.N TABLE 3.3.3-1 (Continutd)

~

E h-EMERGENCY CORE COOLING SYSTEM ACTUATION INSTRUMENTATION R

MINIMUM NUMBER APPLICABLE OPERABLE CHANNELS, OPERATIONAL E

TRIP FUNCTION AND INSTRUMENT NUMBER PER TRIP SYSTEM CONDITIONS ACTION I

s u

4.

-ADS a.

Drywell Pressure - High, coincident with (E11-PS-N010A,B,C,D) 2 1,.2, 3

30 b.

Reactor Vessel Water Level - Low, Level #3

_2 1,2,3 30 (B21-LIS-NO31A,B,C,D) 2Q c.

Reactor Vessel Water level - Low level #1 1

1,2,3 30 Do (B21-LIS-N042A,B) 8$

d.

ADS Timer 1

1,2,3 31

.i QW

.(B21-TDPU-K5A,B) 0 Core Spray Pump Discharge Pressure - High (Permissive) 2 1,2,3 31 e.

m (E21-PS-N008A,B and-E21-PS-N009A,B) f.

RHR-(LPCI MODE) Pump Discharge Pressure - High (Permissive) 2/ pump 1, 2, 3.

31 oN (E11-PS-N016A,B,C,D and E11-PS-N020A,B,C,D) sNS g.

Bus Power Monitor #

1/ bus 1, 2, 3 32 3*

(B21-K1A,B) 1 APPLICABLE Y

TOTAL NO.

CHANNELS MINIMUM CHANNELS OPERATIONAL U

JNCTIONAL UNIT OF CHANNELS TO TRIP OPERABLE CONDITIONS ACTION 5.

LOSS OF POWER a.

4.16 kv. Emergency Bus 1/ bus 1/ bus 1/ bus 1, 2, 3, 4##, 5##

34 Undervoltage'(Loss of Voltage). Relay Type IAV53K, Device Number.27/59E b.

4.16 kv Emergency Bus

'3/ bus 2/ bus-2/ bus 1,2,3,4##, 5##

35 l

)

Undervoltage (Degraded f

Voltage) Device Number 27/DV a

I e a

}[

  • Not applicable when two core spray system subsystems are OPERABLE per Specification 3.5.3.1.

,o

    • Provides signal to HPCI pump suction > valves only..
  1. Alarm only.
    1. Required when ESF equipment is required to be OPERABLE.

1 i

~

TABLE 3.3.3-2 (Continued) as E

EMERGENCY CORE COOLING SYSTEM ACTUATION INSTRUMENTATION SETPOINTS 5

R FUNCTIONAL UNIT TRIP VALUE ALLOWABLE VALUES c:

5.

LOSS OF POWER

-i a.

4.16 kv Emergency Bus Undervoltage-a.

4.16 kv Basis - 3430 i 172 volts b3 (Loss of Voltage) Relay Type IAV53K, b.

120 v Basis - 98 i 4.9 volts j( 1.575 sec. at 0 volts Device Number 27/59E c.

b.

4.16 kv Emergency Bus Undervoltage a.

4.16 kv Basis - 3727 i 9 volts 3727 t 21 volts (Degraded Voltage) b.

120 v Basis - 106.5 t 0.25 volts 106.5 t 0.60 volts Device Number 27/DV c.

10 i 0.5 sec. time delay 10 i 1.0 sec. time delay l

l Y

s~

Y a

m I

a

  • This is an inverse time delay voltage-relay. The relay will not trip for voltages greater than the trip setpoint.

For. voltages less than the trip setpoint, allowable values are determined by the inverse time characteristic.

TABLE 4.3.3-1 (Continued)

Ey EMERGENCY CORE COOLING SYSTEM ACTUATION INSTRUMENTATION SURVEILLANCE REQUIREMENTS 5

-Q_

OPERATIONAL CHANNEL CONDITIONS IN WHICH CHANNEL FUNCTIONAL CHANNEL SURVEILLANCE h

FUNCTIONAL UNIT CHECK TEST CALIBRATION REQUIRED H

5.

LOSS OF POWER a.

4.16 kv Emergency Bus NA NA R

1, 2, 3, 4*, 5*

Undervoltage (Loss of Voltage) Relay Type IAV53K, l

Device Number 27/59E I

b.

