1 CRYSTAL RIVER UNIT NO. 3 NRC DOCKET 50-302 ENVIRONMENTAL QUALIFICATION STATUS (SUBMITTAL FOR 10CFR50.49, TER RESPONSE, AND PROVISION OF CURRENT JUSTIFICATIONS FOR CONTINUED OPERATION)

O PREPARED FOR FLORIDA POWER CORPORATION MAY 20, 1983 t NUS CORPORATION 8305270095 830520 PDR ADOCK 05000302 P PDR

TABLE OF CONTENTS 2

Page No.

1.0 INTRODUCTION

1 1.1 Objectives 1 1.2 Background -1 1.3 Summary 4 2.0 ONGOING QUALIFICATION EFFORTS 5 2.1 General Activities 5 2.2 Review Approach and Status for Specific Components 6 3.0 EQUIPMENT REVIEWED FOR ENVIRONMENTAL QUALIFICATION 37 3.1 Procedure for Identifying Equipment in Scope (10 CFR 50.49 (b) (1)) 37 3.2 Electrical Equipment Addressed by 10 CFR 50. 49 (b) (2) 37 APPENDICES APPENDIX A QUALIFICATION STATUS

SUMMARY

SHEETS AND JUSTIFICATIONS FOR CONTINUED OPERATION APPENDIX B ENVIRONMENTAL ZONE DATA SHEETS l

s

1 l.0 INTRODUCTION 2

1.1 Objectives The objectives of this submittal are to:

1. Comply with 10 CFR 50. 49 (g) by: (a) identifying electric equipment important to safety within the scope of 10 CFR 50.49 that is already considered qualified; and (b) submitting corrective action schedules for the remaining electric equipment important to safety within the scope of 10 CFR -
2. Provide respanses to the items of concern outlined in the Technical Evaluation Report as forwarded with the January 11, 1983 Safety Evaluation for Crystal River Unit 3 (TER Categories I.8, II.A, II.B and IV).

~

3. Provide current Justifications for Continued Operation for equipment whose qualification cannot be substantiated;
4. Present the level of compliance of previous submittals with 10 CFR 50.49 paragraphs (a) and (b), as requested by NRC letter dated March 23, 1983.
5. Provide a discussion of the methods used to identify the equipment covered by paragraph 10 CFR 50.49 (b) (2) , as well as any qualification programs for such equipment as requested by NRC letter dated March 23, 1983.

I l.2 Background

! General Design Criterion 4 of Appendix A to 10 CFR 50 establishes the general requirement for environmental qualification of l

,q safety-related equipment. It states in part that " structures, U systems, and components important to safety shall be designed to accommodate the effects of and to be compatible with the 2 environmental conditions associated with normal operation, maintenance, testing, and postulated accidents, including loss-of-coolant accidents". While the Crystal River Unit 3 Nuclear Plant (CR3) was designed to meet General Design Criterion 4, only recently has the NRC developed specific guidelines to implement this requirement for operating reactors.

IEEE 323-1974, "IEEE Standards for Qualifying Class lE Equipment for Nuclear Power Generating Stations", is the current industry standard for environmental qualification of safety-related electrical equipment. This standard was first issued as a trial-use standard, IEEE 323-1971. After substantial revision, the current version was issued in 1974. Both versions of this standard set forth generic requirements for equipment qualification, but the 1974 standard includes specific requirements for aging, margins, and maintaining documentation records that were not included in the 1971 trial-use standard.

The standard was endorsed by the NRC in Regulatory Guide 1.89 for new plants, i.e., existing construction permit applicants.

However, no regulatory guide was ever issued adopting the 1971 IEEE 323 standard.

In 1978, the NRC issued IE Circular 78-08 requesting licensees to examine installed safety-related electrical equipment and assure appropriate documentation of its qualification to function under accident conditions. The following year, IE Bulletin 79-01 was issued requiring licensees to provide written evidence of electrical equipment qualification. Although these documents l requested qualification reviews and information, neither provided specific guidelines for conducting detailed qualification l

i reviews.

l 2

Subsequently, in late 1979 the NRC staff developed definitive criteria for reviewing the environmental qualification of safety-related electrical equipment. The Division of Operating 2 Reactors' " Guidelines for Evaluating Environmental Qualification of Class lE Electrical Equipment in Operating Reactors" (DOR Guidelines) was developed specifically for operating reactors.

In addition, for reactors under licensing review, the NRC issued NUREG-0588, " Interim Staff Position on Environmental Qualification of Safety-Related Equipment".

The intent of the DOR guidelines is not to provide guidelines for implementing either version of IEEE 323 for operating reactors.

The intent is rather to provide a basis for judgements required to confirm that operating reactors are in compliance with General Design Criterion 4. The intent of NUREG-0588 is to implement IEEE 323 for plants under licensing review. It provides a number of NRC staff positions on selected areas of the qualification issue. These positions are divided into two categories.

O (1) Category I positions apply to equipment qualified in accordance with IEEE 323-1974.

(2) Category II positions apply to equipment qualified in accordance with IEEE 323-1971.

After the NRC staff completed their initial review of licensees' responses to IE Bulletin 79-01, IE Bulletin 79-01B was issued in January, 1980 requiring additional qualification information in a specified format for electrical equipment evaluated against the DOR Guidelines. NUREG-0588 was also referenced as a source of l supplemental information to be used with the DOR Guidelines.

On May 23, 1980, the NRC Commissioners issued a Memorandum and Order (CLI-80-21) which endorsed the NRC staff's use of the DOR Guidelines to review operating plants and NUREG-0588 to review

. plants under licensing review. Additional administrative l 3 l

requirements were mandated in amendments to this order (i.e.,

establishing an equipment qualification central file) and the governing criteria for procuring spare parts and replacement 2 parts were established. Florida Power Corporation was not previously licensed to either IEEE-323-1971 OR IEEE-323-1974. In anticipation of the codification of the requirements for environmental qualification, FPC initiated steps to conform to the final rule. FPC chose to wait until the rule was implemented prior to initiating the required changes to the FPC Operating and Design Procedures due to the changes in the content of the proposed final rule.

As a result of the development of detailed environmental data for CR3, which will be required for future work, FPC obtained better specific zonal environmental information which resulted in signi-ficant changes to the list of equipment considered to be within the scope of 10 CFR 50.49(a). These changes, brought about by refinements in specified environmental parameters, revision of the radiation damage cutoff value, review of equipment safety functions, and plant modifications, could cause an inconsistency between previous submittals and that required by 10 CFR 50.49.

The FPC approach in preparing this submittal is discussed briefly in Section 2.2 in an attempt to explain any inconsistency.

1.3 Summary The equipment lists requested by 10 CFR 50.49 (g) and the January 11, 1983 Safety Evaluation are included in Section 2.2. Appendix A provides an item by item response for equipment previously provided to the NRC via the 79-018 submittal (previously provided SCEW sheets).

Chapter 3 discusses the current scope of equipment and describes the methodology for identifying such equipment. The means of addressing associated equipment is also discussed in Chapter 3.

4 l

2.0 ONGOING QUALIFICATION EFFORTS 2.1 General Activities 2 FPC has performed an extensive reevaluation of electrical equip-ment used in the CR3 plant. The evaluation includes the 4 establishment of zones in the plant and defining the environment in each of these zones. A matrix of equipment by zone has been developed and the zones and equipment have been identified as being in a harsh or mild environment.

Engineering design is in progress for those items which have been identified as not having adequate qualification documentation.

Resolution for equipment having qualification documentation defi-ciencies is being handled in one of four ways, replacement, modification, relocation or elimination. The elimination

) alternative includes either eliminating the equipment or eliminating the equipment's safety function.

O A procurement manual has been established for procurement of

. nuclear equipment which addresses the environmental qualification aspects of spare parts or their modification. Two day training sessions have been conducted in the use of the system described by the manual. Major contractor personnel have been trained in use of the manual.

FPC has developed a guide specification for the procurement of environmentally qualified equipment. The specification provides guidance for each section of a procurement specification.

I l

Environmental zone maps have been developed for the CR-3 plant and environmental data sheets have been created for each zone.

The zone maps, data sheets, and the guide specification have been provided to FPC and major contractor's engineers for use in pro-curing items in future purchases of equipment. Training in the use of these guidance documents is being developed.

5

I O A program has been initiated to determine the environmental

' qualification of spare parts presently in stock. Identification 2 of spares which are presently specified for use in harsh environ-ments will be expanded to assure that the existing spares are appropriate for the intended use.

A plant walkdown is being performed during the current outage to verify that the equipment in place'is that which has been listed I as being in the plant. The walkdown will provide verification of identification and location and will provide information on equipment orientation and proximity to high temperature or high J radiation sources.

FPC has also developed a computerized data bank system which will retain current qualification status on equipment within the scope of 10 CFR 50.49. This system was initially loaded with informa-

tion from the latest 79-OlB submittal so it is currently "SCEW sheet" specific. Following this submittal the data bank will 4

duplicate records for SCEW sheets having more than one piece.of i

equipment listed thereon to become " equipment specific." The current long term goal is to integrate this data bank system with l the Qualification Central File,- as well as maintenance and

! installation activities.

l Finally, FPC is evaluating the current surveillance and maintenance programs to determine the need for any changes as a result of electrical equipment qualification requirements or.

commitments.

2.2 Review Approach and Status for Specific Components As pointed out earlier, Florida Power Corporation's ongoing qualification efforts would result in inconsistencies between previous submittals and the list of equipment now required by 10 CFR 50.49 if only a list was submitted. In an effort to 6

alleviate any inconsistencies or incomplete coverage of equip-ment, Florida Power Corporation has taken the steps outlined below. 3 First, coverage of the Technical Evaluation Report (TER) was determined by listing the equipment identified to the NRC which was not subsequently removed from consideration and yet not addressed in the TER.

These items (30) were reviewed to determine if they were considered to be in a mild environment or not. Those that were not in a mild environment were categorized using the categories described in the TER. Items added to a TER category contain the suffix "-A". For example, an item added to category I.B would be labeled as category I.B-A. It should be pointed out that the radiation damage threshold value used in the specification of a mild environment, has been increased f rom 1 x 10 4 to 1x 10 R;5 this change is based on information developed over the past few

,Q years (EPRI Report No. NP-2129). The subject mild environment definition does not apply to components which contain electronic components, Teflon and a few other materials.

Next, all items in categories I.B, II.A, IIB, and IV, including items added, were reviewed and the TER concerns evaluated. If Florida Power Corporation concurred with the TER concerns, corrective action has been identified, and current JCOs submitted as appropriate. (Current JCOs are attached to the associated Qualification Status Summary sheet or referenced thereon). If the concerns could be resolved by documentation currently within our qualification files, there is a discussion sheet attached to the Qualification Status Summary sheets in Appendix A which provides such discussion. Numbers in parentheses are file code references.

The results of this review provide the list of equipment s considered qualified (see Table 2-1) and the list of equipment s requiring corrective action (see Table 2-2).

7

. s

\ \,

~

TABLE 2-1 FLORIDA POWER CORPORATION CRYSTAL RIVER 3 QUALIFIED EQUIPMENT LIST RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS


.. _ = _ - . _ ==_

0001 AHF-1A FAN MOTOR QUALIFIED.

TER CONCERNS RESOLVED.

PREV. PAGE NO. MANUFACTURER MODEL 2-2 WESTINGHOUSE LLA


....-----.----.... __ .. - ____=_- - .....

RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS 0002 AHF-1B FAN MOTOR QUALIFIED.

AHF-lC TER CONCERNS RESOLVED.

PREV. PAGE NO. MANUFACTURER MODEL 03 2-3 WESTINGHOUSE TYPE LLA "

RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION ST TUS 0000 MTMC-7 WALL MOUNTED QUALIFIED FOR CURRENT APPLICATION.

CONTACTOR PREV. PAGE NO. MANUFACTURER MODEL 2-9 ALLEN BRADLEY SERIES K RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS

_= =.--

0015 BSP-1A/IB PUMP MOTOR QUALIFIED FOR CURRENT APPLICATION.

PREV. PAGE NO. MANUFACTURER MODEL 2-23 WESTINGHOUSE TYPE LAC


.....--- ....._- __=_- - _ ......--------...=. = - - - - - - _ -__----

RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS 0017 BSV 4 VALVE MOTOR OPERATOR QUALIFIED FOR CURRENT APPLICATION.

PREV. PAGE NO. MANUFACTURER

  • MODEL 2-24 LIMITORQUE SMB-040

~ ._ __

On i V ..

V) .

U 1

TABLE 2-1 (CONTINUED)

FLORIDA PONER CORPORATION

, CRYSTAL RIVER 3

) QUALIFIED BQUIPMENT LIST I

3

, RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS


-----~~-- __ _

0018 BSV-3 VALVE MOTOR OPERATOR QUALIFIED FOR CURRENT APPLICATION.

d PREV. PAGE NO. MANUFACTURER MODEL 2-24A LIMITORQUE SMB-040


-_ _. -- =-- -_-------------= _ - _ - - - -

RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS 0019 BSV-16/17 VALVE MOTOR OPERATOR QUALIFIED FOR CURRENT APPLICATION.

1 PREV. PAGE NO. MANUFACTURER MODEL 2-25 LIMITORQUE SMB-00-25 U3 ------------~~ ._

RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS 0020 BSV-36/37 VALVE MOTOR OPERATOR QUALIFIED FOR CURRENT APPLICATION.

PREV. PAGE NO. MANUFACTURER MODEL

  • 2-26 LIMITORQUE SMB-000-5

-~~-- -------- _- ___-_- . _ _ _.....-------------__ _

RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS


_ - --- --- - _ _ = -_ -_----

l 0028 CAV-4/5 VALVE MOTOR QUALIFIED FOR CURRENT APPLICATION.

OPERATOR PREV. PAGE NO. MANUFACTURER MODEL

~~------ - .. .....

2-37 LIMITORQUE SMB-000-2

~

~~

RbCURb bbkBbR kD NUMBER DESCRIPTION QbALIFICATION STETUS ~~~~ ~~

0030 CAV-2 SOLENOID VALVE QUALIFIED FOR CURRENT APPLICATION.

PREV. PAGE NO. MANUFACTURER MODEL 2-39 TARGET ROCK 77CC-001

--- ----------~~---~~----------------------- _ -_ -__-------------------------

6.

f" p 5

b I

b (s,s 1

TABLE 2-1 (COWTINUED)

FLORIDA POWER CORPORATION CRYSTAL RIVER 3 j QUALIFIED BOUIPMENT LIST RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS 3

0035 CF-1,3,4 TERMINAL BOX QUALIFIED FOR CURRENT APPLICATION.

PREV. PAGE NO. MANUFACTURER MODEL 2-49 FIELD FABRICATED STATES TYPE NT TERMINAL BLOCKS

__ - _ = = - . _ _ - - . - - - - -

RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS 0042 DHP-1A/lB PUMP MOTOR QUALIFIED FOR CURRENT APPLICATION.

PREV. PAGE NO. MANUFACTURER MODEL Fd 2-55 WESTINGHOUSE TYPE LAC o

RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS 0048 DH-43-FIS FLOW INDICATING QUALIFIED FOR CURRENT APPLICATION.

SWITCH PREV. PAGE NO. MANUFACTURER MODEL 2-60 BARTON 28BA RECORD NUMBER ID NUMBER

  • DESCRIPTION QUALIFICATION STATUS 0049 DH-44-FIS FLOW INDICATING QUALIFIED FOR CURRENT APPLICATION.

