ML20076J834

From kanterella
Jump to navigation Jump to search
Rev to McGuire Nuclear Station Selected Licensee Commitment Manual, List of Effective Pages,Table 16.8-1a,Table 16.8-1b & Page 16.11-4
ML20076J834
Person / Time
Site: McGuire, Mcguire  
Issue date: 10/31/1994
From:
DUKE POWER CO.
To:
References
PROC-941031, NUDOCS 9410260385
Download: ML20076J834 (68)


Text

DtSPOSITION OF THE ORIGINAL r

PRIORITY NORMAL 7$,,",s",'[dat** M yy$, "

LEJA RECfPIENT IS OTHERWISE 90E4TIF'JJ BELOW.

DUKE POWER COMPANY 010005 0 A COPP EC050 DATE:

10/12/94 (2) 2702 U N MATillEUS MG01EE DOCUMENT TRANSMITTAL FORM DOCUMENT TRANSM!TTAL,

19,605 1311236 D V ETilINGTON EC130 18)4409 S A GEUEllR EC050 (5)3379 D E CALDUELL MG01RC O vts B "o (613/tg MrG Cl!EM SilIFI LEN Sl!PV N00lCll OA cONost:0~

(D 3133 li E PACETII itG02ME

REFERENCE:

ts)1996 J S MURANSKY Er0811 OTHER ACMNOWLEDGEMENT REQUfRED YES (9) 0777 T A REEO, OrlRR UASit DC MCGUIRE NUCLEAR STATION IF OA OR OTHER ACKNOWLEDGEMENT REQUIRED. PLE ASE 0013607 L K CRIMIN(WR RP SUPV MGOJRI' SELECTED LICENSEE QN,OW RECEIPT BY RE TURNING THIS FORM OR DPC o

043744 NEG DIR SIM (LINDSAY) MG030T COMMITHENTS MANUAL Mcoo., Nocio,, staten 0213044 MCG DUC CNikL MISC MAN f1002Dii PO Box 12700 11310422 MCG SAFETY REVIEU OROUP MG01SR

((,'r "b"" "'

0465079 G C DOVER CN01RC Huntarsvdle North Carchna 28078 0516593 0 E 1101 DEN MG03A2 0612257 R A llARRIS MG02iiE n,c a g, o,,,

043759 U S NUCLEAR REG UASil, DC QUAlirLCHEGEED L S H810297 REGION ADiilNISTRATIOR REG II PAGE 1 0F 4

DOCUMENTNO.

5 M

17 18 MM i

C D C ' D*

'u MCGU1RL NUCIEAR STATION NA 10/12/94 MADM-03 V1 V1 V1 V1 V1 V1 V1 V1 V1 V1 V2 V7 V2 V1 V1 L81 V7 ')1 73 l

SELECTED LICrinFE COMMI IMENT NA 10/12/94 MANtlAL NA 10/12/94 1ADLE 16.0-1A NA 10/12/94 16.0-1D NA 10/12/94 FAGE 14.11-4 NA 10/12/94 y,

\\

C 'T C

F -4 Ci 9410260385 941031 REMARKS PDR ADOCK 0500 P

T C MCMEEKIN VICE PRESIDENT MCGUIRE NUCLEAR STATION o

3 BY KAY L. CRANE KLC/CJB

___n____________

s O

October 4,1994

Subject:

McGuire Nuclear Station Selected Licensee Commitments Please find attached a revision to the McGuire Selected Licensee Commitment Manual.

Please revise your copy as follows:

Remove these pages Insert these pages LOEP 1 through 10 LOEP 1 through 7, Rev 0 Table 16.8-la Table 16.8-la pages 1 through 39 pages 1 through 28 Table 16.8-1b Table 16.8-1b pages 1 through 39 pages 1 through 30 page 16.11-4, dated 9/93 page 16.11-4 dated 9/94 O

Questions or problems should be directed to Kay Crane, Regulatory Compliance at extension 4306.

W Kay Crane Regulatory Compliance Attachment O

)

McGuire Nuclear Station Selected Licensee Commitments List of Effective Pages Page Revision Date LOEP Tab List of Effective Pages 0

1 through 7 Tab 16.0 16.0-1 16.0-2 Tab 16.1 16.1-1 Tab 16.2 16.2-1 3/91 16.2-2 5/91 16.2-3 16.2-4 Tab 16.3 16.3-1 Tab 16.4 Tab 16.5 16.5-1 01/94

~~

16.5-2 01/94 16.5-3 3/93 16.5-4 3/93 16.5-5 3/93 16.5-6 3/93 16.5-7 3/93 16.5-8 3/53 16.5-9 3/93 16.5-10 3/93 Tab 16.6 A

Tab 16.7 16.7-1 Revision 0

2 Page Revision Date Tab 16.8 16.8-1 10/90 Table 16.8-la 1 of 28 10/94 Table 16.8-la 2 of 28 10/94 Table 16.8-la 3 of 28 10/94 Table 16.8-la 4 of 28 10/94 Table 16.8-la 5 of 28 10/94 Table.16.8-la 6 of 28 10/94 Table 16.8-la 7 of 28 10/94 Table 16.8-la 8 of 28 10/54 Table 16.8-la 9 of 28 10/94 Table 16.8-la 10 of 28 10/94 Table 16.8-la 11 of 28 10/94 Table 16.8-la 12 of 28 10/94 Table 16.8-la 13 of 28 10/94 Table 16.8-la 14 of 28 10/94 Table 16.8-la 15 of 28 10/94 Table 16.8-la 16 of 28 10/94 Table 16.8-la 17 of 28 10/94 Table 16.8-la 18 of 28 10/94 Table 16.8-la 19 of 28 10/94 Table 36.8-la 20 of 28 10/94 Table 16.8-la 21 of 28 10/94 Table 16.8-la 22 of 28 10/94 Table 16.8-la 23 of 28 10/94 Table 16.8-la 24 of 28 10/94 Table 16.8-la 25 of 28 10/94 Table 16.8-la 26 of 28 10/94 Table 16.8-la 27 of 28 10/94 Table 16.8-la 28 of 28 10/94

  • ble 16.8-Ib 1 of 30 10/94 O.

Table 16.8-1b 2 of 30 10/94 2

Revision 0

i Pago Revision Date Table 16.8-1b 3 of 30 10/94 Table 16.8-1b 4 of 30 10/94 Table 16.8-Ib 5 of 30 10/94 Table 16.8-lb 6 of 30 10/94 Table 16.8-Ib 7 of 30 10/94 4

Table 16.8-1b 8 of 30 10/94 Table 16.8-Ib 9 of 30 10/94 Table 16.8-1b 10 of 30 10/94 Table 16.8-lb 11 of 30 10/94 Table 16.8-1b 12 of 30 10/94 Table 16.8-1b 13 of 30 10/94 Table 16.8-1b 14 of 30 10/94 Table 16.8-Ib 15 of 30 10/94 Table 16.8-1b 16 of 30 10/94 Table 16.8-lb 17 of 30 10/94 Table 16.8-1b 18 of 30 10/94 Table 16.8-lb 19 of 30 10/94 Table 16.8-Ib 20 of 30 10/94 Table 16.8-lb 21 of 30 10/94 Table 16.8-lb 22 of 30 10/94 Table 16.8-lb 23 of 30 10/94 Table 16.8-1b 24 of 30 10/94 Table 16.8-1b 25 of 30 10/94 Table 16.8-lb 26 of 30 10/94 Table 16.8-lb 27 of 30 10/94 Table 16.8-lb 28 of 30 10/94 Table 16.8-lb 29 of 30 10/94 Table 16.8-Ib 30 of 30 10/94 Tab 16.9 16.9-1 2/91 16.9-2 b'

16.9-3 3

Revision 0

i Page Revision Date 16.9-4 16.9-5 Table 16.9-1 16.9-6 16.9-7 16.9-8 16.9-9 Table 16.9-2 8/90 Table 16.9-2 (cont'd) 16.9-10 6/94 16.9-11 6/94 16.9-12 12/90 16.9-13 16.9-14 Table 16.9-3 12/90 Table 16.9-3 (cont'd) 12/90 Table 16.9-3 (cont'd) 12/90 Table 16.9-3 (cont'd) 12/90 Table 16.9-3 (cont'd)

~12/90 Table 16.9-3 (cont'd) 16.9-15 2/91 16.9-15a 2/91 16.9-16 16.9-17 16.9-18 16.9-19 Table 16.9-4 Table 16.9-5 16.9-20 08/93 16.9-21 08/93 Table 16.9-6 C

j Tab 16.10 4

Revision 0

....g Page Revision Date Tab 16.11 16.11-1 9/93 16.11-2 9/93 16.11-3 9/93 16.11-4 10/94 16.11-5 9/93 16.11-6 9/93 16.11-7 9/93 16.11-8 9/93 16.11-9 9/93 16.11-10 9/93 16.11-11 9/93 16.11-12 9/93 16.11-13 9/93 16.11-14 9/93 16.11-15 9/93 16.11-16 9/93 16.11-17 9/93 16.11-18 9/93 16.11-19 9/93 16.11-20 9/93 16.11-21 9/93 16.11-22 9/93 16.11-23 9/93 16.11-24 9/93 16.11-25 9/93 16.11-26 9/93 16.11-27 9/93 16.11-28 9/93 16.11-29 9/93 16.11-30 9/93 O

16.11-31 9/93 5

Revision O

Page Revision Date 16.11-32 9/93 16.11-33 9/93 16.11-34 12/93 16.11-35 12/93 16.11-36 12/93 16.11-37 12/93 16.11-38 9/93 16.11-39 9/93 16.11-40 9/93 16.11-41 9/93 16.11-42 9/93 16.11-43 9/93 I

16.11-44 9/93 16.11-45 9/93 16.11-46 9/93 16.11-47 9/93 l

16.11-48 9/93 l

i j

16.11-49 9/93 16.11-50 1/93 j

l 16.11-51 9/93 16.11-52 9/93 l

l 16.11-53 9/93 16.11-54 9/93 16.11-55 9/93 16.11-56 9/93 16.11-57 9/93 16.11-58 9/93 16.11-59 9/93 16.11-60 9/93 16.11-61 9/93 16.11-62 9/93 16.11-63 9/93 6

Revision O i

i

- - ~ -

i j

Page Revision Date 16.11-64 9/93 16.11-65 9/93 16.11-66 9/93 16.11-67 9/93 16.11-68 9/93 Tab 16.12 Tab 16.13 16.13-1 Tab 16.14 Tab 16.15 Appendix Tab 1

2 3

l 4

5 i

j 6

l l

7 l'

I I

l l

I l

I l

l L

1 I

Revision O l

l

\\J TABLE 16.8-la (Page 1 of 28)

UNIT 1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 1.

6900 VAC-Swgr Primary Bkr-RCPIA 5.0 15.4 @ 25A Reactor Coolant Pump 1A Backup Brk-1TA-5 5.0 16.5 @ 20A Primary Bkr-RCP1B 5.0 15.4 0 25A Reactor Coolant Pump 1B Backup Brk-1TB-5 5.0 16.5 @ 20A Primary Bkr-RCP1C 5.0 15.4 @ 25A Reactor Coolant Pump 1C Backup Brk-1TC-5 5.0 16.5 @ 20A Primary Bkr-RCP1D 5.0 15.4 @ 25A Reactor Coolant Pump 1D Backup Brk-1TD-5 5.0 16.5 @ 20A 2.

600 VAC-MCC IEMXA-2 1D Primary Bkr 20 45 @ 60A NC Pump 1C Thermal Barrier Backup Fuse 20 N.A.

Outlet Auto Isol Vlv 1KC345A i

1EMXA-2 1E Primary Bkr 20 45 @ 60A NC Pump 1A Thermal Barrier Backup Fuse 20 N.A.

Outlet Auto Isol Vlv 1KC394A 1EMXA-2 2A Primary Bkr 20 45 @ 60A Cont Air Return Fan 1A Damper Backup Fuse 20 N.A.

1RAF-D-2 1EMXA-2 2B Primary Bkr 20 45 @ 60A N2 to Prt Cont Isol Inside Backup Fuse 20 N.A.

Vlv 1NC54A 0

1EMXA-2 2C 2

Primary Bkr 20 45 @ 60A RCP Mtg Brg Oil Fill Isol Backup Fuse 20 N.A.

