -

50- 400

~

CP&L y

Carolina Power & Light Company P. O. Box 101, New Hill, N. C. 27562 December 13,1983 Mr. James P. O'Reilly NRC-153 United States Nuclear Regulatory Commission Region II 101 Marietta Street, Northwest (Saite 2900)

Atlanta, Georgia 30303 CAROLINA POWER & LIGHT COMPANY SHEARON HARRIS NUCLEAR POWER PLANT 1986 900,000 KW - UNITS 1 & 2 WELDING DEFICIENCIES IN CLASS lE AUXILIARY CONTROL PANEL, PURCHASE ORDER NY-435190, ITEM 125

Dear Mr. O'Reilly:

Attached is the final report on the subject item which was deemed reportable per the provisions of 10CFR50.55(e), on April 26,1983. With this report, Carolina Power & Light Company considers this matter closed.

If you have any questions regarding this matter, please do not hesitate to contact me.

Yours very truly, g

^:: A R. M. Parsons Project General Manager Shearon Harris Nuclear Power Plant RMP/sh Attachment ee:

Messrs. G. Maxwell /R. Prevatte (NRC-SHNPP)

Mr. R. C. DeYoung OFFICI AL COPY 8312200205 831213 PDR ADOCK 05000400 S

PDR g;7 I \\

P CAROLINA POWER & LIGHT COMPANY SHEARON HARRIS NUCLEAR POWER PLANT UNIT NO. 1 FINAL REPORT AUXILIARY CONTROL PANEL ITEM NO. 125 DECEMBER 13, 1983 REPORTABLE UNDER 10CFR50.55(e)

~

\\

SUBJECT:

Shearon Harris Nuclear Power Plant Unit 1 10CFR50.55(e) reportable deficiency in the Auxiliary Control Panel supplied under Purchase Order NY-435190 ITEM:

Etructural welding SUPPLIED BY:

Reliance Electric Company, Stone Mountain, Georgia NATURE OF DEFICIENCY:

The subject Unit i equipment h'as been received at the site. Several welding deficiencies were noted when the equipment was inspected as compared to the vendor drawings.

DATE PROBLEM OCCURRED:

The problem was identified during receipt inspection on March 17, 1983.

DATE PROBLEM REPORTED:

On April 1, 1983, CP&L (Mr. K. V. Hate')

notified the NRC (Mr. A. Hardin) that this item was potentially reportable under 10CFR50.55(e).

On April 26, 1983, CP&L (Mr. N. J.Chiangi) notified the NRC (Mr. A. Hardin) that this item was reportable under 10CFR50.55(e).

SCOPE OF PROBLEM:

The equipment was manufactured in three (3) sections.

It will be bolted together and installed as a single unit. Deficient welds were identified in each section; eight (8) welds total.

SAFETY IMPLICATIONS:

Seismic qualification of the subject panel is required to assure structural integrity during a seismic event. Safety-related components are located in the cabinet; thus, structural failure would jeopardize operation of the safety-related equipment.

e REASON DEFICIENCY IS REPORTABLE:

Welding inspection at the site was done using the vendor's QA manual (QCP 5.3).

Deficient welds did not adhere to the manual.

CORRECTIVE ACTION:

CP&L originated a Field Change Request (FCR-AS-2879) to have the welds repaired by site personnel. The welds have been repaired.

The vendor has been given a copy of the weld deficiency report, the rework done, and has been requested to provide comment and an analysis.

CP&L letter with this information and request is H0-83158 dated May 9, 1983.

PREVENTATIVE ACTION:

The vendor has been instructed to rigorously follow his QA manual for Unit 2 equipment.

FINAL REPORT:

Final analysis by vendor and HPES indicate the deficient welds possess sufficient structural integrity to survive a design basis seismic event.

Therefore, repairs made will only further reinforce the structure.

!