SWITCH PREV. PAGE NO. MANUFACTURER P 3 DEL 2-61 BARTON 288A

_____.s-..___. -- __.._____......

RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS I 0050 DH-DPT-3,4 DIFFERENTIAL QUALIFIED FOR CURRENT APPLICATION.

PRESSURE TRANSMITTER PREV. PAGE NO. MANUFACTURER MODEL 2 ... ..-_-_...-__ .____

2-63A ROSEMOUNT 1153B

\ \

N N/

TABLE 2-1 (CONTINUED)

FIARIDA POWER CORPORATION CRYSTAL RIVER 3 QUALIFIED EQUIPMENT LIST RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS 0053 EFP-1 PUMP MOTOR QUALIFIED FOR CURRENT APPLICATION PREV. PAGE NO. MANUFACTURER MODEL 2-66 ELECTRIC MACHINERY 2419-S

__ ___ ...-_-_.---_...--------- _-=- __- -_ _ -.___.....-_____ . ..___-_

RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS 0055 EFV-3/4 VALVE MOTOR QUALIFIED FOR CURRENT APPLICATION.

OPERATOR PREV. PAGE NO. MANUFACTURER MODEL F" 2-67 W LIMITORQUE SMB-000 RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS 0056 EFV-7 & 8 VALVE MOTOR QUALIFIED FOR CURRENT APPLICATION.

OPERATOR PREV. PAGE NO. MANUFACTURER MODEL 2-68 LIMITORQUE SMB-2 RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS 0057 EFV-11/32 VALVE MOTOR QUALIFIED FOR CURRENT APPLICATION.

OPERATOR PREV. PAGE NO. MANUFACTURER MODEL 2-69 LIMITORQUE SMB-0 RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS 0058 EFV-14/33 VALVE MOTOR QUALIFIED FOR CURRENT APPLICATION.

OPERATOR PREV. PAGE NO. MANUFACTURER MODEL 2-70 LIMITORQUE SMB-0 6

d v b

TABLE 2-1 (CONTINUED)

FLORIDA POWER CORPORATION CRYSTAL RIVER 3 QUALIFIED EQUIPMENT LIST RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS 0061 EF-3,4 TERMINAL BOX QUALIFIED FOR CURRENT APPLICATION.

PREV. PAGE NO. MANUFACTURER MODEL 2-73 FIELD FABRICATED STATES TYPE NT

) TERMINAL BLOCKS

-- _ __ -- ----- --......-__ .----- ____ .__=____ _...- .... -.....

RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS

~

b097 POWER AND CONTROL QUALIFIED FOR CURRENT APPLICATION.

CABLE PREV. PAGE NO. MANUFACTURER MODEL Ed 2-122 KERITE FR & HT to


~~------ ___-_ ....---- ----

_____. =----....---..----

RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS j 0098 CONT. & THERMOCOUPLE QUALIFIED FOR CURRENT APPLICATION.

EXTENSION CABLE I

PREV. PAGE NO. MANUFACTURER MODEL 2-123 ROCKBESTOS SILICONE RUBBER

..-- =_ _ - _ - . _- -

-_=-__ ------------------..- =- -- ------

RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS 0099 INST CABLE &THERMO- QUALIFIED FOR CURRENT APPLICATION.

f COUPLE EXTENSION CBL 4

PREV. PAGE NO. MANUFACTURER MODEL 2-124 CONTINENTAL WIRE SILICONE RUBBER INS.

& CABLE COMPANY SCC-2193 RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS l' ___-__--- ---

0100 CONTROL & INSTRUMENT QUALIFIED FOR CURRENT APPLICATION CABLE BY TEST AND ANALYSIS.

PREV. PAGE NO. MANUFACTURER MODEL 2-124A BOSTON INSULATED EPR INSULATION BOS-WIRE AND CABLE CO. TRAD 7 CSPE JACKET

()

\ l D\ l

\

%l  %)

j TABLE 2-1 (CONTINUED)

FLORIDA POWER CORPORATION

]

CRYSTAL RIVER 3 QUALIFIED EQUIPMENT LIST RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS

.. _==

0101 CABLE CONNECTORS QUALIFIED FOR CURRENT APPLICATION.

i PREV. PAGE NO. MANUFACTURER MODEL 2-127 T& B F1

_. _------.....-_____ _ ___ _ ... __ = = _ __ __-_... ......

RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS 0103 TERMINAL LUGS QUALIFIED FOR CURRENT APPLICATION.

! (COMPLETELY METALLIC) i PREV. PAGE NO. MANUFACTURER MODEL Fa 2-129 BURNDY CRIMP TYPE LJ RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS 0062 FWV-14/IS VALVE MOTOR QUALIFIED FOR CURRENT APPLICATION.

OPERATOR PREV. PAGE NO. MANUFACTURER MODEL 2-74 LIMITORQUE SMB-1 RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS 0063 FWV-29/30 VALVE MOTOR QUALIFIED FOR CURRENT APPLICATION.

OPERATOR PREV. PAGE NO. MANUFACTURER MODEL 2-76 LIMITORQUE SMB-4T RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS 0064 FWV 31/32 VALVE MOTOR QUALIFIED FOR CURRENT APPLICATION.

OPERATOR PREV. PAGE NO. MANUFACTURER MODEL 2-77 LIMITORQUE SMB-1

[~ f~ % rh i TABLE 2-1 [ CONTINUED)

FLORIDA PONER CORPORATION CRYSTAL RIVER 3 QUALIFIED EQUIPMENT LIST RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS 0073 FW-22 TERMINAL BOX QUALIFIED FOR CURRENT APPLICATION.

, PREV. PAGE NO. MANUFACTURER MODEL


= --------

i 2-86 FIELD FABRICATED STATES TYPE NT i TERMINAL BLOCKS


= -------------------- -

] RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS 0079 MS-S & 6 TERMINAL BOX QUALIFIED FOR CURRENT APPLICATION.

PREV. PAGE NO. MANUFACTURER MODEL Fa 2-98 FIELD FABRICATED STATES TYPE RT

    • TERMINAL BLOCKS RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS 0082 MS-17 TERMINAL BOX QUALIFIED FOR CURRENT APPLICATION. ,

PREV. PAGE NO. MANUFACTURER MODEL 2-101 FIELD FABRICATED STATES TYPE NT TERMINAL BLOCKS RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS 0083 MS-18 TERMINAL BOX QUALIFIED FOR CURRENT APPLICATION.

1 1

PREV. PAGE NO. MANUFACTURER MODEL 2-102 FIELD FABRICATED STATES TYPE NT TERMINAL BLOCKS

-_ ------------------------------ _------------------- ----------~~--

RECORD NUMBER 10 NUMBER DESCRIPTION QUALIFICATION STATUS 0085 MTMC-3 MOTOR CONTROL CENTER QUALIFIED FOR CURRENT APPLICATION.

PREV. PAGE NO. MANUFACTURER MODEL 2-104 ALLEN BRADLEY BULLETIN 798

b\ , \ [D

\_)

s .

t V

v TABLE 2-1 (CONTINUED)

FLORIDA PONER CORPORATION CRYSTAL RIVER 3 QUALIFIED EQUIPMENT LIST RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS

.-..--....... --. --- ... _=__.

0088 MTMC-7 MOTOR CONTROL CENTER QUALIFIED FOR CURRENT APPLICATION.

PREV. PAGE NO. MANUFACTURER MODEL 2-108 ALLEN BRADLEY BULLETIN 798 RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS 0089 MTBD-2A ELECTRICAL PENETRA- QUALIFIED FOR CURRENT APPLICATION.

TION ASSEMBLY PREV. PAGE NO. MANUFACTURER MODEL ps 2-113 CONAX CANISTER TYPE U1 RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS

.------------ --------. _=- ......--------------

0090 MTBD-2B ELECTRICAL PENETRA- QUALIFIED FOR CURRENT APPLICATION.

TION ASSEMBLY PREV. PAGE NO. MANUFACTURER MODEL 2-114 CONAX CANISTER TYPE RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS 0091 MTBD-2C ELECTRICAL PENETRA- QUALIFIED FOR CURRENT APPLICATION.

TION ASSEMBLY PREV. PAGE NO. MANUFACTURER MODEL 2-115 CONAX ' CANISTER TYPE

.--- --. -...----- .=____ __

RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS 0092 MTBD-8A ELECTRICAL PENETRA- QUALIFIED FOR CURRENT APPLICATION.

TION ASSEMBLY PREV. PAGE NO. MANUFACTURER MODEL 2-116 CONAX CANISTER TYPE 6e

O .

O O I

TABLE 2-1 (CONTINUED)

FIDRIDA POWER CORPORATION CRYSTAL RIVER 3 j QUALIFIED BQUIPMENT LIST 1

RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS 0093 MTBD-8B ELECTRICAL PENETRA- QUALIFIED FOR CURRENT APPLICATION.

TION ASSEMBLY l

PREV. PAGE NO. MANUFACTURER MODEL 2-117 CONAX CANISTER TYPE i

j RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS 0094 MTBD-8C & 8D ELECTRICAL PENETRA- QUALIFIED FOR CURRENT APPLICATION.

TION ASSEMBLY I

PREV. PAGE NO. MANUFAFTURER MODEL F" 2-118 CONAX CANISTER TYPE 04 i RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS 0095 MTBD-9A & 9B ELECTRICAL PENETRA- QUALIFIED FOR CURRENT APPLICATION.

TION ASSEMBLY PREV. PAGE NO. MANUFACTURER MODEL


~ , -----

2-119 CONAX CANISTER TYPE RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS 0096 MTBD-9C & 9D ELECTRICAL PENETRA- QUALIFIED FOR CURRENT APPLICATION.

TION ASSEMBLY PREV. PAGE NO. MANUFACTURER MODEL 2-120 CONAX CANISTER TYPE RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS 0106 TERMINATION QUALIFIED FOR CURRENT APPLICATION.

PROCEDURE-PREV. PAGE NO. MANUFACTURER MODEL 2-132 KERITE 39-69 hD

r r%

(s l

+

[.\ v

._)

TABLE 2-1 (CONFINUED)

FIDRIDA POWER CORPORATION CRYSTAL RIVER 3 QUALIFIED BOUIPMENT LIST RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS 4 __-__.. _....

0108 MUP-IA,lB,1C PUMP MOTOR QUALIFIED FOR CURRENT APPLICATION, PREV. PAGE NO. MANUFACTURER MODEL 1

2-141 WESTINGHOUSE 688.5"S* " CSP" RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STA

=----

0111 MUV-23 & 24 VALVE MOTOR QUALIFIED FOR CURRENT APPLICATION.

OPERATOR PREV. PAGE NO. MANUFACTURER MODEL j 2-143 L MITORQUE SMB-00-25

_- _.- =---- ___ _ _.._.-

RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS 0112 MUV-25 & 26 VALVE MOTOR QUALIFIED FOR CURRENT APPLICATION.

OPERATOR 4

PREV. PAGE NO. MANUFACTURER MODEL 6 2-144 LIMITORQU5 SMB-00-25

=-- _ -----------

RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS 0113 MUV-27 VALVE MOTOR QUALIFIED FOR CURRENT APPLICATION.

OPERATOR PREV. PAGE NO. MANUFACTURER MODEL I 2-145 LIMITORQUE SMB-00-10 1

, -.- ___ --. ___. _ ....... _ . . . . - - - .. _ ____-.... _--___-...._=_ ------

RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS

, ------.....-- --------- -.....___.......- e.

0118 MUV-258 & 259 VALVE MOTOR QUALIFIED FOR CURRENT APPLICATION.
MUV-260 & 261 OPERATOR PREV. PAGE NO. MANUFACTURER MODEL 2-152 LIMITORQUE SMB-000 6

_ _ ___ _ _ _ _ _ _ _ _ _ . _ . _, ____ . _ _ _ - _ _ . .__ .__ _ ,m, h f g

N

\

(/

TABLE 2-1 (CONTINUED)

FIDRIDA PONER CORPORATION CRYSTAL RIVER 3 QUALIFIED EQUIPMENT LIST 1

RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS 0123 MU-23/24 MOTOR STARTER QUALIFIED FOR CURRENT APPLICATION.

MU-25/26 PREV. PAGE NO. MANUFACTURER MODEL 2-157 GOULD I-T-E SERIES 5600

_ _-_.... =

_ -___ ===

RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS 0129 MU-21 TERMINAL BOX QUALIFIED FOR CURRENT APPLICATION.

PREV. PAGE NO. MANUFACTURER MODEL 1 --. ------.... --------.... -.---

hh 2-163 FIELD FABRICATED STATfS TYPE NT TERMINAL BLOCKS

.........-~~.

RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS 0130 MU-22 TERMINAL BOX QUALIFIED FOR CURRENT APPLICATION.

PREV. PAGE NO. MANUFACTURER MODEL 2-164 FIELD FABRICATED STATES TYPE NT TERMINAL BLOCKS

--.-----------------_ ---------------- .__ ==--- _--- --------.

RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS 0131 MU-23-DPT-5,6,7,8 DIFFERENTIAL QUALIFIED FOR CURRENT APPLICATION.

PRESSURE TRANSMITTER PREV. PAGE NO. MANUFACTURER MODEL 2-166A ROSEMOUNT 1153B RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS j 0132 RCV-Il VALVE MOTOR QUALIFIED FOR CURRENT APPLICATION.

OPERATOR PREV. PAGE NO. MANUFACTURER MODEL 2-168 LIMITORQUE

--- =... ------......--.----- _-- .-- ---------------- _....-.........-.. --

6.

v j ..

TABLE 2-1 (CONTINUED)

FLORIDA POWER CORPORATION CRYSTAL RIVER 3 QUALIFIED EQUIPMENT LIST RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS 4 0137 RC-4A34B TEl,4 TEMP. ELEMENT QUALIFIED FOR CURRENT APPLICATION.

RC-5A35B TE1,2,3,4 i

PREV. PAGE NO. MANUFACTURER MODEL 2-174 ROSEMOUNT RTD-177HW RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS 0167 SW-7 TERMINAL BOX QUALIFIED FOR CURRENT APPLICATION.

I PREV. PAGE NO. MANUFACTURER MODEL F" 2-206 FIELD FABRICATED STATES TYPE NT U3 TERMINAL BLOCKS I

RECORD NUMBER ID NUMBuR DESCRIPTION QUALIFICATION STATUS 1 ___ - -_ ---. ...

0168 SW-8 TERMINAL BOX QUALIFIED FOR CURRENT APPLICATION.

PREV. PAGE NO. MANUFACTURER MODEL 2-207 FIELD FABRICATED STATES TYPE NT TERMINAL BLOCKS RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS i

0169 SW-9 TERMINAL BOX QUALIFIED FOR CURRENT APPLICATION.

1 PREV. PAGE NO. MANUFACTURER MODEL 2-208 FIELD FABRICATED STATES TYPE NT TERMINAL BLOCKS RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS 0173 SW-IS TERMINAL BOX QUALIFIED FOR CURRENT APPLICATION.

PREV. PAGE NO. MANUFACTURER MODEL 2bl2 FIELD FABRICATED STATES TYPE NT

- - _ TERMI,NAL -- _.

BLOCKS -____ -- ...-- -------------------------------.-----

1 h$

- ___ . ~ . .- . - .-._ -

p n j ,.

TABLE 2-1 (CONTINUED)

FLORIDA POWER CORPORATION CRYSTAL RIVER 3 QUALIFIED EQUIPMENT LIST RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS

, 0176 WDV-60 VALVE MOTOR OPERATOR QUALIFIED FOR CURRENT APPLICATION.