Viv 1NC196A 1EMXA-2 3A Primary Bkr 30 45 @ 90A Accumulator 1A Disch Isol Backup Fuse 30 N.A.

Viv 1NI54A

?

)

TABLE 16.8-la (Page 2 of 28)

UNIT 1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) lEMXA-2 3B Primary Bkr 30 45 @ 90A Accumulator 1C Disch Isol Backup Fuse 30 N.A.

Vlv INI76A 1EMXA-2 3C Primary Bkr 20 45 @ 60A Test Hdr Inside Cont Isol Backup Fuse 20 N.A.

Vlv 1NI95A 1EMXA-2 4A Primary Bkr Note 1 20 45 @ 60A UHI Check Vlv Test Line Isol Backup Fuse 20 N.A.

Vlv 1NI266A 1EMXA-2 4B Primary Bkr Note 1 20 45 @ 60A UHI Check Vlv Test Line Isol Backup Fuse 20 N.A.

Vlv 1NI267A 1EMXA-2 4C Primary Bkr 20 45 @ 60A Accum 1A Vent to INC34 for Backup Fuse 20 N.A.

Blkout Vlv 1NI430A j

1EMXA-2 5A Primary Bkr 20 45 @ 60A RN Containment Isolation Backup Fuse 20 N/A Vlv 1RN253A lEMXA-2 5B Primary Bkr 20 45 0 60A RN Containment Isolation Backup Fuse 20 N/A Vlv 1RN276A 1EMXA-3 2C Primary Bkr 20 45 @ 60A RV Containment Isolation Backup Fuse 20 N/A Vlv 1RV76A R

1EMXA-5 1B y

Primary Bkr 20 45 @ 60A Pzr Steam Sample Line Inside Backup Fuse 20 N.A.

Cont Isol Vlv INM3A 1EMXA-5 2C Primary Bkr 20 45 @ 60A Pzr Steam Sample Line Inside Backup Fuse 20 N.A.

Cont Isol Vlv 1NM6A

TABLE 16.8-la (Page 3 of 28)

UNIT 1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 1EMXA-5 3B Primary Bkr 20 45 @ 60A NC Hotleg 1A Sample Line Cont Backup Fuse 20 N.A.

Isol Vlv 1NM22A lEMXA-5 2D Primary Bkr 20 45 @ 60A NC Hotleg ID Sample Line Cont Backup Fuse 20 N.A.

Isol Viv 1NM25A 1EMXA-2 7A Primary Bkr 20 45 @ 60A SG 1A Upper Shell Sample Cont Backup Fuse 20 N.A.

Isol Vlv 1NM187A 1EMXA-2 7B Primary Bkr 20 45 @ 60A SG 1A Blowdown Line Sample Backup Fuse 20 N.A.

Cont Isol Vlv 1NM190A 1EMXA-2 7C i

Primary Bkr 20 45 @ 60A SG IC Upper Shell Sample Backup Fuse 20 N.A.

Cont Isol Viv 1NM207A 1EMXA-2 8A Primary Bkr 20 45 @ 60A SG IC Blowdown Line Sample Backup Fuse 20 N.A.

Cont Isol Viv 1NM210A lEMXA-4 1B Primary Bkr 20 45 @ 60A NC Pump Seal Return Cont i

Backup Fuse 20 N.A.

Vlv INV94AC i

1EMXA-3 3A Primary Bkr 20 45 @ 60A H2 Purge Exhaust Cont Vessel Backup Fuse 20 N.A.

Isol Vlv IVESA E

~lEMXA-3 4A 2

Primary Bkr 20 45 @ 60A H2 Skimmer Fan lA Suction Backup Fuse 20 N.A.

Isol Viv IVX1A 1EMXA-3 SB Primary Bkr 20 45 @ 60A RCDT Pump Disch Cont Isol i

Backup Fuse 20 N.A.

Vlv lWL2A 4

i

t

\\

TABLE 16.8-la (Page 4 of 28)

UNIT 1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) lEMXA-3 SC Primary Dkr 20 45 @ 60A RCDT Vent Cont Isol Viv Backup Fuse 20 N.A.

lWL39A lEMXA-3 6A Primary Bkr 20 45 @ 60A RB Sump Pump Disch Cont Isol Backup Fuse 20 N.A.

Vlv IWL64A 1EMXA-3 6B Primary Bkr 20 45 @ 60A cont Vent Unit condensate Backup Fuse 20 N.A.

Cont Isol Viv IWL321A 1EMXB-4 1B Primary Bkr 20 45 @ 60A NC Pump 1B Thermal Barrier Backup Fuse 20 N.A.

Outlet Auto Isol Vlv 1KC364B 1EMXB-4 1C Primary Bkr 20 45 @ 60A NC Pump 1D Thermal Barrier Backup Fuse 20 N.A.

Auto Isol Vlv 1KC413B lEMXB-4 2A Primary Bkr 20 45 @ 60A NC Pumps Return Hdr Pend Inside Backup Fuse 20 N.A.

Isol Vlv'1KC4248 lEMXB-4 2B Primary Bkr 20 45 @ 60A Reactor Bldg Drn Hdr Inside Cont Backup Fuse 20 N.A.

Isol Vlv 1KC429B IEMXB-4 2C Primary Bkr 30 45 @ 90A Accumulator 1B Disch Isol viv Backup Fuse 30 N.A.

1NI65B R

1EMXB-4 3D y

Primary Bkr 30 45 @ 90A Accumulator ID Disch Isol viv Backup Fuse 30 N.A.

INI88B IEMXB-4 3E Primary Bkr 20 45 @ 60A Hotleg Inj Check 1NI124, 1NI128 Backup Fuse 20 N.A.

Test Isol Viv 1NI122B

r n

t TABLE 16.8-la (Page 5 of 28)

UNIT 1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME t

DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued)

IEMXB-4 4A Primary Bkr 20 45 @ 60A Cont Air Return Fan IB Damper Backup Fuse 20 N.A.

IRAF-D-4 IEMXB-4 4C Primary Bkr 20 45 @ 60A NI Accum 1A Sample Line Inside i

Backup Fuse 20 N.A.

Cont Isol Vlv INM72B 1EMXB-4 5A Primary Bkr 20 45 @ 60A NI Accum IB Sample Line Backup Fuse 20 N.A.

Inside Cont Isol Vlv 1NM75B i.

1EMXB-4 5B Primary Bkr 20 45 0 60A NI Accum 1C Sample Line Backup Fuse 20 N.A.

Inside Cont Isol Vlv INM788 1EMXB-4 SC Primary Bkr 20 45 @ 60A Accum IB Vent to INC32 for Backup Fuse 20 N.A.

Blkout Vlv 1NI431B 1EMXB-4 6A Primary Bkr 20 45 @ 60A NI Accum 1D Sample Line Backup Fuse 20 N.A.

Inside Cont Isol Valve INM81B 1EMXB-4 6B Primary Bkr 20 45 0 60A SG 1B Upper Shell Sample Backup Fuse 20 N.A.

Cont Isol Viv 1NM197B 1EMXB-4 6C Primary Bkr 20 45 @ 60A SG 1B Blowdown Line Sample l

Backup Fuse 20 N.A.

Cont Isol Viv 1NM200B b

1EMXB-4 7B

[

D Primary Bkr 20 45 @ 60A SG ID Uper Shell Sample Backup Fuse 20 N.A.

Cont Isol Vlv 1NM217B 1EMXB-4 7C Primary Bkr 20 45 0 60A SG ID Blowdown Line Sample Backup Fuse 20 N.A.

Cont Isol Viv 1NM220B l

t l

O O

~

TABLE 16.8-la (Page 6 of 28)

UNIT 1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 1EMXB-5 1B Primary Bkr 20 45 @ 60A RV Containment Isolaticn Backup Fuse 20 N/A Vlv 1RV33B IEMXB-5 1C Primary Bkr 20 45 @ 60A H2 Skimmer Fan 1B Suction Backup Fuse 20 N.A.

Isol Viv IVX2B 1EMXC-1A Primary Bkr 200 250 @ 600A Lower Containment Cooling Backup Fuse 200 N.A.

Unit No. lA j

1EMXC-2A Primary Bkr 200 250 @ 600A Lower containment Cooling Backup Fuse 200 N.A.

Unit No. 1C IEMXC-3C Primary Bkr 100 110 @ 300A Control Rod Drive Vent Fan Backup Fuse 100 N.A.

No. 1A 1EMXC-3D Primary Bkr 100 110 0 300A Control Rod Drive Vent Fan

[

Backup Fuse 100 N.A.

No. 1C 1EMXC-4C Primary Bkr 90 110 @ 270A Containment Air Return Fan l

Backup Fuse 90 N.A.

No. lA 1EMXC-4D Primary Bkr 90 110 0 270A Hydrogen Recombiner Backup Fuse 90 N.A.

No. lA R

1EMXC-6A f

Primary Bkr 40 45 @ 120A Containment Pipe Tunnel Backup Fuse 40 N.A.

Booster Fan CPT-BF-1A 1EMXC-6B Primary Bkr 30 45 0 90A Upper Containment Air Backup Fuse 30 N.A.

Handling Unit 1A

f l

1 j

TABLE 16.8-la (Page 7 of 28)

UNIT 1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES i

TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) lEMXC-6C Primary Bkr 30 45 0 90A Upper Containment Air Hdig Backup Fuse 30 N.A.

Unit 1C lEMXC-6D Primary Bkr 90 110 @ 270A Hydrogen Skimmer Fan Backup Fuse 90 N.A.

No. lA 1EMXC-7C Primary Bkr 30 45 0 90A Upper Cont Return Air Fan Backup Fuse 30 N.A.

No. 1C 1EMXC-7D Primary Bkr 20 45 @ 60A Pzr Pwr Oper Relief Backup Fuse 20 N.A.

Isol Viv 1NC33A lEMXC-8C Primary Bkr 20 45 @ 60A Incore Instrumentation Rm Backup Fuse 20 N.A.

Air Hdig Unit 1A lEMXC-8D Primary Bkr 20 45 @ 60A Upper Containment Return Backup Fuse 20 N.A.

Air Fan No. lA 1EMXA-4 3C Primary Bkr 30 45 0 90A NC Loop 1C Discharge to ND Backup Fuse 30 N.A.

System Cont Isol Vlv.lND2A,C lEMXD-1A Primary Bkr 200 250 0 600A Lower Containment Cooling Backup Fuse 200 N.A.

Unit No. 1B 5

lEMXD-2A 3

Primary Bkr 200 250 @ 600A Lower containment Cooling Backup Fuse 200 N.A.

Unit No. 1D lEMXD-3B Primary Bkr 40 45 0 120A Containment Pipe Tunnel Backup Fuse 40 N.A.

Booster Fan CPT-BF-1B

(

TABLE 16.8-la (Page 8 of 28)

UNIT 1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 1EMXD-3C Primary Bkr 100 110 @ 300A Control Rod Drive Vent Fan Backup Fuse 100 N.A.

No. 1B 1EMXD-3D Primary Bkr 100 110 @ 300A Control Rod Drive Vent Fan Backup Fuse 100 N.A.

No. ID 1EMXD-4C Primary Bkr 90 110 @ 270A Containment Air Return Fan Backup Fuse 90 N.A.

No. 1B Fan CPT-BF-1A 1EMXD-4D Primary Bkr 90 110 0 270A Hydrogen Recombiner No. IB Backup Fuse 90 N.A.

1EMXD-6C Primary Bkr 30 45 @ 90A Upper Containment Air Hdig Unit Backup Fuse 30 N.A.

No. 1B 1EMXD-6D Primary Bkr 30 45 @ 90A Upper Containment Air Hdig Unit Backup Fuse 30 N.A.

No. 1D 1EMXD-6E Primary Bkr 90 110 @ 270A Hydrogen Skimmer Fan No. 1B Backup Fuse 90 N.A.

lEMXD-7B Primary Bkr 30 45 @ 90A Upper Cont Return Air Fan Backup Fuse 30 N.A.

No. 1D e

C 1EMXD-7C y

Primary Bkr 20 45 @ 60A Pzr No. 1 Pwr Oper Safety Backup Fuse 20 N.A.

Relief Isol Viv 1NC31B 1EMXD-7D Primary Bkr 20 45 @ 60A Pzr No. 1 Pwr Oper Safety Backup Fuse 20 N.A.

