ML20082E299

From kanterella
Jump to navigation Jump to search
Forwards IE Insp Repts 50-317/83-26 & 50-318/83-26 on 830919-23 & Notice of Violation
ML20082E299
Person / Time
Site: Calvert Cliffs  
Issue date: 11/09/1983
From: Martin T
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To: Lundvall A
BALTIMORE GAS & ELECTRIC CO.
Shared Package
ML20082E300 List:
References
NUDOCS 8311280135
Download: ML20082E299 (2)


See also: IR 05000317/1983026

Text

.

._

-

.

.

._-.

.

.

s

.

NOV 0 01983

Docket Nos.

50-317/50-318

Baltimore Gas and Electric Company

ATTN: Mr. A. E. Lundvall, Jr.

. Vice President, Supply

'

P. O. Box 1475

Baltimore, Maryland 21203

Gentlemen:

Subject: Inspection Nos. 50-317/83-26; 50-318/83-26

,

This refers to the routine inspection conducted by Mr. Bissett of this office

on September 19-23, 1983 of activities at the Calvert Cliffs Nuclear Power

4

i

Station and your Baltimore, Maryland Corporate Offices authorized by NRC

License Nos. DPR 53 and 69 and to the discussions of our findings held by Mr.

Bissett with Mr. J. Carroll and other members of your staff at the conclusion

of the inspection.

Areas examined during this inspection are described in the NRC Region I In-

spection Report which is enclosed with this letter. Within these areas, the

inspection consisted of selec.fve examinations of procedures and representative

records, interviews with personnel, and observations by the inspector.

Based on the results of this inspection, it appears that one of your activities

was not conducted in full compliance with NRC requirements, as set forth in the

Notice of Violation, enclosed herewith as Appendix A.

This violation has been

categorized by severity level in accordance with the NRC Enforcement Policy (10 CFR 2, Appendix C) published in the Federal Register Notice (47 FR 9987) dated

March 9, 1982. You are required to respond to this letter and in preparing

your response, you should follow the instructions in Appendix A.

In accordance with 10 CFR 2.790(a), a copy of this letter and the enclosure

will be placed in the NRC Public Document Room unless you notify this office,

by telephone, within ten days of the date of this letter and submit written

application to withhold information contained therein within thirty days of

the date of this letter.

Such application must be consistent with the re-

quirements of 2.790(b)(1). The telephone notification of your intent to

request withholding, or any request for an extension of the 10-day period

which you believe necessary, should be made to the Supervisor, Files, Mail and

t

.

Records, USNRC Region I, at (215) 337-5223.

The responses directed by this letter and the accompanying Notice are not

subject to the clearance procedures of the Office of Management and Budget

as required by the Paperwork Reduction Act of 1980, PL 96-511.

8311280135 831109

PDR ADOCK 05000317

G

PDR

\\( b

OFFICIAL RECORD COPY

191BISSETT10/6/83 - 0001.0.0

10/19/83

l

I

.-

.

-

__- -_

---.

. - - _ .

- _ _

- - - . _.

. - . -

-

. -

-

.

Calvert Cliffs NPS, Un'it 1

2

Your cooperation with us in this matter is appreciated.

Sincerely,

iginal sio%d bf

5, p, Ebp*

Thomas T. Martin, Director

Division of Engineering and

Technical Programs

Enclosures:

Appendix A, Notice of Violation

NRC RI Insptction Report

cc w/ enc 1:

R. M. Douglass, Manager, Quality Assurance

L. B. Russell, Plant Superintendent

5. M. Davis, General Supervisor,-Operations QA

Thomas Magette, Administrator, Nuclear Evaluations

R. C. L. Olson, Principal Engineer

J. A. Tiernan, Manager, Nuclear Power

R. E.-Denton, General Supervisor, Training and Technical Services

Public Document Room (PDR)

Local Public Document Room (LPDR)

Nuclear Safety Information Center (NSIC)

NRC Resident Inspector

State of Maryland (2)

bec w/ encl:

Region I Docket Room (with concurrences)

Senior Operations Officer (w/o encis)

DPRP Section Chief, Section #1A

,;

,

RI:DETPh

RI:DETP-

I:DETP

RI:DETP

Bissett/bz

Caphto

Ebneter

Martin

10/6/83

10//f/83

16/f/83

1)/f/83

0FFICIAL-RECORD COPY

191BISSETT10/6/83 - 0002.G.0

10/19/83

.- -

.

.

-

.

.

..

.

-

-- --

-

.

1

APPENDIX A

NOTICE OF VIOLATION

s

Baltimore Gas and Electric Company

Docket No. 50-317

Calvert Cliffs Nuclear Power Station

DPR-53

Unit 1

Baltimore, Maryland 21203

,

As a result of the inspection conducted on September 19-23, 1983, and in

accordance with the NRC Enforcement Policy (10 CFR2, Appendix C), the following

violation was identified:

Technical Specification 6.8.1.a requires that written procedures be

established, implemented and maintained. Operr. ting Instruction (01)-15,

Service Water System, Revision 14 dated June 21, 1982, requires that the

Service Water side of the Spent Fuel Pool Ccolers have their outlet valves

open and inlet valves positioned as desired, depending on the operational

status of the coolers.

Surveillance Test Procedure (STP) 0-7-1, Revision

27 requires that the #11 Spent Fuel Pool Cooler Service Water Inlet Valve

be opened following testing of the Containment Spray Actuation System

,

(CSAS) which closes the valve.

Contrary to the above, (a) STP 0-7-1 was not properly established in that

the procedure did not restore the Spent Fuel Pool Cooler Water Valve

lineup to that specified in 01-15; and, (b) STP 0-7-1 was not properly

implemented on September 20, 1983 in that the #11 Spent Fuel Pool Cooler

Service Water Inlet Valve was not opened following testing of the CSAS.

This is a Severity Level IV Violation (Supplement I) applicable to DPR-53.

Pursuant to the provisions of 10 CFR2.201, Baltimore Gas and Electric Company

'

is hereby required to submit to this office within thirty days of the date of

this Notice, a written statement or explanation in reply, including: (1) the

corrective steps which have been taken and the results achieved; (2) corrective

steps which will be taken to avoid further violations; and (3) the date when

full compliance will be achieved.

Where good cause is shown, consideration will be given to extending this

response time.

O hddk7

PDR

OFFICIAL RECORD COPY

191BISSETT10/6/83 - 0003.0.0

10/26/83

. - _.

. _

_ _ . - _ _ _ _ _ .

-

-

-

. . .

.

. .

.

.

. . .

__

_ . _ ,