I r

j PREV. PAGE NO. MANUFACTURER MODEL 2-215 LIMITORQUE SMB-000-5 l

RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS j 0177 WDV-94 VALVE MOTOR OPERATOR QUALIFIED FOR C RRENT APPLICATION.

PREV. PAGE NO. MANUFACTURER MODEL bJ 2-216 LIMITORQUE SMB-000-2 o

RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS

...-------... -_ .-----..... .--.... _=_

0178 WDV-405 VALVE MOTOR OPERATOR QUALIFIED FOR CURRENT APPLICATION.

I 3

PREV. PAGE NO. MANUFACTURER MODEL

2-217 LIMITORQUE SMB-000 1 RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS 0179 WDV-406 VALVE MOTOR OPERATOR QUALIFIED FOR CURRENT APPLICATIOP -

PREV. PAGE NO. MANUFACTUkER MODEL 2-218 LIMITORQUE SMB-000 i

1

RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS 4 0180 WDV-407 VALVE MOTOR OPERATOR QUALIFIED FOR CURRENT APPLICATION, i

l l PREV. PAGE NO. MANUFACTURER MODEL 2-219 LIMITOROUE SMB-000

- - ....---....--........------ =...... ---- - --............... ---------

b he

v .

x s TABLE 2-1 (CONTINUED)

FLORIDA PONE.1 CORPORATION CRYSTAL RIVER 3 QUALIFIED EQUIPMENT LIST RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS 0186 WS-2 TERMINAL BOX QUALIFIED FOR CURRENT APPLICATION.

PREV. PAGE NO. MANUFACTURER MODEL 2-227 FIELD FABRICATE 7 STATES TYPE NT TERMINAL BLOCKS RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS 0187 WS-3 TERMINAL BOX QUALIFIED FOR CURRENT APPLICATION.

PREV. PAGE NO. MANUFACTURER MODEL pa 2-228 FIELD FABRICATED STATES TYPE NT TERMINAL BLOCKS RECORD NUMBER ID NUMBER DESCRIPTION QUALIFICATION STATUS PREV. PAGE NO. MANUFACTURER MODEL

_-_ --_--_-.-.....W.W..---.6....... ___....- -----------' _ --. -

k

_ ._ m - _ _ _ . _ .

( ,

( .

d \

TABLE 2-2 FIDRIDA POWER CORPORATION CRYSTAL RIVER 3 EQUIPMENT REQUIRING CORRECTIVE ACTION RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED 0006 AHV-1B VALVE MOTOR OPERATOR REPLACE MOTOR; REMOVE BRAKES AHV-lC PREV. PAGE NO. MANUFACTURER MODEL 2-5 LIMITORQUE SMB-1-40lH3BC


............--------- --_ _ _ _ = _ -

j RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED 0011 ASV-5 VALVE MOTOR OPERATOR REPLACE MOTOR PREV. PAGE NO. MANUFACTURER MODEL 1 ------........ ......-_----

$$ 2-19 LIMITOROUE SMB-00 f RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED 0012 SV S LOCAL MOTOR STARTER RELOCATE f

PREV. PAGE NO. MANUFACTURER MODEL i 2-20 ALLEN BRADLEY BULLETIN 205 t ...----_......--._.-- _

RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED 0013 AS-1 LOCAL CONTROL RELOCATE.

STATION 4

PREV. PAGE NO. MANUFACTURER MODEL I 2-21 FIELD FABRICATED G.E. TYPE UA202 SW.

] G.E. TYPE UC212 LIGHT RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED

...-= -------.- ... .-- - --- --

0014 AS-1 TERMINAL BOX RELOCATE PREV. PAGE NO. MANUFACTURER MODEL 2-22 FIELD FABRICATED STATES TYPE NT d

TERMINAL BLOCKS


_--....-_-_____. --...--..... . - =__------_-_......-......----....--- - ....------

6.

n

Q r) f

% ,l TABLE 2-2 (CONTINUED)

FLORIDA POWER CORPORATION CHYSTAL RIVER 3 EQUIPMENT REQUIRING CORRECTIVE ACTION RECORD NUMBER ID NUHJER DESCRIITION CORRECTIVE ACTION REQUIRED 0016 BSP-1A & IB LUBRICANT INCORPORATE LUBRICANT ANALYSES RESULTS INTO PM PROGRAM.

PREV. PAGE NO. MANUFACTURER MODEL 2-23A GULF GULF HARMO"Y 68

-- _ _ _ _ _ = ____=_- ._ ___ _.___- ---- ..__-.

RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED 0024 BS-PT-16,17 PRESSURE TRANSMITTER REPLACE.

PREV. PAGE NO. MANUFACTURER MODEL DJ 2-35 L& N 1973-215-2 OJ RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED 0025 BS-90-PT PRESSURE TRANSMITTER (INSTALLATION)

BS-91-PT PREV. PAGE NO. MANUFACTURER MODEL 2-35A ROSEMOUNT 1153

-- .____.-- =-

_= - - - - . . _ _ . ...

RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED 0026 BS-1-dPT 162 FLOW TRANSMITTER REPLACE.

PREV. PAGE NO. MANUFACTURER MODEL 2-35B BAILEY MOTOR CO. BY-8240-A RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED 0027 CAV-1/3 VALVE MOTOR REPLACE.

OPERATOR PREV. PAGE NO. MANUFACTURER MODEL

.___-___-_-_.. ___ __=_ -_-..

2-36 LIMITORQUE SMB-000-2 O

6

,q

  • f {y f

> I

'N, \ \, ,

O -

TABLE 2-2 (CONTINUED)

FLORIDA POWER CORPORATION CRYSTAL RIVER 3 EQUIPMENT REQUIRING CORRECTIVE ACTION RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED 0029 CAV-126 VALVE MOTOR REPLACE.

OPERATOR PREV. PAGE NO. MANUFACTURER MODEL 2-38 LIMITORQUE SMB-000-5 RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED 0188 CA 1,2,3 LOCAL CONTROL REMOVE.

STATION PREV. PAGE NO. MANUFACTURER MODEL bJ 2-40 GENERAL ELECTRIC CO. G.E. TYPE UA202 SW.

G.E. TYPE UC212 LIGHT RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED 0032 CFV-ll/12 VALVE MOTOR REPLACE MOTOR WITH CLASS RH MOTOR.

OPERATION REPLACE LIMIT & TORQUE SWITCHES WITH CONTAINMENT TYPE SWITCHES; ADD GREASE PREV. PAGE NO. MANUFACTURER MODEL RELIEF VALVE AND MOTOR "T" DRAINS.

2-43 LIMITORQUE SMB-000-2 RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIP.ED 0033 CFV-15/16 VALVE MOTOR REPLACE MOTOR WITH CLASS RH MOTOR.

OPERATION REPLACE LIMIT & TORQUE SWITCHES WITH CONTAINMENT TYPE SWITCHES: ADD GREASE PREV. PAGE NO. MANUFACTURER MODEL RELIEF VALVE AND MOTOR "T" DRAINS.

2-44 LIMITORQUb SMB 000-2 RECORD NUMBER ID NUMBER DESCRIPTION . CORRECTIVE ACTION REQUIRED 0034 CFV-25,26,29,42 SOLENOID VALVE REPLACE.

PREV. PAGE NO. MANUFACTURER MODEL 2-45 ASCO THB 830281R I

7" \ , y l I f )

U 4

% J TABLE 2-2 (CONTINUED)

FIDRIDA POWER CORPORATION CRYSTAL RIVER 3 BQUIPMENT REQUIRING CORRECTIVE ACTION RECORD NUMBER ID NL?RER DESCRIPTION CORRECTIVE ACTION REQUIRED 0189 CF 1,5,6 LOCAL CONTROL REMOVE.

STATION PREV. PAGE NO. MANUFACTURER MODEL 2-47 GENERAL ELECTRIC CO. G.E. TYPE UA202 SW.

G.E. TYPE UC212 LIGHT RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED 0043 DHP-1A & IB LUBRICANT INCORPORATE LUBRICANT ANALYSES RESULTS INTO PM PROGRAM.

PREV. PAGE NO. MANUFACTURER MODEL h3 2-55A GULF GULF HARMONY 68 Un RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED 0044 DHV-5/6 VALVE MOTOR REPLACE MOTOR.

OPERATOR PREV. PAGE NO. MANUFACTURER MODEL 2-56 LIMITORQUE SMB-3-100 RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED

_--_..__..... _. _=-

.. J 0046 DHV-34/35 VALVE MOTOR C; PLACE MOTOR.

OPERATOR PREV. PAGE NO. MANUFACTURER MODEL f 2-58 LIMITORQUE SMB-2-40

.= ------ - -- -.._.._ _...._.-- - _ - - --..._.....

RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED 0047 DHV-110/111 VALVE MOTOR REPLACE MOTOR OPERATOR PREV. PAGE NO. MANUFACTURER MODEL 2-59 LIMITORQUE SMB-1-25

-___...._..._-_..........___. =- =- ...

9 t

4 -

s

)

b.

(O[) -

(w)  %)

TABLR 2-2 (CONTINUED),

FLORIDA' POWER CORPORATION CRYSTAL RIVER 3 EQUIPMENT REQUIRING CORRECTIVE ACTION 1

e i

RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED 0051 DH-DPT-38 DIFFERENTIAL REPLACE.

PRESSURE TRANSMITTER a

PREV. PAGE NO. MANUFACTURER MODEL 2-64 BM CO. BY8240X-A RECORP NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED 0054 EFP-1 LUBRICANT INCORPORATE LUBRICANT ANALYSES RESULTS INTO PM PROGRAM.

PREV. PAGE NO. MANUFACTURER MODEL bJ 2 66A GULF GULF HARMONY 68 j Ch RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED 0059 EFV-ll,14 MOTOR STARTER. RELOCATE.

32, 6 33 4

PREV. PAGE NO. MANUFACTURER MODEL 2-71 ALLEN BRADLEY BULLETIN 205 RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED 9060 EF-3,4 LOCAL CONTROL RELOCATE.

STATION PREV. PAGE NO. MANUFACTURER MODEL 2-72 FIELD FABRICATED G.E. TYPE UA202 SW.

G.E. TYPE UC212 LIGHT RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED 0102 TERMINAL BLOCKS REPLACE.

PREV. PAGE NO. MANUFACTURER MODEL 2-128 KULKA 7TB & STB

c+s g s s

\

O -/

) h TABLE 2-2 (CONTINUED)

FLORIDA POWER CORPORATION CRYSTAL RIVER 3 EQUIPMENT REQUIRING CORRECTIVE ACTION RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED 0065 FWV-33,34,35 & 36 VALVE MOTOR REPLACE MOTORS ON FWV-34 AND FWV-35.

OPERATOR PREV. PAGE NO. MANUFACTURER MODEL 2-78 LIMITORQUE SMB-0

__--...._..___---___- ....--........--____ =- __

__=_____

RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED 0067 FWV-33,34,35,36 LOCAL MOTOR DURING EPIC INSTALLATION REMOVE FWV 33 &

STARTER FWV 363 RELOCATE FWV 34 & FWV 35.

PREV. PAGE NO. MANUFACTURER MODEL ba 2-80 ALLEN BRADLEY BULLETIN 205 4

RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED

--_-...._ .___=

0069 FWV-161,162 LOCAL MOTOR STARTER REMOVE DURING EPIC INSTALLATION.

PREV. PAGE NO. MANUFACTURER MODEL 2-81 ALLEN BRADLEY BULLETIN 205 RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED

-_...-..... . - _..-_-_ _ _-=

0069 FW-5,6 LOCAL CONTROL REMOVE.

STATION PREV. PAGE NO. MANUFACTURER MODEL 2-82 FIELD FABdICATED G.E. TYPE UA202 SW.

G.E. TYPE UC212 LIGil?

RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED 0070 FW-11,12 LOCAL CONTROL REMOVE DURING EPIC INSTALLATION.

STATION PREV. PAGE NO. MANUFACTURER MODEL 2-83 FIELD FABRICATED G.E. TYPE UA202 SW.

G.E. TYPE UC212 LIGIIT

\/ %  % ,/

TABLE 2-2 (CONTINUED)

FLORIDA PONER CORPORATION CRYSTAL RIVER 3 EQUIPMENT REQUIRING CORRECTIVE ACTION RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED 0071 FW-3 & 4 TERMINAL BOX QUALIFIED FOR CURRENT APPLICATION.

PREV. PAGE NO. MANUFACTURER MODEL 2-84 FIELD FABRICATED STATES TYPE NT

_a_----_.-...... =----......... --..

RECORD NUMBER ID NUMBER DESCRIPTIOi4 CORRECTIVE ACTION REQUIRED 0074 FW-312-FE FLOW ELEMENT (INSTALLATION)

FW-313-FE PREV. PAGE NO. MAltUFACTURER MODEL

$$ 2-87A CONTROLATION RECORD NUMBER ID NUMB R DESCRIPTkON CORRECTIVE ACTION REQUIRED

._ _---- - =-- _ . -.

0075 MSV-55 & 56 VALVE MOTOR REPLACE MOTO2 OPERATOR PREV. PAGE NO. MANUFACTURER MODEL 2-88 LIMITORQUE SMB-0-15 RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED 0076 MSV-55 & 56 LOCAL MOTOR RELOCATE.

STARTER PREV. PAGE NO. MANUFACTURER MODEL 2-89 ALLEN BRADLEY BULLETIN 205 RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED 0077 MSV-411,412, SOLENOID VALVE REPLACE VALVE PARTS 413,414-SV1,2,3 PREV. PAGE NO. MANUFACTURER MODEL 2-90 ASCO HT8320A34V,A20V 6.

t) - w

) v. )

TABLE 2-2 (OONTINUED)

FIDRIDA PONER CORPORATION CRYSTAL RIVER 3 EQUIPMENT REQUIRING CORRBCTIVE ACTION i

RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED

____ _ = _ - - - --

l 0078 MS-5 & 6 LOCAL CONTROL RELOCATE.

! STATION PREV. PAGE NO. MANUFACTURER MODEL 2-93 FIELD FABRICATED G.E. TYPE UA202 SW.

G.E. TYPE UC212 LIGHT

....._........__. -_ =

__ n==_

RECORD NUMBER ID taUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED Ob84 MS-92-PSI & 2 PRESSURE SNITCH REPLACE.

PREV. PAGE NO. MANUFACTURER MODEL i bJ 2-103 STATIC-O-RING 9R2YY5NCXJ W

-=_ ..

.... - _ __=_

RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED i 0104 TERMINATION REPLACE.

PROCEDURE PREV. PAGE NO. MANUFACTURER MODEL 2-130 KERITE T-INS-HT RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED 0105 TERMINATION REPLACE.

PROCEDURE PREV. PAGE NO. MANUFACTURER MODEL 2-131 KERITE T-5NS-HT

.._...._...=_--.=- -

RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED

_.._ .___=

0107 SPLICE TERMINAL REPLACE.

PREV. PAGE NO. MANUFACTURER MODEL I

2-138 BURNDY INSULINK

O .

J O I

TABLE 2-2 (CONTIIPJED)

FIDRIDA PONER CORPORATION CRYSTAL RIVER 3 EQUIPNENT REQUIRING CORRBCTIVE ACTION RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED 0109 MUP-1A,lB & IC LUBRICANT INCORPORATE LUBRICANT ANALYSES RESULTS INTO PM PROGRAM.

