Amend 102 to License NPF-49,revising TS to Incorporate Different Setpoint & Transient Methodology for Determining Max Allowable Power Range Neutron Flux Setpoint
ML20078H437
Person / Time
Site: Millstone 
Issue date: 01/31/1995
From: Mckee P
Office of Nuclear Reactor Regulation
To:
Shared Package
ML20078H440 List:
References
NUDOCS 9502060210
Download: ML20078H437 (7)


Text

-. -

a us,I u

t UNITED STATES g

NUCLEAR REGULATORY COMMISSION E

E WASHINGTON, D.C. 20066 0001 l

f 4,*****,o NORTHEAST NVCLEAR ENERGY COMPANY. ET AL.

DOCKET NO. 50-423 MILLSTONE NUCLEAR POWER STATION. UNIT NO. 3 AMENDMENT TO FACILITY OPERATING LICENSE r

Amendment No.102 License No. NPF-49 1.

The Nuclear Regulatory Comission (the Comission) has found that:

A.

The application for amendment by Northeast Nuclear Energy Company, et al. (the licensee), dated July 22, 1994, complies with the standards and requirements of the Ato,iic Energy Act of' 1954, as amended (the Act), and the Commission's rules and regulations set forth in 10 CFR Chapter I; B.

The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Comission; C.

There is reasonable assurance (1) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Ccmission's regulations; i

D.

The issuance of this amendment will not be inimical to the comon i

defense and security or to the health and safety of the public; and E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the Comission's regulations and all applicable requirements have been satisfied.

{

L i

9502060210 950131 PDR ADOCK 05000423 P

PDR

! l L

2.

Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment, and paragraph 2.C.(2) of Facility Operating License No. NPF-49 is hereby amended to read as follows:

(2)

Technical Specifications The Technical Specifications contained in Appendix A, as revised through Amendment No.102

, and the Environmental Protection Plan contained in Appendix B, both of which are attached hereto are hereby incorporated in the license. The licensee shall operatn the facility in accordance with the Technical Specifications and the Environmental Protection Plan.

3.

This license ameadment is effective as of the date of its issuance, to i

be implemented within 30 days of issuance.

FOR THE NUCLEAR REGULATORY COMISSION Phillip F. McKee Director Project Directorate I-4 Division of Reactor Projects - I/II Office of Nuclear Reactor Regulation

Attachment:

Changes to the Technical Specifications Date of Issuance:

January 31, 1995

ATTACHMENT TO LICENSJ AMENDMEWT NO. 102 FACILITY OPEp6 TING LICENSE NO. NPF-49 j

DOCKET NO. 50-423 Replace the following pages of the Appendix A Technical Specifications with the enclosed pages.

The revised pages are identified by amendment number and j

contain vertical lines indicating the areas of change.

I Remove Insert 3/4 7-2 3/4 7-2

)

B 3/4 7-1 B 3/4 7-1 i

B 3/4 7-2 B 3/4 7-2 B 3/4 7-2a j

P i

l i

J

s TABLE 3.7-1 MAXIMUM ALLOWABLE POWER RANGE NEUTRON FLUX HIGH SETPOINT WITH INOPERABLE STEAM LINE SAFETY VALVES DURING FOUR LOOP OPERATION MAXIMUM NUMBER OF INOPERABLE MAXIMUM ALLOWABLE POWER RANGE SAFETY VALVES ON ANY NEUTRON FLUX HIGH SETPOINT OPERATING STEAM GENERATOR (PERCENT OF RATED THERMAL POWER) 1 65 2

46 3

28 TABLE 3.7-2 MAXIMUM ALLOWABLE POWER RANGE NEUTRON FLUX HIGH SETPOINT WITH INOPERABLE STEAM LINE SAFETY VALVES DURING THREE LOOP OPERATION MAXIMUM NUMBER OF INOPERABLE MAXIMUM ALLOWABLE F0WER RANGE SAFETY VALVES ON ANY NEUTRON FLUX HIGH SE1 POINT OPERATING STEAM GENERATOR *

(PERCENT OF RATED THERMAL POWER) i 47 2

33 3

19

  • At least two safety valves shall be OPERABLE on the non-operating steam l

generator.

l MILLSTONE - UNIT 3 3/4 7-2 Amendment No. 102 0273

3/4.7 PLANT SYSTEMS BA525 1

3/4.7.1 TURBINE CYCLE 3/4.7.1.1 SAFETY VALVES The OPERABILITY of the main steam line Code safety valves ensures that the Secondary System pressure will be limited to within 110% (1305 psig) of its design pressure of 1185 psig during the most severe anticipated system operational transient. The maximum relieving capacity is associated with a Turbine trip from 1001 'ATED THERMAL POWER coincident with an, assumed loss of condenser heat sink (i.e., no steam bypass to the condenser).

