ML20083A102

From kanterella
Jump to navigation Jump to search
Monthly Operating Rept for Nov 1983
ML20083A102
Person / Time
Site: Salem PSEG icon.png
Issue date: 11/30/1983
From: Miller L, Zupko J
Public Service Enterprise Group
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE)
References
NUDOCS 8312200162
Download: ML20083A102 (19)


Text

.. _ _ _ _

"6 AVERAGE DAILY UNIT POWER LEVEL Docket No.

50-311 Unit Name Salem # 2 Date Dec.10, 1983 Completed by L. K. Miller Telephone 609-935-6000 Extension 4455 Month November 1983

' Day Average Daily Power Level Day Average Daily Power Level (MWe-NET)

(MWe-NET) 1 0

16 0

2 0

17 0

3 0

18 0

4 0

19 0

5 0

20 0

6 0

21 0

7 0

22 0

8 0

23 0

9 0

24 0

10 0

25 0

11 0

26 0

12 0

27 0

13 0

28 0

14 0

29 0

15 0

30 0

Pg. 8,1-7 R1 8312200162 831130

~

PDR ADOCK 05000311 R

PDR Page 2 of 19

/ VI

OPERATING DATA REPORT Docket No.

50-311 Date Dec.10, 1983 Telephone 935-6000 Completed by L.

K. Miller Extension 4455 Operating Status 1.

Unit Name Salem No. 2 Notes 2.

Reporting Period November 1983 3.

Licensed Thermal rower (MWt) 3411 4.

Nameplate Rating (Gross MWe) 1162 5.

Design Electrical Rating (Net MWe) 1115 6.

Maximum Dependable Capacity (Gross MWe)1149 7.

Maximum Dependable Capacity (Net MWe) 1106 8.

If Changes Occur in Capacity Ratings (items 3 through 7) since Last Report, Give Reason N/A 9.

Power Level to Which Restricted, if any (Net MWe)

N/A

10. Reasons for Restrictions, if any N/A This Month Year to Date Cumulative
11. Hourn in Reporting Period 720 8016 18722
12. No. of Hrs. Reactor was Critical 0

1252.9 11708.5

13. Reactor Reserve Shutdown Hrs.

720 1310.1 1346.6

14. Hours Generator On-Line 0

1080.1 11417.3

15. Unit Reserve Shutdown Hours 0

0 0

16. Gross Thermal Energy Generated (PUGI) 0 2954523 33471072
17. Gross Elec. Energy Generated (MWH) 0 852040 10868250
18. Net Elec. Energy Generated (MWH)

(4557) 747706 10321353

19. Unit Service Factor 0

13.5 61.0

20. Unit Availability Factor 0

13.5 61.0

21. Unit Capacity Factor (using MDC Net) 0 8.4 49.8
22. Unit Capacity Factor (using DER Net) 0 8.4 49.4
23. Unit Forced Outage Rate 100 70.7 20.5
24. Shutdowns scheduled over next 6 months (type, date and duration of each)

N/A

25. If shutdown at end of Report Period, Estimated Date of Startup:

1-30-84

26. Units in Test Status (Prior to Commercial Operation):

Forecast Achieved Initial Criticality 6/30/80 8/2/80 Initial Electricity 9/1/80 6/3/81 Commercial Operation 9/24/81 10/13/81 8-1-7.R2 Page 3 of 19

UNIT SHUTDOWN AND POWER REDUCTIONS Dock 0t No. 50-311 REPORT MONTH NOVEMBER 1983 Unit N me S31ra No.2 Date Dec. 10, 1983 Completed by L.K. Miller Telephone 609-935-6000 Extension 4455 Method of Duration Shutting License Cause and Corrective No.