PREV. PAGE NO. MANUFACTURER MODEL 2-141A GULF GULF CREST 32

. - - = ___.

RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED 0110 MUV-18 VALVE MOTOR REPLACE MOTOR.

OPERATOR PREV. PAGE NO.

MANUFACTURER MODEL LJ 2-142 LIMITORQUE SMB-50 0

RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED 0114 MUV-40 & 41 VALVE MOTOR REPLACE MOTOR.

OPERATOR PREV. PAGE NO. MANUFACTURER MOTEL 2-147 u MITORQUE SMB-00-5 RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED 0120 MUV-64-SVI,2,3,4,5,6 SOLENOID VALVE REPLACE.

PREV. PAGE NO. MANUFACTURER MODEL

. 2-154 ASCO HT831657,HT8211B54 F78211B33 RECURD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED

== ..

0121 MUV-253/SVl/SV2 SOLENOID VALVE REPLACE.

PREV. PAGE NO. MANUFACTURER MODEL 2-155 ASCO HT831655 FOR SV1 8320A38 FOR SV2 b

__ _ .- = . . _ - = - - - - - - - . -

x .

v TABLE 2-2 (CONTINUED)

FLORIDA POWER CORPORATION CRYSTAL RIVER 3 500IPMENT REQUIRING CORRBCTIVE ACTION 4

1 RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED l _____._...... ._-__ ______..... ______

0122 MU-25-SV SOLENOID VALVE REPLACE.

l i

PREV. PAGE NO. MANUFACTURER MODEL 2-156 ASCO 8320 A 92 RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED 0124 MU-4 & MU-5 LOCAL CONTROL REPLACE.

STATION PREV. PAGE NO. MANUFACTURER MODEL LJ 2-158 FIELD FABRICATED G.E. TYPE UE202 SW.

! Fd G.E. TYPE UC212 LIGHT ,

RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED i

0126 MU-16 LOCAL CONTROL REMOVE.

STATION PREV. PAGE NO. MANUFACTURER MODEL 2-160 FIELD FABRICATED G.E. TYPE UA202 SN.

G.E. TYPE UC212 LIGHT RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED 0133 RC-3A-PT2,RC-3A-PTl PRESSURE TRANSMITTER REPLACE.

RC-38-PT1,RC-3B-PT2 PREV. PAGE NO. MANUFACTURER MODEL 2-170 ROSEMOUNT 1152 GP RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED j --

0134 RC-3A-PT3,RC-3A-PT4 PRESSURE TRANSMITTER REPLACE. I RC-3B-PT3 PREV. PAGE NO. MANUFACTURER MODEL 2-171 FOXBORO EllGHINM2 j -

b

u i

a TABLE 2-2 (CONTINUED)

FIDRIDA PONER CORPORATION CRYSTAL RIVER 3 EQUIPMENT REQUIRIWG CORRECTIVE ACTION i

1 RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED 0135 RC-PT-132 PRESSURE TRANSMITTER REPLACE.

j PREV. PAGE NO. MANUFACTURER MODEL

_____ -____... _=- __ _.

2-172 ROSEMOUNT 1152 GP

. . ____....=

RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED

.____..__._-_ ._____.-- = _ - ..

0136 RC-14A-DPT-1, DPT-2 FLOW TRANSMITTER REPLACE.

RC-148-DPT-1, DPT-2 PREV. PAGE NO. MANUFACTURER MODEL

[j 2-173 BM CO. BY 3241-A RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED 1 0138 RC-1-LT 1,2,3 LEVEL TRANSMITTER REPLACE.

PREV. PAGE NO. MANUFACTURER MODEL 2-175 ROSEMOUNT 1152 DP

--- ==_ _-_

RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED

j. ________ . _ .___. --

0144 SPIA-LT1 LEVEL TRANSMITTERS REPLACE.

SPIB-LTl PREV. PAGE NO. MANUFACTURER MODEL 2-183 BM CO. BY8B41X-A

_...._-__..._.--- --_ _ _ - _ . . . - - - _ _ _ ---- =--

_==__- ---_-_.._.

RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED

...___.._____ ...______ -_ =---

0145 SPIA-LT2,3 I.EVEL TRANSMITTERS REPLACE.

SPIB-LT2,3 I

PREV. PAGE NO. MANUFACTUdER MODEL 2-184 BM CO. BY8B41X-A

___ __________ __--- _ . --- _.... ===- --

t 6

U) s)

/

(.

O

  • TABLE 2-2 (CONTINUED)

FLORIDA POttBR CORPORATION CRYSTAL RIVER 3 EQUIPMENT REQUIRING CORRECTIVE ACTION RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED 0147 SPIA-LT4,5 LEVEL TRANSMITTER REPLACE.

SPIB-LT4,5 PREV. PAGE NO. MANUFACTURER MODEL 2-185 BM CO. BY8841X-A RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED 0149 SP-6A-PT3,4 PRESSURE TRANSMITTER REPLACE.

SP-6B-PT3,4 PREV. PAGE NO. MANUFACTURER MODEL ca 2-186A FOXBORO 1153 oJ RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED 0150 SP-8A-DPT1, 2, & 3 DIFFERENTIAL REPLACE.

SP-8B-DPT1, 2, & 3 PRESSURE TRANSMITTER PREV. PAGE NO. MANUFACTURER MODEL 2-187 BM CO. BY 6241-A RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED 0155 SWV-47,48,49 & 50 SOLENOID VALVE REPLACE.

PREV. PAGE NO. MANUFACTURER MODEL 2-191 ASCO LB8321AB RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED 0156 SWV-79,80,81,82,83 SOLENOID VALVE REPLACE.

84,85 & 86 PREV. PAGE NO. MANUFACTURER MODEL 2-192 ASCO LB8321A8


..........--------......---------- ............-- _ _- _=__ = - - _ - ...-....-..

t

- - - - _ - - - ~ - .- . __ -_ _ .- . _ _ . - -

TABLE 2-2 (CONTINUED)

I FLORIDA POWER CORPORATION 1

CRYSTAL RIVER 3 EQUIPMENT REQUIRING CORRECTIVE ACTION RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED 0157 SWV-119 & SOLENOID VALVE REPLACE.

110-SJ-3/4

, PREV. PAGE NO. MANUFACTURER MODEL 2-193 ASCO HT831655 RECORD NUMBER ID NUMBER DESCRIPTION- CORRECTIVE ACTION REQUIRED 0160 SW.7 LOCAL CONTROL RELOCATE. ,

STATION i

i PREV. PAGE NO. MANUFACTURER MODEL LJ 2-198 FIELD FABRICATED G.E. TYPE UA202 SW.

G.E. TYPE UC212 LIGHT ,


_ -=- - ___ = - - - - - - - - _ - -  !

RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED 0161 SW-9 LOCAL CONTROL RELOCATE.

STATION i PREV. PAGE NO. MANUFACTURER MODEL j

, 2-200 FIELD FABRICATED G.E. TYPE UA202 SW.

4 G.E. TYPE UC212 LIGHT RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED


.....-- --------- =  :--

0166 SW-6 TERMINAL BOX REPLACE.

PREV. PAGE NO. MANUFACTURER MODEL

! 2-205 FIELD FABRICATED STATES TYPE NT TERMINAL BLOCKS j . - - _ . . . . - - - ==---

j RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED j 0172 SW-14 TERMINAL BOX REPLACE.

PREV. PAGE NO. MANUFACTURER MODEL


...= ------. ..--

2-211 FIELD FABRICATED STATES TYPE NT TERMINAL BLOCKS a

....-------- - ...-- ==...---------.....

l

, 6.

[ }

V,O b V TABLE 2-2 (CONTINUED)

FIDRIDA POWER CORPORATION CMYSTAL RIVER 3 EQUIPNENT REQUIRING CORRBCTIVE ACTION RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED

..... _ .____ .._______ .....______ ........ =.____

0190 SW 6 LOCAL CONTROL RELOCATE.

STATION PREV. PAGE NO. MANUFACTURER MODEL 2-197 GENERAL ELECTRIC CO. G.E. TYPE UA202 SW.

G.E. TYPE UC212 LIGHT RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED 0175 WDV-3 VALVE MOTOR REPLACE MOTOR.

OPERATOR PREV. PAGE NO. MANUFACTURER MODEL La 2-214 LIMITORQUE SMB-000-2 U1 RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED 0181 WDV-4 SOLENOID VALVE REPLACE.

PREV. PAGE NO. MANUFACTURER MODEL 2-220 ASCO 8320A20 RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED 0182 WDV-61 & 62 SOLENOID VALVE REPLACE.

PREV. PAGE NO. MANUFACTURER MODEL

, 2-221 ASCO 8320A20 RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED 0183 WD-3 TERMINAL BOX REPLACE.

PREV. PAGE NO. MANUFACTURER MODEL 2-223 FIEI.D FABRICATED STATES TYPE NT TERMINAL 3 LOCKS 6.

_ m _ _ . _ _

v v D'

, TABLE 2-2 (CONTINUED)

FLORIDA POWER CORPORATION CRYSTAL RIVER 3 EQUIPMENT REQUIRING CORRECTIVE ACTION RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED 0184 WD-300-LT, WD-301-LT TRANSMITTER (INSTALLATION)

WD-302-LT, WD-303-LT PREV. PAGE NO. MANUFACTURER MODEL 2-224B DELAVAL (GEMS) AND XM-54854 CABLE CO. XM-54852

___ =__=-_=_= _ - _=__ __=_- ..

RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED 0192 WD 1 LOCAL CONTROL RELOCATE.

STATION PREV. PAGE NO. MANUFACTURER MODEL LJ 2-222 GENERAL ELECTRIC CO. G.E. TYPE UA202 SW.

Ch G.E. TYPE UC212 LIGHT


------ -= - ---- ......-_ --- -. -..---

RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED 0185 WSV-3,4,5, & 6 SOLENOID VALVE REPLACE.

PREV. PAGE NO. MANUFACTURER MODEL 2-225 ASCO 8317A29 RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED 0193 WS 1,2,3,4 LOCAL CONTROL REMOVE.

STATION PREV. PAGE NO. MANUFACTURER MODEL 2-226 GENERAL ELECTRIC CO. G.E. TYPE UA202 SW.

G.E. TYPE UC212 LIGHT


.. . _-....... _ .... =- =- ..___ __--- -- -...-.

RECORD NUMBER ID NUMBER DESCRIPTION CORRECTIVE ACTION REQUIRED

---_ _ __ .....-... --- = =___- ...--.- _-_----...

PREV. PAGE NO. MANUFACTURER MODEL

--... 6- -. " = . . . . . . . . . - - - - . . . - - _ .. ...--e.---...-m.-....----.---- _=_= ..--...es............--e.

I I

e ' Oe

n 3.0 EQUIPMENT REVIEWED FOR ENVIRONMENTAL QUALIFICATION a

3.1 Procedure for Identifying Equipment in Scope 10CFR50. 49 (b) (1)

The safety-related electrical equipment required to safely achieve cold shutdown is based on the list of systems considered standard for B&W PWR reactors received from the NRC via tele-copier on 10/17/80 (refer to Section I.5 of Volume 2 of the Environmental Qualification of Class IE Equipment Report for IEB 79-018). Using the subject list, system flow diagrams and instrument drawings were reviewed to identify the actual flow loop components required to remain operational to assure proper system function for safe plant shutdown in the event of a LOCA of HELB. The identification of required electrical power distribu-tion equipment was then based on the individual power requirements of the required system components. Electrical elementary and block diagrams were used to identify specific electrical components.

3.2 Electrical Equipment Addressed by 10CRF 50. 49 (b) (2)

Non-safety-related electrical equipment whose failure could impact safe shutdown operation in the event of a LOCA or HELB was determined from the Plant Emergency Operating Procedures. These procedures were reviewed to identify components whose environ-mentally induced failure could result in providing misleading information to the plant operators; these components were then considered to be necessary to meet the qualification requirements of IE Bulletin 79-OlB and the equipment was either removed from the Emergency Procedures, or clarifying notes were added to refer the operator to alternate safety grade measurements (see Section 3 of Volume 2 of the Environmental Qualification of Class IE l Equipment Report for IEB 79-018).

f3 37

3.3 Compliance of Previous Submittals

By letter dated March 23, 1983, the NRC requested Florida Power Corporation to describe the level of compliance of previous submittals with 10 CFR 50.49.

All previous submittals comply with 10 CFR 50.49 except that those devices included in 10 CFR 50.49 paragraph (b) (2) were determined as requested by the original NRC SER (discussed in section 3.2). This submittal is based on previous submittals and hence carries the same icvel of compliance.

O d

O 38

APPENDIX A 3 During the TER review, Qualification Status Summary Sheets were completed and are included herein. The results of the review provide:

1. The list of equipment considered qualified;
2. The list of equipment requiring corrective actions (hence requiring justification for continued operation); and
3. Identification of equipment no longer within the scope of 10 CFR 50.49.

Current justifications for continued operation are also provided herein for items requiring such.

Two " areas" are addressed throughout Appendix A by the generic discussions below.

LUBRICANTS Title 10, Code of Federal Regulations, Part 50.49, provides the legal basis for the equipment to be considered as within the scope of the rule. In particular, paragraph (k) states that:

l

" Applicants for and holders of operating licenses are not

required to requalify electrical equipment important to safety in accordance with the provisions of this section if the Commission has previously required qualification of that equipment in accor-dance with " Guidelines for Evaluating Environmental Qualification l of Class IE Electrical Equipment in Operating Reactors," November f

1979 (DOR Guidelines) . . . ."

O A-1

Since Florida Power Corporation has been required to qualify the electrical equipment at CR3 in accordance with the referenced DOR 2 Guidelines, and no explicit requirement for consideration of lubricants is specified therein, they are being addressed from two distinct approaches.

As part of the CR3 preventative maintenance program, Procedure PM-133 identifies the lubrication frequencies and the lubricants which are based on manufacturer's recommendations. Furthermore, lubricants, which are used in safety-related equipment, are pur-chased under the Safety-Related Catalog Purchase system using a Catalog Evaluation Sheet.

To supplement the above activity, an investigation of all lubri-cants used in Class lE equipment is ongoing; the aim of this study is to determine if the lubricants are susceptible to the respective environmental conditions. The results of the investigation will be a documented analysis of lubricants

(-

~ acceptable for use in the specified environment and recommendations for replacement of those which are unacceptable for the specified conditions. The analysis results will be incorporated into the PM program.

In summary, it is the position of Florida Power Corporation that lubricants should be controlled as part of a preventative main-tenance program which includes specifications based on electrical equipment vendor recommendations and documented evidence of acceptability for the specified environment.

STATES TYPE NT TERMINAL BLOCKS Non-metallic materials used in the construction of Multi-Amp, States Co. terminal blocks are General Purpose Phenolic (Durez

  1. 791) and Polypropylene (RTP 150); these materials have been O

A-2

evaluated for their suitability in the specified environment for a desired service life of 40 years, and the results of the evalu-ation are summarized below. 4 The Micro-switch Engineering Report No. LTR-15027-1 submitted by f Hooker Chemical, Durez Division contains an evaluation of Durez
  1. 791 material temperature / life expectancy. Arrhenius metholodogy l

was used to describe the temperature dependence of the velocity coefficient of a chemical reaction to approximate the relation-ship between material life and temperature. It should be noted that parameters (time and temperature) were applied to establish failure criteria relative to flexual and impact strengths.