Relief Isol Viv INC35B

F m.._._._-. _ _ - _.-.

1 0

l TABLE 16.8-la (Page 9 of 28)

UNIT 1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (continued) 1EMXD-8B Primary Bkr 20 45 @ 60A Incore Instrumentation Rm l

Backup Fuse 20 N.A.

Air Hdig Unit 1B

{

1EMXD-8C Primary Bkr 20 45 @ 60A Upper Containment Return Air Backup Fuse 20 N.A.

Fan 1B 1EMXD-8D Primary Bkr 30 45 0 90A NC Loop 1C Disch to ND Systam Backup Fuse 30 N.A.

Cont Isol Vlv 1ND1B 1MXM F1A Primary Bkr 40 45 @ 120A Lighting Pnlbd ILR14 Backup Nse 40 N.A.

t IMXM F1B Primary Bkr 40 45 @ 120A Lighting Pnibd ILR15 Backup Fuse 40 N.A.

1MXM Flc Primary Bkr 30 45 @ 90A S/G Boost Fan 1C

{

Backup Fuse 30 N/A 1MXM F1D Primary Bkr 20 45 @ 60A Ice Cond AHU 1A1 Blower A Backup Fuse 20 N.A.

i 1MXM F1E Primary Bkr 20 45 @ 60A Ice Cond AHU 1A2 Blower A Backup Fuse 20 N.A.

1MXM F2A 3

Primary Bkr 40 45 @ 120A Lighting Pnlbd lLR16 Backup Fuse 40 N.A.

1MXM F2B Primary Bkr 40 45 @ 120A Lighting Pnibd 1LR17 Backup Fuse 40 N.A.

1 1.

m.

m

. m...

O O

C

~

i TABLE 16.8-la (Page 10 of 28)

UNIT 1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 1MXM F2C Primary Bkr 25 45 @ 75A Reactor Bldg Equip Hdig 5 Ton Backup Fuse 25 N.A.

Jib Crane IMXM F2D Primary Bkr 20 45 @ 60A Ice cond AHU 1A3 Blower A Backup Fuse 20 N.A.

1MXM F2E Primary Bkr 20 45 0 60A Ice cond AHU 1A4 Blower A Backup Fuse 20 N.A.

IMXM F3A Primary Bkr 20 45 0 60A Ice Cond AHU 1A5 Blower A Backup Fuse 20 N.A.

IMXM F3B Primary Bkr 20 45 @ 60A Ice cond AHU 1A6 Blower A Backup Fuse 20 N.A.

IMXM F3C Primary Bkr 20 45 @ 60A Incore Inst Room Sump Pump Backup Fuse 20 N.A.

1MXM F3D Primary Bkr 100 110 @ 300A Upper Cont Welding Recpt Backup Fuse 100 N.A.

IMXM F4A Primary Bkr 20 45 0 60A Ice Cond AHU 1A7 Blower A Backup Fuse 20 N.A.

b 1M7F F4B D

Primary Bkr 20 45 @ 60A Ice Cond AHU 1A8 Blower A I

Backup Fuse 20 N.A.

IMXM F4D Primary Ekr 100 110 0 300A Welding Feeder Backup Fuse 100 N.A.

l l

~

c o

TABLE 16.8-la (Page 11 of 28)

UNIT 1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 1MXM F5C Primary Bkr 50 110 0 150A Ice Cond Floor Cooling Backup Fuse 50 N.A.

Defrost Heater IA 1MXM F6C Primary Bkr 60 110 @ 180A Reactor Coolant Drain Tank Backup Fuse 60 N.A.

Pump 1A 1MXM F7A Primary Bkr 20 45 @ 60A Ice Cond AHU 1A9 Blower A Backup Fuse 20 N.A.

l 1MXM F7B Primary Bkr 20 45 @ 60A Ice Cond AHU 1A10 Blower A Backup Fuse 20 N.A.

IMXM F7C Primary Bkr 30 45 @ 90A Lower Cont Aux Charcoal Filter Backup Fuse 30 N.A.

Fan IA iMXM F8A Primary Bkr 20 45 @ 60A Ice Cond AHU 1A11 Blower A Backup Fuse 20 N.A.

1MXM F8B Primary Bkr 20 45 @ 60A Ice Cond AHU 1A12 Blower A Backup Fuse 20 N.A.

1MXM F8C Primary Bkr 20 45 0 60A Ice Cond AHU 1A13 Blower A Backup Fuse 20 N.A.

~

R IMXM R1A Primary Bkr 20 45 @ 60A Ice Cond AHU IB1 Blower A e

Backup Fuse 20 N.A.

1MXM R1B Primary Bkr 20 45 0 60A Ice Cond AHU 1B2 Blower A Backup Fuse 20 N.A.

V 3

TABLE 16.8-la (Page 12 of 28)

UNIT 1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 1MXM RlC Primary Bkr 20 45 @ 60A Ice Cond AHU IB3 Blower A Backup Fuse 20 N.A.

1MXM RID Primary Bkr 30 45 0 90A RCP 1A Oil Lift Pump Backup Fuse 30 N.A.

1MXM R2A Primary Bkr 40 45 @ 120A Lighting Pnlbd ILR12 Backup Fuse 40 N.A.

IMXM R2D Primary Bkr 20 45 @ 60A Ice Cond AHU 1B4 Blower A Backup Fuse 20 N.A.

1MXM R2E Primary Bkr 30 45 0 90A RCP 1B Oil Lift Pump Backup Fuse 30 N.A.

IMXM R3D Primary Bkr 20 45 0 60A Ice Cond AHU IB5 Blower A Backup Fuse 20 N.A.

IMXM R3E Primary Bkr 20 45 @ 60A Ice Cond AHU IB6 Blower A Backup Fuse 20 N.A.

1MXM R3F Primary Bkr 30 45 @ 90A RCP 1C Oil Lift Pump Backup Fuse 30 N.A.

'i k

1MXM R4D y

Primary Bkr 20 45 @ 60A Ice Cond AHU IB7 Blower A Backup Fuse 20 N.A.

I 1MXM R4E Primary Bkr 20 45 0 60A Ice Cond AHU 188 Blower A Backup Fuse 20 N.A.

r TABLE 16.8-la (Page 13 of 28)

UNIT 1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED i

2.

600 VAC-MCC (Continued)

IMXM R4F Primary Bkr 30 45 0 90A RCP 1D Oil Lift Pump Backup Fuse 30 N.A.

IMXM R5B Primary Bkr 20 45 @ 60A Ice Cond AHU 189 Blower A Backup Fuse 20 N.A.

IMXM R5C Primary Bkr 20 45 @ 60A Ice cond AHU 1B10 Blower A Backup Fuse 20 N.A.

1MXM R5D Primary Bkr 175 200 @ 525A Ice Cond Equip Pwr Pnlbd IB Backup Fuse 175 N.A.

1MXM R6A Primary Bkr 20 45 0 60A Rod Cntrl Cluster Change Backup Fuse 20 N.A.

Fixture Hoist Drive 1MXM R6B Primary Bkr 20 45 @ 60A Ice Cond AHU 1B11 Blower A Backup Fuse 20 N.A.

IMXM R7A Primary Bkr 20 45 @ 60A Stud Tensioner Hoist Backup Fuse 20 N.A.

1MXM R6E Primary Bkr 150 110 @ 450A 175 Ton Polar Crane Backup Fuse 150 N.A.

~

R IMXM R7B y

Primary Bkr 20 45 0 60A Incore Inst Drive 1A Backup Fuse 20 N.A.

1MXM R7D Primary Bkr 20 45 @ 60A Ice Cond AHU 1B12 t

Backup Fuse 20 N.A.

m m.

a

TABLE 16.8-la (Page 14 of 28)

UNIT 1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued)

IMXM R7E Primary Bkr 20 45 @ 60A Ice cond AHU 1813 Blower A Backup Fuse 20 N.A.

IMXM R8A Primary Bkr 20 45 @ 60A Incore Inst Drive IB Backup Fuse 20 N.A.

4 1MXM R8B Primary Bkr 20 45 @ 60A Incore Inst Drive 1C Backup Fuse 20 N.A.

I 1MXM R8D Primary Bkr 20 45 @ 60A Ice Cond AHU 1814 Blower A Backup Fuse 20 N.A.

1MXM R8E Primary Bkr 20 45 @ 60A Ice Cond AHU 1815 Blower A Backup Fuse 20 N.A.

1MXMA-1B Primary Bkr 30 45 @ 90A Vent Press Boost Fan 1B Backup Fuse 30 N/A iMXMA-ID Primary Bkr 20 45 @ 60A Ice Cond AHU 1A14 Blower A Backup Fuse 20 N.A.

1MXMA-1E Primary Bkr 20 45 @ 60A Cont Floor & Equip Sump 1A Backup Fuse 20 N.A.

Pump 1A1 R

IMXMA-2A g

Primary Bkr 25 45 @ 75A RCPM Maintenance Crane Recpt Backup Fuse 25 N.A.

lA, IB, 1C, & ID IMXK'l-2B Primary Bkr 25 45 @ 75A Lighting Pnlbd ILR6 Backup Fuse 25 N.A.

I

_...~_..__..__....___..-.____..._..._....m..____.

O O

TABLE 16.8-la (Page 15 of 28)

UNIT 1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued)

IMXMA-2C Primary Bkr 40 45 @ 120A Lighting Pnlbd 1LR18 Backup Fuse 40 N.A.

1MXMA-2D Primary Bkr 20 45 @ 60A Ice Cond AHU 1A15 Blower A Backup Fuse 20 N.A.

1MXMA-3A Primary Bkr 25 45 @ 75A Lighting Pnibd ILR9 Backup Fuse 25.

N.A.

IMXMA-3B Primary Bkr 20 45 @ 60A Ice Cond Equip Access Backup Fuse 20 N.A.

Door IA IMXMA-3C Primary Bkr 50 110 @ 150A Ice Cond Floor Cooling Backup Fuse 50 N.A.

Pump 1A 1MXMA-3D Primary Bkr 20 45 @ 60A Cont Floor & Equip Sump 1B Backup Fuse 20 N.A.

Pump 1B1 IMXN-F1A Primary Bkr 20 45 @ 60A Ice Cond AHU 1A1 Blower B Backup Fuse 20 N.A.

IMXN-F1B Primary Bkr 20 45 @ 60A Ice Cond AHU 1A2 Blower B Backup Fuse 20 N.A.

~

0 1MXN-FlC y

Primary Bkr 20 45 @ 60A Ice Cond AHU 1A3 Blower B Backup Fuse 20 N.A.

1MXN-F1D Primary Bkr 20 45 @ 60A Ice cond AHU 1A4 Blower B Backup Fuse 20 N.A.

TABLE 16.8-la (Page 16 of 28)

UNIT 1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (continued) i IMXN-F2A Primary Bkr 20 45 @ 60A Ice Cond AHU 1A5 Blower B Backup Fuse 20 N.A.

1MXN-F2B Primary Bkr 20 45 0 60A Ice Cond AHU 1A6 Blower B Backup Fuse 20 N.A.

IMXN-F2C Primary Bkr 20 45 @ 60A Ice Cond AHU 1A7 Blower B Backup Fuse 20 N.A.

1MXN-F2D Primary Bkr 20 45 @ 60A Ice Cond AHU 1A8 Blower B Backup Fuse 20 N.A.

I 1MXN-F3A Primary Bkr 25 45 @ 75A Lighting Pnibd ILR1 Backup Fuse 25 N.A.

IMXN-F3B Primary Bkr 30 45 0 90A S/G Booster Fan IB Backup Fuse 30 N/A 1MXN-F3C Primary Bkr 25 45 @ 75A Lighting Pnibd ILR2 f

Backup Fuse 25 N.A.

i 1MXN-F3D Primary Bkr 20 45 0 60A Ice Cond AHU 1A9 Blower B Backup Fuse 20 N.A.

C 1MXN-F3E Primary Bkr 20 45 @ 60A Ice Cond AHU 1A10 Blower B e"

Backup Fuse 20 N.A.

1MXN-F4A Primary Bkr 20 45 @ 60A Incore Inst Drive No. 1D Backup Fuse 20 N.A.

s

'l I

I

______.___________._.___m.._________._.____.__,___________.______.___.__,_m__

C O

O TABLE 16.8-la (Page 17 of 28)

UNIT 1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued)

IMXN-F4B Primary Bkr 20 45 0 60A Incore Inst Drive No. lE Backup Fuse 20 N.A.