Date Type Hours Reason Down Event System Component Action to 1

2 Reactor Report Code 4 Code 5 Prevent Recurrence Other Hydrogen System 83-114 10/07 F

408 A

4 HA HTEXCH Problems Generator Sta tor 83-116 11/17 312 GENERA Winding Problems 1

2 Reason 3 Method 4 Exhibit G 5 Exhibit 1 F: Forced A-Equipment Failure-explain 1-Manual Instructions Salem as S: Scheduled B-Maintenance or Test 2-Manual Scram, for Prepara-Source C-Re fueling 3-Automatic Scram. tion of Data D-Regulatory Restriction 4-Continuation of Entry Sheets E-Operator Training & Licensing Exam Previous Outage for Licensee F-Administrative 5-Load Reduction Event Report G-Operational Error-explain 9-Other (LER) File H-Other-explain (NUREG 0161)

Page 4 of 19

DOCKET NO3 50-311 MAJOR PLANT MODIFICATIONS UNIT NAME:

SALEM 2 REPORT MONTH NOVEMBER 1983 DATE:

DECEMBER 10, 1983 COMPLETED BY:

L.

K. MILLER TELEPHONE:

(609) 339-4455

-(s\\

v

  • DCR NO.

PRINCIPLE SYSTEM SUBJECT 2EC-0650 Steam Generator Blow-Modify the steam ge'erator blowdown n

down system.

2EC-0719 Turbine Drains High pressure turbine interstage drain replacement using type 304 stainless steel.

2EC-0734 MSR's 2nd Reheater Design modification of all 6 HP Head Modification reheater MSR's from a two pass hemi-head design to full access davitted channel head with four pass internal arrangement.

2EC-ll29 Auxiliary Feedwater Change power supply as follows:

a) #21 pump suction & discharge pressure indication, b) #24 & 24 Steam Generator Auxiliary Feedwater Flow indication, c) #23 & 24AF21 indicator power supply, d) Auxiliary Feedwater Storage Tank level

('S indicator, e) #23 pump - speed,

(,/

speed demand, suction pressure, discharge pressure and steam pressure indicators.

2EC-1131 Control Air Change the power supply for the 2A and 2B header pressure transmitters.

2EC-ll33 Auxiliary Feedwater Change power supply as follows:

a) #21 pump suction & discharge pressure indicators, b) #21 & 22 steam generator HFW flow indicators c) #21 & 22AF21 indicators.

2EC-1250 Diesel Generators Power supplies to all of the

" indicators" for voltage, frequency, watts and amps of each one of the diesel generators- (lA, B, C) shall be changed from MAC panels (11 & 12) to the respective vital buses.

2EC-1422' Vital Instrument and Install circuit breakers and line Essential Control filters in the inverters cooling Inverters fan circuit, g

Y

  • DESIGN CHANGE REOUFST 9-1-7.R1 Page 5 of 19 I

DOCKET NO:

50-311 MAJOR PLANT MODIFICATIONS UNIT NAME:

SALEM 2

, REPORT MONTH NOVEMBER 1983 DATE:

DECEMBER 10, 1983" L. K.

MILLER COMPLETED BY:_

[ 'N TELEPHONE:

(609) 339-4455 (j

  • DCR NO.

PRINCIPLE SYSTEM SUBJECT 2EC-1633 Protection Systems-Revise setpoint of steam generator Steam Generator Level lo-lo level from 18% to 8.5%.

2EC-1657 Emergency Diesel Change the setpoint of the lube Generators oil temperatgre initial alarm from g

185 F to 190 F.

2EC-1666 Pressurizer Change scale on pressurizer relief tank temperature indicator on the Control Room console and cagibrate indicator for a range of 50 to 350 F also the low level amplifier.

2EC-1669 Environmental Change containment spray additive Qualification transmitter FA-218 to an environmentally qualified model -

Rosemount 1153D.

2EC-1726 Bleed Steam and Heater Increase water level setpoints by Drain two inches on all low pressure

(~' i feedwater heaters which include (m /

21A,B,C; 22A,B,C.

2SC-0305 Fan Coil Unit Service Modify overhead alarms C2, C10, C18, Water Flow C26, C34 containment fan coils.

2SC-0606

. Service Water Vent oil level columns in the (Only No. 23, 24, 25 bearing oil lubrication system and 26 completed) on No. 21, 22, 23, 24, 25 and 26 Service Water Pump Motors.

2SC-0621 Diesel Turbo Boost Install a low pressure air alarm for each diesel.

2SC-0655 Emergency Diesel Replace existing starting air and Generator turbo air compressor pressure

~

controllers.