Dielectric property of the material remained within acceptable levels without any failure. The approximate material life at ambient temperature is in excess of the 40 year plant life, and therefore the Durez #791 material exceeds performance require-

ments.

- The Micro-switch Engineering Report LTR-15027-1 also provides radiation qualification test data for Phenolic materials. The materials tested were not exactly Durez #791, but they were of the same general purpose compounds. Durez #791 is a general

. purpose phenolic filled with wood flour as the main ingredient.

The report demonstrated similarity of materials with respect to comparable reactions to radiation. It was concluded that a i

material exposure to a TID of 1.3 x 10 8 rads caused the Phenolic to be brittle, but did not affect the performance properties of the component. A qualification program of Multi-Amp, States Co.

included a test for terminal blocks to TID values of 2.2 x 108 rads, but no documentation is available at this time.

Heat stable Polypropylene material has a U.L. temperature index of 115 C (Allen-Bradley Co., Bulletin 798 Control Center - Serial No. 967929 Non-Metallic Component List). The U.L. temperature index is considered the maximum temperature at which the material can be used continuously. An article ("A New Temperature Index:

,O G

A-3

. _ _ . - . . ~ . . . . _ . _ . . _ _ _ . ___ __ _ _ ._. _ _ _ _ _ _ _ _ _ .

(^\ Who Needs It"), published September 1970 in Modern Plastics discusses the index and how it was established. The temperature index is the point where the property of impact strength, tensile strength and dielectric strength is reduced to one half of its new value at the conclusion of 5 x 10 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />. Using the 10 C rule it was concluded that the approximate life of the Polypropylene material is in excess of 40 years.

Based on information provided in the document by J. F. Kirsher and R. E. Bowman, " Effects of Radiation on Materials and Components", Reinholf Publishing Corp. (1964), radiation threshold values for polyethylene, which are believed to be comparable or lower than those of Polypropylene, are in excess of 1.7 x 107 rads for the properties which may be of importance for the particular application in terminal blocks.

In summary, the non-metallic materials used in the construction of Multi-Amp, States Co. terminal blocks were evaluated for their suitability in the specified environment for a desired service life of 40 years. The States Co. conducted qualification tests to meet requirements of IEEE 323-1974, but no data or test results are known or published. Several independent analyses were conducted to determine the equipment qualification and it is expected that these results, when released, would only confirm the results of these analyses. Information provided by the manu-I facturer indicates that the terminal blocks were successfully tested under postulated environmental conditions of DBE.

Terminal blocks in several locations at CR3 (SW-6 & 14; WD-3) l will be exposed to higher radiation doses during the equipment service life than the radiation threshold value of Polypropylene material. These terminal blocks are scheduled for relocation to a less hostile environment prior to November, 1985.

l l

C N

j A-4 l

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS

~

ID NUMBER: AHF-1A RECORD NUMBER: 0001 SCEW PAGE NUMBER: 2-2 a

DESCRIPTION: FAN MOTOR LOCATION:

CONTAINMENT ELEV. 119 MANUFACTURER: WESTINGHOUSE TER EQUIPMENT NO.:

62 MODEL: LLA o TER CATEGORY:

II.A SYSTEM: AH ZONE LOCATION:

39 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL
2. EQUIP VS TEST SPECIMEN
3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED QUALIFICATION STATUS:

QUALIFIED.

TER CONCERNS RESOLVED.

l CORRECTIVE ACTION:

NOT APPLICABLE.

i l

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

l JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

O A-5 l

t

i i

DISCUSSION ON O AHF-1A, AHF-1B, AHF-lc

! Records 0001, 0002 2 There is adequate documentation in the FPC Qualification File to l resolve the concerns expressed in the TER.

l- By letter to FPC (W120-3VC-001) , Westinghouse has indicated that

[ the Reactor Containment fan coolers (RCFC) in use at Crystal River Unit 3 do include the motor heat exchanger. This corres-i pondence also indicates the form wound motor insulation system is Class F (National Electric Manufacturing Association rated total.

l temperature at 155 C) thermalastic epoxy. Furthermore the design I

of these units is such that the motor environment is essentially a " closed system" and will not mix with the containment ambient, this means that plateout of p emitters on stator insulation is not a concern. (Further, it should be noted that this concern is not covered by IEB 79-01B, i.e., FPC should not have been evaluated against this criteria during the TER evaluations). The l Westinghouse correspondence also indicates WCAP 7829 is -l applicable to the thermalastic epoxy insulation in the RCFCs.

i This WCAP sufficiently documents preaging and no further aging analysis will be provided.

i l

I i

  • 4
O A-6

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS

("% ID NUMBER: AHF-1B RECORD NUMBER: 0002 V AHF-lC SCEW PAGE NUMBER: 2-3 ,

DESCRIPTION: FAN MOTOR LOCATION:

CONTAINMENT ELEV. 103'-9" MANUFACTURER: WESTINGHOUSE TER EQUIPMENT NO.:

63 MODEL: TYPE LLA TER CATEGORY:

II.A SYSTEM: AH ZONE LOCATION:

38 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL
2. EQUIP VS TEST SPECIMEN
3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED O

QUALIFICATION STATUS:

QUALIFIED.

TER CONCERNS RESOLVED.

SEE DISCUSSION FOR AHF-1A, RECORD 0001.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

! JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

A-7

FLORIDA PONER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: AHF-1A,lB & 1C RECORD NUMBER: 0003 SCEW PAGE NUMBER: 2-3A 2

DESCRIPTION: LUBRICANT LOCATION:

CONTAINMENT ELEV. 103'-9" AND 119' MANUFACTURER: GULF TER EQUIPMENT NO.:

63 MODEL: HIGH TEMPERATURE TER CATEGORY:

II.A SYSTEM: AH ZONE LOCATION:

38/39 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL
2. EQUIP VS TEST SPECIMEN
3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED O

QUALIFICATION STATUS:

ADDRESSED GENERICALLY VIA PM PROGRAM (PM-133). SEE APPENDIX A.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

O A-8

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS N ID NUMBER: AHF-15A RECORD NUMBER: 0004 s AHF-15B SCEW PAGE NUMBER: 2-4 a

DESCRIPTION: FAN MOTOR LOCATION:

AUXILIARY BLDG ELEV. 95 MANUFACTURER: CENTURY ELECTRIC TER EQUIPMENT NO.:

65 MODEL: SC/80T TER CATEGORY:

II.A SYSTEM: AH ZONE LOCATION:

11 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL O

QUALIFICATION STATUS:

NOT IN SCOPE. SUBSEQUENT REVIEW SHOWS THESE ITEMS ARE LOCATED IN A MILD ENVIRONMENT. (ENVIRONMENTAL ZONE INDICATED ABOVE.) SEE SECTION 2.2 DISCUSSION.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

A-9 i

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: AHF-15A & 15B RECORD NUMBER: 0005

(

SCEW PAGE NUMBER: 2-4A 2

DESCRIPTION: LUBRICANT LOCATION:

AUXILIARY BLDG ELEV. 95' MANUFACTURER: GULF TER EQUIPMENT NO.:

65 MODEL: HIGH TEMPERATURE TER CATEGORY:

II.A SYSTEM: AH ZONE LOCATION:

11 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL O

QUALIFICATION STATUS:

NOT IN SCOPE. SUBSEQUENT REVIEW SHOWS THESE ITEMS ARE LOCATED IN A MILD ENVIRONMENT. (ENVIRONMENTAL ZONE INDICATED ABOVE) SEE SECTION 2.2 DISCUSSION.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

O A-10

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: AHV-1B RECORD NUMBER: 0006

('

t AHV-lC SCEW PAGE NUMBER: 2-5 a

DESCRIPTION: VALVE MOTOR OPERATOR LOCATION:

CONTAINMENT ELEV.119 MANUFACTURER: LIMITORQUE TER EQUIPMENT NO.:

06 MODEL: SMB-1-40lH3BC TER CATEGORY:

II.A SYSTEM: AH ZONE LOCATION:

39 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL
2. EQUIP VS TEST SPECIMEN
3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED
10. RADIATION EXPOSURE O

QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS. SEE DISCUSSION ATTACHED.

CORRECTIVE ACTION:

REPLACE MOTOR; REMOVE BRAKES CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER 1985 i

MAR NUMBER: 82-05-24-06 JUSTIFICATION FOR CONTINUED OPERATION:

SEE ATTACHED.

A-ll

DISCUSSION ON AHV-1B, AHV-lC Record 0006 2 Correspondence from Limitorque (L200-3VC-007) indicated that Qualification Report 600198 plus Addendum (L200-3TR-005) apply to these actuators. A walkdown was conducted and the results (1200-WW-001) show these actuators have Reliance motors with insulation Class H. These are 3 phase, 460 volt motors. Because the radiation resistance of Class H insulation is uncertain, the vendor was again contacted and requested to identify activities required to upgrade these actuators such that Qualification Report 600456 (L200-3TR-001) would apply, thereby ensuring radi-ation would not be a concern. The vendor response (L200-3VC-010) indicates motor and brake assembly replacement with Reliance RH insulated motors without brakes will be required.

O O

A-12

, JUSTIFICATION FOR CONTINUED OPERATION for AHV-1B and AHV-lC 3 TER Item 6 References

1) Technical Specifications for Crystal River Unit 3
2) Final Safety Analysis Report, Volume 7, Appendix 14B
3) Air Handling Flow Diagram, FPC Drawing Number FD-302-751, Revision 16
4) Environmental and Seismic Qualification Guide Specifications and Data, Section 4 (draft)

In the interim between the present and scheduled upgrades, the following justifications for continued operation are given.

N 1. Radiation is the main item of concern. Table 3.6-1 of Reference 1 however, shows these valves would complete their safety function in less than one (1) minute. Reference 4 shows that the 40 year dose in the equipment's environmental zone (39) is only 2.8 x 10 4R. Therefore, the only time radiation could affect operation is during post accident purging not initial containment isolation.

2. Reference 3 shows AHV-1B and AHV-lC are located in contain-ment. It also shows there are redundant isolation valves (in series), AHV-1A and AHV-lD respectively, located outside containment. Hence, a single failure during post-accident purging will not compromise containment integrity.

Based on the discussions provided, continued operation with the subject equipment does not jeopardize the safe operation of CR3.

O A-13

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: MTMC-4,5 RECORD NUMBER: 0007 SCEW PAGE NUMBER: 2-8 s

DESCRIPTION: WALL MOUNTED LOCATION:

CONTACTOR 3B,AHF-1B AUXILIARY BLDG. ELEV. 119 MANUFACTURER: ALLEN BRADLEY TER EQUIPMENT NO.:

92 MODEL: SERIES K TER CATEGORY:

I.B SYSTEM: AH ZONE LOCATION:

25/24-RESP .

TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL Z

F

/

/

Q-J , .

i t '

QUALIFICATION STATUS:

7 F,OT IN SCOPE. SUBSEQUENT REVIEW SHOWS THESE ITEMS ARE LOCATED IN A MILD '

ENVIRONMENT. (ENVIRONMENTAL ZONE INDICATED ABOVE) SEE SECTION 2."2 ,

DISCUSSION. ,

CORNECTIVF. ACTION: -

j /

NOT APPLICABLE. s ,' . '_, , , -

e "~ ' ,

j i- -

s )#

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE. ,

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

k A-14 r

7 f-m L_

FLORIDA POWER CORPORAT' ION -

QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: MTMC-7 RECORD NUMBER:- 0008 SCEW PAGE NUMBER: 2-9 s

DESCRIPTION: WALL MOUNTED LOCATION:

CONTACTOR. AUXILIARY BLDG.

ELEV.-119 MANUFACTURER: ALLEN BRADLEY TER EQUIPMENT NO.:-

91 2*.

.n MODEL: SERIES K b f i TER CATEGORY: g ,

I.B N SYSTEM: AH ZONE LOCATION: i ,~

i 28

\

TER QUALIFICATION DEFICIENCIES NOTED:

l. DOCUMENTED EVIDENCE OF QUAL 3

4 t t g i >

y i s s

QUALIFICATION STATUS: ,

P.

T S, t

\

QUALIFIED BY ANALYSIS. Ifg '

y ~ 3 SEE MTMC-3 (RECORD 0085). '

l \ ,

3 CORRECTIVE ACTION: . s. ;t -

g r

NOT APPLICABLE.  !

+

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

l MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

l NOT REQUIRED.

  • W l A-15 \
i -s s

i k

FLORIDA POWER CORPORATION QUALIFICATION STATUS SUMMAkY SHEETS ID NUMBER: AH-312-SV RECORD NUMBER: 0009 AH-313-SV

( ~') SCEW PAGE NUMBER: 2-15 a

DESCRIPTION: ,

SOLENOID VALVE LOCATION:

AUXILIARY BLDG.

4 ELEV. 95' s 4 MANUFACTURER: JOHNSON CONTROL el 4

s TER EQUIPMENT NO.:

MODEU: V-24-2

, TER CATEGORY:

1 N/A SYSTEM: AH ZONE LOCATION:

11 TER QUALIFICATION DEFICIENCIES NOTED:

NOT INCLUDED IN EVALUATION

~

QUALIFICATION STATUS:

.y NOT IN SCOPE. SUBSEQUENT REVIEW SHOWS THESE ITEMS ARE LOCATED IN A MILD ENVIRONMENT. (ENVIRONMENTAL ZONE INDICATED ABOVE) SEE SECTION 2.2 DISCUSSION.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

()

A-16

',i e . - ,, , _ _ . _ . _ . _ . _ _ . _ . _ __. _ _ _ _ _ _ _ _ _ _ _ _ _ _ . _ _ . _ _ _

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS g ID NUMBER: AH-315-TS RECORD NUMBER: 0010 Q AH-410-TS SCEW PAGE NUMBER: 2-16 2

DESCRIPTION: TEMPERATURE SWITCH LOCATION:

AUXILIARY BLDG.

ELEV. 95' MANUFACTURER: PENN CONTROLS TER EQUIPMENT NO.:

MODEL: A70KA-I TER CATEGORY:

N/A SYSTEM: AH ZONE LOCATION:

11 TER QUALIFICATION DEFICIENCIES NOTED:

NOT INCLUDED IN EVALUATION O

QUALIFICATION STATUS:

NOT IN SCOPE. SUBSEQUENT REVIEW SHOWS THESE ITEMS ARE LOCATED IN A MILD ENVIRONMENT. (ENVIRONMENTAL ZONE INDICATED ABOVE) SEE SECTION 2.2 DISCUSSION.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

A O

A-17

_,-m-

- ~ -

I FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: ASV-5 RECORD NUMBER: 0011 SCEW PAGE NUMBER: 2-19 2

DESCRIPTION: VALVE MOTOR OPERATOR LOCATION:

INTERMEDIATE BLDG.

ELEV. 95'-0" MANUFACTURER: LIMITORQUE TER EQUIPMENT NO.:

23 MODEL: SMB-00 TER CATEGORY:

II.A SYSTEM: AS ZONE LOCATION:

14 TER QUALIFICATIOli DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL O

QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

CORRECTIVE ACTION:

REPLACE MOTOR CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER 1985 MAR NUMBER: 82-05-24-06 JUSTIFICATION FOR CONTINUED OPERATION:

SEE ATTACHED.

. O A-18

DISCUSSION ON O. ASV-5 Record 0011 2 A walkdown was conducted for this valve and the results (L200-WW-001) show this actuator has a D.C. motor with class B insulation. The vendor was contacted and requested to identify activities required to upgrade this actustor such that Qualification Report B0009 (L200-3TR-008) would apply, thereby encompassing the environmental specifications for Zone 14. The ,

vendor response (L200-3VC-008) indicates a motor replacement with a Peerless D.C. motor with Class RH insulation will be required.