1MXN-F4C Primary Bkr 20 45 0 60A Incore Inst Drive No. 1F Backup Fuse 20 N.A.

IMXN-F4D Primary Bkr 20 45 @ 60A Cont Floor & Equip Sump 1A Backup Fuse 20 N.A.

Pump 1A2 IMXN-F5C Primary Bkr 60 110 0 180A Reactor Coolant Drain Tank Backup Fuse 60 N.A.

Pump 1B IMXN-F6B Primary Bkr 20 45 @ 60A Cont Floor & Equip Sump 1B

'i Backup Fuse 20 N.A.

Pump 1B2 I

1MXN-F6C Primary Bkr 50 110 0 150A Ice Cond Floor Cooling Backup Fuse 50 N.A.

Defrost Htr 1B IMXN-F7A Primary Bkr 25 45 0 75A Lighting Pnlbd lLR4 Backup Fuse 25 N.A.

1MXN-F7B i

Primary Bkr 25 45 0 75A Lighting Pnlbd ILR5 Backup Fuse 25 N.A.

R IMXN-F7C y

Primary Bkr 20 45 @ 60A Fuel Transfer Sys Reactor Backup Fuse 20 N.A.

Side Fdr j

1MXN-F7D Primary Bkr 20 45 0 60A Ice Cond AHU 1All Blower B Backup Fuse 20 N.A.

O O

+

~

TABLE 16.8-la (Page 18 of 28)

UNIT 1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-Mcc (Continued)

IMXN-F8B Primary Bkr 30 45 0 90A S/G Booster Fan lA Backup Fuse 30 N/A 1MXN-F8D Primary Bkr 20 45 @ 60A Ice Cond AHU 1A12 Blower B Backup Fuse 20 N.A.

1MXN-F8E Primary Bkr 20 45 @ 60A Ice Cond AHU 1A13 Blower B Backup Fuse 20 N.A.

1MXN-R1D Primary Bkr 20 45 @ 60A Ice Cond AHU IB1 Blower B Backup Fuse 20 N.A.

1MXN-RlE Primary Bkr 20 45 @ 60A Ice Cond AHU IB2 Blower 13 Backup Fuse 20 N.A.

1MXN-R1F Primary Bkr 30 45 @ 90A RCP 1A Oil Lift Pump No. 2 Backup Fuse 30 N.A.

1MXN-R2C Primary Bkr 30 45 @ 90A Reactor Cavity Manipulator Backup Fuse 30 N.A.

Crane IMXN-R2F Primary Bkr 30 45 @ 90A RCP 1B Oil Lift Pump No. 2 Backup Fuse 30 N.A.

~

C-1MXN-R3A y

Primary Bkr 20 45 @ 60A Ice Cond AHU 1B3 Blower B Backup Fuse 20 N.A.

1MXN-R3B Primary Bkr 20 45 0 60A Ice Cond AHU 1B4 Blower B Backup Fuse 20 N.A.

m.

.....m...

m_

-_...__._._._.m

_._....m.m.m____..__

m.._..

..__._..m_m__.

... _ _ m_

TABLE 16.8-la (Page 19 of 28)

UNIT 1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM PCWERED 2.

600 VAC-MCC (Continued) 1MXN-R3C I

Primary Bkr 20 45 @ 60A Ice Cond AHU IB5 Blower B Bac)2p Fuse 20 N.A.

1MXN-R3D Primary Bkr 30 45 @ 90A RCP IC Oil Lift Pump No. 2 Backup Fuse 30 N.A.

1MXN-R4A Primary Bkr 50 110 @ 150A Ice Cond Bridae Crane Backup Fuse 50 N.A.

IMXN-R4B Primary Bkr 30 45 @ 90A RB Equip " tch Hoist No. 1 Backup Fuse 30 N.A.

IMXN-R4C Primary Bkr 30 45 @ 90A S/G Booster Fan lA Backup Fuse 30 N/A 1MXN-R4D Primary Bkr 20 45 @ 60A Ice Cond AHU 1B6 Blower B Backup Fuse 20 N.A.

1MXN-R4E Primary Bkr 30 45 @ 90A RCP 1D Oil Lift Pump No. 2 Backup Fuse 30 N.A.

1MXN-RSD Primary Bkr 175 200 @ 525A Ice Cond Equip Pwr Pnibd 1A Backup Fuse 175 N.A.

R IMXN-R6A y

Primary Bkr 20 45 @ 60A Ice Cond AHU IB7 Blower B Backup Fuse 20 N.A.

r 1MXN-R6B Primary Bkr 20 45 @ 60A Ice Cond AHU IB8 Blower B Backup Fuse 20 N.A.

l

L O

t TABLE 16.8-la (Page 20 of 18)

UNIT 1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 1MXN-R6C Primary Bkr 20 45 0 60A Ice Cond AHU 1B9 Blower B Backup Fuse 20 N.A.

1MXN-R6D Primary Bkr 100 110 @ 300A Welding Fdr Backup Fuse 100 N.A.

IMXN-R7A Primary Bkr 20 45 @ 60A Ice cond AHU 1B10 Blower B Backup Fuse 20 N.A.

IMXN-R7B Primary Bkr 20 45 @ 60A Ice Cond AHU 1B11 Blower B Backup Fuse 20 N.A.

1MXN-R7C Primary Bkr 20 45 @ 60A Ice Cond AHU 1B12 Blower B Backup Fuse 20 N.A.

1MXN-R7D Primary Bkr 50 110 @ 150A Ice Cond Floor Cooling Backup Fuse 50 N.A.

Pump 1B 1MXN-R8D Primary Bkr 20 45 0 60A Ice Cond AHU 1813 Blower B Backup Fuse 20 N.A.

1MXN-R83 Primary Bkr 20 45 @ 60A Ice Cond AHU 1Bli Blower B Bachip Fuse 20 N.A.

R IMXN rSF f

Prirary Bkr 20 45 @ 60A Ice Cond AHU 1B15 Blower B Backup Fuse 20 N.A.

IMXNA-1E Primary Bkr 30 45 0 90A Lower Cont Aux Charcoal Backup Fuse 30 N.A.

Filter Fan IB

N N

N TABLE 16.8-la (Page 21 of 28)

UNIT 1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 1MXNA-2A Primary Bkr 30 45 @ 90A Vent Press Boost Fan 1A Backup Fuse 30 N/A i

1MXNA-2B t.

Primary Bkr 25 45 @ 75A Lighting Pnibd ILR7 Backup Fuse 25 N.A.

1MXNA-2C Primary Bkr 25 45 0 75A Lighting Pnlbd 1LR8 Backup Fuse 25 N.A.

1MXNA-2D Primary Bkr 20 45 @ 60A Ice Cond AHU 1A14 Blower B Backup Fuse 20 N.A.

1MXNA-2E Primary Bkr 20 45 @ 60A Ice Cond AHU 1A15 Blower B Backup Fuse 20 N.A.

1MXNA-3A Primary Bkr 20 45 @ 60A 2 Ton CRDM Hdig Jib Crane Backup Fuse 20 N.A.

1MXNA-38 Primary Bkr 30 45 0 90A cont Air Compressor Backup Fuse 30 N/A SMXG-F3G Primary Bkr 20 45 0 60A Standby Makeup Pump to Backup Fuse 20 N.A.

Cont Sump Isol Viv 1NV1012C

-R SMXG-F4G y

Primary Bkr 20 45 0 60A Standby Makeup Pump to NC Backup Fuse 20 N.A.

Pump Seals Isol Viv 1NV1013C 1MXNA-3C Primary Bkr 2C 45 @ 60A NC Pump Motor Drain Tank Backup Fuse 20 N.A.

Pump No. 1 4

. u r

O O

TABLE 16.8-la (Page 22 of 28)

UNIT 1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Cont,ued) 1MXNA-3D Primary Bkr 20 45 0 60A Ice Cond Equip Access Door 1B Backup Fuse 20 N.A.

SMXC-7D Primary Bkr 15 45 @ 45A Unit 1 Personnel Lock i

Backup Fuse 15 N.A.

SMXA-F4A Primary Bkr 15 45 0 45A Unit 1 Emergency Personnel Lock Backup Fuse 15 N.A.

3.

600 VAC-Press Htr Pwr Pnis Backup Press Htr Pwr Pnl 1A-1A Primary Bkr 90 110 @ 270A Pressurizer Heaters 1, 2,

& 22 Backup Fuse 90 N.A.

Backup Press Htr Pwr Pnl 1A-1B Primary Bkr 90 110 0 270A Pressurizer Heaters 5, 6,

& 27 Backup Fuse 90 N.A.

Backup Press Htr Pwr Pnl 1A-1C Primary Bkr 90 110 0 270A Pressurizer Heaters 9, 10, Backup Fuse 90 N.A.

& 32 Backup Press Htr Pwr

~

R Pnl 1A-2C y

Primary Bkr 90 110 @ 270A Pressurizer Heaters 11, 12, Backup Fuse 90 N.A.

& 35 Backup Press Htr Pwr Pnl 1A-2D Primary Bkr 90 110 0 270A Pressurizer Heaters 13, 14 Backup Fuse 90 N.A.

& 37

t TABLE 16.8-la (Page 23 of 28)

UNIT 1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 3.

600 VAC-Press Htr Pwr Pnis (Continued)

~

Backup Press Htr Pwr Pnl 1A-2E Primary Bkr 90 110 @ 270A Pressurizer Heaters 17, 18, Backup Fuse 90 N.A.

& 42 Backup Press Htr Pwr Pnl 1B.-1A Primary Bkr 90 110 0 270A Pressurizer Heaters 21, 47, Backup Fuse 90 N.A.

& 48 Backup Press Htr Pwr Pnl IB-1B Primary Bkr 90 110 9 270A Pressurizer Heaters 26, 53, Backup Fuse 90 N.A.

& 54 Backup Press Htr Pwr Pnl 1B-1C Primary Bkr 90 110 0 270A Pressurizer Heaters 31, 59, Backup Fuse 90 N.A.

& 60 Backup Press Htr Pwr Pnl 1B-2C Primary Bkr 90 110 9 270A Pressurizer Heaters 36, 65, Backup Fuse 90 N.A.

& 66 Backup Press Htr Pwr Pnl 1B-2D Primary Bkr 90 110 0 270A Pressurizer Heaters 41, 71, Backup Fuse 90 N.A.

& 72 k

Backup Press Htr Pwr e

Pnl 1B-2E Primary Bkr 90 110 0 270A Pressurizer Heaters 46, 77, Backup Fuse 90 N.A.

& 78 Backup Press Htr Pwr Pnl 1C-1A Primary Bkr 90 110 @ 270A Pressurizer Heaters 7, 8,

TABLE 16.8-la (Page 24 of 28)

UNIT 1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED Backup Fuse 90 N.A.

& 30 i

I J

4 1

i O3 e

l

1 o

TABLE 16.8-la (Page 25 of 28)

UNIT 1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 3.

600 VAC-Press Htr Pwr Pnis (Continued)

Backup Press Htr Pwr Pnl IC-1B Primary Bkr 90 110 @ 270A Pressurizer Heaters 19, 20, Backup Fuse 90 N.A.

& 45 i

Backup Press Htr Pwr Pnl 1C-1C Primary Bkr 90 110 0 270A Pressurizer Heaters 24, 51, Backup Fuse 90 N.A.

& 52 Backup Press Htr Pwr Pnl 1C-1D Primary Bkr 90 110 @ 270A Pressurizer Heaters 29, 57, Backup Fuse 90 N.A.

& 58 Backup Press Htr Pwr Pnl 1C-2C Primary Bkr 90 110 @ 270A Pressurizer Heaters 34, 63, Backup Fuse 90 N.A.

& 64 Backup Press Htr Pwr Pnl 1C-2D Primary Bkr 90 110 @ 270A Pressurizer Heaters 39, 69, Backup Fuse 90 N.A.

& 70 Backup Press Htr Pwr Pnl 1C-2E Primary Bkr 90 110 0 270A Pressurizer Heaters 44, 75, Backup Fuse 90 N.A.