2SC-0927 Steam Generator Blow-Remove present GBl86 valves.

down A

NY

  • DESIGN GHANGE REOUEST 9-1-7.Rl Page 6 of 19

MAJOR PLANT MODIFICATIONS DOCKET NO.:

50-311 REPORT MONTH November UNIT NAME:

Salem 2 DATE:

December 10, 1983 COMPLETED BY:

L.K. Miller TELEPHONE:

609/339-4455 DCR NO.

10CFR 50.59 SAFETY EVALUATION 2EC-0650 The installation of this DCR will improve steam generator water chemistry and will actually decrease the effluent discharge to both the river and the atmosphere.

No unreviewed safety or environmental questions are involved.

2EC-0719 The installation of this DCR does not result in any reviewed safety or environmental questions.

2EC-0734~

This design change does not affect any presently performed safety analysis, nor does it create any new safety hazards.

No unreviewed safety or environmental questions are' involved.

2EC-1129 This design change improves the system reliability of the

.feedwater system.

No unreviewed safety or environmental questions are involved.

2EC-1131 This design change improves the system reliability.

The logic functions of the system remain as is.

No unreviewed safety or environmental questions are involved.

2EC-1133 This design change is to improve the system reliability.

The _ logic functions of. the system remain the same.

No unreviewed safety or environmental questions are involved.

2EC-1250 This design improves the' reliability of the diesel generator system but does not alter the functional requirements cur the Technical Specifications.

No unreviewed safety or environmental questions are involved.

2EC-1422-

-This design change improves the reliability of the effected components but does not -alter their function or reliability.

No unreviewed safety or environmental questions are involved.

-2EC-1633 Implementation of this DCR improves system reliability by correcting potential level indication error due to reference leg heatup and environmental effects on the transmitters.

No unreviewed safety or environmental questions are involved.
  • DCR.- Design Change Request Page 7 of 19

MAJOR PLANT MODIFICATIONS DOCKET NO. :

50-311 REPORT MONTH November 1983 UNIT'NAME:

Salem 2 DATE:- December 10, 1983 COMPLETED BY:

L.K. Miller TELEPHONE:

609/935-6000 X4455

  • DCR NO.

10CFR50.59 SAFETY EVALUATION

-2EC-1657 The setpoint change to'the diesel generator high lube oil temperature-warning alarm is within the manufacturers operating parameters.

No unreviewed safety or environmental-questions are involved.

2EC-1666

-Changing the indicator scale does alter the system N

function and will not-effect the safe shutdown of the reactor._ No unreviewed safety or environmental questions are involved.

2EC-1669 The. reliability of the system is improved by using an environmentally qualified instrument.

No unreviewed safety or environmental questions are involved.

2EC-1726 Installation of.this DCR does not involve any unreviewed safety or environmental questions.

2SC-0305 This change is not safety.related and does not affect any safety related equipment.

No unreviewed safety or environmental questions are involved.

2SC-0606 The modification of the oil' sight level gauge vent will

-improve, accuracy of the' oil level indication.

No unreviewed safety or environmental questions are involved.

2SC-0621.

Implementation of this design change improves the diesel reliability fof startup within 10 seconds, by informing

'the. operators of'a' low air pressure in the turbo-boost air receivers.

No unreviewed safety or environmental questions are involved.

2SC-0655 Implementation of this DCR does not alter the calculations for any presently performed safety analysis.

No unreviewed safety or environmental questions are involved.

2SC-0927 The implementation of this DCR does not alter the original design concept of the blowdown system.

No unreviewed safety or environmental questions are involved.

  • DCR

~ Design Change Request s

Page 8 of 19

P S E & G. SALEM GENERMFING STATICN SAFErY RELATED WCRK @ DER IOG SALEM UNIT NO. 2 WO NO DEPT UNIT EQUIPMENT IDENI'IFICATIN 931044-FD 2

21 SW 161 FAIIURE DESCRIPTICN:

CONNECT FLANGE WITH HOSE '10 RUN SERVICE NATER EOR INSPICPIN T BIOCKAGE OR

^

DEBRIS DURING FIUSHING.

830428-CORRECTIVE JCTIN:

FIUSHED LINE - NO EVIDENCE & BIOCKAGE CR SHELL FISH. 830428-d

.931050 MD 2

2B DIESEL FAIIERE DESCRIPTICN:

INSPECT MO CLEAN IDBE OIL NO WATER u~ACKEP C00ERS.

