1 e-
'mme E8 y
TABLE 15.3.5-1 (Continued) c0 (Page 2 of 2)
M
- p:0 PJ O
NO.
FUNCTIONAL UNIT CHANNEL SETTING LIMIT uD OU OO OU
- g 9.
Degraded Voltage (4.16 KV)
Disconnection of affected
>3875 volts 12%
- co-bus from offsite power.
Time delay: less than 60 sec at 0-100% of voltage setting
<4 10.
Loss of Voltage a.
4.16 KV Disconnection of affected 3220 volts 12%
bus from offsite power.
Time delay:
<1 sec +10% at I
Start diesel.
0-100% of voltage setting i
b.
480 V Load shedding.
256 volts 13%
Time delay:
<0.75 sec 110%
at 0 volts