ML20073K469

From kanterella
Jump to navigation Jump to search
Forwards Revs to McGuire Selected Licensee Commitment (SLC) Manual,Involving Changes to Tables 16.8-1a,16.8-1b & 16.11-1
ML20073K469
Person / Time
Site: McGuire, Mcguire  
Issue date: 10/03/1994
From: Mcmeekin T
DUKE POWER CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
NUDOCS 9410110249
Download: ML20073K469 (66)


Text

__.__

ll l

Dukeibuer Company T.C Matfrm s McGuve Nuclear Generation Department Vice hesident

~

12700Hagers FerryRoad(MG011F)

. (704)8754800 -

Huntersmile.NC28078MS (TC>l)8754809 Fax i

October 3,1994 j

U.S. Nuclear Regulatory Commission Document Control Desk Washington, D. C..

20555 4

Subject:

McGuim Nuclear Station,

Dockets Nos. 50-369.-370 i

Selected Licensee Commitments Manual (SLC) l Tables 16.8-la,16.8 lb and 16.11-1 l

Gentlemen:

Attached are seven copics of the latest revisions to the McGuire Selected Licensee Commitment (SLC) l Manual invohing changes to Tables 16.8-la,16.8-lb and 16.11-1. The SLC Manual is Chapter 16.0.of the McGuire FSAR. This manual contains commitments and other station issues that warrant control, but are not appropriate for Technical Specifications. The SLC Manual is updated as needed during the year.

l For questions regarding these revisions, please contact Dwin Caldwcil at (704) 875 - 4328.

Very truly yours.

%At T. C. McMeckin i

cc:

(with attachments)

Mr. S. D. Ebneter Mr. Bob Martin Regional Administrator, Region 11 U. S. Nuclear Regulatory Commission U S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation 101 Marietta St. NW Suite 2900 One White Flint North, Mail Stop 9H3 Atlanta, Georgia 30323 Washington, D. C.

20555 Mr. Victor Nerses Mr. George Mawell U. S. Nuclear Regulatory Commission Senior Resident inspector Office of Nuclear Reactor Regulation McGuire Nuclear Station One White Flint North, Mail Stop 9H3 Washington, D. C 20555

<*n+,

9410110249 941003 h

DR A

ADOCK 05000369 p

(i((

PDR a

'o d'

3 h

1 TABLE 16.B-la (Page 1 of 28)

UNIT 1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES 1

TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED

[

1.

6900 VAC-Swgr Primary Bkr-RCPlA 5.0 15.4 @ 25A Reactor Coolant Pump 1A Backup Brk-lTA-5 5.0 16.5 @ 20A Primary Bkr-RCPIB 5.0 15.4 @ 25A Reactor Coolant Pump 1B Backup Brk-lTB-5 5.0 16.5 @ 20A,

Primary Bkr-RCPIC 5.0 15.4 @ 25A Reactor Coolant Pump IC Backup Brk-lTC-5 5.0 16.5 @ 20A Primary Bkr-RCP1D 5.0 15.4 @ 25A Reactor Coolant Pump ID Backup Brk-lTD-5 5.0 16.5 @ 20A 2.

600 VAC-MCC 1EMXA-2 1D Primary Bkr 20 45 @ 60A NC Pump IC Thermal Barrier Backup Fuse 20 N.A.

Outlet Auto Isol Viv IKC345A j

lEMXA-2 lE Primary Bkr 20 45 @ 60A

-NC Pump 1A. Thermal Barrier Backup Fuse 20 N.A.

Outlet Auto Isol Viv IKC394A lEMXA-2 2A Primary Bkr 20 45 @ 60A' Cont Air Return Fan lA Damper 7

Backup Fuse 20 N.A.

1RAF-D-2 l

r l

lEMXA-2 2B Primary Bkr 20 45 @ 60A N2 to Prt Cont Isol Inside

[

Backup Fuse 20 N.A.

Viv 1NC54A s

W O

1EMXA-2 2C I

D Primary Bkr 20 45 @ 60A RCP Mtg Brg Oil Fill Isol j

Backup Fuse 20 N.A.

Viv'lNC196A

?

-1EMXA-2 3A Primary Bkr 30

_45 @ 90A Accumulator lA Disch Isol Backup Fuse 30 N.A.

.Vlv INI54A l

l

1 l

TABLE 16.8-la (Page 2 of 28)

UNIT 1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 1EMXA-2 3B Primary Bkr 30 45 0 90A Accumulator IC Disch Isol Backup Fuse 30 N.A.

Vlv INI76A 1EMXA-2 3C Primary Bkr 20 45 0 60A Test Hdr Inside Cont Isol Backup Fuse 20 N.A.

V1v INI95A 1EMXA-2 4A Primary Bkr Note 1 20 45 0 60A UHI check Vlv Test Line Isol Backup Fuse 20 N.A.

Viv 1NI266A 1EMXA-2 4B Primary Bkr Note 1 20 45 0 60A UHI Check V1v Test Line Isol Backup Fuse 20 N.A.

Viv INI267A 1EMXA-2 4C Primary Bkr 20 45 0 60A Accum 1A Vent to INC34 for Backup Fuse 20 N.A.

Bikout Viv 1NI430A 1EMXA-2 SA Primary Bkr 20 45 0 60A RN Containment Isolation Backup Fuse 20 N/A V1v 1RN253A 1EMXA-2 SB Primary Bkr 20 45 0 60A RN Containment Isolation Backup Fuse 20 N/A Viv 1RN276A 1EMXA-3 2C Primary Bkr 20 45 0 60A RV Containment Isolation Backup Fuse 20 N/A Viv 1RV76A w

R 1EMXA-5 IB p

Primary Bkr 20 45 0 60A Pzr Steam Sample Line Inside Backup Fuse 20 N.A.

Cont Isol Vlv INM3A 1EMXA-5 2C Primary Bkr 20 45 0 60A Pzr Steam Sample Line Inside Backup Fuse 20 N.A.

Cont Isol Vlv INM6A

TABLE 16.8-la (Page 3 of 28)

UNIT 1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) lEMXA-5 3B Primary Bkr 20 45 0 60A NC Hotleg 1A Sample Line Cont Backup Fuse 20 N.A.

Isol Viv 1NM22A 1EMXA-5 2D Primary Bkr 20 45 @ 60A NC Hotleg 1D Sample Line Cont Backup Fuse 20 N.A.

Isol Viv INM25A 1EMXA-2 7A Primary Bkr 20 45 @ 60A SG 1A Upper Shell Sample Cont Backup Fuse 20 N.A.

Isol Vlv 1NM187A 1EMXA-2 7B Primary Bkr 20 45 @ 60A SG 1A Blowdown Line Sample Backup Fuse 20 N.A.

Cont Isol Viv 1NM190A IEMXA-2 7C Primary Bkr 20 45 0 60A SG IC Upper Shell Sample Backup Fuse 20 N.A.

Cont Isol Viv 1NM207A lEMXA-2 8A Primary Bkr 20 45 @ 60A SG IC Blowdown Line Sample Backup Fuse 20 N.A.

Cont Isol Vlv INM210A 1EMXA-4 IB Primary Bkr 20 45 @ 60A NC Pump Seal Return Cont Backup Fuse 20 N.A.

Vlv INw'94AC IEMXA-3 3A Primary Bkr 20 45 0 60A H2 Purge Exhaust Cont vessel j

Backup Fuse 20 N.A.

Isol Vlv IVESA

~o 1EMXA-3 4A D

Primary Bkr 20 45 @ 60A H2 Skimmer Fan IA Suction Backup Fuse 20 N.A.

Isol Viv IVX1A 1EMXA-3 SB Primary Bkr 20 45 @ 60A RCDT Pump Disch Cont Isol Backup Fuse 20 N.A.

Vlv IWL2A

TABLE 16.8-la (Page 4 of 28) f

^

UNIT 1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-HCC (Continued) 1EMXA-3 SC Primary Bkr 20 45 0 60A RCDT Vent Cont Isol Viv Backup Fuse 20 N.A.

IWL39A 1EMXA-3 6A Primary Bkr 20 45 0 60A RB Sump Pump Disch Cont Isol Backup Fuse 20 N.A.

Viv 1WL64A 1EMXA-3 6B Primary Bkr 20 45 0 60A Cont Vent Unit Condensate Backup Fuse 20 N.A.

Cont Isol Viv IWL321A 1EMXB-4 IB Primary Bkr 20 45-9 60A NC Pump 1B Thermal Barrier Backup Fuse 20 N.A.

Outlet Auto Isol Vlv 1KC364B 1EMXB-4 1C Primary Bkr 20 45 @ 60A NC Pump ID Thermal Barrier Backup Fuse 20 N.A.

Auto Isol Vlv 1KC413B IBMXB-4 2A Primary Bkr 20 45 0 60A NC Pumps Return Hdr Pend Inside Backup Fuse 20 N.A.

Isol V1v 1KC424B 1EMXB-4 2B Primary Bkr 20 45 9 60A Reactor Bldg Drn Hdr'Inside Cont Backup Fuse 20 N.A.

Isol Vlv 1KC429B I

1EMXB-4 2C 45 e 90A Accumulator IB Disch Isol Viv Primary Bkr 30

_ N.A.

INI65B Backup Fuse 30 R

1EMXB-4 3D y

Primary Bkr 30 45 0 90A Accumulator ID Disch Isol Vlv i

Backup Fuse 30 N.A.

1NI888 1EMXB-4 3E Primary Bkr 20 45 0 60A Hotleg Inj Check 1NI124, INI128 Backup Fuse 20 N.A.

Test Isol Viv 1NI1228

I l

l TABLE 16.8-la (Page 5 of 28) l UNIT 1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) l 1EMXB-4 4A Primary Bkr 20 45 0 60A Cont Air Return Fan IB Damper Backup Fuse 20 N.A.

1RAF-D-4 1EMXB-4 4C Primary Bkr 20 45 0 60A NI Accum 1A Sample Line Inside Backup Fuse 20 N.A.

Cont Isol Viv INM72B f

IEMXB-4 5A Primary Bkr 20 45 9 60A NI Accum 1B Sample Line Backup Fuse 20 N.A.

Inside Cont Isol Viv INM75B 1EMXB-4 5B Primary Bkr 20 45 0 60A NI Accum IC Sample Line Backup Fuse 20 N.A.

Inside Cont Isol Vlv INM78B 1EMXB-4 SC Primary Bkr 20 45 0 60A Accum IB Vent to INC32 for Backup Fuse 20 N.A.

Blkout Viv INI431B 1EMXB-4 6A Primary Bkr 20 45 0 60A NI Accum ID Sample Line Backup Fuse 20 N.A.

Inside Cont Isol Valve INM81B 1EMXB-4 6B Primary Bkr 20 45 0 SOA SG 1B Upper Shell Sample Backup Fuse 20 N.A.

Cont Isol viv 1NM197B IEMXB-4 6C Primary Bkr 20 45 6 60A SG 1B Blowdown Line Sample Backup Fuse 20 N.A.

Cont Isol Viv INM2008 5

1EMXB-4 7B D

Primary Bkr 20 45 e 60A SG ID Uper Shell Sample Backup Fuse 20 N.A.

Cont Isol Vlv 1NM217B 1EMXB-4 7C Primary Bkr 20 45 0 60A SG 1D Blowdown Line Sample Backup Fuse 20 N.A.

Cont Isol Viv 1NM220B

(

~

TABLE 16.8-la (Page 6 of 28)

UNIT 1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 1EMXB-5 IB Primary Bkr 20 45 0 60A RV Containment Isolation Backup Fuse 20 N/A Viv 1Rv33B IEMIB-5 1C Primary Bkr 20 45 0 60A H2 Skimmer Fan 1B Suction Backup Fuse 20 N.A.

Isol Viv IVX2B IEMXC-1A Primary Bkr 200 250 0 600A Lower Containment cooling Backup Fuse 200 N.A.

Unit No. lA 1EMXC-2A Primary Bkr 2G0 250 0 600A Lower containment Cooling Backup Fuse 200 N.A.

Unit No. 1C 1EMXC-3C Primary Bkr 100 110 0 300A Control Rod Drive Vent Fan Backup Fuse 100 N.A.

No. lA 1EMXC-3D Primary Bkr 100 110 0 300A Control Rod Drive Vent Fan Backup Fuse 100 N.A.

