(([ }&ofessional Loss Control, Inc.

i 1

i i

STRUCTURAL STEEL ANALYSIS l

for LIMERICK GENERATING STATION i

Spray Pond Pump Structure El. 251' ESW and RHRSW Pump Area

. Fire Area 122C December 20, 1983 P. O. Box 446

  • Oak Ridge, Tennessee 37830 e (G15) 482-3541 8401190478 840113 PDR ADOCK 05000352 PDR F

4

.o L*MERICK GENERATING STATION 1.

AREA DESCRIPTION The area under consideration is the ESW and RHRSW Pipeway on the 251' ele-vation of the Spray Pond Pump Structure (Fire Area 122C).

The Dounding walls of the' area are of reinforced concrete construction with an average thickness of 2 ft.

The total surface area for heat transfer is 2372 ft2 (see Attachment A for sketch and calculation of surface areas).

2.

COMBUSTIBLE LOADING All cabling in this area is routed in conduit, thcre are no cable trays.

There are ne combustible liquids in this area.

3.

VENTILATION PARAMETERS Ventilation to the area is through a hatch located in the Southwest corner

'of the area and is open to the 268' elevation.

4.

CASES EXAMINED With no exposed combustible cabling and no combustible liquids in the area, there is no fuel in the area to support a fire.

5.

.RESULTS Tne structural steel in this area will not fail due to a fire as there are no fixed combustibles in the-area to support a fire.

1 l'

v M

M M

V

_.3 1SP C

O O

,l J'

....l*

YI

~

~

I l

I Spray Pond Pump Structure El. 251' ESW and RHRSW Pipeway Surface Area. Calculation Walls North wall (38' x 17')

646 ft2 South wall (38' x'17')

646 ft2

' East wall (15' x 17')

255 ft2-West wall (15' x 17')

255 ft2 TBNf Ttt

< Ceiling

-(38' x 15')