O A-19

i O

a JUSTIFICATION FOR CONTINUED OPERATION for ASV-5 Limitorque Motor Operator TER Item 23 References

1) Limitorque Test Report B0003, "Limitorque Valve Actuator Qualification Report for Class IE Service Outside Containment."
2) Environmental and Seismic Qualification Guide Specifications and Data, Section 4.

/

As stated in the discussion, walkdown results show these operators have class B insulated DC motors. Class B insulated 0

motors were tested in reference 1 to 250 F. Reference 2 indicaces all parameters are encompassed by testing with the exception of temperature. Temperature during the accident, however, returns to below 250 F within 10 seconds. This initial temperature peak is not of sufficient duration to effect motor l internals. Therefore, reliability of this motor within the required 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> operating time is not expected to degrade.

l Hence, the safe operation of Crystal River Unit 3 is not jeopardized by interim operation with the current equipment configuration.

l l

l lO A-20

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS

~g ID NUMBER: ASV-5 RECORD NUMBER: 0012 SCEW PAGE NUMBER: 2-20 2

DESCRIPTION: LOCAL MOTOR STARTER LOCATION:

INTERMEDIATE BLDG.

ELEV. 95'-0" MANUFACTURER: ALLEN BRADLEY TER EQUIPMENT NO.:

86 MODEL: BULLETIN 205 TER CATEGORY:

II.A SYSTEM: AS ZONE LOCATION:

14 "TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL

/~T _

()

QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

CORRECTIVE ACTION:

RELOCATE TO MILD ENVIRONMENT.

CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER 1985 MAR NUMBER: 82-05-24-02 JUSTIFICATION FOR CONTINUED OPERATION:

SEE ATTACHED.

A-21

I)

's)

JUSTIFICATION FOR CONTINUED OPERATION for .

^

ASV-5; EFV-11, 14, 32, & 33; FWV-34, 35, 46, 37, 161, 162; MSV-55 & 56 Allen Bradley Motor Starter TER Item 86 Reference

1) FPC IE Bulletin 79-OlB Response, Figure 4-4.

The motor starters will be removed from the Intermediate Building and relocated in a mild environment prior to November, 1985.

In the interim between the present time and scheduled relocation, the following justifications for continued operation are given:

1. Specification environment radiation values were compared to

[)

v radiation values for the typical materials from the DOR Guidelines Appendix C for motor control centers. This com-parison revealed that the specification environment radiation is at or below radiation susceptibility acceptance levels; thereby indicating radiation is not a restraint to the safety-related operation of the motor control centers.

2. The motor starters are used to position valves immediately after the occurrence of a HELB in the intermediate building.

Although a failure analysis has shown that if repositioning of the valves is postulated, repositioning will occur sub-sequent to the maximum thermal and pressure conditions, allowing operator access to correct the repositioning should it occur.

O A-22

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS

. ID NUMBER: AS-1 RECORD NUMBER: 0013 SCEW PAGE NUMBER: 2-21 2

DESCRIPTION: LOCAL CONTROL LOCATION:

STATION INTERMEDIATE BLDG.

ELEV. 95'-0" MANUFACTURER: FIELD FABRICATED TER EQUIPMENT NO.:

90 MODEL: G.E. TYPE UA202 SW.

G.E. TYPE UC212 LIGHT TER CATEGORY:

I.B SYSTEM: AS ZONE LOCATION:

14 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL O

QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

CORRECTIVE ACTION:

RELOCATE TO MILD ENVIRONMENT.

CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER 1985 MAR NUMBER: 82-05-24-02 JUSTIFICATION FOR CONTINUED OPERATION:

SEE ATTACHED.

A-23

JUSTIFICATION FOR CONTINUED OPERATION for AS-1; CA-1, 2, & 3; CF-1, 5, & 6; EF-3 & 4; FW-5, 6, 11, & 12; 2 MS-5 & 6; MU-4 & 5; SW-6; SW-7 & 9; SW-8; WD-1; WS-1, 2, 3, & 4 GE Switches and Lights TER Item 90

, References

, 1) FPC IE Bulletin 79-OlB Response, Figure 4-4.

The motor starters will be relocated in a mild environment prior to November, 1985.

In the interim between the present time and scheduled relocation, the following justifications for continued operation are given:

1. Specification environment radiation values were compared to radiation values for the typical materials from the DOR Guidelines Appendix C for motor control centers. This com-parison revealed that the specification environment radiation is at or below radiation susceptibility acceptance levels; thereby indicating radiation is not a restraint to the safety-related operation of the motor control centers.

I 4 2. The motor starters are used to position valves immediately af ter the occurrence of a HELB in the intermediate building.

4 Although a failure analysis has shown that if repositioning of the valves is postulated, repositioning will occur sub-sequent to the maximum thermal and pressure conditions, allowing operator access to correct the repositioning should it occur.

i

!O A-24 m -e -* -d--e= a.-%9 p.--ary =y 9.-ye--,.e.-*9.-y-y -------m--9 -yy- m.-- w.4 .,ww e -mww ,y.mmg- r,m-,yem,g-.yyp9--my.----- -e-=c,,-9-myi---------g----yymm--- ye-m-um------

FLORIDA POWER CORPORATION QUALIFICATION STATUS SLMY SHEETS ID NUMBER: AS-1 RECORD NUMBER: 0014

{"}

v SCEW PAGE NUMBER: 2-22 2

DESCRIPTION: TERMINAL BOX LOCATION:

INTERMEDIATE BLDG.

ELEV. 95'-0" MANUFACTURER: FIELD FABRICATED 1

TER EQUIPMENT NO.:

75 MODEL: STATES TYPE NT TERMINAL BLOCKS TER CATEGORY:

I.B SYSTEM: AS ZONE LOCATION:

14 TER QUALIFICATION DEFICIENCIES NOTED:

3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED O

QUALIFICATION STATUS:

QUALIFIED BY ANALYSIS.

CORRECTIVE ACTION:

> NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

O A-25

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS p ID NUMBER: BSP-1A/lB RECORD NUMBER: 0015 SCEW PAGE NUMBER: 2-23 s

DESCRIPTION: PUMP MOTOR LOCATION:

AUXILIARY BLDG.

ELEV. 75'-0" MANUFACTURER: WESTINGHOUSE TER EQUIPMENT NO.:

60 MODEL: TYPE LAC TER CATEGORY:

II.A SYSTEM: BS ZONE LOCATION:

7 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL O .

QUALIFICATION STATUS:

QUALIFIED FOR CURRENT APPLICATION.

SEE DISCUSSION ATTACHED.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

i  %

A-26

DISCUSSION 03 O BSP-la & 1B Westinghouse Motors Type LAC 3 References

1) WCAP 8754 " Environmental Qualification of Class lE Motors for Nuclear Out-of-Containment Use" dated June, 1976.

Although these motors were purchased prior to the issuance of IEEE 323 1971, they are similar in design to motors tested in the reference indicated.

The function of the DHP motors is to provide decay heat removal in the auxiliary building Harsh environment is limited to ,

radiation since the motor need only operate for conditions inside containment, and its location is outside containment.

The total integrated dose for the motors is 5.1 x 10 6 R (40 year TID of 4.9 x 106 R plus one day post accident exposure of 1.2 x 10 6R). Since the integrated dose for lifetime is significantly greater than the dose received during the accident, the radiation cusceptibility of motor components if any, should i

be detectable via periodic surveillances.

Currently, the motors are tested and inspected annually (PM-105)

I This equipment is functionally tested at 18 for abnormalities.

month intervals.

It is the FPC position that there is adequate surveillance on l this equipment and it is considered qualified for its current l- appl'ication.

O

A-27

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS p ID NUMBER: BSP-1A & 1B RECORD NUMBER: 0016 O SCEW PAGE NUMBER: 2-23A 2

DESCRIPTION: LUBRICANT LOCATION:

AUXILIARY BLDG.

ELEV. 75' MANUFACTURER: GULF TER EQUIPMENT NO.:

60 MODEL: GULF HARMONY 68 TER CATEGORY:

II.A SYSTEM: BS ZONE LOCATION:

7 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL QUALIFICATION STATUS:

LUBRICATION ANALYSIS AND DOCUMENTATION IN PROGRESS.

l CORRECTIVE ACTION:

i INCORPORATE RESULTS INTO .

PM PROGRAM.

CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER, 1985.

MAR NUMBER: 82-05-24-05 JUSTIFICATION FOR CONTINUED OPERATION:

SEE ATTACHED.

O A-28

JUSTIFICATION FOR CONTINUED OPERATION O for BSP-1A & BSP-1B Lubricant i Gulf Harmony 68 TER Item 60 The lubricants are being investigated in regard to radiation resistance and appropriate action will be taken subsequent to this investigation. However, engineering judgement indicates that relative to the accident radiation, the required safety operability due to the lubricants will not be a restraint to the

safety operation of the motors.

O -

i i

I O

A-29 h

--.------,,._y y.,--._,--,_,,,m,. . , _ _ _ _ _ , . . _ , . , _ _ _ _ . _ _ _ _ _ _ . _ , , _ , . , , _, , ,__ _ _ _ _ _ . . _ _ _ _ , , _ _ _ , . , _ _ _ , , _ _ _ , , , , , , _

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: BSV 4 RECORD NUMBER: 0017

)

SCEW PAGE NUMBER: 2-24 2

DESCRIPTION: VALVE MOTOR OPERATOR LOCATION:

AUXILIARY BLDG.

ELEV. 95'-0" MANUFACTURER: LIMITORQUE TER EQUIPMENT NO.:

24 MODEL: SMB-040 TER CATEGORY:

II.A-A SYSTEM: BS ZONE LOCATION:

36 TER QUALIFICATION DEFICIENCIES NOTED:

NOT INCLUDED IN EVALUATION '

em U

QUALIFICATION STATUS:

QUALIFIED FOR CURRENT APPLICATION.

SEE DISCUSSION ATTACHED.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

l NOT REQUIRED.

O A-30

DISCUSSION ON O BSV 4 Record 0017 2 Vendor correspondence (L 200-3VC-004 ) indicates that Test Report 80003 (L200-3TR-003) is applicable to this valve motor opera-tor. Although the radiation specification for zone 36 is greater than 1 x 10 8R a location specific calculation (GAI file code CR3.118 [ 2 ] ) shows Total Integrated Dose (40 year plus accident) 5 is 1.9 x 10 R.

This equipcent is considered qualified for its current applica-tion.

O O

A-31

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: BSV-3 RECORD NUMBER: 0018 SCEW PAGE NUMBER: 2-24A a

DESCRIPTION: VALVE MOTOR OPERATOR LCCATION:

AUXILIARY BLDG.

ELEV. 95'-0" MANUFACTURER: LIMITORQUE TER EQUIPMENT NO.:

24 MODEL: SMB-0-40 TER CATEGORY:

II.A SYSTEM: BS ZONE LOCATION:

36 TER QUALIFICATION DEFICIENCIES NOTED:

2. EQUIP VS TEST SPECIMEN
3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED O

QUALIFICATION STATUS:

QUALIFIEL FOR CURRENT APPLICATION.

SEE DISCUSSION ATTACHED.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

lO l

A-32 l

l

DISCUSSION ON

~) BSV 3 Record 0018 2 Vendor correspondence (L200-3VC-004) indicates that Test Report B0003 (L200-3TR-003) is applicable to this valve motor opera-tor. Although the radiation specification for zone 36 is greater than 1 x 10 8 a location specific calculation (GAI file code CR3. ll8 ( 2] ) shows Total Integrated Dose (40 year plus accident)

R.

is 2.2 x 105 This equipment is considered qualified for its current applica-tion.

O O

A-33

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS s ID NUMBER: BSV-16/17 RECORD NUMBER: 0019

! )

SCEW PAGE NUMBER: 2-25 s

DESCRIPTION: VALVE MOTOR OPERATOR LOCATION:

AUXILIARY BLDG.

ELEV. 75'-0" MANUFACTURER: LIMITORQUE TER EQUIPMENT NO.:

11 MODEL: SMB-00-25 TER CATEGORY:

II.A SYSTEM: BS ZONE LOCATION:

7 TER QUALIFICATION DEFICIENCIES NOTED:

2. EQUIP VS TEST SPECIMEN
3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED O

QUALIFICATION STATUS:

QUALIFIED FOR CURRENT APPLICATION.

SEE DISCUSSION ATTACHED.

CORRECTIVE ACTION:

NOT APPLICABLE.

I CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE. ,

i MAR NUMBER: NOT APPLICABLE.

, JUSTIFICATION FOR CONTINUED OPERATION:

I NOT REQUIRED.

D l

A-34

DISCUSSION ON BSV-16/17 Record 0019 2 i

Vendor correspondence (L200-3VC-012) indicates that Test Report i B0003 (L200-3TR-003) is applicable to this valve motor opera-tor. Review of this report indicates all environmental parameters for zone 7 are enveloped by testing.

6 i

O O

A-35

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: BSV-36/37 RECORD NUMBER: 0020 SCEW PAGE NUMBER: 2-26 DESCRIPTION: VALVE MOTOR OPERATOR LOCATION:

AUXILIARY BLDG.

ELEV. 75'-0" MANUFACTURER: LIMITORQUE TER EQUIPMENT NO.:

24 MODEL: SMB-000-5 TER CATEGORY:

II.A SYSTEM: BS ZONE LOCATION: '

7 TER QUALIFICATION DEFICIENCIES NOTED:

l 2. EQUIP VS TEST SPECIMEN

3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED O

QUALIFICATION STATUS:

QUALIFIED FOR CURRENT APPLICATION.

SEE DISCUSSION ATTACHED.

> CORRECTIVE ACTION:

NOT APPLICABLE.

1 CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

i O

A-36 7

. . . . - - - . . . . - - - - , - - , - . . - . - - . . . , . ----.__----y. ,

DISCUSSION ON BSV-36/37 Record 0020 Vendor correspondence (L200-3VC-007) indicates that Test Report 80003 (L200-3TR-003) is applicable to these valve motor opera-tors. Review of this report indicates all environmental parameters for Zone 7 are enveloped by testing.  !

O I

A-37 I

. _ _ , -..-_m. ,

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS T ID NUMBER: BS-5/6 RECORD NUMBER: 0021

\ )

SCEW PAGE NUMBER: 2-27 a DESCRIPTION: TERMINAL BOX LOCATION:

AUXILIARY BLDG.

ELEV. 95'-0" MANUFACTURER: FIELD FABRICATED TER EQUIPMENT NO.:

NA MODEL: STATES TYPE NT TERMINAL BLOCKS TER CATEGORY:

N/A SYSTEM: BS ZONE LOCATION:

6 TER QUALIFICATION DEFICIENCIES NOTED:

NOT INCLUDED IN EVALUATION O

QUALIFICATION STATUS:

NOT IN SCOPE. SUBSEQUENT REVIEW SHOWS THESE ITEMS ARE LOCATED IN A MILD ENVIRONMENT. (ENVIRONMENTAL ZONE INDICATED ABOVE) SEE SECTION 2.2 l DISCUSSION.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

(vh A-38

FLORIDA POWER CORPORATION )

QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: BS-79-FIS RECORD NUMBER: 0022 SCEW PAGE NUMBER: 2-33 a

DESCRIPTION: FLOW INDICATOR LOCATION:

SWITCH AUXILIARY BLDG.