830430 CORRECTIVE 1CPION:

INSPECTED AND CLEANED.

INSTATJm NEW O RINGS AND GASKETS. 830512 931167 MD 2

22 SW 24 FAIIURE DESCRIPTICN:

REPAIR VALVE - LINER RIPPED. AIEO INSPECT PIPE FOR CORROSICN AND INSPECT BOLTING. 830512 CORRIUTIVE ACTI(N:

REPLACED VALVE BCDY. PD REPIACED VALVE 'IOP AND CPERA'IOR. 830512 931210 MD 2

CNTRL RM A/C DAMPERS FAIIDRE DESCRIPTIW:

I/O #200867: LUBE LINE SHAFT BEARINGS WITH 10W OIL 2CAA3 - 2CAA4. 830516

l Cu<xtL'nVE ACTION:

OTTm LINE SHAFT BEARINGS WITH 10W OIL.

830520 931276 MD 2

22 AUX BLDG EKH FAN

- FAIIURE DESCRIPTICN:

REPAIR CR REPIACE FLEX BOOT CN EKHAUST SIDE OF FAN. 830522 CumtI;nVE ACTION:

INSTArJm NEW FLEX BOOP IN 22 AUX BLDG EXHAUST FAN.

830605 i

931311 MD 2

2C VITAL INVERFER FAIIURE DESCRIPTICN:

NO VOLTAGE (UTPUT - TROLELESHOOT AND REPAIR. 830525 CuMKtL'nVE ACTION:

REPIACED BAD THYRISIOR, A25X100 EUSES AND TRIGGER INDICATICN FUSES. REPIACED CR46 & CR34 'IHYRISTORS. REENERGIZED INVERTER - OPERATING PROPERLY. 830531 Page 9 of 19

PSE&G SALEM GENEEUCING STATICN SAFEIT REIATED WORK GDER IOG SALEM UNIT NO. 2 WO NO DEPT UNIT EQUIPMENT IDENTIFICATIm 931342 FD 2

130' AIRLOCK IBN DR FAILURE DESCRIPTION:

INNER DOOR I7fECH BOLIERS CRACKED. REPIJCE 830527 CumE1'nVE ACTION:

REPLACED R(YJER BEARINGS AND REGECKED SEALS FCR IFAKAGE (SAT) 830527 931366 ND 2

21 BCDP PMP FAIIURE DESCRIPTIW:

OPEN AND INSPFICT FOR IMPFJJER BIOCKAGE. 830601 CORRECTIVE ACTION:

OPENED PLNP, 'lhERE WAS NO BLOCKAGE - IMPMIRR WAS 'IUBNING BACKWARDS.

(MOIOR WAS WIRED hRCNG) 830609 931608 MD 2

22SW20 FAILURE.DESCRIPTICN:

MIOR GROUtDED - PULL MOICR, FIDSH WTIH FRESH WATER AND BAKE OUT.

830625 CumrL'nVE ACTION:

INSTNJE NEW MOICR 22SW20 LIMrIORQUE VALVE.

830710 931611 MD 2-22 RHR IMP MOIOR FAILURE DESCRIPTICN:

RENOVE AfD REPIJCE WITH SPARE MDFOR #22 RHR MOICR. 830628 CumrL'nVE ACTION:

REPLACED MIDR SEALS AND IMPMIRR. M-11G DCNE Uf0ER 405P.

830701 931620 MD 2

22SW24 FAIIURE DESCRIPTICN:

REPLACE VALVE DIA1HRAGM. 830627 CuterL'nVE ACTION:

FOUND TGN DIAPHRACE AND DEFERIORATED BUBBER BCDY. REPIACED WTIE A NEW BCDY AND DIAPHRACE. 830712 931689 MD 2

24MS11 'IERU 15 FAIIURE DESCRIPTICN:

LIFT SET CHECK 830705 FATTHRE DESCRIPTION:

TESTED SAFETIES - 24MS12 42 IBS IDW AT 1066, 24MS13 2 IBS ION AT 1099. 830707 Page 10 of 19

...m.