No. IC' 1EMXC-4C Primary Bkr 90 110 0 270A Containment Air Return Fan Backup Fuse 90 N.A.

No. 1A 1EMXC-4D Primary Bkr 90 110 0 270A Hydrogen Recombiner Backup Fuse 90 N.A.

No. IA R

1EMXC-6A y

Primary Bkr 40 45 0 120A Containment Pipe Tunnel Backup Fuse 40 N.A.

Booster Fan CPT-BF-1A 1EMXC-6B Primary Bkr 30 45 0 90A Upper Containment Air Backup Fuse 30 N.A.

Handling Unit 1A

(

TABLE 16.8-la (Page 7 of 28)

UNIT 1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 1EMXC-6C Primary Bkr 30 45 0 90A Upper Containment Air Hdig Backup Fuse 30 N.A.

Unit IC IEMXC-6D Primary Bkr 90 110 0 270A Hydrogen Skimmer Fan Backup Fuse 90 N.A.

No. 1A 1EMXC-7C Primary Bkr 30 45 0 90A Upper Cont Return Air Fan Backup Fuse 30 N.A.

No. 1C 1EMXC-7D Primary Bkr 20 45 0 60A Pzr Pwr Oper Relief l

Backup Fuse 20 N.A.

Isol Viv INC33A 1EMXC-8C Primary Bkr 20 45 0 60A Incore Instrumentation Rm i

Backup Fuse 20 N.A.

Air Hdig Unit 1A 1EMXC-BD Primary Bkr 20 45 0 60A Upper Containment Return Backup Fuse 20 N.A.

Air Fan.No. lA L

1EMXA-4 3C Primary Bkr 30 45 0 90A NC Loop IC Discharge to ND Backup Fuse 30 N.A.

System Cont Isol Viv IND2A,C 1EMXD-1A Primary Bkr 200 250 0 600A Lower Containment Cooling Backup Fuse 200 N.A.

Unit No. IB o

IEMXD-2A 3

Primary Bkr 200 250 0 600A Lower Containment Cooling Backup Fune 200 N.A.

Unit No. 1D 1EMXD-3B Primary Bkr 40 45 0 120A Containment Pipe Tunnel Backup Fuse 40 N.A.

Booster Fan CPT-BF-1B

-~. -

TABLE 16.8-la (Page 8 of 28)

UNIT 1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 1EMXD-3C Primary Bkr 100 110 0 300A-Control Rod Drive Vent Fan Backup Fuse 100 N.A.

No. 1B IEMXD-3D Primary Bkr 100 110 0 300A Control Rod Drive Vent Fan Backup Fuse 100 N.A.

No. 1D 1EMXD-4C Primary Bkr 90 110 0 270A Containment Air Return Fan Backup Fuse 90 N.A.

No. 1B Fan CPT-BF-1A 1EMXD-4D Primary Bkr 90 110 0 270A Hydrogen Recombiner No. IB Backup Fuse 90 N.A.

1EMXD-6C Primary Bkr 30 45 @ 90A Upper Containment Air Hdig Unit Backup Fuse 30 N.A.

No. IB 1EMXD-6D Primary Bkr 30 45 0 90A Upper Containment Air Hdig Unit Backup Fuse 30 N.A.

No. 1D 1EMXD-6E Primary Bkr 90 110 @ 270A Hydrogen Skimmer Fan No. 1B Backup Fuse 90 N.A.

1EMXD-7B Primary Bkr 30 45 0 90A Upper Cont Return Air Fan Backup Fuee 30 N.A.

No. 1D 0

1EMXD-7C y

Primary Bkr 20 45 0 60A Pzr No. 1 Pwr Oper Safety Backup Fuse 20 N.A.

Relief Isol Vlv 1NC31B 1EMXD-7D Primary Bkr 20 45 @ 60A Pzr No. 1 Pwr Oper Safety Backup Fuse 20 N.A.

Relief Isol Viv 1NC35B

.m.__

._._.___...._.,_.__m..

i TABLE 16.8-la (Page 9 of 28)

UNIT 1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 1EMXD-8B Primary Bkr 20 45 0 60A Incore Instrumentation Rm Backup Fuse 20 N.A.

Air Hdig Unit IB IEMXD-8C Primary Bkr 20 45 9 60A Upper Containment Return Air Backup Fuse 20 N. T..

Fan IB IEMXD-8D Primary Bkr 30 45 0 9CA NC Loop IC Disch to ND System Backup Fuse 30 N.A.

Cont Isol Vlv IND1B IMXM FIA Primary Bkr 40 45 0 120A Lighting Pnibd ILR14 Backup Fuse 40 N.A.

IMXM FIB Primary Bkr 40 45 @ 120A Lighting Pnlbd ILR15 Backup Fuse 40 N.A.

1MXM FIC Primary Bkr 30 45 0 90A S/G Boost Fan 1C Backup Fuse 30 N/A IMXM FID Primary Bkr 20 45 0 60A Ice Cond AHU 1A1 Blower A

[

Backup Fuse 20 N.A.

1MXM FIE Primary Bkr 20 45 @ 60A Ice cond AHU 1A2 Blower A Backup Fuse 20 N.A.

3 E

IMXM F2A 3

Primary Bkr 40 45 0 120A Lighting Pnibd ILR16 Backup Fuse 40 N.A.

IMXM'F2B Primary Bkr 40 45 0 120A Lighting Pnibd ILR17 Backup Fuse 40 N.A.

t TABLE 16.8-la (Page 10 of 28)

~

c UNIT 1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES t

{

TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-Mcc (Continued)

IMXM F2C Primary Bkr 25 45 @ 75A Reactor Bldg Equip Hdig 5 Ton Backup Fuse 25 N.A.

Jib Crane-IMXM F2D Primary Bkr 20 45 @ 60A Ice Cond AHU 1A3 Blower A Backup Fuse 20

'N.A.

IMXM F2E Primary Bkr 20 45 0 60A Ice Cond AHU 1A4 Blower A Backup Fuse 20 N.A.

IMXM F3A Primary Bkr 20 45 0 60A Ice Cond AHU 1A5 Blower A Backup Fuse 20 N.' A.

IMXM F3B Primary Bkr 20 45'O 60A Ice Cond AHU 1A6 Blower A Backup Fuse 20 N.A.

1MIM F3C Primary Bkr 20 45 0 60A Incore Inst Room Sump Pump Backup Fuse 20 N.A.

IMXM F3D Primary Bkr 100 110 0 300A Upper cont Welding Recpt Backup Fuse 100

.N.A.

IMXM F4A Primary Bkr 20 45 0 60A Ice Cond AHU 1A7 Blower A Backup Fuse 20 N.A.

o 1MXM F4B D

Primary Bkr 20 45 0 60A Ice Cond AHU 1A8 Blower A' Backup Fuse 20 N.A.

1MXM F4D Primary Bkr 100 110 0 300A Welding Feeder Backup Fuse 100 N.A.

f TABLE 16.8-la (Page 11 of 28)

UNIT 1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DIVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued)

IMXM F5C Primary Bkr 50 110 0 150A Ice Cond Floor Cooling Backup Fuse 50 N.A.

Defrost Heater 1A IMXM F6C Primary Bkr 60 110 0 180A Reactor Coolant Drain Tank Backup Fuse 60 N.A.

Pump 1A 1MXM F77.

4 Primary Bkr 20 45 0 60A Ice Cond AHU 1A9 Blower A L

Backup Fuse 20-N.A.

IMXM F7B Primary Bkr 20 45 @ 60A Ice Cond AHU 1A10 Blower A Backup Fuse 20 N.A.

IMXM F7C Primary Bkr' 30 45 0 90A Lower Cont Aux Charcoal Filter Backup Fuse 3G N.A.

Fan 1A l

IMXM F8A Primary Bkr 20 45 0 60A Ice Cond AHU 1A11 Blower A Backup Fuse 20 N.A.

1MXM F8B Primary Bkr 20 45 0 60A Ice Cond AHU 1A12 Blower A Backup Fuse 20 N.A.

1MIM F8C Primary Bkr 20 45 e 60A Ice Cond AHU 1A13 Blower A 4

Backup Fuse 20 N.A.

wR IMXM R1A-Primary Bkr 20 45 0 60A Ice Cond AHU 181 Blower A e

Backup Fuse 20 N.A.

1MXM R1B Primary Bkr 20 45 0 60A Ice Cond AHU 1B2 Blower A j.

' Backup Fuse 20 N.A.

__._____m.-_________--____-____,vu r

-uam.-

we-.--i wr

+-.n-----=~-.*----.-.

  • =

e.

+ ++-r-o

=

=

1

--e i- <

2w -

--- -t

TABLE 16.8-la (Page 12 of 28)

UNIT 1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

t CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 1MXM R1C.

Primary Bkr 20 45 0 60A Ice Cond AHU 183 Blower A Backup Fuse 20 N.A.

IMXM RID Primary Bkr 30 45 6 90A RCP 1A Oil Lift Pump Backup Fuse 30 N.A.

1MXM R2A Primary Bkr 40 45 0 120A Lighting Pnibd ILR12 Backup Fuse 40 N.A.

IMXM R2D Primary Bkr 20 45 0 60A Ice Cond AHU IB4 Blower A Backup Fuse 20 N.A.

IMXM R2E Primary Bkr 30 45 0 90A RCP 1B Oil Lift Pump Backup Fuse 30 N.A.

1MXM R3D Primary Bkr 20 45 0 60A Ice Cond AHU 1B5 Blower A Backup Fuse 20 N.A.

IMXM R3E Primary Bkr 20 45 9 60A Ice Cond AHU 1B6 Blower A Backup Fuse 20 N.A.

IMXM R3F Primary Bkr 30 45 0 90A RCP IC Oil Lift Pump Backup Fuse 30 N.A.

~

R IMXM R4D y

Primary Bkr 20 45 0 60A Ice Cond AHU 187 Blower A Backup Fuse 20 N.A.

1MXM R4E Primary Bkr 20 45 0 60A Ice Cond AHU 188 Blower A Backup Fuse 20 N.A.

t TABLE 16.8.?a (Page 13 of 28)

UNIT 1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 1MXM R4F Primary Bkr 30 45 0 90A RCP-1D Oil Lift Pump Backup Fuse 30 N.A.

1MXM R5B Primary Bkr 20 45 0 60A Ice Cond AHU 1B9 Blower A Backup Fuse 20 N.A.

1MXM R5C Primary Bkr 20 45 0 60A Ice Cond AHU 1810 Blower A Backup Fuse 20 N.A.

IMXM RSD Primary Bkr 175 200 0 525A Ice Cond Equip Pwr Pnibd IB Backup Fuse 175 N.A.

1MIM R6A Primary Bkr 20 45 0 60A Rod Cntrl Cluster Change Backup Fuse 20 N.A.

Fixture Holst Drive 1MXM R6B Primary Bkr 20 45 0 60A Ice Cond AHU IB11 Blower A Backup Fuse 20 N.A.

1MXM R7A Primary Bkr 20 45 0 60A Stud Tensioner Hoist Backup Fuse 20 N.A.

1MXM R6E Primary Bkr 150 110 0 450A 175 Ton Polar Crane Backup Fuse 150 N.A.

R IMIM R7B y

Primary Bkr 20 45 0 60A Incore Inst Drive 1A Backup Fuse 20 N.A.

1MXM R7D Primary Bkr 20 45 0 60A Ice Cond AHU 1B12 Backup Fuse 20 N.A.

m

.__z...

_ _ - _ _ ~...

..._ ~. _ _. _ -.. _

___.-.._._.m.~_...

-...- -.m _ m.

~__

._..__m._..._-u..

TABLE 16.8-la (Page 14 of 28) t UNIT 1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)'

SYSTEM POWERED t

2.

600 VAC-MCC (Continued)

IMXM R7E i

Primary Bkr 20 45 0.60A' Ice Cond AHU 1B13 Blower A Backup Fuse 20 N.A.

1MXM R8A' Primary Bkr 20 45 0 60A Incore Inst Drive IB Backup Fuse 20 N.A.

IMXM R8B Primary Bkr 20 45 e 60A Incore Inst Drive IC Backup Fuse 20 N.A.

IMXM R8D Primary Bkr 20 45 9 60A Ice Cond AHU 1B14 Blower A Backup Fuse 20 N.A.

IMXM R8E Primary Bkr 20 45 9 60A Ice Cond AHU 1815 Blower A Backup Fuse-20 N.A.

