Deficiency Rept Re Use of ASTM-A307 Nuts & Bolts for Bolted Connection in Lieu of Required ASTM-A325 Nuts & Bolts. Initially Reported on 820903.Ebasco Svcs Currently Evaluating Problem.All Bolts Replaced/Reinspected
ML20071N485
Person / Time
Site: Harris  
Issue date: 09/30/1982
From: Parsons R
CAROLINA POWER & LIGHT CO.
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
CON-NRC-7 10CFR-050.55E, 10CFR-50.55E, NUDOCS 8210080180
Download: ML20071N485 (1)


Text

y r

v i

j Carolina Power & Light Company P. O. Box 101, New Hill, N. C.

27562 j

September 30, 1982 Mr. James P. O'Reilly NRC-7 United States Nuclear Regulatory Commission Region II 101 Marietta Street, Northwest (Suite 3100)

Atlanta, Georgia 30303 CAROLINA POWER & LIGHT COMPANY SHEARON HARRIS NUCLEAR POWER PLANT 1985 900,000 KW - UNITS 1 & 2 USE OF ASTM-A307 NUTS AND BOLTS FOR BOLTED CONNECTIONS WHERE ASTM-A325 NUTS AND BOLTS WERE REQUIRED - ITEM 97

Dear Mr. O'Reilly:

On September 3, 1982, Mr. L. E. Jones notified the NRC (Mr. A. Hardin) of a potentially reportable item, per the provisions of 10CFR50.55(e). Thi concerned the use of ASTM-A307 bolts in bolted connections in the conta ment No. 1 recirculating sump cover structural steel in lieu of the ASTM-A32 bolts 7 "2

specified.

en 4

w This item has been referred to our architect / engineers, Ebasco Services, for? o evaluation and is still being evaluated. We expect the evaluation tode

,af r

complete by mid October, 1982. Since the bolts used throughout the R3tform"p were incorrect, the entire platform must be evaluated using the design and M e seismic loading, considering the lower strength bolts. To date, all polts)l2 have been replaced with ASTM-A325 bolts and reinspected.

As soon as the evaluation is complete, we will advise you immediately of the status of reportability.

Yours very truly, N

f: ;&

R. M. Parsons Project General Manager Shearon Harris Nuclear Power Plant RMP/sh cc:

Mr. G. Maxwell t*y Ab Mr. V. Stello (Nld) l i OFFICIALCOPV.]