& 76 Backup Press Htr Pwr

-o Pnl ID-1A D

Primary Bkr 90 110 @ 270A Pressurizer Heaters 3, 4,

Backup Fuse 90 N.A.

& 25 Backup Press Htr Pwr Pnl 1D-1B Primary Bkr' 90 110 @ 270A Pressurizer Heaters 15, 16, Backup Fuse 90 N.A.

& 40'

f'"

,/' %

f'

/

\\

/

\\

/

\\

\\

N TABLE 16.8-la (Page 26 of 28)

UNIT 1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP EETPOINT OR

RESPONSE

CON'.y. RATING TIME DEVICE NUMBER & LOCATION (A) PERES)

(SECONDS)

SYSTEM POWERED 3.

600 VAC-Press Htr Pwr Pnis (Continued)

Backup Press Htr Pwr Pnl 1D-lc Primary Bkr 90 110 @ 270A Pressurizer Heaters 23, 49, Backup Fuse 90 N.A.

& 50 MCC SMXG-FSA Primary Bkr 90 110 @ 270A Pressurizer Heaters 28, 55, Backup Fuse 90 N.A.

& 56 Backup Press Htr Pwr Pnl 1D-2C Primary Bkr 90 110 @ 270A Pressurizer Heaters 33, 61, Backup Fuse 90 N.A.

& 62 Backup Press Htr Pwr Pnl 1D-2D Primary Bkr 90 110 @ 270A Pressurizer Heaters 38, 67, Backup Fuse 90 N.A.

& 68 Backup Press Htr Pwr Pnl 1D-2E Primary Bkr 90 110 @ 270A Pressurizer Heaters 43, 73, Backup Fuse 90 N.A.

& 74 4.

120 VAC-Panelboards 1KM-1 Primary Bkr 30 45 @ 90A RCP 1B Space Htr Backup Fuse 30 N.A.

1KM-2

_c Primary Bkr 30 45 @ 90A RCP 1C Space Htr 2

Backup Fuse 30 N.A.

n 1KN-1 Primary Bkr 30 45 @ 90A RCP 1B Space Heater Backup Fuse 30 N.A.

O O

TABLE 16.8-la (Page 27 of 28)

UNIT 1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 4.

120 VAC-Panelboards (continued) 1KN-2 Primary Bkr 30 45 0 90A RCP 1D Space Heater Backup Fuse 30 N.A.

1KN-27 Primary Bkr 20 36 0 60A Fuel Handling Control Backup Fuse 20 N.A.

Console 5.

250 VDC-Lighting 2

i RB Deadlight Pnlbd 1DLD #1 Primary Bkr 20 40 0 60A Ltg Pnl Nos. ILR1 & ILR2 1

i 20 N.A.

Backup Fuse RB Deadlight Pnlbd 1DLD #3 Primary Bkr 20 40 0 60A Ltg Pnl Nos. ILR4, ILR5, &

Backup Fuse 20 N.A.

1LR6 RB Deadlight Pnlbd 1DLD #4 Primary Bkr 20 40 @ 60A Ltg Pnl Nos. lLR7, ILR8, Backup Fuse 20 N.A.

& 1LR9 RB Deadlight Pnlbd 1DLD #6 Primary Bkr 20 40 0 60A Ltg Pnl Nos. 1LR12 Backup Fuse 20 N.A.

k RB Deadlight Pnlbd e

1DLD #7 Primary Bkr 20 40 @ 60A Ltg Pnl No. 1LR16 Backup Fuse 20 N.A.

O O

TABLE 16.8-la (Page 28 of 28)

UNIT 1 CONTAINMENT JENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 5.

250 VDC-Lighting (continued)

RB Deadlight Pnlbd 1DLD #9 Primary Bkr 20 40 @ 60A Ltg Pnl Nos. ILR18 & ILR17 Backup Fuse 20 N.A.

6.

600 VAC - LC Outage Power Fuse Box 1A Primary Fuse 150 N/A Upper Containment Safety Backup Fuse 150 N/A Switch 1A Primary Fuse 150 N/A Upper Containment Safety Backup Fuse 150 N/A Switch IB Primary Fuse 200 N/A Outage Power Distr. Pnl 1A Backup Fuse 200 N/A Primary Fuse 225 N/A Outage Power Distr. Pnl 1B Backup Fuse 225 N/A

$3 e

i 4-

... ~. - - - _ _. - -.,.

O O

TABLE 16.8-ib re de 1 of 30)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME I

DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 1.

6900 VAC-Swgr Primary Bkr-RCP2A 5.0 15.4 @ 25A Reactor Coolant Pump 2A Backup Brk-2TA-5 5.0 16.5 0 20A Primary Bkr-RCP2B 5.0 15.4 0 25A Reactor Coolant Pump 2B Backup Brk-2TB-5 5.0 16.5 0 20A Primary Bkr-RCP2C 5.0 15.4 @ 25A Reactor Coolant Pump 2C Backup Brk-2TC-5 5.0 16.5 @ 20A Primary Bkr-RCP2D 5.0 15.4 @ 25A Reactor Coolant Pump 2D Backup Brk-2TD-5 5.0 16.5 @ 20A 2.

600 VAC-MCC 2EMXA-2 1D Primary Bkr 20 45 @ 60A NC Pump 2C Thermal Barrier Backup Fuse 20 N.A.

Outlet Auto Isol Vlv 2KC345A 2EMXA-2 lE Primary Bkr 20 45 @ 60A NC Pump 2A Thermal Barrier Backup Fuse 20 N.A.

Outlet Auto Isol Vlv 2KC394A 2EMXA-2 2A l

Primary Bkr 20 45 @ 60A Cont Air Return Fan 2A Damper Backup Fuse 20 N.A.

2RAF-D-2 2EMXA-2 2B Primary Bkr 20 45 @ 60A N2 to Prt Cont Isol Inside Backup Fuse 20 N.A.

Vlv 2NC54A 2EMXA-2 2C Primary Bkr 20 45 @ 60A RCP Mtg Brg Oil Fill Isol o

Backup Fuse 20 N.A.

Vlv 2NC196A 2

e 2EMXA-2 3A Primary Bkr 30 45 @ 90A Accumulator 2A Disch Isol Backup Fuse 30 N.A.

Vlv 2NI54A

TABLE 16.8-lb

.. e 2 of 30) be UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

~

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 2EMXA-2 3B Primary Bkr 30 45 @ 90A Accumulator 2C Disch Isol Backup Fuse 30 N.A.

Vlv 2NI76A 2EMXA-2 3C Primary Bkr 20 45 @ 60A Test Hdr Inside Cont Isol Backup Fuse 20 N.A.

Vlv 2NI95A 2EMXA-2 4A ^

Primary Bkr Note 1 20 45 @ 60A UHI Check Vlv Test Line Isol Backup Bkr 20 N.A.

Vlv 2NI266A 2EMXA-2 4B Primary Bkr 20 45 @ 60A PALS Pnl Smple Ret to Backup Fuse 20 N/A Cont Isol Vlv 2WL1302A 2EMXA-2 4C Primary Bkr 20 45 @ 60A Accum 2A Vent to 2NC34 for Backup Fuse 20 N.A.

Blkout Vlv 2NI430A 2EMXA-2 5A Primary Bkr 20 45 @ 60A RN Containment Isolation Backup Fuse 20 N/A Valve 2RN253A 2EMXA-2 5B Primary Bkr 20 45 @ 60A RN Containment Isolation Backup Fuse 20 N/A Valve 2RN276A 2EMXA-5 1B Primary Bkr 20 45 @ 60A Pzr Steam Sample Line Inside Backup Fuse 20 N.A.

Cont Isol Vlv 2NM3A 5

2EMXA-5 2C 2

Primary Bkr 20 45 @ 60A Pzr Steam Sample Line Inside Backup Fuse 20 N.A.

Cont Isol Vlv 2NM6A 2EMXA-5 3B Primary Bkr 20 45 @ 60A NC Hotleg 2A Sample Line Cont Backup Fuse 20 N.A.

Isol Vlv 2NM22A

O

)

TABLE 16.8-lb (Page 3 of 30)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 2EMXA-5 2D Primary Bkr 20 45 @ 60A NC Hotleg 2D Sample Line Cont Backup Fuse 20 N.A.

Isol Vlv 2NM25A 2EMXA-2 7A Primary Bkr 20 45 @ 60A SG 2A Upper Shell Sample Cont Backup Fuse 20 N.A.

Isol Vlv 2NM187A 2EMXA-2 7B Primary Bkr 20 45 @ 60A SG 2A Blowdown Line Sample Backup Fuse 20 N.A.

Cont Isol Vlv 2NM190A 2E4XA-2 7C Primary Bkr 20 45 @ 60A SG 2C Upper Shell Sample Backup Fuse 20 N.A.

Cont Isol Vlv 2NM207A 2EMXA-2 8A Primary Bkr 20 45 @ 60A SG 2C Blowdown Line Sample Backup Fuse 20 N.A.

Cont Isol Vlv 2NM210A 2EMXA-4 1B Primary Bkr 20 45 @ 60A NC Pump Seal Return Cont Backup Fuse 20 N.A.

Viv 2NV94AC 2EMXA-3 1A Primary Bkr 20 45 @ 60A Lower Cont. Vent. Unit Discharge Backup Fuse 20 N.A.

Cont. Isol. Vlv. 2RV76A 2EMXA-3 3A Primary Bkr 20 45 @ 60A H2 Purge Exhaust Cont

~

R Backup Fuse 20

, N.A.

Vessel Isol Vlv 2VESA e

2EMXA-3 3B Primary Bkr 20 45-@ 60A Cont H2 Purge Blower Backup Fuse 20 N.A.

Inlet Valve 2VE8A

TABLE 16.8-lb (hge 4 of 30)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-Mcc (Continued) 2EMXA-3 3C Primary Bkr 20 45 @ 60A H2 Purge Inlet Cont Backup Fuse 20 N.A.

Vessel Isol Vlv 2VE10A 2EMXA-4 2C Primary B,kr 20 45 @ 60A Standby Makeup Pump Inlet Backup Fuse 20 N.A.

Isol valve 2NV842AC 2EMXA-3 4A Primary Bkr 20 45 @ 60A H2 Skimmer Fan 2A Suction Backup Fuse 20 N.A.

Isol Viv 2VX1A 2EMXA-3 SB Primary Bkr 20 45 @ 60A RCDT Pump Disch Cont Isol Backup Fuse 20 N.A.

Vlv 2WL2A 2EMXA-3 SC Primary Bkr 20 45 @ 60A RCDT Vent Cont Isol Backup Fuse 20 N.A.

Vlv 2WL39A 2EMXA-3 6A Primary Bkr 20 45 @ 60A RB Sump Pump Disch cont Backup Fuse 20 N.A.

Isol V1v 2WL64A 2EMXA-3 6B Primary Bkr 20 45 0 60A Cont Vent Unit Condensate Backup Fuse 20 N.A.

Cont Isol Vlv 2WL321A 2EMXB-4 1B Primary Bkr 20 45 @ 60A NC Pump 2B Thermal Barrier R

Backup Fuse 20 N.A.

Outlet Auto Isol Vlv 2KC364B e

2EMXB-4 1C Primary Bkr 20 45 @ 60A NC Pump 2D Thermal Barrier Backup Fuse 20 N.A.

Auto Isol Vlv 2KC413B

TABLE 16.8-1b e 5 of 30)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 2EMXB-4 2A Primary Bkr 20 45 @ 60A NC Pumps Return Hdr Pend Backup Fuse 20 N.A.

Inside Isol Viv 2KC424B 2EMXB-4 2B Primary Bkr 20 45 0 60A Reactor Bldg Drn Hdr Backup Fuse 20 N.A.

Inside Cont Isol Viv 2KC4298 2EMXB-4 2C Primary Bkr 30 45 @ 90A Accumulator 2B Disch Isol Vlv Backup Fuse 30 N.A.

2NI65B 2EMXB-4 3D Primary Bkr 30 45 0 90A Accumulator 2D Disch Isol Viv Backup Fuse 30 N.A.

2NI88B 2EMXB-4 3E Primary Bkr 20 45 @ 60A Hotleg Inj Check 2NI124, Backup Fuse 20 N.A.

2 nil 28 Test Isol Viv 2NI122B 2EMXB-4 4A Primary Bkr 20 45 0 60A Cont Air Return Fan 2B Backup Fuse 20 N.A.