4.16 kv Emergency Bus NA M

R 1, 2, 3, 4*,-5*

l 23 Undervoltage (Degraded Voltage) y Device Number 27/DV m

I

$n

  • Required when ESF equipment is required to be OPERABLE.

TABLE 3.3.3-1 (centinued)

E y

EMERGENCY CORE COOLING SYSTEM ACTUATION INSTRUMENTATION 8m MINIMUM NUMBER APPLICABLE OPERABLE CHANNELS OPERATIONAL y

TRIP FUNCTION AND INSTRUMENT NUMBER PER TRIP SYSTEM CONDITIONS ACTION

~

4.

ADS (continued) c.

Reactor Vessel Nater Level - Low Level #1 1

1,2,3 30 (B21-LT-N042A, B; B21-LTM-N042A-1, B-1) d.

ADS Timer 1

1,2,3 31 (B21-TDPU-K5A, B) e.

Core Spray Pump Discharge Pressure - High (Permissive) 2 1,2,3 31 (E21-PS-N008A, B and E21-PS-N009A, B) f.

RHR (LPCI MODE) Pump Discharge Pressure - High (Permissive) 2/ pump 1,2,3 31 (E11-PS-N016A,B,C,D and E11-PS-N020A,B,C,D) g.

Bus Power Monitor #

1/ bus 1, 2, 3 32 (321-K1A, B) u3 MINIMUM APPLICABLE w

d, TOTAL NO.

CHANNELS CHANNELS OPERATIONAL D'

0F CHANNELS

[9] TRIP OPERABLE CONDITIONS ACTION 5.

LOSS OF POWER a.

4.16 kv Emergency Bus 1/ bus 1/ bus 1/ bus 1, 2, 3, 4##, 5##

34 Undervoltage (Loss of Voltage)

Relay Type IAV53K, l

Device Number 27/59E

[

b.

4.16 kv Emergency Bus 3/ bus 2/ bus 2/ bus 1, 2, 3, 4

,5 35 Undervoltage (Degraded Voltage)

Device Number 27/DV r

8 Bn z

  1. Alarm only.
    1. Required when ESF equipment is required to be OPERABLE.

m TABLE 3.3.3-2 (Continued)

E

'M EMERGENCY CORE COOLING SYSTEM ACTUATION INSTRUMENTATION SETPOINTS 5

Q ALLOWABLE TRIP FUNCTION AND INSTRUMENT NUMBER TRIP SETPOINT VAL *JE C

4.

ADS (continued)

H g.

Bus Power Monitor (B21-K1A, B)

NA NA 5.

LOSS OF POWER a.

4.16 kv Emergency Bus Undervoltage a.

4.16 kv Basis - 3430 t 172 volts (Loss of Voltage) Relay Type LAV53K, b.

120 v Basis - 98 t 4.9 volts Device Number 27/59E c.

[ 1.575 sec. at 0 volts b.

4.16 kv Emergency Bus Undervoltage a.

4.16 kv Basis - 3727 i 9 volts 3727 i 21 volts ti (Degraded Voltage) b.

120 v Basis - 106.5 t 0.25 volts 106.5 t 0.60 volts Device Numbtr 27/DV c.

10 i 0.5 sec. time delay 10 i 1.0 sec. time dela,y y

1 0u N

a

  • This is an inverse time delay voltage relay. The relay will not trip for voltages greater than the trip setpoint.

2 For voltages less than the trip setpoint, allowable values are determined by the inverse time characteristic.

m TABLE 4.3.3-1 (Continued)

EMEP.GENCY CORE COOLING SYSTEM ACTUATION INSTRUMENTATION SURVEILLANCE REQUIREMENTS 5

4 l

9 OPERATIONAL CHANNEL CONDITIONS IN WHICH CHANNEL FUNCTIONAL CHANNEL SURVEILLANCE g

FUNCTIONAL UNIT CHECK TEST CALIBRATION REQUIRED r.a 5.

LOSS OF POWER a.

4.16 kv Emergency Bus NA NA R

1, 2, 3, 4*, 5*

Undervoltage (Loss of Voltage) Relay Type IAV53K, Device Number 27/59E b.

4.16 kv Emergency Bus NA M

R 1, 2, 3, 4*, 5*

ti Undervoltage (Degraded Voltage) Device Number 27/DV Y

u er a

i g

a l

8"

  • Required when ESF equipment is required to be OPERABLE.