. _. ~

-~

. P S E & G SALEM GENERRPING SDLTION SAFETY RE[ATED NDEK CRDER IOG SALEM WIT 2 WO NO DEPT LNIT Bgula4ENT linwnrICATIN

'931690- 2 2

23MS11 'IHRU 15 FAILURE DESCRIPTIN :

LIFT SEff CHECK 830718 1

CORRECTIVE ACPIN:

SETF SAFEPIES 23MS11 'HIRU 15.

23MS14 2 IBS Im AT 1087, 23MS15 64 IBS Im AT 995.

830718 931691

.m 2

22MS11 'IERU 15 FAIIURE DESCRIPTIm:

LIPT SET CHECK 830705 CORRECTIVE ACTION:

LIPr SET 22MS11 '1HRU 15.

22MS1415 IBS IN AT 1074.

830706 i

9?1692 MD 2

VALVE 21MS13 i

FAILURE DESCRIPTIm:

LIFf SE7f CHECK.

830705 j.

Cumr.LnVE ACTION:

TESTED SAFETIES.

21MS13 LIPfED 3 PSI Im AT 1099. 830707 931735 MD 2

CONT AIR IOCK EL 130 FAIIURE DESCRIPTIW:

INNER DOOR IATG BOLLER CRACKED AND SEAL LEAKS. 830708 l

CuturJt nVE ACTION:

INSTALLED NEW R(YJER BEARING CN DOOR IA'ICH AND REPIACED SEAL.

830708 j

931742 MD 2

VALVE 2CV141 FAIIURE DESCRIPTIW:

VALVE IEAKS 'IERCXEH. 830709 i

Cu<tm'r1VE ACTION:

INSTALLED NEW DISC AND RESET RELIEF PRESSURE. 830711 932162 MD 2

VALVE 22SJ39 l

FAIIURE DESCRIPTIN:

RELIEF VALVE PASSES 'IEROUGH AT 100 isI. 830412 CORRECTIVE ACTION:

REBUILT VALVE.

830427 1

Page 11 of 19 i

I

-P S E & G ~ SALEM GENERATING SDCIN SAFEIY RELATED WORK WDER IOG SALEN INIT 2 WO ND Drrr UNIT EQUIPMENT 1DENnFICATIN 932202 MD

'2 BREAKER 2AADC CAB FAIIURE DESCRIPTION:

CANNOT GET EMERG. FEED TO 2AADC CABINET. 830416 CORRBCTIVE ACTION:

RENDVED SPARE BKR FRCN 2CDCZ4 AND PUT IN POSITIm 2AADC. 830417 932233 MD 2

22RfIR SUMP PLNP FAIIURE DESCRIPTICN:

SUMP PLMP WILL NOT START WITII HIGH LEVEL IN F'2.

830423 Cu(Krcr1VE ACTION:

INSTALLED NEW CALIBRATED LEVEL DEVICE.

L.

932313 MD 2

VALVE 22T7 FAIIURE DESCRIPTIN:

VALVE HAS BROKEN HANDWHEEL. 830513 Cui<Rrl;nVE ACTION:

REPIACED STEM AND PIDG ASSY AND INSTALLED NEW HAtOWHEEL. REPACKED VALVE.

830616 932781 MD 2

CCNT AIR IOCK EL 100 -

FAIIURE DESCRIPTICN:

EK'IERIm DOOR CANNDI BE FULLY C[DSED WITH '11{E HANDIE INSIDE 'IffE AIRIOCK.

830706 CORRECTIVE ACTICN:

REPLACED 'IWO MITER GEARS CN G7IER DOOR AND AIXJUSTED DOOR. 830709 932783 MD 2

VALVE 22MS10 FAIIURE DESCRIPTIW:

VALVE HAS BCDY TO BONNET IIAK. 830706 CuuxtA;nVE ACTION:

FACED TF GASKET SEAT SURFACE. REPIACED SEAT RING, STEN, PIDG AND PIDG PIN.

830712-932805 MD 2

21 BCDP PtNP FAIIURE DESCRIPTICN:

PUMP TRIPS AFTER AB W T 30 SEC. 830629 CORRECTIVE ACTION:

REPIACED BURNT M0fIOR CAUSED BY MISC DEBRIS IN BOITCM T TANK AND LINE.830703 Page 12 of 19

PSE&G SALEM GENERATING SIATION SAFETY REIATED WORK CEDER IDG SALEM WIT 2 WO NO DEPT LNIT EQUIPMENT IDENTIFICATICN 932830. OD

-2 22 BAT P W P.