Damper 2RAF-D-4 2EMXB-4 4C Primary Bkr 20 45 @ 60A NI Accum 2A Sample Line Backup Fuse 20 N.A.

Inside Cont Isol Vlv 2NM72B 2EMXA-4 3B Primary Bkr 20 45 @ 60A Standby Makeup cont Isol

~

C Backup Fuse 20 N.A.

Valve Outside 2NV849AC eE 2EMXB-4 5A Primary Bkr 20 45 @ 60A NI Accum 2B Sample Line Backup Fuse 20 N.A.

Inside Cont Isol Viv 2NM75B

O O(Page6of30)

O TABLE 16.8-lb UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 2EMXB-4 5B Primary Bkr 20 45 0 60A NI Accum 2C Sample Line Backup Fuse 29 N.A.

Inside Cont Isol Vlv 2NM78B 2EMXB-4 SC Primary Bkr 20 45 0 60A Accum 2B Vent to 2NC32 Backup Fuse 20 N.A.

for Blkout Vlv 2NI431B 2EMXB-4 6A Primary Bkr 20 45 @ 60A NI Accum 2D Sample Line Backup Fuse 20 N.A.

Inside Cont Isol Valve 2NM81B 2EMXB-4 6B Primary Bkr 20 45 @ 60A SG 2B Upper Shell Sample Backup Fuse 20 N.A.

Cont Isol Vlv 2NM1978 2EMXB-4 6C Primary Bkr 20 45 @ 60A SG 2B Blowdown Line Sample Backup Fuse 20 N.A.

Cont Isol Vlv 2NM200B 2EMXB-4 7B Primary Bkr 20 45 @ 60A SG 2D Uper Shell Sample Backup Fuse 20 N.A.

Cont Isol Vlv 2NM217B 2EMXB-4 7C Primary Bkr 20 45 @ 60A SG 2D Blowdown Line Sample Backup Fuse 20 N.A.

Cont Isol viv 2NM220B o

2EMXB-5 1A 2

Primary Bkr 20 45 @ 60A H2 Purge Exhaust Cont Vessel Backup Fuse 20 N.A.

Isol V1v 2VE6B 2EMXB-5 1B Primary Bkr 20 45 @ 60A Lower Cont. Vent. Unit Supply Backup Fuse 20 N.A.

Cont. Isol. Vlv. 2RV33B

TABLE 16.8-1'b trug)e 7 of 30)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES i

TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWEFED 2.

600 VAC-MCC (Continued) 2EMXB-5 1C Primary Bkr 20 45 @ 60A H2 Skimmer Fan 28 Suction Backup Fuse 20 N.A.

Isol Viv 2VX2B 1

2EMXC-1A Primary Bkr 200 250 @ 600A Lower Containment Cooling Backup Fuse 200 N.A.

Unit No. 2A 2EMXC-2A Primary Bkr 200 250 @ 600A Lower containment Cooling Backup Fuse 200 N.A.

Unit No. 2C 2EMXC-3C Primary Bkr 100 110 @ 300A Control Rod Drive Vent Fan Backup Fuse 100 N.A.

No. 2A 2EMXC-3D Primary Bkr 100 110 @ 300A Control Rod Drive Vent Fan Backup Fuse 100 N.A.

No. 2C 2EMXC-4C Primary Bkr 90 110 @ 270A Containment Air Return Fan Backup Fuse 90 N.A.

No. 2A 2EMXC-4D Primary Bkr 90 110 @ 270A Hydrogen Recombiner Backup Fuse 90 N.A.

No. 2A 2EMXC-6A Primary skr 40 45 @ 120A Containment Pipe Tunnel Backup Fuse 40 N.A.

Bocster Fan CPT-BF-2A 2

2EMXC-6B Primary Bkr 30 45 @ 90A Upper Containment Air Handling Backup Fuse 30 N.A.

Unit 2A 2EMXC-6C Primary Bkr 30 45 @ 90A Upper Containment Air Hdig Backup Fuse 30 N.A.

Unit 2C No. 2C

TABLE 16.8-1b (vcoe 8 of 30)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES i

TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-McC (Continued) 2EMXC-6D Primary Bkr 90 110 0 270A Hydrogen Skimmer Fan 2A Backup Fuse 90 N.A.

2EMXC-7C Primary Bkr 20 45 @ 6CA Upper Cont Return Air Fan Backup Fuse 20 N.A.

No. 2C 2EMXC-7D Primary Bkr 20 45 0 60A

?zr Pwr Oper Relief Backup Fuse 20 N.A.

Isol V1v 2NC33A 2EMXC-8C Primary Bkr 20 45 0 60A Incore Inetrumentation Rm Backup Fuse 20 N.A.

Air Hdig Unit 2A 2EMXC-7B Primary Bkr 20 45 @ 60A Upper Containment Return Backup Fuse 20 N.A.

Air Fan No. 2A 2EMXA-4 3C Primary Bkr 30 45 0 90A NC Loop 2C Discharge to ND Backup Fuse 30 N.A.

System Cont Isol Vlv 2ND 2AC 2EMXD-1A Primary Bkr 200 250 @ 600A Lower containment Cooling Unit Backup Fuse 200 N.A.

No. 2B 2EMXD-2A Primary Bkr 200 250 0 600A Lower Containment Cooling Unit Backup Fuse 200 N.A.

No. 2D

-o 2

2EMXD-3B Primary Bkr 40 45 @ 120A Containment Pipe Tunnel Booster Backup Fuse 40 N.A.

Fan CPT-BF-2B 2EMXD-3C Primary Bkr 100 110 @ 300A Control Rod Drive Vent Backup Fuse 100 N.A.

Fan No. 2B

O TABLE 16.8-lb (euge 9 of 30)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 2EMXD-3D Primary Bkr 100 110 0 3OOA Control Rod Drive Vent Backup Fuse 100 N.A.

Fan No. 2D 2EMXD-4C Primary Bkr 90 110 @ 270A Containment Air Return Backup Fuse 90 N.A.

Fan No. 2B Fan CPT-BF-2B 2EMXD-4D Primary Bkr 90 110 @ 270A Hydrogen Recombiner Backup Fuse 90 N.A.

No. 2B 2EMXD-6C Primary Bkr 30 45 @ 90A Upper Containment Air Backup Fuse 30 N A.

Edig Unit No. 2B 2EMXD-6D Primary Bkr 30 45 0 90A Upper Containment Air Hdig Backup Fuse 30 N.A.

Unit No. 2D 2EMXD-6E Primary Bkr 90 110 0 270A

. Hydrogen Skimmer Fan Backup Fuse 90 N.A.

No. 2B 2EMXD-7B Primary Bkr 20 45 @ 60A Upper Cont Return Air Fan Backup Fuse 20 N.A.

No. 2D 2EMXD-7C Primary Bkr 20 45 @ 60A Pzr Pwr Oper Safety Relief Backup Fuse 20 N.A.

Isol Vlv 2NC31B 2EMXD-7D Primary Bkr 20 45 0 60A Pzr Pwr Oper Relief Backup Fuse 20 N.A.

Isol Vlv 2NC35B

n TABLE 16.8-lb h 4 e 10 of 30)

\\

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 2EMXD-8B Primary Bkr 20 45 @ 60A Incore Instrumentation Backup Fuse 20 N.A.

Rm Air Hdig Unit 2B 2EMXD-5C Primary Bkr 20 45 @ 60A Upper Containment Return Backup Fuse 20 N.A.

Air Fan 2B 2EMXD-8D Primary Bkr 30 45 0 90A NC Loop 2C Disch to ND Backup Fuse 30 N.A.

System Cont Isol Viv 2NDlB 2MXM F2A Primary Bkr 40 45 @ 120A Lighting Pnlbd 2LR14 Backup Fuse 40 N.A.

2MXM F2B Primary Bkr 40 45 @ 120A Lighting Pnibd 2LR15 Backup Fuse 40 N.A.

2MXM F2C Primary Bkr 20 45 @ 60A Pzr Compt Fan B Backup Fuse 20 N/A 2MXM F2D Primary Bkr 20 45 @ 60A Ice Cond AHU 2Al Blower A Backup Fuse

'20 N.A.

2MXM F2E E

Primary Bkr 20 45 0 60A Ice Cond AHU 2A2 Blower A 2

Backup Fuse 20 N.A.

p 2MXM F3A Primary Bkr 40 45 @ 120A Lighting Pnlbd 2LR16 Backup Fuse 40 N.A.

TABLE 16.8-lb hmge 11 of 30)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES 4

TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 2MXM F3B Primary Bkr 40 45 @ 120A Lighting Pnlbd 2LR17 Backup Fuse 40 N.A.

2MXM F3C I

Primary Bkr 25 45 0 75A Reactor Bldg Equip Hdig 5 Ton Backup FQse 25 N.A.

Jib Crane 2MXM F3D Primary Bkr 20 45 @ 60A Ice Cond AHU 2A3 Blower A Backup Fuse 20 N.A.

2MXM F3E Primary Bkr 20 45 @ 60A Ice Cond AHU 2A4 Blower A Backup Fuse 20 N.A.

2MXM F4A Primary Bkr 20 45 @ 60A Ice Cond AHU 2A5 Blower A Backup Fuse 20 N.A.

2MXM F4B Primary Bkr 20 45 @ 60A Ice Cond AHU 2A6 Blower A Backup Fuse 20 N.A.

2MXM F4C Primary Bkr 20 45 0 60A Incore Inst Room Sump Pump Backup Fuse 20 N.A.

2MXM F4D 1

Primary Bkr 100 110 @ 3OOA Upper cont Welding Recpt i

Backup Fuse 100 N.A.

2MXM F5A Primary Bkr 20 45 @ 60A Ice Cond AHU 2A7 Blower A Backup Fuse 20 N.A.

~

fhJ v

TABLE 16.B-lb (h ge 12 of 30)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

i CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 2MXM F5B l

Primary Bkr 20 45 0 60A Ice Cond AHU 2A8 Blower A Backup Fuse 20 N.A.

2MXM F5D Primary Bkr 100 110 0 300A Welding Feeder Backup Fuse 100 N.A.

l 2MXM F1C Primary Bkr 50 110 @ 150A Ice Cond Floor Cooling Backup Fuse 50 N.A.

Defrost Heater 2A 2MXM F8C Primary Bkr 60 110 @ 180A Reactor Coolant Drain Tank Backup Fuse 60 N.A.

Pump 2A 2MXM F6A Primary Bkr 20 45 @ 60A Ice Cond AHU 2A9 Blower A Backup Fuse 20 N.A.

2MXM F6B Primary Bkr 20 45 @ 60A Ice Cond AHU 2A10 Blower A Backup Fuse 20 N.A.

2MXM F6C Primary Bkr 30 45 @ 90A Lower cont Aux Charcoal Backup Fuse 30 N.A.

Filter Fan 2A 2MXM F7A Primary Bkr 20 45 @ 60A Ice Cond AHU 2A11 Blower A Backup Fuse 20 N.A.

y k

i e

2MXM F7B Primary Bkr 20 45 @ 60A Ice Cond AHU 2A12 Blower A Backup Fuse 20 N.A.

O(sege13of30)

TABLE 16.8-1b UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 2MXM F7C Primary Bkr 20 45 @ 60A Ice Cond AHU 2A13 Blower A Backup Fuse 20 N.A.

2MXM RlA Primary Bkr 20 45 @ 60A Ice Cond AHU 2B1 Blower A 6

Backup FQse 20 N.A.

2MXM RlB Primary Bkr 20 45 @ 60A Ice Cond AHU 2B2 Blower A

. Backup Fuse 20 N.A.

2MXM RlC Primary Bkr 20 45 @ 60A Ice Cond AHU 2B3 Blower A Backup Fuse 20 N.A.

2MXM RlD Primary Bkr 30 45 0 90A RCP 2A Oil Lift Pump

. Backup Fuse 30 N.A.

2MXM R2A Primary Bkr 40 45 @ 120A Lighting Pnibd 2LR12 Backup Fuse 40 N.A.

2MXM R2D Primary Bkr 20 45 @ 60A Ice Cond AHU 2B4 Blower A Backup Fuse 20 N.A.