The specified valve lift settings and relieving capacities are in accordance with the requirements of Section III of the ASME Boiler and Pressure i

Code, 1971 Edition. The design minimum total relieving capacity for all valves on l all of the steam lines is 1.579 X 10 lbs/h which is 105% of the total secondary 1

7 steam flow of 1.504 X 10 lbs/h at 1005 RATED THERMAL POWER. A minimum of two 7

OPERABLE safety valves per steam generator ensures that sufficient relieving j

capacity is available for the allowable THERMAL POWER restriction in Table 3.7-2.

STARTUP and/or POWER OPERATION is allowable with safety valves inoperable within the limitations of the ACTION requirements on the basis of the reduction in Secondary Coolant System steam flow and THERMAL POWER required by the reduced Reactor trip settings of the Power Range Neutron Flux channels. The-Reactor Trip Setpoint reductions are derived on the following bases:

  1. 1 $ =(100/0) where:

f Hiil - Safety Analysis power range high neutron flux setpoint, percent Q

= Nominal NSSS power rating of the plant (including reactor coolant pump heat), Mwt K

- Conversion factor, 947.82 (Btu /sec)

Mwt hg-heat of vaporization for steam at the highest MSSV opening pressure including tolerance (t 3%) and accumulation, as appropriate, Btu /lba N

= Number of loops in plant i

4 NILLSTONE - UNIT 3 8 3/4 7-1 Amendment 2.102 0274

PLANT SYSTEMS BASES SAFETY VALVES (Continued) w,

- Minimum total steam flow rate capability of the operable MSSVs on any one steam generator at the highest MSSV opening pressure including tolerance and accumulation, as appropriate, in 1b/sec.

For example, if the maximum number of inoperable MSSVs on any one steam generator is one, then w should be a summation of the capacity of the operable MSSVs at the highest operable MSSV operating pressure, excluding the highest capacity MSSV.

If the maximum number of inoperable MSSVs per steam generator is three, then w, should be a summation of the capacity of the operable MSSVs at the highest operable MSSV operating pressure, excluding the three highest capacity MSSVs. The following plant specific safety valve flow rates were used:

SG Safety Main Steam System Valve Number (Bank No.)

Set Pressure (psia)

Flow (1bm/hr per loop) 1 1200 893,160 2

1210 900,607 3

1220 908,055 4

1230 915,502 5

1240 922,950 3/4.7.1.2 AUXILIARY FEEDWATER SYSTEM The OPERABILITY of the Auxiliary Feedwater System ensures that the Reactor Coolant System can be cooled down to less than 350*F from normal operating or accident conditions coincident with a total loss-of-offsite power.

The auxiliary feedwater system is capable of delivering a total feedwater flow of 480 gpm at a pressure of 1236 psia to the entrance of at least three steam generators while allowing for (1) any spillage through the design worst-i case break of the Normal feedwater line, (2) the design worst-case single fail-ure; and (3) recirculation flow. This capacity is sufficient to ensure that adequate feedwater flow is available to remove decay heat and reduce the Reactor Coolant System temperature to less than 350'F at which point the Residual Heat Removal System may be placed into operation.

MILLSTONE - UNIT 3 8 3/4 7-2 Amendment No. 102 0274

+

PLANT SYSTEMS BASES SAFETY VALVES (Continued) 3/4.7.1.3 DENINERALIZED WATER STORAGE TANK The OPERABILITY of the demineralized water storage tank with the minimum water volume ensures that sufficient water is available to maintain the RCS at HOT STANDBY conditions for 10 hours1.157407e-4 days <br />0.00278 hours <br />1.653439e-5 weeks <br />3.805e-6 months <br /> with steam discharge to the atmosphere i

concurrent with total loss-of-offsite power, and with an additional 6-hour cooldown period to reduce reactor coolant temperature to 350*F. The contained water volume limit includes an allowance for water not usable because of tank discharge line location or other physical characteristics.

3/4.7.1.4 SPECIFIC ACTIVITY The limitations on Secondary Coolant System specific activity ensure that the resultant offsite radiation dose will be limited to a small fraction of 10 CFR Part 100 dose guideline values in the event of a steam line rupture.

This dose also includes the effects of a coincident I gpm primary-to-secondary tube leak in the steam generator of the affected steam line. These values are consistent with the assumptions used in the safety analyses, MILLSTONE - UNIT 3 B 3/4 7-2a Amendment No.

u74 102