FAILURE DESCRIPTIW:

PUMP HAS BAD SEAL EAK.

830625 Cueci.nVE ACTION:

REPLACED MBCHANICAL SEAL.

830708 L

932844 CD 2

2B 480/240 VIT TRANS FAIIURE DESCRIPTIN:

INVESTIGMPE/ REPAIR CAUSE W FIRE IN TRANSFORMER /CR ITRE COIIS ARE BURNED.

830620 CORRECTIVE ACTIN:

REMOVED GD TRANSFCENER. REPIACED WITH SPARE.

830624 932858 OD 2

CNT AIR-IOCK EL 100 I

FAILURE DESCRIPTICN:

EXTERICR DOOR HAS BAD SEAL EAK.

830625 CORRECTIVE ACTION:

REPLACED SEALS.

830625 932861 CD 2

CONr AIR IOCK EL 130 FAIIURE DESCRIPTICN:

INNER DOOR HAS A SEAL LEAK. 830625 CutecirnVE ACTION:

REPLACED DOOR SEAL.

830625 937793 OD 2

24 BC PLMP FAIIDE DESCRIPTICN:

PUMP TRIPPED WHEN TRYING 'IO START.

830719 CuceLnVE ACTION:

PRCELEM WAS IN IOCKED ROIDR REIAY. REIAY DEPT CORRECTED. TEST SAT. 830720 937802 CD 2

2C EMERG DIESEL FAIIURE DESCRIPTICN:

IUBE OIL TEMP IS 102 DEG AND HEATER HAS N0f IGCKED IN.

830720 i

i CORRECTIVE ACTION:

RECALIBRATED 2'ID-7518 IUIS 1 & 2. ALSO EVUND CCNTACPS WIRED WRONG. CORRECTED WIRING. TEMP NOW READING 110 DEG.

830721 i

Page 13 of 19

P S E & G-SALEM GENERMING STATICN SAFETfY REIATED WORK ORDER IOG SALEM UNIT 2 WO NO DEPT UNIT 10UIPMENT IDENTIFICATIN 938533 CD

.2 21 BA 'IRANS PCMP FAIIURE DESCRIPTIW:

PUMP HAS LEAK AROUf0 PACKING. 830628 CutetL'nVE ACTION:

REPIACED MECHANICAL SEAL, SINGLE BEARING, DOUBLE BEARING, OIL SEALS, SHAFT AND IMPFHER.

830701 938577 OD 2

PX TRIP BREAKER B FAILURE DESCRIPTICN:

INVESTIG RE/ REPAIR RK TRIP BKR B.

830702 CumtL'nVE ACTION:

EOUND BREAKER TRIPPING FREE IN PIACE. INSTATIFD B BYPASS BKR IN B POSITIN AND CEOSED SAT. REPIACED I1nUI RELAY IN B BKR. RETEST SAT. 830707 l

938641 OD 2

CCNP AIR IOCK EL 100 FAILURE DESCRIPTICN:

SEAL IEAKING SEVERELY, IDWER IEPf HAND CORNER MIEN LOOKING AT DOOR FROM CCNTAIINENI SIDE.- 830705 CORRECTIVE ACTICN:

REPLACED DNER SEAL CN DNER DOOR.

830705 939254 MD 2

CCNr AIR IOCK EL 100 FAILURE DESCRIPTICN:

AIR IOCK HAS BROKEN CAM.

830712 CustL'nVE ACTION:

REPIACED BROKEN CAM.

830712 944806 OD 2

21 BAST FAIIURE DESCRIPTICN:

BorH HEATERS ARE LEAKING AT FLANGE. 801215 CumtL~nVE ACTION:

REPIACED ONE HEATER AND BOIH HEATER GASKETS.