2MXM R2E Primary Bkr 30 45 @ 90A RCP 2B Oil Lift Pump e

Backup Fuse 30 N.A.

e 2MXM R3D Primary Bkr 20 45 @ 60A Ice Cond AHU 2B5 Blower A Backup Fuse 20 N.A.

P n(wge 14 of 30)

O TABLE 16.8-lb UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 2MXM R3E Primary Bkr 20 45 @ 60A Ice Cond AHU 2B6 Blower A Backup Fuse 20 N.A.

2MXM R3F Primary Bkr 30 45 @ 90A RCP 2C Oil Lift Pump Backup Ftise 30 N.A.

2MXM R4D Primary Bkr 20 45 @ 60A Ice Cond AHU 2B7 Blower A Backup Fuse 20 N.A.

2MXM R4E Primary Bkr 20 45 @ 60A Ice Cond AHU 2B8 Blower A Backup Fuse 20 N.A.

2MXM R4F Primary Bkr 30 45 @ 90A RCP 2D Oil Lift Pump Backup Fuse 30 N.A.

2MXM R5B Primary Bkr 20 45 @ 60A Ice Cond AHU 2B9 Blower A Backup Fuse 20 N.A.

2MXM RSC Primary Bkr 20 45 0 60A Ice Cond AHU 2B10 Blower A Backup Fuse 20 N.A.

2MXM R5D Primary Bkr 175 200 @ 525A Ice Cond Equip Pwr Pnl5d 2B Backup Fuse 175 N.A.

2 e

2MXM R6A Primary Bkr 20 45 @ 60A Rod Cntrl Cluster Backup Fuse 20 N.A.

Change Fixture Holst Drive

\\

TABLE 16.8-Ib Iw1ge 15 of 30) w/

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 2MXM R6B Primary Bkr 20 45 0 60A Ice Cond AHU 2B11 Blower A Backup Fuse 20 N.A.

2MXM R7A Primary Bkr 20 45 0 60A Stud Tensioner Holst Backup Fuse 20 N.A.

2MXM R6D Primary Bkr 150 110 @ 450A 175 Ton Polar Crane Backup Fuse 150 N.A.

2MXM R7B

+

Primary Bkr 20 45 0 60A Incore Inst Drive 2A Backup Fuse 20 N.A.

2MXM R7C Primary Bkr 30 45 @ 90A S/G Compt 2D Fan Backup Fuse 30 n/a 2MXM R7D Primary Bkr 20 45 @ 60A Ice Cond AHU 2B12 Backup Fuse 20 N.A.

2MXM R7E Primary Bkr 20 45 @ 60A Ice Cond AHU 2B13 Blower A Backup Fuse 20 N.A.

2MXM R8A

[

Primary Bkr 20 45 @ 60A Incore Inst Drive 2B Q

Backup Fuse 20 N.A.

p 2MXM R8B Primary Bkr 20 45 @ 60A Incore Inst Drive 2C Backup Fuse 20 N.A.

c n(rege16of30)

O TABLE 16.8-lb UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED L

2.

600.VAC-MCC (Continued) 2MXM R8C Primary Bkr 30 45 @ 90A S/G Compt 2A Fan Backup Fuse 30 N/A 2MXM R8D Primary Bkr 20 45 @ 60A Ice Cond AHU 2B14 Blower A Backup Fuse 20 N.A.

2MXM R8E Primary Bkr 20 45 @ 60A Ice Cond AHU 2B15 Blower A Backup Fuse 20 N.A.

2MXMA-lD Primary Bkr 20 45 @ 60A Ice Cond AHU 2A14 Blower A Backup Fuse 20 N.A.

2MXMA-1E Primary Bkr 20 45 0 60A Cont Floor & Equip Sump 2A Backup Fuse 20 N.A.

Pump 2Al 2MXM-R2C Primary Bkr 20 45 0 60A RCPM Maintenance Crane Recpt 2A, Backup Fuse 20 N.A.

2B, 2C, & 2D 2MXMA-2B Primary Bkr 40 45 0 120A Lighting Pnibd 2LR6 Backup Fuse 40 N.A.

2MXMA-2C Primary Bkr 40 45 @ 120A Lighting Pnlbd 2LR18

-o Backup Fuse 40 N.A.

e 2MXMA-2D Primary Bkr 20 45 @ 60A Ice Cond AHU 2A15 Blower A Backup Fuse 20 N.A.

m._._

O O}Page17of30)

O TABLE 16.8-lb UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 2MXMA-3A Primary Bkr 25 45 @ 75A Lighting Pnibd 2LR9 Backup Fuse 25 N.A.

2 MJtMA-3 B Primary Bkr 20 45 0 60A Ice Cond Equip Access Backup F'se 20 N.A.

Door 2A u

2MXMA-3C Primary Bkr 50 110 @ 150A Ice Cond Floor Cooling Backup Fuse 50 N.A.

Pump 2A 2MXMA-3D Primary Bkr 20 45 @ 60A Cont Floor & Equip Sump 2B Backup Fuse 20 N.A.

Pump 2B1 2MXN-F2A Primary Bkr 20 45 @ 60A Ice Cond AHU 2Al Blower B Backup Fuse 20 N.A.

2MXN-F2B Primary Bkr 20 45 0 60A Ice cond AHU 2A2 Blower B Backup Fuse 20 N.A.

2MXN-F2C Primary Bkr 20 45 @ 60A Ice Cond AHU 2A3 Blower B Backup Fuse 20 N.A.

2MXN-F2D Primary Bkr 20 45 @ 60A Ice Cond AHU 2A4 Blower B o

Backup Fuse 20 N.A.

e 2MXN-F3A Primary Bkr 20 45 @ 60A Ice Cond AHU 2A5 Blower B Backup Fuse 20 N.A.

IN TABLE 16.8-Ib (edge 18 of 30)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED i

2.

600 VAC-McC (Continued) 4 2MXN-F3B Primary Bkr 20 45 @ 60A Ice Cond AHU 2A6 Blower B Backup Fuse 20 N.A.

2MXN-F3C Primary Bkr 20 45 @ 60A Ice Cond AHU 2A7 Blower B Backup Fuse 20 N.A.

2MXN-F3D 4

Primary Bkr 20 45 @ 60A Ice Cond AHU 2A8 Blower B Backup Fuse 20 N.A.

2MXN-F4A Primary Bkr 25 45 @ 75A Lighting Pnlbd 2LR1 Backup Fuse 25 N.A.

2MXN-F4B Primary Bkr 30 45 @ 90A S/G Compt 2C Fan Backup Fuse 30 N/A 2MXN-F4C Primary Bkr 25 45 @ 75A Lighting Pnibd 2LR2 Backup Fuse 25 N.A.

2MXN-F4D Primary Bkr 20 45 @ 60A Ice cond AHU 2A9 Blower B Backup Fuse 20 N.A.

R e

2MXN-F4E Primary Bkr 20 45 @ 60A Ice Cond AHU 2A10 Blower B Backup Fuse 20 N.A.

2MXN-FSA Primary Bkr 20 45 @ 60A Incore Inst Drive No. 2D Backup Fuse 20 N.A.

l

{

/

\\'/

U TABLE 16.8-lb (h ge 19 of 30)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-McC (Continued) 2MXN-F5B Primary Bkr 20 45 @ 60A Incore Inst Drive No. 2E Backup Fuse 20 N.A.

2MXN-F5C Primary Bkr 20 45 @ 60A Incore Inst Drive No. 2F Backup Fuse 20 N.A.

2MXN-F5D Primary Bkr 20 45 0 60A Cont Floor & Equip Sump 2A Backup Fuse 20 N.A.

Pump 2A2 2MXN-FIC Primary Bkr 60 110 0 180A Reactor Coolant Drain Tank Backup Fuse 60 N.A.

Pump 2B 2MXN-F8B Primary Bkr 20 45 @ 60A Cont Floor & Equip Sump 2B Backup Fuse 20 N.A.

Pump 2B2 i

2MXN-F8C Primary Bkr 50 110 0 150A Ice Cond Floor Cooling Backup Fuse 50 N.A.

Defrost Htr 2B 2MXN-F6A Primary Bkr 25-45 0 75a Lighting Pnlbd 2LR4 Backup Fuse 25 N.A.

2MXN-F6B Primary Bkr 40 45 @ 120A Lighting Pnlbd 2LR5 E

Backup Fuse 40 N.A.

2 e

2MXN-F6C Primary skr 20 45 @ 60A Fuel Transfer Sys Reactor Side Fdr Backup Fuse 20 N.A.

u

^

O@e20of30 O

TABLE 16.8-lb p-J UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DE" ICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 2MXN-F6D Primary Bkr 20 45 0 60A Ice Cond AHU 2All Blower B Backup ;use 20 N.A.

2MXN-F7B Primary Bkr 30 45 0 90A Pzr Compt Fan A Backup Fuse 30 N/A 2MXN-F7D Primary Bkr 20 45 @ 60A Ice Cond AHU 2Al2 Blower B Backup Fuse 20 N.A.

2MXN-F7E Primary Bkr 20 45 0 60A Ice Cond AHU 2A13 Blower B l

Backup Fuse 20 N.A.

i 2MXN-RlD Primary Bkr 20 45 @ 60A Ice Cond AHU 2B1 Blower B Backup Fuse 20 N.A.

2MXN-RIE Primary Bkr 20 45 @ 60A Ice Cond AHU 2B2 Blower B Backup Fuse 20 N.A.

2MXN-RlF Primary Bkr 30 45 0 90A RCP 2A Oil Lift Pump No. 2 Backup Fuse 30 N.A.

2MXN-R2C o

Primary Bkr 30 45 0 90A Reactor Cavity Manipulator 3

Backup Fuse 30 N.A.

Crane v~

2MXN-R2F Primary Bkr 30 45 @ 90A RCP 2B Oil Lift Pump No. 2 Backup Fuse 30 N.A.

r

c<dge21of30)

TABLE 16.8-lb UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 2MXN-R3A Primary Bkr 20 45 @ 60A Ice Cond AHU 283 Blower B Backup Fuse 20 N.A.

2MXN-R3B Primary Bkr 20 45 @ 60A Ice Cond AHU 2B4 Blower B Backup Fuse 20 N.A.

2MXN-R3C Primary Bkr 20 45 0 60A Ice Cond AHU 2B5 Blower B Backup Fuse 20 N.A.

2 MIN-R3D Primary Bkr 30 45 0 90A RCP 2C Oil Lift Pump No. 2 Backup Fuse 30 N.A.

2MXN-R4A Primary Bkr 50 110 @ 150A Ice Cond Bridge Crane Backup Fuse 50 N.A.

2 MIN-R4B Primary Bkr 30 45 @ 90A RB Equip Hatch Holst i

Backup Fuse 30 N.A.

2MXN-R4C Primary Bkr 25 45 @ 75A S/G Compt 2B Fan i

Backup Fuse 25 N/A 2MXN-R4D Primary Bkr 20 45 @ 60A Ice Cond AHU 2B6 Blower B Backup Fuse 20 N.A.

2MXN-R4E Primary Bkr 30 45 0 90A RCP 2D Oil Lift Pump No. 2 Backup Fuse 30 N.A.

\\

TABLE 16.8-lb

(#.ge 22 of 30)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED I

2.

600 VAC-MCC (Continued) 2MXN-RSD i

Primary Bkr 175 200 0 525A Ice Cond Equip Pwr Pnlbd 2A Backup Fuse 175 N.A.

2MXN-R6A Primary Bkr 20 45 0 60A Ice Cond AHU 2B7 Blower B Backup Fuse 20 N.A.

2MXN-R6B Primary Bkr 20 45 @ 60A Ice cond AHU 2B8 Blower B Backup Fuse 20 N.A.

2MXN-R6C Primary Bkr 20 45 0 60A Ice Cond AHU 2B9 Blower B Backup Fuse 20 N.A.

2MXN-R6D Primary Bkr 100 110 @ 300A Welding Fdr Backup Fuse 100 N.A.

C 2MXN-R7A Primary Bkr 20 45 0 60A Ice Cond AHU 2B10 Blower B Backup Fuse 20 N.A.

(

2MXN-R7B Primary Bkr 20 45 @ 60A Ice Cond AHU 2B11 Blower B Backup Fuse 20 N.A.