1MXMA-1B Primary Bkr 30 45 0 90A Vent Press. Boost Fan IB Backup Fuse 30 N/A 1MXMA-1D Primary Bkr 20 45 0 60A Ice Cond AHU 1A14 Blower A Backup Fuse 20 N.A.

[

IMXMA-1E Primary Bkr 20 45 0 60A Cont Floor & Equip Sump 1A Backup Fuse 20 N.A.

Pump 1Al'

~

R IMXMA-2A y

Primary Bkr 25 45 @775A RCPM Maintenance Crane Recpt Backup Fuse 25 N.A.

lA, 1B, 1C, & ID IMXMA-2B-Primary Bkr_

25 45 6 75A Lighting Pnibd ILR6 Backup Fuse 25 N.A.

.-m..m.

m m.a..

m m

m w-

TABLE 16.8-la (Page 15 of 28) r UNIT 1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

  • 0FCONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued)

IMXMA-2C Primary Bkr 40 45 0 120A Lighting Pnibd ILR18 Backup Fuse 40 N.A.

1MXMA-2D Primary Bkr 20 45 0 60A Ice Cond AHU 1A15 Blower A Backup Fuse 20 N.A.

I 1MXMA-3A Primary Bkr 25 45 6 75A Lighting Pnibd ILR9 Backup Fuse 25 N.A.

1MXHA-3B Primary Bkr 20 45 0 60A Ice Cond Equip Access Backup Fuse 20 N.A.

Door 1A 1MXMA-3C Primary Bkr 50 110 0 150A Ice Cond Floor Cooling Backup Fuse 50 N.A.

Pump 1A 1MXMA-3D Prindry Bkr 20 45 0 60A Cont Floor & Equip Sump 1B Backup muse 20 N.A.

Pump 1B1 1MXN-F1A Primary Bkr 20 45 0 60A Ice Cond AHU 1A1 Blower B Backup Fuse 20 N.A.

1MXN-F1B Primary Bkr 20 45 0 60A Ice Cond AHU 1A2 Blower B Backup Fuse 20 N.A.

k l

1MXN-FIC y

Primary Bkr 20 45 0 60A Ice Cond AHU 1A3 Plower B Backup Fuse 20 N.A.

1MXN-F1D Primary Bkr 20 45 0 60A Ice Cond AHU 1A4 Blower B i

Backup Fuse 20 N.A.

1 l

l

TABLE 16.8-la (Page 16 of 28)

UNIT 1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME-DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued)

IMXN-F2A Primary Bkr 20 45 0 60A Ice Cond AHU 1A5 Blower B.

Backup Fuse 20 N.A.

IMXN-F2B Primary Bkr 20 45 6 60A Ice Cond AHU 1A6 Blower B Backup Fuse 20 N.A.

1MXN-F2C Primary Bkr 20 45 @ 60A Ice Cond AHU 1A7 Blower B Backup Fuse 20 N.A.

IMXN-F2D Primary Bkr 20 45 6 60A Ice Cond AHU 1A8 Blower B Backup Fuse 20 N.A.

1MXN-F3A Primary Bkr 25 45 6 75A Lighting Pnibd ILR1 Backup Fuse 25 N.A.

1MXN-F3B Primary Bkr 30 45 0 90A.

S/G Booster Fan 1B Backup Fuse 30 N/A 1MXN-F3C Primary Bkr 25 45 0-75A Lighting Pnibd ILR2 Backup Fuse 25 N.A.

IMXN-F3D Primary Bkr 20 45 6 bvA Ice cond AHU-1A9 Blower B Backup Fuse 20 N.A.

~R IMXN-F3E Primary Bkr 20 45 0 60A Ice Cond AHU 1A10 Blower B e

Backup Fuse 20 N.A.

IMXN-F4A Primary Bkr 20 45 0 60A Incore Inst Drive No. ID Backup Fuse 20 N.A.

I

f TABLE 16.8-la (Page 17 of 28)

UNIT 1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued)

IMXN-F4B Primary Bkr 20 45 0 60A Incore Inst Drive No. 1E Backup Fuse 20 N.A.

1MXN-F4C Primary Bkr 20 45 0 60A Incore Inst Drive No. 1F Backup Fuse 20 N.A.

IMXN-F4D Primary Bkr 20 45 @ 60A Cont Floor & Equip Sump 1A Backup Fuse 20 N.A.

Pump 1A2 1MXN-F5C Primary Bkr 60 110 0 180A Reactor Coolant Drain Tank Backup Fuse 60 N.A.

Pump 1B IMIN-F6B Primary Bkr 20 45 @ 60A Cont Floor & Equip Sump 1B Backup Fuse 20 N.A.

Pump 1B2 1MXN-F6C Primary Bkr 50 110 @ 150A Ice Cond Floor Cooling Backup Fuse 50 N.A.

Defrost Htr 1B 1MXN-F7A Primary Bkr 25 45 @ 75A Lig..ing Pnlbd ILR4 Backup Fuse 25 N.A.

IMXN-F7B Primary Bkr 25 45 @ 75A Lighting Pnlbd ILR5 Backup Fuse 25 N.A.

R IMIN-F7C y

Primary Bkr 20 45 @ 60A Fuel Transfer Sys Reactor Backup Fuse 20 N.A.

Side Fdr IMXN-F7D Primary Bkr 20 45 @ 60A Ice Cond AHU 1A11 Blower B Backup Fuse 20 N.A.

TABLE 16.8-la (Page 18 of 28)

UNIT 1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME t

DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued)

IMXN-F8B Primary Bkr 30 45 0 90A S/G Booster Fan 1A Backup Fuse 30 N/A 1MXN-F8D Primary Bkr 20 45 0 60A Ice cond AHU 1A12 Blower B Backup Fuse 20 N.A.

IMXN-F8E Primary Bkr 20 45 0 60A Ice Cond AHU 1A13 Blower B Backup Fuse 20 N.A.

IMXN-RID Primary Bkr 20 45 0 60A Ice Cond AHU 1B1 Blower B Backup Fuse 20 N.A.

-1MXN-RIE Primary Bkr 20 45 0 60A Ice Cond AHU IB2 Blower B Backup Fuse 20 N.A.

IMXN-R1F Primary Bkr 30 45 9 90A RCP 1A Oil Lift Pump No. 2 Backup Fuse 30 N.A.

IMXN-R2C Primary Bkr 30 45 9 90A Reactor Cavity Manipulator Backup Fuse 30 N.A.

Crane 1MXN-R2F Primary Bkr 30 43 0 90A RCP 1B Oil Lift Pump No. 2 Backup Fuse 30 N.A.

R IMXN-R3A Primary Bkr 20 45 e 60A Ice Cond AHU 1B3 Blower B e

Backup Fuse 20 N.A.

IMXN-R3B Primary Bkr 20 45 0 60A Ice Cond AHU 1B4 Blower B 1

Backup Fuse 20 N.A.

TABLE 16.8-la (Page 19 of 28)

UNIT 1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued)

P IMIN-R3C Primary Bkr 20 45 0 60A Ice Cond AHU 1B5 Blower B Backup Fuse 20 N.A.

IMXN-R3D Primary Bkr 30 45 0 90A RCP IC Oil Lift Pump No. 2 Backup Fuse 30 N.A.

IMXN-R4A Prbnary Bkr 50 110 0 150A Ice Cond Bridge Crane Backup Fuse 50 N.A.

IMXN-R4B Primary Bkr 30 45 0 90A RB Equip Hatch Hoist No. 1 Backup Fuse 30 N.A.

IMXN-R4C Primary Bkr 30 45 0 90A S/G Booster Fan 1A Backup Fuse 30 N/A 1MXN-R4D Primary Bkr 20 45 0 60A Ice Cond AHU IB6 Blower B Backup Fuse 20 N.A.

IMXN-R4E Primary Bkr 30 45 0 90A RCP ID Oil Lift Pump No. 2 Backup Fuse 30 N.A.

IMXN-RSD Primary Bkr 175 200 0 525A Ice Cond Equip Pwr Pnlbd 1A Backup Fuse 175 N.A.

wR IMXN-R6A y

Primary Bkr 20' 45 0 60A Ice cond AHU IB7 Blower B Backup Fuse 20 N.A.

1MXN-R6B Primary Bkr 20 45 0 60A Ice Cond AHU 188 Blower B Backup Fuse 20 N.A.

TABLE 16.8-la (Page 20 of 28)

UNIT 1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued)

IMXN-R6C Primary Bkr 20 45 0 60A Ice Cond AIIU 189 Blower B Backup Fuse 20 N.A.

IMXN-R6D Primary Bkr 100 110 0 300A Welding Fdr Backup Fuse 100 N.A.

IMXN-R7A Primary Bkr 20 45 0 60A Ice Cond AHU 1B10 Blower B Backup Fuse 20 N.A.

1MXN-R7B Primary Bkr 20 45 @ 60A Ice Cond AHU 1811 Blower B Backup Fuse 20 N.A.

IMXN-R7C Primary Bkr 20 45 @ 60A Ice Cond AHU IB12 Blower B Backup Fuse 20 N.A.

IMXN-R7D Primary Bkr 50 110 0 150A Ice Cond Floor Cooling Backup Fuse 50 N.A.

Pump 1B 1MXN-R8D Primary Bkr 20 45 0 60A Ice Cond AHU-1813 Blower B l

Backup Fuse 20 N.A.

I IMXN-R8E Primary Bkr 20 45 0 60A Ice Cond AHU 1814 Blower B Backup Fuse 20 N.A.

~R IMXN-R8F y

Primary Bkr 20 45 @ 60A Ice Cond AHU 1D15 Blower B Backup Fuse 20 N.A.

1MXNA-1E Primary Bkr 30 45 @ 90A Lower Cont Aux Charcoal Backup Fuse 30 N.A.

Filter Fan IB

TABLE 16.8-la (Page 21 of 28)

UNIT 1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 1MINA-2A Primary Bkr 30 45 0 90A Vent Press Boost Fan IA Backup Fuse 30 N/A 1MXNA-2B Primary Bkr 25 45 0 75A Lighting Pnibd ILR7 Backup Fuse 25 N.A.

1MXNA-2C Primary Bkr 25 45 0 75A Lighting Pnlbd ILR8 Backup Fuse 25 N.A.

1MXNA-2D Primary Bkr 20 45 0 60A Ice Cond AHU 1A14 Blower B Backup Fuse 20 N.A.

1MXNA-2E Primary Bkr 20 45 0 60A Ice Cond AHU 1A15 Blower B Backup Fuse 20 N.A.

1MXNA-3A Primary Bkr 20 45-0 60A 2 Ton CRDM Hdig Jib Crane Backup Fuse 20 N.A.

1MXNA-3B Primary Bkr 30 45 0 90A cont Air Compressor Backup Fuse 30 N/A SMKG-F3G Primary Bkr 20 45 0 60A Standby Makeup Pump to Backup Fuse 20 N.A.

Cont Sump Isol Viv INV1012C k

SMXG-F4G y

Primary Bkr 20 45 0 60A Standby Makeup Pump to NC Backup Fuse 20 N.A.

Pump Seals Isol Viv 1NV1013C 1MXNA-3C Primary Bkr 20 45 0 60A NC Pump Motor Drain Tank Backup Fuse 20 N.A.

Pump No. 1

4 TABLE 16.8-la (Page 22 of 28)

UNIT 1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR RESPONSE-l CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-Mcc (Continued)

IMINA-3D Primary Bkr 20 45 0 60A Ice Cond Equip Access Door 1B Backup Fuse 20 N.A.

SMIC-7D Primary Bkr 15 45 0 45A Unit 1 Personnel Lock Backup Fuse 15 N.A.

SMXA-F4A Primary Bkr 15 45 0 45A Unit 1 Emergency Personnel Lock Backup Fuse 15 N.A.

3.

600 VAC-Press Htr Pwr Pnis Backup Press Htr Pwr Pnl 1A-1A Primary Bkr 90 110 0 270A Pressurizer Heaters 1, 2, & 22 Backup Fuse 90 N.A.

Backup Press Htr Pwr Pnl IA-1B Primary Bkr 90 110 0 270A Pressurizer Heaters 5, 6,

& 27 Backup Fuse 90 N.A.