830510 984877 MD 2

VALVE 23MS15 FAIIURE DESCRIPTICE:

REPIACE SAFETY VALVE AT NEXT REFUELING. 820707 CORRECTIVE ACTION:

REPIFFD VALVE WI'IH NEN WE FRCM CROSBY. 830203 Page 14 of 19

PSE&G SALEM GENERATING SIATION SAFEIY RELATED WORK ORDER IOG SALEM UNIT 2 WO NO. DEPT UNIT EQUIPMENT IDENTIFICATIm 987830 OD 2

VALVE 22MS14 FAILURE DESCRIPTIm:

SAFEIT VALVE APPEARS 'IO BE IEAKING BY ITS SEAT. 811230 Cuum'nVE ACTION:

REPIFm VALVE INTERNALS.

830610 987831 CD 2

VALVE 22MS15 FAILURE DESCRIPTICN:

VALVE APPEARS TO BE IEAKING PAST SEAT. 811230 Cu<xtL'nVE PCTION:

REPIACED VALVE INTERNALS.

830610 993025 2

CCNTAINMENT AIR IOCK FAILURE DESCRIPTICN:

INSTALL /RENOVE STRCNGB7CKS CN 100 AND 130 ELEVATIm CCNTAIIEENT AIR IOCKS EDR LEAK RATE TESTING.

820606 CORRECT 1VE PCTICN:

INSTAT.Tm NEW SEAIS (N EL 130 INNER DOOR.

INSTALLED /RENOVED STRmGBICKS.

830518 931603 MD 2

100' AIRLOCK l

FAIIURE DESCRIPTICN:

BALL IS SIUCK IN FIDW METER W EK'IERIOR DOOR. ISOLATIm VALVES AND TATFm 0FF VALVES ARE MISSING.

INVESTIGATE AND REPAIR.

830624 CORRECTIVE PCTICN:

CLEANED FICW 'IUBE AIO BALL CHBCKS m.

'IUBING AND VALVES INSTAT.TE AGREE WITH PRINT 240675.

830625 932334 OD 2

PZR LEVEL 012 FAILURE DTSCRIPTICN:

CHANNEL FAILED ILW.

830516 CUHurL'nVE PCTION:

REPIFm CAPACITORS C2, 3, 4, 6 AND 7 IN ISOIATOR 21M-460.

830517 Page 15 of 19 m

PSE&G SALEM GENERATING SIATION SAFE 1Y REIATED NORK ORDER IOG SALEM UNIT 2 WO NO DEPT WIT EQUIPMENT IDENTIl'ICATIN 932381 OD 2

RMS 2RllA FAILURE DESCRIPTIO%:

CHANNEL IS FAILED. 830427 CuKKtL"nVE ACTION:

REPIACED BAD BATTERY PACK IN REMOTE UNIT POWER SUPPLY.

INSTALLED NEW ACIA'S IN YtrAL AND RENOTE CWTROTTRRS.

830430 932521 IC 2

VALVE 2PS1 FAILURE DESCRIPTIW:

VALVE IEAKING DIROLGH. CHECK EOR PROPER SEATING. 830707 CunatL'nVE PCTION:

ADJUSTED ZERO ON POSITINER, VALVE SLIGHTLY OFF SEAT.

830708 932522 IC 2

VALVOP 2PS3 FAIIURE DESCRIPTIN:

VALVE LEAKING HIROLGH. GECK VALVE FOR PROPER SEATING. 830707 Cu<xtL'nVE ACTION:

ADJUSTED ZERO ON POSITIGER. VALVE SLIGHTLY OFF SEAT.

830708 937797 OD 2

24 RCP BKR RELAYS FAIIURE DESCRIPTIW:

GECK RELAYS EDIILWING RCP TRIP. 830720 CuMRtL'nVE ACTION:

PERFORMED SETTING CHFCK N KD-10 & CO-ll LOCKED ROIOR PROTECTION.

830720 938309 OD 2

VALVE 2MS132 FAIIURE DESCRIPTIW:

VALVE ACIUATOR DIAMIRAM APPEARS 'IO BE BROKEN. 830710 Cu<urL'nVE ACTION:

REPIN'm BIDWN DIAPHRAM. AIDUSTED OPEN LIMIT SWIIGIES.

830710 938320 OD 2

VALVES 2I411 & 2RH2 FAIIURE DESCRIPTIW:

GECK ]NTERIOCK IAW IOP-6.

830712 CORRECTIVE ACTION:

PERFORMED AUIO ISOLATION INTERIOCK EUNCTINAL.