2MXN-R7C Primary Bkr 20 45 @ 60A Ice Cond AHU 2B12 Blower B Backup Fuse 20 N.A.

k 2MXN-R7D Primary Bkr 50 110 0 150A Ice Cond Floor Cooling Pump 2B i

Backup Fuse 50 N.A.

s h

TABLE 16.8-lb (rege 23 of 30)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME J

DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 2MXN-R8D Primary Bkr 20 45 0 60A Ice Cond AHU 2B13 Blower B Backup Fuse 20 N.A.

s 2MXN-R8E s

Primary Bkr 20 45 @ 60A Ice Cond AHU 2B14 Blower B Backup Fuse 20 N.A.

2MXN-R8F Primary Bkr 20 45 0 60A Ice Cond AHU 2B15 Blower B Backup Fuse 20 N.A.

SMXG-R3G Primary Bkr 20 45 0 60A Standby Makeup Pump to cont Backup Fuse 20 N.A.

Sump Isol Valve 2NV1012C 2MXNA-lE I

Primary Bkr 30 45 0 90A Lower Cont Aux Charcoal Backup Fuse 30 N.A.

Filter Fan 2B 2MXNA-2B Primary Bkr 25 45 @ 75A Lighting Pnlbd 2LR7 Backup Fuse 25 N.A.

2MXNA-2C Primary Bkr 25 45 @ 75A Lighting Pnibd 2LR8 Backup Fuse 25 N.A.

I 2MXNA-2D Primary Bkr 20 45 @ 60A Ice Cond AHU 2A14 Blower B i

Backup Fuse 20 N.A.

o Q

2MXNA-2E i

Primary Bkr 20 45 0 60A Ice Cond AHU 2A15 Blower B e

Backup Fuse 20 N.A.

[

O y

TABLE 16.8-lb a-uge 24 of 30)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES l

TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED I

2.

600 VAC-MCC (Continued) i 2MXNA-3A Primary Skr 20 45 @ 60A 2 Ton CRDM Hdig Jib Crane Backup Fuse 20 N.A.

2MXNA-3B Primary Bkr 30 45 0 90A cont Air Compressor Backup Fuse 30 N/A SMXG-R4F Primary Bkr 20 45 @ 60A standby Makeup Pump to NC Backup Fuse 20 N.A.

Pump Seals Isol Valve 2NV1013C 2MXNA-3C Primary Bkr 20 45 @ 60A NC Pump Motor Drain Tank Backup Fuse 20 N.A.

Pump No. 1 2MXNA-3D Primary Bkr 20 45 @ 60A Ice Cond Equip Access Door 2B Backup Fuse 20 N.A.

SMXD-3E Primary Bkr 15 45 @ 45A Unit 2 Personnel Lock Backup Fuse 15 N.A.

SMXV-2F Primary Bkr 15 45 0 45A Unit 2 Emergency Pernonnel Lock Backup Fuse 15 N.A.

3.

600 VAC-Press Htr Pwr Pnis o

Q Backup Press Htr Pwr e

Pnl 2A-1A Primary Bkr 90 110 0 270A Pressurizer Heaters 1, 2, & 22 Backup Fuse 90 N.A.

l

TABLE 16.8-lb b tle 25 of 30)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 3.

600 VAC-Press Htr Pwr Pnis (Continued)

Backup Press Htr Pwr Pnl 2A-1B Primary Bkr 90 110 @ 270A Pressurizer Heaters 5, 6, & 27 Backup Fuse 90 N.A.

Backup Press Htr Pwr Pnl 2A-1C Primary Bkr 90 110 @ 270 Pressurizer Heaters 9, 10, Backup Fuse 90 N.A.

& 32 Backup Press Htr Pwr Pnl 2A-2C Primary Bkr 90 110 @ 270A Pressurizer Heaters 11, 12, Backup Fuse 90 N.A.

& 35 Backup Press Htr Pwr Pnl 2A-2D Primary Bkr 90 110 @ 270A Pressurizer Heaters 13, 14, Backup Fuse 90 N.A.

& 37 Backup Press Htr Pwr Pnl 2A-2E Primary Bkr 90 110 @ 270A Pressurizer Heaters 17, 18, Backup Fuse 90 N.A.

& 42 Backup Press Htr Pwr Pnl 2B-1A Primary Bkr 90 110 @ 270A Pressurizer Heaters 21, 47, Backup Fuse 90 N.A.

@ 48 Backup Press Htr Pwr Pnl 2B-1B g

Primary Bkr 90 110 @ 270 Pressurizer Heaters 26, 53, e

Backup Fuse 90 N.A.

& 54 Backup Press Htr Pwr Pnl 2B-1C Primary Bkr 90 110 @ 270A Pressurizer Heaters 31, 59, & 60 Backup Fuse 90 N.A.

TABLE 16.8-Ib w 4e 26 of 30)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 3.

600 VAC-Press Htr Pwr Pnis (Continued) 1 Backup Press Htr Pwr Pnl 2B-2C i

Primary Bkr 90 110 0 270A Pressurizer Heaters 36, 65, & 66 Backup Fuse 90 N.A.

l l

Backup Press Htr Pwr Pnl 2B-2D Primary B'kr 90 110 @ 270A Pressurizer Heaters 41, 71, & 72 Backup Fuse 90 N.A.

Backup Press Htr Pwr Pnl 2B-2E Primary Bkr 90 110 @ 270A Pressurizer Heaters 46, 77, & 78 Backup Fuse 90 N.A.

Backup Press Htr Pwr Pnl 2C-1A Primary Bkr 90 110 @ 270A Pressurizer Heaters 7, 8,

& 30 Backup Fuse 90 N.A.

Backup Press Htr Pwr Pnl 2C-1B Primary Bkr 90 110 @ 270A Pressurizer Heaters 19, 20, & 45 Backup Fuse 90 N.A.

Backup Press Htr Pwr Pnl 2C-1C Primary Bkr 90 110 @ 270A Pressurizer Heaters 24, 51, & 52 Backup Fuse 90 N.A.

Backup Press Htr Pwr

~o Pnl 2C-1D D

Primary Bkr 90 110 @ 270A Pressurizer Heaters 29, 57, & 58 Backup Fuse 90 N.A.

Backup Press Htr Pwr i

Pnl 2C-2C Primary Bkr 90 110 0 270A Pressurizer Heaters 34, 63, & 64 i

Backup Fuse 90 N.A.

)

TABLE 16.8-lb (Page 27 of 30)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

Y CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 3.

600 VAC-Press Htr Pwr Pnle (Continued) i Backup Press Htr Pwr Pnl 2C-2D Primary Bkr 90 110 @ 270A Pressurizer Heaters 39, 69, & 70 Backup Fuse 90 N.A.

Backup Press Htr Pwr Pnl 2C-2E Primary Bkr 90 110 @ 270A Pressurizer Heaters 44, 75, & 76 Backup Fuse 90 N.A.

Backup Press Htr Pwr Pnl 2D-1A Primary Bkr 90 110 @ 270A Pressurizer Heaters 3, 4,

& 25 Backup F.ase 90 N.A.

Backup Press Htr Pwr Pnl 2D-1B Primary Bkr 90 110 @ 270A Pressurizer Heaters 15, 16, & 40 Backup Fuse 90 N.A.

Backup Press Htr Pwr Pnl 2D-IC Primary Bkr 90 110 @ 270A Pressurizer Heaters 23, 49, & 50 Backup Fuse 90 N.A.

SMXG-RSA Primary Bkr 90 110 @ 270A Pressurizer Heaters 28, 55, & 56 Backup Puse 90 N.A.

j Backup Press Htr Pwr

-o Pnl 2D-2C 3

Primary Bkr 90 110 0 270A Pressurizer Heaters 33, 61, & 62 Backup Fuse 90 N.A.

Backup Press Htr Pwr Pnl 2D-2D Primary Bkr 90 110 0 270A Pressurizer Heaters 38, 67, & 68 Backup Fuse 90 N.A.

I

..- m.

m m.

m

~.

n

C O(hge 28 of 30)

O TABLE 16.8-1b UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES

{

TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME JEVICE ""' DER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 3.

600 VAC-Press Htr Pwr Pnis (Continued)

Backup Press Htr Pwr Pnl 2D-2E Primary Bkr 90 110 @ 270A Pressurizer Heaters 43, 73,

& 74 Backup Fuse 90 N.A.

4.

120 VAC-Panelboards 2KM-19 Primary Bkr 20 45 @ 90A RCP 2A Space Htr Backup Fuse 20 N.A.

2KM-20 Primary Bkr 20 45 @ 90A RCP 2C Space Htr Backup Fuse 20 N.A.

2KN-19 Primary Bkr 20 45 @ 90A RCP 2B Space Htr Backup Fuse 20 N.A.

2KN-20 Primary Bkr 20 45 @ 90A RCP 2D Space Htr Backup Fuse 20 N.A.

2KN-27 Primary Bkr 20 36 @ 60A Fuel Handling Control Console Backup Fuse 20 N.A.

2KN-25 Primary Bkr 30 36 @ 60A Unit 2 Incore Inst Backup Fuse 20 N.A.

Dehum #2 O

f TABLE 16.8-lb age 29 of 30)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 5.

250 VDC-Lighting RB Deadlight Pnibd 2DLD #1 Primary Bkr 20 40 @ 60A Ltg Pnl Nos. 2LR1 & 2LR2 Backup Fuse 20 N.A.

RB Deadlight Pnlbd 2DLD #3 l

Primary Bkr 20 40 @ 60A Ltg Pnl Nos. CLR4, 2LRS, &

Backup Fuse 20 N.A.

2LR6 RB Deadlight Pnlbd 2DLD #4 Primary Bkr 20 40 @ 6CA Ltg Pnl Nos. 2LR7, 2LR8, & 2LR9 Backup Fuse 20 N.A.

RB Deadlight Pnibd 2DLD #6 Primary Bkr 20 40 @ 60A Ltg Pnl Nos. 2LR12 Backup Fuse 20 N.A.

RB Deadlight Pnlbd 2DLD #7 Primary Skr 20 40 0 60A Ltg Pnl No. 2LR16 Backup Fuse 20 N.A.

RB Deadlight Pnlbd 2DLD #9 Primary Bkr 20 40 @ 60A Ltg Pnl Nos. 2LR18 & 2LR17 Backup Fuse 20 N.A.

f 6.

600 VAC - LC 5

Outage Power Fuse Box 2A 2

Primary Fuse 150 N.A.

Upper Containment safety Backup Fuse 150 N.A.

Switch 2A Primary Fuse 150 N.A.

Upper Containment Safety Backup Fuse 150 N.A.

Switch 2B l

l 1

i m -

4

F O

(h s

t 1

TABLE 16.8-lb b..ge 30 of 30)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME I

DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 6.

600 VAC -LC (continued)

Primary Fuse 200 N.A.

Lower Containment Outage Backup Fuse 200 N.A.

Power Distr. Pnl 2A Primary Fuse 225 N.A.

Lower Containment Outage Backup Fuse 225 N.A.

Power Distr. Pnl 2B 1

l L

C3e

\\

TABLE 16.11-1 (Page 1 of 3)

PADICACTIVE LIQUID WASTE SAMPLING AND ANALYSIS PROGRAM LIQUID RELEASE SAMPLING MINIMUM TYPE OF LOWER LIMIT TYPE FREQUENCY ANALYSIS ACTIVITY OF DETECTION FREQUENCY ANALYSIS (LLD)

(ucI/ML) 1.

Batch Waste P

P Release Tanks Each Batch Each Batch Principal 5 x 10 ~ '

Gamma Emitters I-131 1x10" (Waste

?

M Dissolved Monitor Tanks One Batch /M and 1x10

and Recycle Entrained Monitor Tank)

Gases (Gamma emitters)

P M

H-3 1x10-'

Each Batch Composite'"

Gross Alpha 1 x 10-P Q

Sr-89, Sr-90 5 x 10

Each Batch Composite

2.

Continuous W

Principal Releases Continuous'"

Composite '"

Gamma 5x10" Emitters *

(Containment I-131 1x10'

)

Ventilation Unit M

M Dissolved Condensate Grab Sample and 1x10

Drain Tank Entrained Discharge and Gases (Gamma Conventional l

Emitters)

Waste Water Continuous

M H-3 1 x 10

Treatment Composite '"

System Gross Alpha 1 x 10

i Outlet)

Q Sr-89,Sr-90 5x10-*

Continuous'"

Composite

("

9/94 16.11-4