Backup Press Htr Pwr Pnl 1A-1C Primary Bkr 90 110 0 270A Pressurizer Heaters 9, 10, Backup Fuse 90 N.A.

& 32 Backup Press Htr Pwr R

Pnl 1A-2C y

Primary Bkr 90 110 0 270A Pressurizer Heaters 11, 12, Backup Fuse 90 N.A.

&.35 r

Backup Press Htr Pwr Pnl lA-2D Primary Bkr 90 110 0 270A Pressurizer Heaters 13, 14-Backup Fuse 90 N.A.

& 37

___m TABLE 16.8-la (Page 23 of 28)

UNIT 1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 3.

600 VAC-Press Htr Pwr Pnis (Continued)

Backup Press Htr Pwr Pnl 1A-2E Primary Bkr 20 110 @ 270A Pressurizer Heaters 17, 18, Backup Fuse 90 N.A.

& 42 Backup Press Hte Pwr Pnl 1B 1A Primary Bkr 90 110 0 270A Pressurizer Heaters 21, 47, Backup Fuse 90 N.A.

& 48 Backup Press Htr Pwr Pnl IB-1B Primary Bkr 90 110 0 270A Pressurizer Heaters 26, 53, Backup Fuse 90 N.A.

& 54 Backup Press Htr Pwr Pnl IB-1C Primary Bkr 90 110 @ 270A Pressurizer Heaters 31, 59, Backup Fuse 90 N.A.

& 60 Backup Press Htr Pwr Pnl IB-2C Primary Bkr 90 110 @ 270A Pressurizer Heaters 36, 65, Backup Fuse 90 N.A.

& 66 Backup Press Htr Pwr Pnl IB-2D Primary Bkr 90 110 0 270A Pressurizer Heaters 41, 71, Backup Fuse 90 N.A.

& 72 k

Backup Press Htr Pwr e

Pnl 1B-2E Primary Bkr 90 110 0 270A Pressurizer Heaters 46, 77, Backup Fuse 90 N.A.

& 78 Backup Press Hte Pwr Pnl 1C-1A Primary Bkr 90 110 @ 270A Pressurizer Heaters 7, 8,

~

TABLE 16.8-la (Page 24 of 28)

UNIT 1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED Backup Fuse 90 N.A.

& 30 l

4 3

l l

l i

TABLE 16.8-la (Page 25 of 28)

UNIT 1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME i

DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 3.

600 VAC-Press Htr Pwr Pnis (Continued)

Backup Press Utr '/wr Pnl IC-1B Primary Bkr 90 110 0 270A Pressurizer Heaters 19, 20, Backup Fuse 90 N.A.

& 45 i

Backup Press Hte Pwr Pnl IC-1C Primary Bkr 90 110 @ 270A Pressurizer Heaters 24, 51, Backup Fuse 90 N.A.

& 52 Backup Press Htr Pwr Pnl IC-1D Primary Bkr 90 110 0 270A Pressurizer Heaters 29, 57, Backup Fuse 90 N.A.

& 58 Backup Press Htr Pwr Pnl 1C-2C Primary Bkr 90 110 0 270A Pressurizer Heaters 34, 63, Backup Fuse 90 N.A.

& 64 i

Backup Press Htr Pwr Pnl 1C-2D Primary Bkr 90 110 @ 270A Pressurizer Heaters 39, 69, i

Backup Fuse 90 N.A.

& 70 l

Backup Presas Htr Pwr Pnl IC-23 Primary Bkr 90 110 0 270A Pressurizer Heaters 44, 75, 6

Backup Fuse 90 N.A.

& 76 i

Backup Press Htr Pwr go Pnl 1D-1A 3

Primary Bkr 90 110 0 270A Pressurizer Heaters 3, 4, Backup Fuse 90 N.A.

& 25 Backup Press Htr Pwr Pnl ID-1B Primary Bkr 90 110 0 270A Pressurizer Heaters 15, 16, Backup Fuse 90 N.A.

& 40

O I

TABLE 16.8-la (Page 26 of 28)

~

UNIT 1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 3.

600 VAC-Press Htr Pwr Pnis (Continued)

Backup Press Htr Pwr Pnl ID-1C Primary Bkr 90 110 0 270A Pressurizer Heaters 23, 49, Backup Fuse 90 N.A.

& 50 MCC SMXG-FSA Primary Bkr 90 110 0 270A Pressurizer Heaters 28, 55, Backup Fuse 90 N.A.

& 56 Backup Press Htr Pwr Pnl 1D-2C Primary Bkr 90 110 0 270A Pressurizer Heaters 33, 61, Backup Fuse 90 N.A.

& 62 Backup Press Htr Pwr Pnl 1D-2D Primary Bkr 90 110 @ 270A Pressurizer Heaters 38, 67, Backup Fuse 90 N.A.

& 68 Backup Press Htr Pwr Pnl 1D-2E Primary Bkr 90 110 0 270A Pressurizer Heaters 43, 73, Backup Fuse 90 N.A.

& 74 4.

120 VAC-Pane 1 boards i

1KM-1 Primary Bkr 30 45 0'90A RCP 1B Space Htr Backup Fuse 30 N.A.

1KM-2 o

Primary Bkr 30 45 0 90A RCP IC Space Htr 2

Backup Fuse 30 N.A.

c-1KN-1 Primary Bkr 30 45 0 90A-RCP IB Space Heater Backup Fuse 30 N.A.

o TABLE 16.8-la (Page 27 of 28)

UNIT 1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 4.

120 VAC-Panelboards (continued) 1KN-2 30 45 e 90A RCP ID Space Heater Primary Bkr 30 N.A.

Backup Fuse 1KN-27 Primary Bkr 20 36 @ 60A Fuel Handling Control 20 N.A.

Console Backup Fuse 5.

250 VDC-Lighting RB Deadlight Pnlbd IDLD #1 20 40 0 60A Ltg Pnl Nos. ILR1 & ILR2 Primary Bkr 20 N.A.

Backup Fuse RB Deadlight Pnibd 1DLD #3 20 40 0 60A Ltg Pnl Nos. ILR4, ILR5, &

Primary Bkr 20 N.A.

ILR6 Backup Fuse RB Deadlight Pnlbd IDLD #4 20 40 @ 60A Ltg Pnl Nos. ILR7, ILR8, Primary Bkr 20 N.A.

& ILR9 Backup Fuse RB Deadlight Pnibd IDLD #6 Primary Bkr 20 40 0 60A Ltg Pnl Nos. ILR12 20 N.A.

Backup Fuse k

RB Deadlight Pnlbd e

IDLD #7 P imary Bkr 20 40 0 60A Ltg Pnl No. ILR16 20 N.A.

?uckup Fuse I

~

.~

TABLE 16.8-la (Pega 28 of 28)

UNIT 1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 5.

250 VDC-Lighting (continued)

RB Deadlight Pnlbd IDLD #9 Primary Bkr 20 40 0 60A Ltg Pnl Nos. ILR18 & ILR17 20 N.A.

Backup Fuse i

6.

600 VAC - LC i

Outage Power Fuse Box 1A Primary Fuse 150 N/A Upper Containment Safety Backup Fuse 150 N/A Switch IA Primary Fuse 150 N/A Upper Containment Safety 150 N/A Switch IB Backup Fuse Primary Fuse 200 N/A Outage Power Distr. Pnl 1A Backup Fuse 200 N/A Primary Fuse 225 N/A Outage Power Distr. Pnl 18 225 N/A Backup Fuse 3

e

..-..~ _.....

o r TABLE 16.8-lb (Page 1 of 30)

UNIT 2 CONTAINMENT PENETRATZON CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION

-(AMPERES)

(SECONDS)

SYSTEM POWERED j

1.

6900 VAC-Swgr Primary Bkr-RCP2A 5.0 15.4 0 25A Reactor Coolant Pump 2A Backup Brk-2TA-5 5.0 16.5 @ 20A l

Primary Bkr-RCP2B 5.0 15.4 @ 25A Reactor Coolant Pump 2B Backup Brk-2TB-5 5.0 16.5 0 20A

. Primary Bkr-RCP2C 5.0 15.4 @ 25A Reactor Coolant Pump 2C Backup Brk-2TC-5 5.0 16.5 @ 20A Primary Bkr-RCP2D 5.0 15.4 0 25A Reactor Coolant Pump 2D Backup Brk-2TD-5 5.0 16.5 0 20A 2.

600 VAC-MCC 2EMXA-2 1D Primary Bkr 20 45 0 60A NC Pump 2C Thermal Barrier Backup Fuse 20 N.A.

Outlet Auto Isol Viv 2KC345A 2EMXA-2 1E Primary Bkr 20 45 0 60A NC Pump 2A Thermal Barrier Backup Fuse 20 N.A.

Outlet Auto Isol Viv 2KC394A 2EMXA-2 2A Primary Bkr 20 45 0 60A Cont Air Return Fan 2A Damper Backup Fuse 20 N.A.

2RAF-D-2 2EMXA-2 2B Primary Bkr 20 45 @ 60A N2 to Prt Cont Isol Inside Backup Fuse 20 N.A.

Viv 2NC54A 2EMXA-2 2C Primary Bkr 20 45 0 60A RCP Mtg Brg Oil Fill Isol E

Backup Fuse 20 N.A.

Vlv 2NC196A De 2EMXA-2 3A Primary Bkr 30 45 @ 90A Accumulator 2A Disch Isol Backup Fuse 30 N.A.

Viv 2NI54A

1 TABLE 16.8-lb (Pegs 2 of 30) l UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 2EMXA-2 3B Primary Bkr 30 45 @ 90A Accumulator 2C Disch Isol Backup Fuse 30 N.A.

-Vlv 2NI76A 2EMXA-2 3C Primary Bkr 20 45 @ 60A-Test Hdr Inside Cont Isol Backup Fuse 20 N.A.

Viv 2NI95A 2EMXA-2 4A ~

Primary Bkr Note 1 20 45 @ 60A UHI Check Vlv-Test Line Isol Backup Bkr 20 N.A.

Viv 2NI266A 2EMXA-2 4B Primary Bkr 20 45 0 60A' PALS Pnl Smple Ret to Backup Fuse 20 N/A Cont Isol Viv 2WL1302A 2EMXA-2 4C Primary Bkr 20 45 @ 60A Accum 2A Vent to 2NC34 for Backup Fuse 20 N.A.

Bikout Viv 2NI430A 2EMXA-2 5A Primary Bkr 20 45 @ 60A RN Containment Isolation Backup Fuse 20 N/A Valve 2RN253A I

2EMXA-2 SB Primary Bkr 20 45 0 60A RN Containment Isolation Backup Fuse 20 N/A Valve 2RN276A 2EMXA-5 IB Primary Bkr 20 45 0 60A Pzr Steam Sample Line Inside Backup Fuse 20 N.A.

Cont Isol Viv 2NM3A o

2EMXA-5 2C 2

Primary Bkr 20 45 @ 60A

.Pzr Steam Sample Line Inside Backup Fuse 20 N.A.

Cont Isol Vlv 2NM6A 2EMXA-5 3B Primary Bkr 20 45 @ 60A NC Hotleg 2A Sample Line Cont Backup Fuse 20 N.A.

Isol Viv 2NM22A i

TABLE 16.8-lb (Paqs 3 of 30) i UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES t

TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED i

i i

2.

600 VAC-MCC (Continued) 2EMXA-5 2D Primary Bkr 20 45 0 60A NC Hotleg 2D Sample Line Cont i

Backup Fuse 20 N.A.

Isol Viv 2NM25A 2EMXA-2 7A Primary Bkr 20 45 0 60A SG 2A Upper Shell Sample cont l

Backup Fuse 20 N.A.

Isol Viv 2NM187A t

2EMXA-2 7B Primary Bkr 20 45 0 60A SG 2A Blowdown Line Sample Backup Fuse 20 N.A.

Cont Isol Vlv 2NM190A

{

2EMXA-2 7C Primary Bkr 20 45 0 60A SG.2C Upper Shell Sample Backup Fuse 20 N.A.

Cont Isol Vlv 2NM207A 2EMXA-2 8A Primary Bkr 20 45 e 60A.

SG 2C Blowdown Line Sample Backup Fuse 20 N.A.

Cont Isol Vlv 2NM210A 2EMXA-4 IB Primary Bkr 20 45 0 60A NC Pump Seal Return Coat Backup Fuse 20 N.A.