830712 Page 16 of 19

PSE&G SAIR4 GENERATIN3 SIATION SAFEIY RE[ATED NORK WDER I4X3 1

SAI2M UNIT 2 WO NO DEPT UNIT EQUIPMENE IDENTIFICATIm 938374 OD 2

RMS 2R41B FAIIDRE DESCRIPTIW:

CHANNEL HAS SPIKED UP 'ID 2 EA.

830706 CORRECI'IVE ACTIN:

REPIACED POWER SUPPLY DUE 'IO -15 VDC READING I4W. VERIFIED V%TAGES AND BOIU TRAINS A AND B TRIPPED SAT.

830706 938701 OD 2

NI CH N-44 FAIIURE DESCRIPTICN:

II)SS W trnCIOR WLTAGE. 830705 CORRECTIVE ACTION:

REPIACED HIGH V1TAGE POWER SUPPLY S/N11006 WI'IU S/N904002 AND ADJUSTED.

830706 1

931309 OD 2

VALVE 2CV5 FAILURE DESCRIPTIN:

PERFORM 4.0.5 V W 2CVS 'IO VERIFY PROPER CPERATIN.

830525 CUKKtUnVE ACTION:

VALVE RESTORED - 4.9 SEC - SAT.

830617 i

4 W

i

)

Page 17 of 19 4

SALEM UNIT 2 OPERATIONS

SUMMARY

REPORT NOVEMBER 1983 Unit No. 2 remained shutdown the entire month as repairs to_the generator continued.

During the repairs, a DC high potential test revealed a ground in the generator stator.

The faulty coil was removed and sent to Westinghouse to be repaired and refurbished.

During investigation of the ground, five additional stator coils were found to.have' internal leaks in their hollow conductors.

These coils have been shipped to Westinghouse for determination of the cause of failure and subsequent repair.

+

4 Page 18 of 19

~

REFUELING INFORMATION DOCKET NO.:

50-311 COMPLETED BY: ' L.K. Miller UNIT NAME:

Salem 2 DATE:

December 10, 1983 TELEPHONE:

609/935-6000 EXTENSION:

4455 Month November 1983 1.

Refueling information has changed from last month:

YES NO X

2.

Scheduled date for next refueling:

September 29, 1984 3.

Scheduled date for restart following refueling:

December 8, 1984 4.

A)

Will Technical Specification changes or other license amendments be rcquired?

YES NO NOT DETERMINED TO DATE 12/1/83 B)

Has the reload fuel design been reviewed by the Station Operating Review Committee?

YES NO X

If no, when is it scheduled? August 1984 5.

Scheduled date (s) for submitting proposed licensing action:

August 1984 (if required) 6.

Important licensing considerations associated with refueling:

NONE i

7.

Number of Fuel Assemblies:

A)

Incore 193 B)

In Spent Fuel Storage 72 8.

Present licensed spent fuel storage capacity:

1170 Future spent fuel storage capacity:

1170 9.

Date of last refueling that can be discharged to spent fuel pool assuming the present

-licensed capacity:

March 2000 4

8-1-7.R4 Page 19 of 19

(.

e

~ '

O PSIEG Public Service Electric and Gas Company P.O. Box E Hancocks Bridge, New Jersey 08038 Salem Generating Station December 10, 1983 Director, Office of Inspection and Enforcement U.S. Nuclear Regulatory Commission Washington, DC 20555

Dear Sir:

MONTHLY OPERATING REPORT SALEM NO. 2 DOCKET NO. 50-311 In Compliance with Section 6.9, Reporting Requirements for the Salem Technical Specifications, 10 copies of the following monthly operating reports for the month of November 1983 are being sent to you.

Average Daily Unit Power Level Operating Data Report Unit Shutdowns and Power Reductions Major Plant Modification Summary of Safety Related Maintenance Operating Summary Refueling Information Sincerely yours,

J. M.

Zupko, Jr.

General Manager - Salem Operations LKM:sbh cc:

Dr. Thomas E.

Murley Regional Administrator USNRC Region I 631 Park Avenue King of Prussia, PA 19406 Director, Office of Management g

(f'

)L (

Information and Program Control U.S.

Nuclear Regulatory Commission Washington, DC 20555 Enclosures Page lof 19 8-1-7.R4 The Energy People 95 2WJ (20M) 118 i

)