ELEV. 95' MANUFACTURER: BARTON TER EQUIPMENT NO.:

MODEL: 288A TER CATEGORY:

N/A SYSTEM: BS ZONE LOCATION:

6 TER QUALIFICATION DEFICIENCIES NOTED:

NOT INCLUDED IN EVALUATION QUALIFICATION STATUS:

NOT IN SCOPE. SUBSEQUENT REVIEW SHOWS THESE ITEMS ARE LOCATED IN A MILD ENVIRONMENT. (ENVIRONMENTAL ZONE INDICATED ABOVE) SEE SECTION 2.2 DISCUSSION.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: 80-09-03 JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

l A-39 l

l

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: BS-80-FIS RECORD NUMBER: 0023 SCEW PAGE NUMBER: 2-34 1

DESCRIPTION: FLOW INDICATOR LOCATION:

SWITCH AUXILIARY BLDG.

ELEV. 95' MANUFACTURER: BARTON TER EQUIPMENT NO.:

MODEL: 288A TER CATEGORY:

N/A SYSTEM: BS ZONE LOCATION:

6 TER QUALIFICATION DEFICIENCIES NOTED:

NOT INCLUDED IN EVALUATION O

QUALIFICATION STATUS:

NOT IN SCOPE. SUBSEQUENT REVIEW SHOWS THESE ITEMS ARE LOCATED IN A MILD ENVIRONMENT. (ENVIRONMENTAL ZONE INDICATED ABOVE) SEE SECTION 2.2 '

DISCUSSION.

CORRECTIVE ACTION:

NOT APPLICALLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: 80-09-03 JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

O

'w)

A-40

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: BS-PT-16,17 RECORD NUMBER: 0024 SCEW PAGE NUMBER: 2-35 2 DESCRIPTION: PRESSURE TRANSMITTER LOCATION:

AUXILIARY BLDG.

ELEV. 95' MANUFACTURER: L&N TER EQUIPMENT NO.:

40 MODEL: 1973-215-2 TER CATEGORY:

I.B SYSTEM: BS ZONE LOCATION:

64/65-RESP TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL

(

QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

I t

CORRECTIVE ACTION:

l REPLACE.

I CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER 1985 MAR NUMBER: 80-07-04 JUSTIFICATION FOR CONTINUED OPERATION:

SEE ATTACHED.

O l

A-41

  • * ~- ~ -
/ <.

j,. , t

, : ../

f

{ ~

,/, l

/

JUSTIFICATION FOR CONTINUED OPERATION

~

[

for '. / 1 1

BS-PT-16, 17 L&N Transmitters e

.TER Item 40 s.

References ,

1) B&W Topical Report BAW 10082 Rev.1, " Environmental Qualifi-cation of Class lE Control Instrumentation Equipment", Table 3-10, FPC File B014-3TR-001.-
2) FPC Crystal Piver FSAR 5ecticn 14.2.2.5.

BS-PT-16 and BS-PT-17 L&N transmitters will be replaced prior to November, 1985. The replacement transmitters. will be supplied with documented evidence of qualification.

In the interim between the present time and scheduled transmitter -

and replacement, the following justifications for continued operation are given: >

1. The function of the reactor . building pressure ' transmitters is to initiate ESFAS as a result of increased building pres- ,

~

sure due to LOCA. The required operating time for the j

reactor building pressure transmitters is 10 seconds for a -

l major LOCA and 15 minutes for small LOCA. The transmitters are located outside containment and are used to sense

(~ accidents inside' containment. Therefore, all LOCA-caused harsh environments, except radiation, are not a considera-tion for this device.

2. The total integrated dose to the transmitter is caused by the sum of the operating dose and the accident dose. The accident dose is assumed to be negligible since it is caused O

A-42

by degraded core fission products in recirculating lirIss and J i 3 i t g ,

the recirculation', phase begins at'a time great'eir th~an the ,

required operating time for the pressure transmitters.! The , ,

ten year operating dose to the transmitters is 2.5 x 10!! <

rads. Radiation effects are signifidant for these' devices.

e 9 .

3. Failure of reactor building pressure transmitters can be '

tolerated because other signals (*(RC' pressure and steam generator pressure) initiate ESFhS ' functions. Containmedt spray may be initiated manually if the) transmitters fu.1.  %

-+

4 k t s I 1

.O ,

4 1

\ '

i.

\

i F

1

( '

g a4 9-s i

u

!O A-43

\

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: BS-90-PT RECORD NUMBER: 0025 BS-91-PT SCEW PAGE NUMBER: 2-35A 4 DESCRIPTION: PRESSURE TRANSMITTER LOCATION:

INTERMEDIATE BLDG.

ELEV. 95' MANUFACTURER: ROSEMOUNT TER EQUIPMENT NO.:

49 MODEL: 1153 TER CATEGORY:

I.B SYSTEM: BS ZONE LOCATION:

64/65-RESP TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL QUALIFICATION STATUS:

(NOT INSTALLED YET.)

SEE DISCUSSION ATTACHED.

l l

CORRECTIVE ACTION:

l (INSTALLATION)

CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER 1985 l

MAR NUMBER: 79-11-68 JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

O A-44

,s

.,- , ~ - . - - . , _ .

DISCUSSION ON l BS-90-PT; BS-91-PT Record 0025 BS-90-PT and BS-91-PT are being added to the system to provide wide range pressure sensing. Their function is to detect containment building pressure. They are used for indication only. Items were in TER Category I.B because the equipment was in test at the time of submittal. Test Reports (results) have been received (R369-3TR-003) and indicate all environmental parameters for zones 64 and 65 are enveloped.

This equipment will be installed prior to November 30, 1985 by the Modification Approval Record indicated.

O l

O A-45

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: BS-1-dPT 1&2 RECORD NUMBER: 0026 SCEW PAGE NUMBER: 2-35B a DESCRIPTION: FLOW TRANSMITTER LOCATION:

AUXILIARY BLDG.

ELEV. 95' MANUFACTURER: BAILEY METER CO.

TER EQUIPMENT NO.:

45 MODEL: BY-8240-A TER CATEGORY:

II.A SYSTEM: BS ZONE LOCATION:

6 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL

/"g b

QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

l CORRECTIVE ACTION:

REPLACE. .

CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER 1985 MAR NUMBER: 82-05-24-04 JUSTIFICATION FOR CONTINUED OPERATION:

SEE ATTACHED.

O A-46 1

l s

JUSTIFICATION FOR CONTINUED OPERATION for ,

BS-1-dPT 1 & 2 Bailey Meter Co. Flow Transmitters TER Item 45  ;

j References i

1) FPC IE Bulletin 79-OlB Response, Figure 4-7.

i 2) B&W Proprietary Document 58-0081-00, " Type Test Report of Bailey Meter By Differential Pressure Transmitter", dated 3/12/73.

l The building spray flow transmitters will be replaced prior to November, 1985. The units will be replaced with transmitters having documented evidence of qualification, or other methods ,

i will be specified to reduce the harsh environment to acceptable [

levels. SCEW sheets for the new transmitters will be completed l upon the receipt of the new transmitters and associated test

. reports.

In the interim between the present time and corrective action, i the following justification is given:

1. The only harsh environment for this transmitter is radiation 5

at a level of 2.6 x 10 rads. Reference 2 indicates quali-4 I fication to greater than 2 x 10 rads.

2. Sinc. the building spray transmitters are required only to detect the onset of spray during the first few minutes of the accident, total integrated dose will be below the quali-fled radiation dose at the onset of building spray, i
3. Failure of the transmitters can be tolerated later in the accident sequence since spray can be detected using other instruments, such as pump operating indicators, pump outlet / inlet pressure, etc.

A-47

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: CAV-1/3 RECORD NUMBER: 0027 SCEW PAGE NUMBER: 2-36 J

DESCRIPTION: VALVE MOTOR LOCATION:

OPERATOR INSIDE CONTAINMENT MANUFACTURER: LIMITORQUE TER EQUIPMENT NO.:

16 MODEL: SMB-000-2 TER CATEGORY:

II.A SYSTEM: CA ZONE LOCATION:

38 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL
2. EQUIP VS TEST SPECIMEN
3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED
8. SPRAY O

QUALIFICATION STATUS:

TO BE REPLACED, OUTAGE IV WITH QUALIFIED UNITS.

CORRECTIVE ACTION:

REPLACE.

CORRECTIVE ACTION SCHEDULE: REFUEL IV; JULY, 1983.

MAR NUMBER: 80-1-11 JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

A-48

. - -. - . . . - . - _ _ _ _ _ _ _ . . _ _ .-. - - .=

l DISCUSSION ON CAV 1 & 3; 126 Limitorque Motor Operators 2 Records 0027; 0029

)

l These units are being replaced during the current outage for operational considerations with equipmen t tested to the environments specified in Test Report 600456. Modificat. ions are being made via the modification approval record indicated on the

, Qualification Summary Sheet. The installation of the new qualified equipment will be verified during an equipment walkdown l scheduled for the Refuel IV outage.

)

l O

O A-49

FLORIDA PONER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: CAV-4/5 RECORD NUMBER: 0028 SCEW PAGE NUMBER: 2-37 ,

DESCRIPTION: VALVE MOTOR LOCATION:

OPERATOR INSIDE CONTAINMENT MANUFACTURER: LIMITORQUE TER EQUIPMENT NO.:

10 MODEL: SMB-000-2 TER CATEGORY:

II.A SYSTEM: CA ZONE LOCATION:

38 TER QUALIFICATION DEFICIENCIES NOTED:

2. EQUIP VS TEST SPECIMEN
3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED QUALIFICATION STATUS:

QUALIFIED FOR CURRENT APPLICATION.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

A-50

DISCUSSION ON CAV-4/5 Limitorque Motor Operators Record 0028 Initial discussions with the vendor using shop order numbers and serial numbers of originally installed equipment indicates Test Reports 600376 (L200-3TR-002), 600198 (L200-3TR-005) and Addendum 1 to 600198 (L200-3TR-006) apply to this equipment.

This report envelops all environmental parameters for the required operating time of this equipment. Walkdowns are scheduled during the current outage to confirm and document qualification. From the current information available, Florida Power Corporation considers this equipment qualified for its current application.

O O

A-51

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: CAV-126 RECORD NUMBER: 0029 SCEW PAGE NUMBER: 2-38 a

DESCRIPTION: VALVE MOTOR LOCATION:

OPERATOR INSIDE CONTAINMENT MANUFACTURER: LIMITORQUE TER EQUIPMENT NO.:

15 MODEL: SMB-000-5 TER CATEGORY:

II.A SYSTEM: CA ZONE LOCATION:

38 TER QUALIFICATION DEFICIENCIES NOTED:

2. EQUIP VS TEST SPECIMEN
3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED
8. SPRAY (D

'w)

QUALIFICATION STATUS:

TO BE REPLACED, OUTAGE IV WITH QUALIFIED UNITS. SEE DISCUSSION FOR CAV-1 & 3, RECORD 0027.

CORRECTIVE ACTION:

REPLACE.

CORRECTIVE ACTION SCHEDULE: REFUEL IV; JULY, 1983.

MAR NUMBER: 80-1-11 l

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

(

A-52

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS

( ID NUMBER: CAV-2 RECORD NUMBER: 0030 SCEW PAGE NUMBER: 2-39 a

DESCRIPTION: SOLENOID VALVE LOCATION:

INTERMEDIATE BLDG.

ELEV. 95' MANUFACTURER: TARGET ROCK TER EQUIPMENT NO.:

34 MODEL: 77CC-001 TER CATEGORY:

I.A ..

SYSTEM: CA ZONE LOCATION:

65 TER QUALIFICATION DEFICIENCIES NOTED:

NONE O

QUALIFICATION STATUS:

QUALIFIED FOR CURRENT APPLICATION.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

O A-53

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: CA-1,2, & 3 RECORD NUMBER: 0188 SCEW PAGE NUMBER: 2-40 2

DESCRIPTION: LOCAL CONTROL LOCATION:

STATION INTERMEDIATE BLDG.

ELEV. 95'-0" MANUFACTURER: FIELD FABRICATED TER EQUIPMENT NO.:

MODEL: G.E. TYPE UA202 SW.

G.E. TYPE UC212 LIGHT TER CATEGORY:

I.B-A SYSTEM: CA ZONE LOCATION:

TER QUALIFICATION DEFICIENCIES NOTED:

NOT INCLUDED IN EVALUATION.

O .

QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

l CORRECTIVE ACTION:

REMOVE.

CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER, 1985.

MAR NUMBER: 82-05-24-02 JUSTIFICATION FOR CONTINUED OPERATION:

SEE JCO FOR AS-1, RECORD 0013.

O A-54

~. _

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS

() ID NUMBER: CA-1,2,3 RECORD NUMBER:

SCEW PAGE NUMBER:

0031 2-41 ,

DESCRIPTION: TERMINAL BOX LOCATION:

INTERMEDIATE BLDG.

ELEV. 95' MANUFACTURER: FIELD FABRICATED TER EQUIPMENT NO.:

74 MODEL: STATES TYPE NT TERMINAL BLOCKS TER CATEGORY:

III.B SYSTEM: CA ZONE LOCATION:

65 TER QUALIFICATION DEFICIENCIES NOTED:

NONE QUALIFICATION STATUS:

NOT IN SCOPE AS STATED IN THE TER.

SEE SECTION 2.2 DISCUSSION.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

O A-55

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS

() ID NUMBER: CFV-ll/12 RECORD NUMBER:

SCEW PAGE NUMBER:

0032 2-43 ,

DESCRIPTION: VALVE MOTOR LOCATION:

OPERATOR INSIDE CONTAINMENT ELEV. 119' MANUFACTURER: LIMITORQUE TER EQUIPMENT NO.:

07 MODEL: SMB-000-2 TER CATEGORY:

II.A SYSTEM: CF ZONE LOCATION:

39 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL
2. EQUIP VS TEST SPECIMEN
3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED 7A. PEAK TEMPERATURE 7B. PEAK PRESSURE
8. SPRAY QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

CORRECTIVE ACTION:

REPLACE MOTOR WITH CLASS RH MOTOR.

REPLACE LIMIT & TORQUE SWITCHES WITH CONTAINMENT TYPE SWITCHES; ADD GREASE RELIEF VALVE AND MOTOR "T" DRAINS.

CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER 1985.

MAR NUMBER: 82-05-24-06 JUSTIFICATION FOR CONTINUED OPERATION:

SEE ATTACHED.

l I A-56

DISCUSSION ON 0% CFV 11/12 Record 0032 2 Correspondence from Limitorque (L200-3VC-004) indicates that Qualification Report B0003 (L200-3TR-003) applies to the equip-ment listed. A walkdown was conducted and the results (L200-WW-001) show these actuators have Porter motors with insulation Class H. These are 3 phase, 230/460 volt motors. The vendor was contacted with walkdown results and requested to identify activities required to upgrade these actuators such that Qualification Report 600456 (L200-3TR-001) would apply, thereby ensuring radiation would not be a concern and that all parameters for zone 39 would be encompassed by testing. The vendor response (L200-3VC-008) indicates it would be necessary to replace the motors with Class RH motors, the limit and torque switches with containment type switches, add a grease relief valve and motor "T" drains.