Viv 2NV94AC I

2EMXA-3 1A Primary Bkr 20 45 0 60A Lower Cont. Vent. Unit Discharge Backup Fuse 20 N.A.

Cont. Isol. Viv. 2RV76A 2EMXA-3 3A Primary Bkr 20

-45 0 60A H2 Purge Exhaust' Cont i

~

R Backup Fuse 20 N.A.

Vessel Isol Viv 2VESA e

2EMXA-3 3B Primary Bkr 20 45 0 60A Cont H2 Purge Blower Backup Fuse.

20 N.A.

Inlet Valve 2VE8A a

. _ _.,. _ _... ~,, _

TABLE 16.8-lb (Pegn 4 of 30)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 2EMXA-3 3C Primary Bkr 20 45 0 60A H2 Purge Inlet Cont Backup Fuse 20 N.A.

Vessel Isol viv 2VE10A 2EMXA-4 2C Primary Bkr 20 45 0 60A Standby Makeup Pump Inlet Backup Fuse 20 N.A.

Isol Valve 2NV842AC 2EMXA-3 4A Primary Bkr 20 45 0 60A H2 Skimmer Fan 2A Suction Backup Fuse 20 N.A.

Isol Vlv 2VX1A 2EMXA-3 5B Primary Bkr 20 45 @ 60A RCDT Pump Disch Cont Isol Backup Fuse 20 N.A.

Vlv 2WL2A 2EMXA-3 SC Primary Bkr 20 45 0 60A RCDT Vent Cont Isol Backup Fuse 20 N.A.

Vlv 2WL39A 2EMXA-3 6A Primary Bkr 20 45 @ 60A RB Sump Pump Disch Cont Backup Fuse 20 N.A.

Isol Vlv 2WL64A 2EMXA-3 6B Primary Bkr 20 45 0 60A cont Vent Unit Condensate Backup Fuse 20 N.A.

Cont Isol Vlv 2WL321A 2EMXB-4 1B Primary Bkr 20 45 0 60A NC Pump 2B Thermal Barrier R

Backup Fuse 20 N.A.

Outlet Auto Isol Viv 2KC3648 e

2EMXB-4 1C Primary Bkr 20 45 0 60A NC Pump 2D Thermal Barrier Backup Fuse 20 N.A.

Auto Isol Vlv 2KC413B

TABLE 16.8-lb (Paga 5 of 30) i UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES I

TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME i

DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 2EMXB-4 2A Primary Bkr 20 45 0 60A NC Pumps Return Hdr Pend Backup Fuse 20 N.A.

Inside Isol Vlv 2KC424B 2EMXB-4 2B Primary Bkr 20 45 0 60A Reactor Bldg Drn Hdr Backup Fuse 20 N.A.

Inside Cont Isol Vlv 2KC4298 2EMXB-4 2C Primary Bkr 30 45 0 90A Accumulator 2B Disch Isol Viv Backup Fuse 30 N.A.

2NI65B 2EMXB-4 3D Primary Bkr 30 45 0 90A Accumulator 2D Disch Isol Vlv Backup Fuse 30 N.A.

2NI888 2EMXB-4 3E Primary Bkr 20 45 0 60A Hotleg Inj Check 2 nil 24, Backup Fuse 20 N.A.

2NI128 Test Isol Vlv 2NI122B 2EMXB-4 4A Primary Bkr 20 45 0 60A Cont Air Return Fan 2B Backup Fuse 20 N.A.

Damper 2RAF-D-4 2EMXB-4 4C Primary Bkr 20 45 0 60A NI Accum 2A Sample Line i

Backup Fuse 20 N.A.

Inside Cont Isol Viv 2NM728 2EMXA-4 3B i

Primary Bkr 20 45 0 60A Standby Makeup Cont Isol

~

R Backup Fuse 20 N.A.

Valve Outside 2Nv849AC e"

2EMXB-4 5A Primary Bkr 20 45 0 60A NI Accum 2B Sample Line Backup Fuse 20 N.A.

Inside Cont Isol Viv 2NM75B

_m_..

+

TABLE 16.B-lb (Paga 6 of 30)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 2EMXB-4 SB Primary Bkr 20 45 @ 60A NI Accum 2C Sample Line Backup Fuse 20 N.A.

Inside Cont Isol Viv 2NM78B 2EMXB-4 SC Primary Bkr 20 45 0 60A Accum 2B Vent to 2NC32 Backup Fuse 20 N.A.

for Blkout Vlv 2NI431B 2EMXB-4 6A Primary Bkr 20 45 @ 60A NI Accum 2D Sample Line Backup Fuse 20 N.A.

Inside Cont Isol Valve 2NM818 2EMXB-4 6B Primary Bkr 20 45 @ 60A SG 2B Upper Shell Sample Backup Fuse 20 N.A.

Cont Isol Viv 2NM197B 2EMXB-4 6C Primary Bkr 20 45 @ 60A SG 2B Blowdown Line Sample Backup Fuse 20 N.A.

Cont Isol Viv 2NM200B 2EMXB-4 7B Primary Bkr 20 45 @ 60A SG 2D Uper Shell Sample Backup Fuse 20 N.A.

Cont Isol Viv 2NM217B 2EMXB-4 7C Primary Bkr 20 45 0 60A SG 2D Blowdown Line Sample Backup Fuse 20 N.A.

Cont Isol Viv 2NM220B o

2EMXB-5 1A D

Primary Bkr 20 45 @ 60A H2 Purge Exhaust Cont Vessel Backup Fuse 20 N.A.

Isol Vlv 2VE6B 2EMXB-5 1B Primary Bkr 20 45 @ 60A Lower Cont. Vent. Unit Supply Backup Fuse 20 N.A.

Cont. Isol. Vlv. 2RV33B

TABLE 16.8-lb (Pagm 7 of 30)

~

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-McC (Continued) 2EMXB-5 IC Primary Bkr 20 45 0 60A H2 Skimmer Fan 28 Suction Backup Fuse 20 N.A.

Isol Vlv 2VX2B 2EMXC-1A Primary Bkr 200 250 0 600A Lower Containment Cooling Backup Fuse 200 N.A.

Unit No. 2A 2EMXC-2A Primary Bkr 200 250 0 600A Lower Containment cooling Backup Fuse 200 N.A.

Unit No. 2C 2EMXC-3C Primary Bkr 100 110 0 300A Control Rod Drive Vent Fan Backup Fuse 100 N.A.

No. 2A 2EMXC-3D Primary Bkr 100 110 0 300A Control Rod Drive Vent Fan Backup Fuse 100 N.A.

No. 2C 2EMXC-4C Primary Bkr 90 110 @ 270A Containment Air Return Fan Backup Fuse 90 N.A.

No. 2A 2EMXC-4D Primary Bkr 90 110 0 270A Hydrogen Recombiner Backup Fuse 90 N.A.

No. 2A 2EMXC-6A Primary Bkr 40 45 0 120A Containment Pipe Tunnel Backup Fuse 40 N.A.

Booster Fan CPT-BF-2A D

2EMXC-6B Primary Bkr 30 45 0 90A Upper Containment Air Handling Backup Fuse 30 N.A.

Unit 2A 2EMXC-6C Primary Bkr 30 45 @ 90A Upper Containment Air Hdig Backup Fuse 30 N.A.

Unit 2C No. 2C

l l

TABLE 16.8-1b (Pegs 8 of 30)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES

~

I TRIP SETPOINT OR

RESPONSE

l CONT. RATING TIME l

DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED i

2.

600 VAC-MCC (Continued) 2EMXC-6D Primary Bkr 90 110 0 270A

. Hydrogen Skimmer Fan 2A Backup Fuse 90 N.A.

2EMXC-7C Primary Bkr 20 45 0 60A Upper Cont Return Air Fan Backup Fu.se 20 N.A.

No. 2C 2EMXC-7D Primary Bkr 20 45 0 60A Pzr Pwr Oper Relief Backup Fuse 20 N.A.

Isol Vlv 2NC33A i

2EMXC-8C Primary Bkr 20 45 0 60A Incore Instrumentation Rm Backup Fuse 20 N.A.

Air Hdig Unit 2A 2EMXC-7B Primary Bkr 20 45 0 60A Upper Containment Return Backup Fuse 20 N.A.

Air Fan No. 2A 2EMXA-4 3C Primary Bkr 30 45 0 90A NC Loop 2C Discharge to ND Backup Fuse 30 N.A.

. System Cont Isol Vlv 2ND 2AC 2EMXD-1A Primary Bkr.

200 250 0 600A Lower Containment Cooling Unit Backup Fuse 200 N.A.

No. 2B 2EMXD-2A Primary Bkr 200 250 @ 600A Lower Containment Cooling Unit Backup Fuse 200 N.A.

No. 2D o2 2EMXD-3B Primary Bkr 40 45 0 120A Containment Pipe Tunnel Booster Backup Fuse 40 N.A.

Fan CPT-BF-2B 2EMXD-3C Primary Bkr 100 110 0 300A Control Rod Drive Vent Backup Fuse 100 N.A.

Fan No. 2B

TABLE 16.8-Ib (Page 9 of 30)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES l

TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 2EMXD-3D Primary Bkr 100 110 0 300A Control Rod Drive Vent Backup Fuse 100 N.A.

Fan No. 2D 2EMXD-4C Primary Bkr 90 110 0 270A Containment Air Return i

Backup Fuse 90 N.A.

Fan No. 2B Fan CPT-BF-2B 2EMXD-4D Primary Bkr 90 110 0 270A Hydrogen Recombiner Backup Fuse 90 N.A.

No. 2B 2EMXD-6C Primary Bkr 30 45 0 90A Upper Containment Air i

Backup Fuse 30 N.A.

Hdig Unit No. 2B 2EMXD-6D Primary Bkr 30 45 0 90A Upper Containment Air Hdig Backup Fuse 30 N.A.

Unit No. 2D 2EMXD-6E Primary Bkr 90 110 0'270A Hydrogen Skimmer Fan Backup Fuse 90 N.A.

No. 2B 2EMXD-7B Primary Bkr 20 45 @ 60A-Upper Cont Return Air Fan Backup Fuse 20 N.A.

No. 2D 2EMXD-7C Primary Bkr 20 45 @ 60A Pzr Pwr Oper Safety Relief Backup Fuse 20 N.A.

Isol Viv 2NC31B 2EMXD-7D Primary Bkr 20 45 0 60A Pzr Pwr Oper Relief Backup Fuse 20 N.A.

Isol Vlv 2NC35B

. - - =

TABLE 16.8-1b (Page 10 of 30)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES

)

TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 2EMXD-8B Primary Bkr 20 45 0 60A Incore Instrumentation Backup Fuse 20 N.A.

Rm Air Hdig Unit 2B 2EMXD-5C I

Primary Bkr 20 45 0 60A Upper Containment Return Backup Fuse 20 N.A.

Air Fan 2B 2EMXD-8D Primary Bkr 30 45 @ 90A NC Loop 2C Disch to ND Backup Fuse 30 N.A.

System Cont Isol Vlv 2NDlB 2MXM F2A Primary Bkr 40 45 @ 120A Lighting Pnibd 2LR14 l

Backup Fuse 40 N.A.

j 2MXM F2B l

Primary Bkr 40 45 @ 120A Lighting Pnibd 2LR15 l

Backup Fuse 40 N.A.

2MXM F2C Primary Bkr 20 45 @ 60A Pzr Compt Fan B Backup Fuse 20 N/A i

2MXM F2D Primary Bkr 20 45 0 60A Ice Cond AHU 2Al Blower A Backup Fuse 20 N.A.

2MXM F2E o

Primary Bkr 20 45 @ 60A Ice Cond AHU 2A2 Blower A 2

Backup Fuse 20 N.A.

s~

2MXM F3A Primary Bkr 40 45 0 120A Lighting Pnlbd 2LR16 Backup Fuse 40 N.A.

a TABLE 16.8-1b (Prqa 11 of 30)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 2MXM F3B Primary Bkr 40 45 0 120A Lighting Pnlbd 2LR17 Backup Fuse 40 N.A.

2MIM F3C Primary Bkr 25 45 0 75A Reactor Bldg Equip Hdig 5 Ton Backup Fuse 25 N.A.

Jib Crane 2MXM F3D Primary Bkr 20 45 0 60A Ice Cond AHU 2A3 Blower A Backup Fuse 20 N.A.

