}(( Professional Loss Control. Inc.
I STRUCTURAL STEEL ANALYSIS l
for-LIMERICK GENERATING STATION I
Unit 1 Reactor Building El. 352' Refueling Floor Fir,e Area 78A I
December 20, 1983 1
l P. O. Box 446
pm
LIMERICK GENERATING STATION 1.
AREA DESCRIPTION The area under. consideration is the Refueling Floor on the 352' elevation of the Unit 1 Reactor Building (Fire Area 78A). The bounding walls of the area are of reinforced concrete construction with an average thickness of 2.5 ft. The total surface area for heat transfer is '28,220 ft2 (see Attach.
- ment A for sketch and calculation of. surface. areas).
2.
COMBUSTIRLE LOADING
. All cabling in this area is routed in conduit, there are no cable trays.
There are no combustible liquids in this area.
3.
VENTILATION PARAMETERS This area is open to the remainder of the 352' elevation of the Reactor Building.
4.
CASES EXAMINED With no exposed combustible cabling and no combustible liquids in the area, there is no fuel in the area to support a fire.
5.
RESULTS The structural steel in ~ this area will not fail due to a fire as there are no fixed combustibles in the area to support a fire.
1
- :, h ;
r s
i
- Gl I_,
sr s<
'~
([,
d[,
I Unit 1 Reactor Building El. 352' Re' fueling Floor Surface Area Calculation
/
. Wall s North wall (160' x 30')
4800 ft2 South wall.
(160'.x 30')
4800 ft2 West wall (98' x-30')
2940 ft2
-12,540 ftt Ceiling
'(160' x 98')
15,680 ft2 Total' Surface Area for Heat Transfer 28,220 ft2 9