2MXM F3E Primary Bkr 20 45 0 60A Ice Cond AHU 2A4 Blower A l

Backup Fuse 20 N.A.

2MXM F4A Primary Bkr 20 45 e 60A Ice Cond AHU 2A5 Blower A Backup Fuse 20 N.A.

2MXM F4B Primary Bkr 20 45 9 60A Ice Cond AHU 2A6 Blower A Backup Fuse 20 N.A.

2MXM F4C Primary Bk1 20 45 0 60A Incore Inst Room Sump Pump Backup Fuse 20 N.A.

2MXM F4D l

I o

Primary Bkr 100 110 0 300A Upper Cont Welding Recpt 3

Backup Fuse 100 N.A.

v 2MXM FSA Primary Bkr 20 45 @ 60A Ice Cond AHU 2A7 Blower A Backup Fuse 20 N.A.

~.

TABLE 16.8-lb (Paga 12 of 30)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-Mcc (Continued) 2MXM FSB Primary Bkr 20 45 0 60A Ice Cond AHU 2A8 Blower A Backup Fuse 20 N.A.

2MXM F5D Primary Bkr 100 110 9 300A Welding Feeder Backup Fuse 100 N.A.

2MXM Flc Primary Bkr 50 110 @ 150A Ice Cond Floor Cooling Backup Fuse 50 N.A.

Defrost Heater 2A 2MXM F8C Primary Bkr 60 110 0 180A Reactor Coolant Drain Tank Backup Fuse 60 N.A.

Pump 2A 2MXM F6A Primary Bkr 20 45 0 60A Ice Cond AHU 2A9 Blower A Backup Fuse 20 N.A.

2MXM F6B Primary Bkr 20 45 6 60A Ice Cond AHU 2A10 Blower A Backup Fuse 20 N.A.

2MXM F6C Primary Bkr 30 45 @ 90A Lower cont Aux charcoal Backup Fuse 30 N.A.

Filter Fan 2A 2MXM F7A Primary Bkr 20 45 0 60A Ice Cond AHU 2A11 Blower A Backup Fuse 20 N.A.

y R

e 2MXM F7B Primary Bkr 20 45 0 60A Ice Cond AHU 2A12 Blower A Backup Fuse 20 N.A.

f l

TABLE 16.8-lb (Prgs 13 of 30) l UNIT 2 CONTAINMENT PENETPATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 2MXM F7C Primary Bkr 20 45 @ 60A Ice Cond AHU 2A13 Blower A Backup Fuse 20 N.A.

2MXM R1A Primary Bkr 20 45 @ 60A Ice Cond AHU 281 Blower A Backup Fnse 20 N.A.

2MXM R1B Primary Bkr 20 45 0 60A Ice Cond AHU 2B2 Blower A Backup Fuse 20 N.A.

2MXM RlC Primary Bkr 20 45 0 60A Ice Cond AHU 2B3 Blower A Backup Fuse 20 N.A.

2MXM RlD Primary Bkr 30 45 0 90A RCP 2A Oil Lift Pump Backup Fuse 30 N.A.

2MXM R2A Primary Bkr 40 45 @ 120A Lighting Pnlbd 2LR12 Backup Fuse 40 N.A.

2MXM R2D Primary Bkr 20 45 @ 60A Ice Cond AHU 2B4 Blower A Backup Fuse 20 N.A.

2MXM R2E Primary Bkr 30 45 0 90A RCP 2B Oil Lift Pump yo Backup Fuse 30 N.A.

e#

2MXM R3D Primary Bkr 20 45 @ 60A Ice Cond AHU 2B5 Blower A Backup Fuse 20 N.A.

e

. -. - ~..

i l

TABLE 16.8-lb (Paga 14 of 30)

+

l UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES l

TRIP SET?OINT OR

RESPONSE

CONT. 9ATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED I

2.

600 VAC-MCC (Continued)

I 2MXM R3E Primary Bkr 20 45 @ 60A Ice Cond AHU 2B6 Blower A

)

Backup Fuse 20 N.A.

2MXM R3F Primary Bkr 30 45 e 90A RCP 2C Oil Lift Pump Backup Fuse 30 N.A.

2MIM R4D Primary Bkr 20 45 0 60A Ice cond AHU 2B7 Blower A Backup Fuse 20 N.A.

2MXM R4E Primary Bkr 20 45 0 60A Ice Cond AHU 2B8 Blower A Backup Fuse 20 N.A.

2MXM R4F Primary Bkr 30 45 0 90A RCP 2D Oil Lift Pump Backup Fuse 30 N.A.

2MXM R5B Primary Bkr 20 45 0 60A Ice Cond AHU 2B9 Blower A Backup Fuse 20 N.A.

2MXM RSC Primary Bkr 20 45 0 60A Ice Cond AHU 2B10 Blower A Backup Fuse 20 N.A.

2MXM RSD Primary Bkr 175 200 @ 525A Ice Cond Equip Pwr Pnlbd 2B Backup Fuse 175 N.A.

2 1

2MXM R6A Primary Bkr 20 45 0 60A Rod Cntrl Cluster Backup Fuse 20 N.A.

Change Fixture Hoist Drive r

r TABLE 16.8-1b (Paga 15 of 30)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 2MXM R6B Primary Bkr 20 45 @ 60A Ice Cond AHU 2B11 Blower A Backup Fuse 20 N.A.

2MXM R7A Primary Bkr 20 45 @ 60A Stud Tensioner Hoist Backup Fuse 20 N.A.

2MXM R6D-Primary Bkr 150 110 0 450A 175 Ton Polar Crane Backup Fuse 150 N.A.

2MXM R7B Primary Bkr 20 45 @ 60A Incore Inst Drive 2A Backup Fuse 20 N.A.

2MXM R7C Primary Bkr 30 45 @ 90A S/G Compt 2D Fan Backup Fuse 30 n/a 2MXM R7D Primary Bkr 20 45 @ 60A Ice cond AHU 2B12 Backup Fuse 20 N.A.

2MXM R7E Primary Bkr 20 45 @ 60A Ice Cond AHU 2B13 Blower A Backup Fuse 20 N.A.

i 2MXM R8A t

"o Primary Bkr 20 45 0 60A Incore Inst Drive 2B 3

Backup Fuse 20 N.A.

s-2MXM R8B r

Primary Bkr 20 45 0 60A Incore Inst Drive 2C Backup Fuse 20 N.A.

i m

4 m.

i

TABLE 16.8-lb (Pign 16 of 30)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) r 2MXM R8C Primary Bkr 30 45 0 90A S/G Compt 2A Fan Backup Fuse 30 N/A 2MXM R8D Primary Bkr 20 45 0 60A Ice Cond AHU 2B14 Blower A Backup Fuse 20 N.A.

2MXM R8E Primary Bkr 20 45 0 60A Ice Cond AHU 2B15 Blower A Backup Fuse 20 N.A.

2MXMA-1D Primary Bkr 20 45 0 60A Ice Cond AHU 2A14 Blower A Backup Fuse 20 N.A.

2MXMA-lE Primary Bkr 20 45 0 60A Cont Floor & Equip Sump 2A Backup Fuse 20 N.A.

Pump 2Al 2MXM-R2C Primary Bkr 20 45 0 60A RCPM Maintenance Crane Recpt 2A, Backup Fuse 20 N.A.

2B, 2C, & 2D 2MXMA-2B Primary Bkr 40 45 0 120A Lighting Pnlbd 2LR6 Backup Fuse 40 N.A.

2MXMA-2C Primary Bkr 40 45 0 120A Lighting Pnibd 2LR18

-o Backup Fuse 40 N.A.

e 2MXMA-2D Primary Bkr 20 45 0 60A Ice Cond AHU 2A15 Blower A Backup Fuse 20 N.A.

t I

i

TABLE 16.8-lb (Pega 17 of 30)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 2MXMA-3A Primary Bkr 25 45 @ 75A Lighting Pnlbd 2LR9 Backup Fuse 25 N.A.

I 2MXMA-3B Primary Bkr 20 45 @ 60A Ice Cond Equip Access Backup Fuse 20 N.A.

Door 2A 2MXMA-3C Primary Bkr 50 110 0 150A Ice Cond Floor Cooling Backup Fuse 50 N.A.

Pump 2A 2MXMA-3D Primary Bkr 20 45 0 60A Cont Floor & Equip Sump 2B Backup Fuse 20 N.A.

Pump 2B1 2MXN-F2A Primary Bkr 20 45 @ 60A Ice Cond AHU 2A1 Blower B Backup Fuse 20 N.A.

2MXN-F2B Primary Bkr 20 45 9 60A Ice Cond AHU 2A2 Blower E Backu,r Fuse 20 N.A.

2MXN-F7C Primary Bkr 20 45 0 60A Ice Cond AHU 2A3 Blower B Backup Fuse 20 N.A.

2MXN-F2D Primary Bkr 20 45 @ 60A Ice Cond AHU 2A4 Blower B o

Backup Fuse 20 N.A.

e i

2MXN-F3A Primary Bkr 20 45 0 60A Ice Cond AHU 2A5 Blower B Backup Fuse 20 N.A.

TABLE 16.8-1b (Paqs 18 of 30)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES l

~ j TRIP-SETPOINT OR

RESPONSE

i CONT. RATIdG TIME I

DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED l

2.

600 VAC-MCC (Continued) 2MXN-F3B Primary Bkr 20 45 0 60A Ice Cond AHU 2A6 Blower B Backup Fuse 20 N.A.

I 2MXN-F3C Primary Bkr 20 45 0 60A Ice Cond AHU 2A7 Blower B Backup Fuse 20 N.A.

2MXN-F3D i

Primary Bkr 20 45 9 60A Ice Cond AHU 2A8 Blower B Backup Fuse 20 N.A.

J 2MXN-F4A f

Primary Bkr 25 45 G 75A Lighting Pnibd 2LR1 Backup Fuse 25 N.A.

2MXN-F4B Primary Bkr 30 45 0 90A S/G' Compt 2C Fan Backup Fuse 30 N/A 2MXN-F4C Primary Bkr 25 45 9 75A Lighting Pnibd 2LR2 Backup Fuse 25 N.A.

2MXN-F4D Primary Bkr 20 45 e 60A Ice Cond AHU 2A9 Blower B Backup Fuse 20 N.A.

~k e

2MXN-F4E Primary Bkr 20 45 @ 60A Ice Cond'AHU 2A10 Blower B Backup Fuse 20 N.A.

2MXN-F5A L

Primary Bkr 20 45 @ 60A Incore Inst Drive No. 2D t

Backup Fuse 20 N.A.

-. m m

. m

.m.

w

.e

-~_er,--m i -

m m

TABLE 16.8-1b (Paga 19 of 30)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES i

TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED i

f 2.

600 VAC-MCC (Continued) 2MXN-F5B Primary Bkr 20 45 0 60A Incore Inst Drive No. 2E Backup Fuse 20 N.A.

2MXN-F5C Primary Bkr 20 45 0 60A Incore Inst Drive No. 2F Backup Fuse 20 N.A.

2MXN-F5D Primary Bkr 20 45 0 60A Cont Floor & Equip Sump 2A Backup Fuse 20 N.A.

Pump 2A2 2MXN-FIC Primary Bkr 60 110 0 180A Reactor Coolant Drain Tank Backup Fuse 60 N.A.

Pump 2B 2MXN-F8B I

Primary Bkr 20 45 0 60A Cont Floor & Equip Sump 2B I

Backup Fuse 20 N.A.

Pump 2B2 2MXN-F8C Primary Bkr 50

.110 0.150A Ice Cond Floor Cooling Backup Fuse 50 N.A.

Defrost Htr 2B 2MXN-F6A Primary Bkr 25 45 6 75A Lighting Pnibd 2LR4 Backup Fuse 25 N.A.

2MXN-F6B Primary Bkr 40 45 0 120A Lighting Pn1bd 2LR5 5

Backup Fuse 40 N.A.

s 2MXN-F6C Primary Bkr 20 45 0 60A Fuel Transfer Sys Reactor Side Fdr Backup Fuse 20 N.A.

I

TABLE 16.8-lb (Paga 20 of 30)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 2MXN-F6D Primary Bkr 20 45 0 60A Ice Cond AHU 2A11 Blower B Backup Fuse 20 N.A.

2MXN-F7B Primary Bkr 30 45 0 90A Pzr Compt Fan A Backup Fuse 30 N/A 2MXN-F7D Primary Bkr 20 45 0 60A Ice Cond AHU 2Al2 Blower B Backup Fuse 20 N.A.

2MXN-F7E Primary Bkr 20 45 0 60A Ice Cond AHU 2A13 Blower B nackup Fuse 20 N.A.

2MXN-RlD Primary Bkr 20 45 0 60A Ice Cond AHU 2B1 Blower B Backup Fuse 20 N.A.

2MXN-RIE Primary Bkr 20 45 0 60A Ice Cond AHU 2B2 Blower B Backup Fuse 20 N.A.

2MXN-RlF Primary Bkr 30 45 @ 90A RCP 2A Oil Lift Pump No. 2 Backup Fuse 30 N.A.

2MXN-R2C o

Primary Bkr 30 45 0 90A Reactor Cavity Manipulator Backup Fuse 30 N.L.

Crane 2MXN-R2F Primary Bkr 30 45 0 90A RCP 2B Oil Lift Pump No. 2 Backup Fuse 30 N.A.

1

f TABLE 16.8-lb (Paga 21 of 30)

UNIT 2' CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED i

2.

600 VAC-MCC (Continued) 2MXN-R3A l

Primary Bkr 20 45 0 60A Ice'Cond AHU 2B3 Blower B Backup Fuse 20 N.A.

2MXN-R3B Primary Bkr 20 45 0 60A Ice Cond AHU 2B4 Blower B Backup Fase 20 N.A.

2MXN-R3C Primary Bkr 20 45 0 60A Ice Cond AHU 2B5 Blower B Backup Fuse 20 N.A.

2MXN-R3D Primary Bkr 30 45 3 90A RCP 2C Oil Lift Pump No. 2 l

Backup Fuse 30 N.A.

2MXN-R4A Primary Bkr 50 110 0 150A Ice'Cond Bridge Crane Backup Fuse 50 N.A.

2MXN-R4B Primary Bkr 30 45 0 90A RB Equip Hatch Holst Backup Fuse 30 N.A.

2MXN-R4C i

Primary Bkr 25 45 0 75A S/G Compt 2B Fan i

Backup Fuse 25 N/A j

2MXN-R4D

~ Primary Bkr 20 45 0 60A Ice Cond AHU 2B6 Blower B Backup Fuse 20 N.A.

i s

2MXN-R4E Primary Skr 30 45 0 90A RCP 2D Oil Lift Pump No. 2 I

Backup Fuse 30 N.A.

i

TABLE 16.8-lb (Pega 22 of 30)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED j

2.

600 VAC-MCC (Continued) 2MXN-R5D Primary Bkr 175 200 0 525A Ice Cond Equip Pwr Pnlbd 2A Backup Fuse 175 N.A.

2MXN-R6A Primary Bkr 20 45 0 60A Ice Cond AHU 287 Blower B Backup Fuse 20 N.A.

2MXN-R6B Primary Bkr 20 45 0 60A Ice Cond AHU 2B8 Blower B Backup Fuse 20 N.A.

2MXN-R6C Primary Bkr 20 45 0 60A Ice Cond AHU 2B9 Blower B Backup Fuse 20 N.A.

2MXN-R6D Primary Bkr 100 110 0 300A Welding Fdr Backup Fuse 100 N.A.

2MXN-R7A Primary Bkr 20 45 0 60A Ice Cond AHU 2B10 Blower B Backup Fuse 20 N.A.

2MXN-R7B Primary Bkr 20 45 @ 60A Ice cond AHU 2B11 Blower B Backup Fuse 20 N.A.

2MXN-R7C Primary Bkr 20 45 0 60A Ice Cond AHU 2B12 Blower B-Backup Fuse 20 N.A.

k 2MXN-R7D Primary Bkr 50 110 0 150A Ice Cond Floor Cooling Pump 2B Backup Fuse 50 N.A.

d i:

TABLE 16.8-lb (Peqa 23 of 301 UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES l

TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-MCC (Continued) 2MXN-R8D Primary Bkr 20 45 0 60A Ice Cond AHU 2B13 Blower B Backup Fuse 20 N.A.

2MXN-R8E Primary Bkr 20 45 @ 60A Ice Cond AHU 2B14 Blower B Backup Fuse 20 N.A.

2MXN-R8F Primary Bkr 20 45 0 60A Ice Cond AHU 2B15 Blower B Backup Fuse 20 N.A.

SMXG-R3G Primary Bkr 20 45 @ 60A Standby Makeup Pump to Cont Backup Fuse 20 N.A.

Sump Isol Valve 2NV1012C 2MXNA-1E Priroary Bkr

-30 45 0 90A Lower Cont Aux Charcoal Backup Fuse 30 N.A.

Filter Fan 2B 2MXNA-2B Drimary Bkr 25 45 6 75A Lighting Pnibd 2LR7 Backup Fuse 25 N.A.

2MXNA-2C Primary Bkr 25 45 6 75A Lighting Pnlbd 2LR8 Backup Fuse 25 N.A.

2MXNA-2D Primary Bkr 20 45 0 60A Ice Cond AHU 2A14 Blower B Backup Fuse 20 N.A.

o3 2MXNA-2E Primary Bkr 20 45 0 60A Ice Cond AHU 2A15 Blower B Backup Fuse 20 N.A.

TABLE 16.8-lb (Psgn 24 of 30) 7 UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 2.

600 VAC-HCC (Continued) i 2MXNA-3A Primary Bkr 20 45 0 60A 2 Ton CRDM Hdig Jib Crane Backup Fuse 20 N.A.

2MXNA-3B Primary Bkr 30 45 0 90A Cont Air Compressor l

Backup Fuse 30 N/A SMXG-R4F Primary Bkr 20 45 0 60A Standby Makeup Pump to NC Backup Fuse 20 N.A.

Pump Seals Isol Valve 2NV1013C 2MXNA-3C Primary Bkr 20 45 @ 60A NC Pump Motor Drain Tank Backup Fuse 20 N.A.

Pump No. 1 2MXNA-3D Primary Bkr 20 45 0 60A Ice Cond Equip Access Door 2B Backup Fuse 20 N.A.

SMXD-3E 1

Primary Bkr 15 45 0 45A Unit 2 Personnel Lock Backup Fuse 15 N.A.

SMXV-2F Primary Bkr 15 45 0 45A Unit 2 Emergency Personnel Lock Backup Fuse 15 N.A.

3.

600 VAC-Press Htr Pwr Pnis i

"o3 Backup Press Htr Pwr e

Pnl 2A-1A Primary Bkr 90 110 0 270A Pressurizer Heaters 1, 2, & 22 Backup Fuse 90 N.A.

l

.~

TABLE 16.8-Ib (PEga 25 of 30)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 3.

600 VAC-Press Htr Pwr Pnis (Continued)

Backup Press Htr Pwr Pnl 2A-1B Primary Bkr 90 110 0 270A Pressurizer Heaters 5, 6, & 27 Backup Fuse 90 N.A.

Backup Press Htr Pwr Pnl 2A-1C Primary Bkr 90 110 0 270 Pressurizer Heaters 9, 10, Backup Fuse 90 N.A.

& 32 j

Backup Press Htr Pwr Pnl 2A-2C Primary Bkr 90 110 0 270A Pressurizer Heaters 11, 12, Backup Fuse 90 N.A.

& 35 Backup Press Htr Pwr Pnl 2A-2D Primary Bkr 90 110 0 270A Pressurizer Heaters 13, 14, Backup Fuse 90 N.A.

& 37 Backup Press Htr Pwr Pnl 2A-2E Primary Bkr 90 110 @ 270A Pressurizer Heaters 17, 18, Backup Fuse 90 N.A.

& 42 Backup Press Htr Pwr Pnl 2B-1A Primary Bkr 90 110 e 270A Pressurizer Heaters 21, 47, Backup Fuse 90 N.A.

@ 48 Backup Press Htr Pwr

'o~'

Pn1 2B-1B g

Primary Bkr 90 110 0 270 Pressurizer Heaters 26, 53, e

Backup Fuse 90 N.A.

& 54 L

Backup Press Htr Pwr Pn1 2B-1C Primary Bkr 90 110 @ 270A Pressurizer Heaters 31, 59, & 60 Backup Fuse 90 N.A.

L o

n

r TABLE 16.8-1b (Paga 26 of 30)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES L

TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED I

3.

600 VAC-Press Htr Pwr Pnis (Continued)

Backup Press Htr Pwr Pnl 2B-2C Primary Bkr 90 110 0 270A Pressurizer Heaters 36, 65, & 66 Backup Fuse 90 N.A.

Backup Press Htr Pwr Pnl 2B-2D Primary Bkr 90 110 0 270A Pressurizer Heaters 41, 71, & 72 Backup Fuse 90 N.A.

Backup Press Htr Pwr Pnl 2B-2E Primary Bkr 90 110 @ 270A Pressurizer Heaters 46, 77, & 78 Backup Fuse 90 N.A.

Backup Press Htr Pwr Pnl 2C-1A Primary Bkr 90 110 @ 270A Pressurizer Heaters 7, 8,

& 30 Backup Fuse 90 N.A.

v Backup Press Htr Pwr Pnl 2C-1B Primary Bkr 90 110 0 270A Pressurizer Heaters 19, 20, & 45 Backup Fuse 90 N.A.

Backup Press Htr Pwr Pnl 2C-1C Primary Bkr 90 110 0 270A Pressurizer Heaters 24, 51, & 52 Backup Fuse 90 N.A.

Backup Press Htr Pwr yo Pnl 2C-1D 2

Primary Bkr 90 110 0 270A Pressurizer Heaters 29, 57, & 58 Backup Fuse

-90 N.A.

Backup Press Htr Pwr Pnl 2C-2C Primary Bkr 90 110 @ 270A Pressurizer *ieaters 34, 63, & 64 Backup Fuse 90 N.A.

TABLE 16.8-1b (Paga 27 of 30)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 3.

600 VAC-Press Htr Pwr Pnis (Continued)

Backup Press Htr Pwr Pnl 2C-2D Primary Bkr 90 110 @ 270A Pressurizer Heaters 39, 69, & 70 Backup Fuse 90 N.A.

Backup Press Htr Pwr Pnl 2C-2E' Primary Bkr 90 110 @ 270A Pressurizer Heaters 44, 75, & 76 Backup Fuse 90 N.A.

Backup Press Htr Pwr Pnl 2D-1A Primary Bkr 90 110 @ 270A Pressurizer Heaters 3, 4,

& 25 Backup Fuse 90 N.A.

4 Backup Press Htr Pwr Pnl 2D-1B Primary Bkr 90 110 0 270A Pressurizer Heaters 15, 16, & 40 Backup Fuse 90 N.A.

Backup Press Htr Pwr i

Pnl 2D-1C Primary Bkr 90 110 0 270A Pressurizer Heaters 23, 49, & 50 Backup Fuse 90 N.A.

SMXG-RSA Primary Bkr 90 110 @ 270A Pressurizer Heaters 28, 55, & 56 Backup Fuse 90 N.A.

Backup Press Htr Pwr go Pnl 2D-2C D

Primary Bkr 90 110 @ 270A Pressurizer Heaters 33, 61, & 62 Backup Fuse 90 N.A.

Backup Press Htr Pwr Pnl 2D-2D Primary Bkr 90 110 @ 270A Pressurizer Heaters 38, 67, & 68 Backup Fuse 90 N.A.

l i

TABLE 16.8-lb (Ptga 28 of 30)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME i

DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED I

3.

600 VAC-Press Htr Pwr Pnis (Continued)

Backup Press Htr Pwr Pnl 2D-2E Primary Bkr 90 110 0 270A Pressurizer Heaters 43, 73,

& 74 Backup Fuse 90 N.A.

4.

120 VAC-Panelboards 2KM-19 Primary Bkr 20 45 0 90A RCP 2A Space Htr Backup Fuse 20 N.A.

2KM-20 Primary Bkr

~ 20 45 0 90A RCP 2C Space Htr Backup Fuse 20 N.A.

2KN-19 Primary Bkr 20 45 0 90A.

RCP 2B Space Htr Backup Fuse 20 N.A.

2KN-20 Primary Bkr 20 45 0 90A RCP 2D Space Htr Backup Fuse 20 N.A.

2KN-27 Primary Bkr 20 36 0 60A Fuel Handling Control Console Backup Fuse 20 N.A.

2KN-25 Primary Bkr 30 36 0 60A Unit 2 Incore Inst Backup Fuse 20 N.A.

Dehum #2 y

8 i

i 7

A

TABLE 16.8-lb (Paga 29 of 30)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 5.

250 VDC-Lighting RB Deadlight Pnibd 2DLD #1 Primary Bkr 20 40 @ 60A Ltg Pnl Nos. 2LR1 & 2LR2 Backup Fuse 20 N.A.

RB Deadlight Pnlbd 2DLD #3 Primary Bkr 20 40 0 60A Ltg Pnl Nos. 2LR4, 2LR5, &

Backup Fuse 20 N.A.

2LR6 RB Deadlight Pnibd 2DLD #4 Primary Bkr 20 40 0 60A Ltg Pnl Nos. 2LR7, 2LR8, & 2LR9 Backup Fuse 20 N.A.

RB Deadlight Pnibd 2DLD #6 Primary Bkr 20 40 0 60A Ltg Pnl Nos. 2LR12 Backup Fuse 20 N.A.

{

RB Deadlight Pnibd j

j 2DLD #7 Primary Bkr 20 40 0 60A Ltg Pnl No. 2LR16 i

Backup Fuse 20 N.A.

RB Deadlight Pnibd 2DLD #9 Primary Bkr 20 40 @ 60A Ltg Pnl Nos. 2LR18 & 2LR17 Backup Fuse 20 N.A.

6.

600 VAC - LC 5

Outage Power Fuse Box 2A 3

Primary Fuse 150 N.A.

Upper Containment Safety e

Backup Fuse 150 N.A.

Switch 2A l

Primary Fuse 150 N.A.

Upper Containment Safety Backup Fuse 150 N.A.

Switch 2B

.a.-

e i

TABLE 16.8-lb (Paqs 30 of 30)

UNIT 2 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES TRIP SETPOINT OR

RESPONSE

CONT. RATING TIME DEVICE NUMBER & LOCATION (AMPERES)

(SECONDS)

SYSTEM POWERED 6.

600 VAC -LC_(continued)

Primary Fuse 200 N.A.

Lower Containment Outage Backup Fuse 200 N.A.

Power Distr. Pnl 2A Primary Fuse 225 N.A.

Lower Containment Outage Backup Fuse 225 N.A.

Power Distr. Pnl 2B 1

P ii 4

r a

(

i o

3 e

I i

4

.... ~, -. _ _,.,,.

-4

--...m..

T A.B L E ;6.11-1 (Page 1 of 3)

RADICACT:VE L: QUID WASTE SAMPLING AND ANALYSIS PROGRAM LIQUID RELEASE SAMPLING MINIMUM TYPE OF LOWER LIMIT TYPE FREQUENCY ANALYSIS ACTIVITY OF DETECTION FREQUENCY ANALYSIS (LLD)

(ucI/ML) 1.

Batch Waste P

P Release Tanks Each Batch Each Batch Principal 5x10" Gamma Emitters I-131 1x10" (Waste P

M Dissolved 4

Monitor Tanks One Batch /M and 1x10 and Recycle Entrained Monitor Tank)

Gases (Gamma emitters)

P M

H-3 1x10" Each Batch Compos ite <2i Gross Alpha 1x10" P

Q Sr-89, Sr-90 5x10" Each Batch Composite <2 2.

Continuous W

Principal Releases Continuous'"

Composite '"

Gamma 5x10" Emitters "'

(Containment I-131 1 x10-'

Ventilation Unit M

M Dissolved Grab Sample and 1x10-5

{

Condensate Drain Tank Entrained Discharge and Gases (Gamma Conventional Emitters)

Waste Water 4

Continuous'"

M H-3 1x10 Treatment Composite '"

System Gross Alpha 1x10" Outlet)

Q Sr-89,Sr-90 5x10" Continuous'"

Composite '"

9/94 16.11-4

TABLE 16.11-1 (Page 1 of 3)

RADICACT:7E L:CUID WASTE SAMPL:NG AND ANALYSIS PROGRAM l

LIQUID RELEASE SAMPLING MINIMUM TYPE OF LOWER LIMIT TYPE FREQUENCY ANALYSIS ACTIVITY OF DETECTION FREQUENCY ANALYSIS (LLD)

(ucI/ML) 1.

Batch Waste P

P Release Tanks Each Batch Each Batch Principal 5x10"

.i Gamma Emitters I-131 1x10" (Waste

?

M Dissolved Monitor Tanks One Batch /M and 1x10" and Recycle Entrained Monitor Tank)

Gases (Gamma emitters)

P M

H-3 1x.10" Each Batch Composite"'

Gross Alpha 1x10' P

Q Sr-89, Sr-90 5x10" Each Batch Composite"'

2.

Continuous W

Principal Releases "

Continuous"'

Composite

")

Gamma 5x10" d'

Emitters (Containment I-131 1x10" Ventilation Unit M

M Dissolved Condensate 4

Grab Sample and 1x10 Drain Tank Entrained l

Discharge and Gases (Gamma Conventional Emitters)

Waste Water 4

Continuous"'

M H-3 1x10 Treatment Composite

")

System Gross Alpha 1x10" I

Outlet)

Q Sr-89,Sr-90 5x10" Continuous"'

Composite "'

9/94 i

16.11-4

i 5

'ABLE '6.11-1 (Page 1 of 3) l l

RAD!.OACT!VE LIQUID WASTE SAMPLING AND ANALYSIS PROGRAM l

l mmmmmmmmmmmmmmmmmmer LIQUID RELEN.,

SAMPLING MINIMUM TYPE OF LOWER LIMIT TYPE FREQUENCY ANALYSIS ACTIVITY OF DETECTION FREQUENCY ANALYSIS (LLD) l (ucI/ML) '"

l1.

Batch Waste P

P Release Tanks Each Batch Each Batch Principal 5x10

.i Gamma Emitters I-131 lx10" (Waste P

M Dissolved Monitor Tanks One Batch /M and 1 x 10

and Recycle Entrained Monitor Tank)

Gases (Gamma emitters)

P M

H-3 1 x.10~'

Each Batch Composite'2 Gross Alpha 1 x 10* '

P Q

Sr-89, Sr-90 5x10-'

Each Batch Composite'2 2.

Continuous W

Principal Releases

Continuous'"

Composite '"

Gamma 5x10-'

Emitters "'

(Containment I-131 1 x10

Ventilation Unit M

M Dissolved Condensate Grab Sample and 1 x 10

Drain Tank Entrained Discharge and Gases (Gamma Conventional Emitters)

Waste Water Continuous'"

M H-3 1x10-'

Treatment Composite

System Gross Alpha 1 x 10

O Sr-89,Sr-90 5 x 10

Outlet)

Continuous'"

Composite

s 9/94 16.11-4 i

\\

TABLE.6.11-1 (Page 1 of 3)

PADICACTIVE LIQUID WASTE SAMPLING AND ANALYSIS PROGRAM

)

LIQUID RELEASE SAMPLING MINIMUM TYPE OF LOWER LIMIT TYPE FREQUENCY ANALYSIS ACTIVITY OF DETECTION FREQUENCY ANALYSIS (LLD)

(ucI/ML) '"

Batch Waste P

P Release Tanks Each Batch Each Batch Principal 5 x 10' '

.i Gamma Emitters I-131 lx10" (Waste P

M Dissolved Monitor Tanks One Batch /M and 1x10~5 and Recycle Entrained Monitor Tank)

Gases (Gamma emitters)

P M

H-3 1 x.10-'

Each Batch Composite <2 Gross Alpha 1x10" P

Q Sr-89, Sr-90 5 x 10 ~'

Each Batch Composite

Continuous W

Principal Releases

Continuous"'

Composite "'

Gamma 5x10

d' Emitters (Containment I-131 1x10~*

Ventilation Unit M

M Dissolved Condensate Grab Sample and 1x10~5 Drain Tank Entrained Discharge and Gases (Gamma Conventional Emitters)

Waste Water Continuous

M H-3 1x10-'

Treatment Composite "'

System Gross Alpha 1x10~'

Outlet)

Q Sr-89,Sr-90 5 x 10-'

Continuous"'

Composite "'

9/94 16.11-4

,s IABLE.6.11-1 (Page 1 of 3)

RADICACT 'E LIQUID WASTE SAMPLING AND ANALYSIS PROGRAM LIQUID RELEASE SAMPLING MINIMUM TYPE OF LOWER LIMIT j

TYPE FREQUENCY ANALYSIS ACTIVITY OF DETECTION FREQUENCY ANALYSIS (LLD)

(ucI/ML) 1.

Batch Waste P

P Release Tanks Each Batch Each Batch Principal 5x10" Gamma Emitters I-131 lx10" (Waste P

M Dissolved Monitor Tanks One Batch /M and 1 x 10

and Recycle Entrained Monitor Tank)

Gases (Gamma emitters)

P M

H-3 1x10-'

Each Batch Composite

Gross Alpha 1x10" P

Q Sr-89, Sr-90 5x10~'

Each Batch Composite

2.

Continuous W

Principal Releases Continuous'"

Composite

Gamma 5x10" Emitters "'

(Containment I-131 1x10~'

Ventilation Unit M

M Dissolved Condensate Grab Sample and 1x10-5 Drain Tank Entrained Discharge and Gases (Gamma Conventional Emitters)

Waste Water Continuous'"

M H-3 1x 10-5 l

Treatment Composite

System Gross Alpha 1x10" Outlet)

Q Sr-89,Sr-90 5 x 10

Continuous

Composite

a 9/94 l

l l

16.11-4 l

W LE 6.11-1 (Page 1 of 3)

RADICACTIVE LIQUID WASTE SAMPLING AND ANALYSIS PROGRAM LIQUID RELEASE SAMPLING MINIMUM TYPE OF LOWER LIMIT 4

TYPE FREQUENCY ANALYSIS ACTIVITY OF DETECTION FREQUENCY ANALYSIS (LLD)

(LicI /ML)

'u 1.

Batch Waste P

P Release Tanks Each Batch Each Batch Principal 5x10" Gamma Emitters I-131 lx10" (Waste P

M Dissolved Monitor Tanks One Batch /M and lx10-5 and Recycle Entrained

~

Monitor Tank)

Gases (Gamma emitters)

P M

H-3 1 x.10 ~ '

Each Batch Composite '2>

Gross Alpha lx10" P

Q Sr-89, Sr-90 5x10

Each Batch Compo sit e

2.

Continuous W

Principal Releases

'5 Continuous

Composite

Gamma 5x10" Emitters "'

(Containment I-131 1x10~'

Ventilation Unit M

M Dissolved Condensate Grab Sample and l x 10

Drain Tank Entrained Discharge and Gases (Gamma Conventional Emitters)

Waste Water Continuous'4 M

H-3 lx 10

Treatment Composite

'2' System Gross Alpha 1x10' Outlet)

Q Sr-89,Sr-90 5 x 10

Continuous

Composite

+

9/94 16.11-4

TABLE 16.11-1 (Page i of 3)

RADICACTIVE LIQUID WASTE SAMPLING AND ANALYSIS PROGRAM LIQUID RELEASE SAMPLING MINIMUM TYPE OF LOWER LIMIT TYPE FREQUENCY ANALYSIS ACTIVITY OF DETECTION FREQUENCY ANALYSIS (LLD)

(ucI/ML) l.

Batch Waste P

P Release Tanks Each Batch Each Batch Principal 5x10" Gamma Emitters I-131 lx10" (Waste P

M Dissolved Monitor Tanks One Batch /M and 1x10-'

and Recycle Entrained Monitor Tank)

Gases (Gamma emitters)

P M

H-3 lx.10-5 Each Batch Composite'"

Gross Alpha lx10' P

Q Sr-89, Sr-90 5 x 10-'

Each Batch Composite (2i 2.

Continuous W

Principal Releases Continuous

Composite

Gamma 5x10-'

Emitters "'

(Containment I-131 l x 10-'

Ventilation Unit M

M Dissolved Condensate Grab Sample and 1 x 10-'

Drain Tank Entrained Discharge and Gases (Gamma Conventional Emitters)

Waste Water Cont inuous

M H-3 l x 10-'

Treatreent Composite

System Gross Alpha lx10" Outlet)

Q Sr-89,Sr-90 5 x 10 -'

Continuous

Composite

9/94 16.11-4

-