O ,

f l 1

O A-57

JUSTIFICATION FOR CONTINUED OPERATION for CFV-11 & 12 2 Limitorque Motorized Valve Operators TER Item 7 4

References

1) NRC Technical Evaluation Report, January, 1983.
2) Limitorque Test Report #B0003, 5/28/76.
3) FPC IE Bulletin 79-01B Response, November, 1981, pg. 2-43.
4) Limitorque Letter, FPC #L200-3VC-004 In the interim between the present and scheduled corrective action, the following justification for continued operation is given:

CFV-ll and CFV-12 are normally closed containment isolation valves which are used to sample core flood tank contents. Since the valves are normally closed, no operation of the valves is required should an accident occur; therefore, failure of the valves can be tolerated. A normally-closed redundant valve outside containment (CFV-42) also provides backup containment isolation.

O A-58 l ,

, -.--,-..-,,e- . - - = .- . ,.,-w----.- . - . - . , . . . , - --,~..% .m.,,_,,--,--c--,__, -- --,-- ,,.-,.w ,- , _ - - - - . - , , - - - - - , . - - . _

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: CFV-15/16 RECORD NUMBER: 0033 SCEW PAGE NUMBER: 2-44 DESCRIPTION: VALVE MOTOR LOCATION:

OPERATOR INSIDE CONTAINMENT ELEV. 119'-0" MANUFACTURER: LIMITORQUE TER EQUIPMENT NO.:

07 MODEL: SMB-000-2 TER CATEGORY:

II.A SYSTEM: CF ZONE LOCATION:

39 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL
2. EQUIP VS TEST SPECIMEN
3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED 7A. PEAK TEMPERATURE 7B. PEAK PRESSURE c 8. SPRAY

(,

QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

CORRECTIVE ACTION:

REPLACE MOTOR WITH CLASS RH MOTOR.

REPLACE LIMIT & TORQUE SWITCHES WITH i CONTAINMENT TYPE SWITCHES; ADD GREASE I RELIEF VALVE AND MOTOR "T" DRAINS. l CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER, 1985.

MAR NUMBER: 82-05-24-06 JUSTIFICATION FOR CONTINUED OPERATION:

SEE ATTACHED.

A-59

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS f~.

( ,j ID NUMBER: CFV-15/16 RECORD NUMBER: 0033 SCEW PAGE NUMBER: 2-44 2 DESCRIPTION: VALVE MOTOR LOCATION:

OPERATOR INSIDE CONTAINMENT ELEV. 119'-0" MANUFACTURER: LIMITORQUE TER EQUIPMENT NO.:

07 MODEL: SMB-000-2 TER CATEGORY:

II.A SYSTEM: CF ZONE LOCATION:

39 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL
2. EQUIP VS TEST SPECIMEN
3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED 7A. PEAK TEMPERATURE 7B. PEAK PRESSURE
8. SPRAY QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

CORRECTIVE ACTION:

REPLACE MOTOR WITH CLASS RH MOTOR.

REPLACE LIMIT & TORQUE SWITCHES WITH CONTAINMENT TYPE SWITCHES; ADD GREASE RELIEF VALVE AND MOTOR "T" DRAINS.

CORRECTIVE ACTION SCHEDULE:

MAR NUMBER: 82-05-24-06 JUSTIFICATION FOR CONTINUED OPERATION:

,, SEE ATTACHED.

( i L. ,)

A-59

3 DISCUSSION ON CFV 15/16 Record 0033 '

Correspondence from Limitorque (L200-3VC-004) indicates that Qualification Report B0003 (L200-3TR-003) applies to the equip-ment listed. A walkdown was conducted and the results (L200-WW-001) show these actuators have Porter motors with insulation

Class H. These are 3 phase, 230/460 volt motors. The vendor was contacted with walkdown results and requested to identify activi-ties required to upgrade these actuators such that Qualification Report 600456 (L 200-3TR-001) would apply, thereby ensuring radi-ation would not be a concern and that all parameters for zone 39 would be encompassed by testing. The vendor response (L200-3VC-008) indicates it would be necessary to replace the motors with Class RH motors, the limit and torque switches with containment type switches, add a grease relief valve and motor "T" drains.

O l

(

O a

A-60

JUSTIFICATION FOR CONTINUED OPERATION for i

CFV-15 & 16 Limitorque Motorized Valve Operators TER Item 7 References

1) NRC Technical Evaluation Report, January, 1983.
2) Limitorque Test Report #B0003, 5/28/76.
3) FPC IE Bulletin 79-01B Response, November, 1981, pg. 2-43.
4) Limitorque Letter, FPC AL200-3VC-004.

In the interim between the present and scheduled corrective action, the following justification for continued operation is given:

CFV-15 and CFV-16 are used as containment isolation valves for waste gas from the core flood tanks. Since the valves are normally closed, no operation of the valves is required should an accident occur; therefore, failure of the valves can be tolerated. Also a normally closed redundant valve outside containment (CFV-29) provides a backup containment isolation.

l l

l l

I lO l

A-61

FLORIDA POWER CORPORATION QUALIFICATION STATUS CUNMARY SHEETS

( ID NUM3ER: CFV-25,26,29,42 RECORD NUMBER: 0034 SCEW PAGE NUMBER: 2-45 ,

DESCRIPTION: SOLENOID VALVE LOCATION:

AUXILIARY BLDG.

ELEV. 119' MANUFACTURER: ASCO TER EQUIPMENT NO.:

28 MODEL: THB 830281R TER CATEGORY:

I.B SYSTEM: CF ZONE LOCATION:

22 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

CORRECTIVE ACTION:

REPLACE.

l

( CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER 1985 MAR NUMBER: 82-05-24-03 JUSTIFICATION FOR CONTINUED OPERATION:

SEE ATTACHED.

l l

A-62

f JUSTIFICATION FOR CONTINUED OPERATION for  ;

CFV-25, 26, 29, 42 TER Item 28 References l

l) FPC Environmental Qualification of Class lE Equipment IE Bulletin 79-OlB Qualification Summary.  !

I

  • j In the interim between the present and scheduled corrective ,

action, the following justification for continued operation, as previously provided in Reference 1, is given:

i  :

i

1. Investigations with the manufacturer indicate the solenoid i valves are good for 10 5 rads.

O affect the components for Accident conditions will not the period of operability required. Also, due to the location of the component when

required to perform its safety function, the accident environment has no impact.

i.

2. Due to the period of operability required as per CRf3 Tech.

Spec. Table 3.6-1 to perform their safety function, and the l fact that the total radiation exposure per the SCEW sheets i

is conservative in regard to the 5-1/2 year operating life

of the plant, these valves are not considered to be a restraint to the safe operation of CR63.

[

O A-63

FLORIDA POWER CORPORATION QUALIFICATION CTATUS

SUMMARY

SHEETS

() ID NUMBER: CF-1, 5, & 6 RECORD NUMBER: 0189 SCEW PAGE NUMBER: 2-47 ,

{ DESCRIPTION: LOCAL CONTROL LOCATION:

STATION AUXILIARY BLDG.

ELEV. 119'-0" MANUFACTURER: FIELD FABRICATED TER EQUIPMENT NO.:

MODEL: G.E. TYPE UA202 SW.

G.E. TYPE UC212 LIGHT TER CATEGORY:

I.B-A SYSTEM: CF ZONE LOCATION:

TER QUALIFICATION DEFICIENCIES NOTED:

NOT INCLUDED IN EVALUATION.

O QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

CORRECTIVE ACTION:

REMOVE.

CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER 1985 1

MAR NUMBER: 82-05-24-02 JUSTIFICATION FOR CONTINUED OPERATION:

SEE JCO FOR AS-1, RECORD 0013.

O A-64

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: CF-1,3,4 RECORD NUMBER: 0035 SCEW PAGE NUMBER: 2-49 4

DESCRIPTION: TERMINAL BOX LOCATION:

AUXILIARY BLDG.

ELEV. 119'-0" MANUFACTURER: FIELD FABRICATED TER EQUIPMENT NO.:

69 MODEL: STATES TYPE NT TERMINAL BLOCKS TER CATEGORY:

I.B SYSTEM: CF ZONE LOCATION:

22 TER QUALIFICATION DEFICIENCIES NOTED:

3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED O .

QUALIFICATION STATUS:

QUALIFIED FOR CURRENT APPLICATION.

SEE APPENDIX A.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

~

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED, A-65

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS

'ID NUMBER: CF-2 RECORD NUMBER: 0036

(

SCEW PAGE NUMBER: 2-50 ,

DESCRIPTION: TERMINAL BOX LOCATION:

INTERMEDIATE BLDG ELEV. 95'-0" MANUFACTURER: FIELD FABRICATED TER EQUIPMENT NO.:

74 MODEL: STATES TYPE NT TERMINAL BLOCKS TER CATEGORY:

III.B SYSTEM: CF ZONE LOCATION:

14 TER QUALIFICATION DEFICIENCIES NOTED:

NONE O

QUALIFICATION STATUS:

NOT IN SCOPE AS STATED IN THE TER.

SEE SECTION 2.2 DISCUSSION.

l l

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

l NOT REQUIRED.

bO A-66

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: CIV-34,35,40,41 RECORD NUMBER: 0037 (m)

SCEW PAGE NUMBER: 2-51 ,

DESCRIPTION: SOLENOID VALVE LOCATION:

AUXILIARY BLDG.

ELEV. 95' MANUFACTURER: ASCO TER EQUIPMENT NO.:

MODEL: HT8320A38 TER CATEGORY:

N/A SYSTEM: CI ZONE LOCATION:

64 TER QUALIFICATION DEFICIENCIES NOTED:

NOT INCLUDED IN EVALUATION O

QUALIFICATION STATUS:

NOT IN SCOPE. SUBSEQUENT REVIEW SHOWS THESE ITEMS ARE LOCATED IN A MILD ENVIRONMENT. (ENVIRONMENTAL ZONE INDICATED ABOVE) SEE SECTION 2.2 DISCUSSION.

CORRECTIVE ACTION:

i l NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

]

A-67

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS S.

ID NUMBER: CI-3,4,5 & 6 RECORD NUMBER: 0038 SCEW PAGE NUMBER: 2-52 ,

DESCRIPTION: LOCAL CONTROL LOCATION:

STATION AUXILIARY BLDG.

ELEV. 95'-0" MANUFACTURER: FIELD FABRICATED TER EQUIPMENT NO.:

MODEL: G.E. TYPE UA202 SW.

TER CATEGORY:

N/A SYSTEM: CI ZONE LOCATION:

64 TER QUALIFICATION DEFICIENCIES NOTED:

NOT INCLUDED IN EVALUATION (3 -

U i

QUALIFICATION STATUS:

NOT IN SCOPE. SUBSEQUENT REVIEW SHOWS THESE ITEMS ARE LOCATED IN A MILD ENVIRONMENT. (ENVIRONMENTAL ZONE INDICATED ABOVE) SEE SECTION 2.2 DISCUSSION.

CORRECTIVE ACTION:

l NGT APPLICABLE.

I CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

O A-68

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: CI-2,3,4 & 9 RECORD NUMBER: 0039 SCEW PAGE NUMBER: 2-53 ,

DESCRIPTION: TERMINAL BOX LOCATION:

AUXILIARY BLDG ELEV. 95'-0" MANUFACTURER: FIELD FABRICATED TER EQUIPMENT NO.:

NA MODEL: STATES TYPE NT

. TERMINAL BLOCKS TER CATEGORY:

N/A SYSTEM: CI ZONE LOCATION:

64 TER QUALIFICATION DEFICIENCIES NOTED:

NOT INCLUDED IN EVALUATION O

QUALIFICATION STATUS:

NOT IN SCOPE. SUBSEQUENT REVIEW SHOWS THESE ITEMS ARE LOCATED IN A MILD

. ENVIRONMENT. (ENVIRONMENTAL ZONE l INDICATED ABOVE) SEE SECTION 2.2 JISCUSSION.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

l l MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

O 1

A-69 l

FLORIDA POWIiR CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: DCP-1A/lB -s RECORD NUMBER: 0040 SCEW PAGE NUMBER: 2-54 ,

DESCRIPTION: PUMP MOTOR LOCATION:

AUXILIARY BLDG.

ELEV. 95'-0" MANUFACTURER: GENERAL ELECTRIC TER EQUIPMENT NO :

64 MODEL: 5K445AK364 TER CATEGORY:

II.A SYSTEM: DC -

ZONE LOCATION:

11

\

? >

TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL O .

QUALIFICATION STATUS:

NOT IN SCOPE. SUBSEQUENT REVIEW SHOWS THESE ITEMS ARE LOCATED IN A MILD ENVIRONMENT. (ENVIRONMENTAL ZONE INDICATED ABOVE) SEE SECTION 2.2 -

DISCUSSION. '

CORRECTIVE ACTION:

NOT APPLICABLE. <

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE'.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION: '

NOT REQUIRED. ,

1 J' \

i A-70 +

\

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS

' (** ' ID NUMBER: DCP-1A & 1B RECORD NUMBER: 0041 4

SCEW PAGE NUMBER: 2-54A .

DESCRIPTION: LUBRICANT LOCATION:

AUXILIARY BLDG.

' ELEV. 95' MANUFACTURER: GULF TER EQUIPMENT NO.:

64 MODEL: GULF HIGH TEMPERATURE TER CATEGORY:

II.A SYSTEM: DC ZONE LOCATION:

11 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL QUALIFICATION STATUS:

NOT IN SCOPE. SUBSEQUENT REVIEW l SHOWS THESE ITEMS ARE LOCATED IN A MILD i ENVIRONMENT. (ENVIRONMENTAL ZONE INDICATED ABOVE) SEE SECTION 2.2 DISCUSSION.

.s CORRECTIVE ACTION:

NOT APPLICABLE.

l l

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

l JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

D l A-71 4

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS O ID NUMBER: DHP-1A/lB RECORD NUMBER: 0042 SCEW PAGE NUMBER: 2-55 DESCRIPTION: PUMP MOTOR LOCATION:

AUXILIARY BLDG. DECAY HEAT PIT ELEV. 75'0" MANUFACTURER: WESTINGHOUSE TER EQUIPMENT NO.:

61 MODEL: TYPE LAC TER CATEGORY:

II.A SYSTEM: DH ZONE LOCATION:

7 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL O

QUALIFICATION STATUS:

QUALIFIED FOR CURRENT APPLICATION (SEE DISCUSSION ATTACHED).

CORRECTIVE ACTION:

~

I j NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

A-72

DISCUSSION ON DHP-1A & 1B Westinghouse Motors Type LAC TER Item 61 References

1) WCAP 8754 " Environmental Qualification of Class lE Motors for Nuclear Out-of-Containment Use" dated June, 1976.

Although these motors were purchased prior to the issuance of IEEE 323 1971, they are similar in design to motors tested in the reference indicated.

The function of the DHP motors is to provide decay heat removal in the auxiliary building. Harsh environment is limited to radiation since the motor need only operate for conditions inside containment, and its location is outside containment.

The total integrated dose for the motors is 6.1 x 10 6 R (40 year TID of 4.9 x 10 6R plus six month post accident exposure of 1.2 x 106R). Since the integrated dose for lifetime is significantly greater than the dose received during the accident, the radiation susceptibility of motor components if any, should be detectable via periodic surveillances.

Currently, the motors are tested End inspected annually (PM-105) for abnormalities. This equipment is functionally tested at 18 month intervals.

FPC feels there are adequate surveillances on this equipment and considers it qualified for its current application.

O A-73

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS

() ID NUMBER: DHP-1A & 1B RECORD NUMBER: 0043 SCEW PAGE NUMBER: 2-55A DESCRIPTION: LUBRICANT LOCATION:

AUXILIARY BLDG.

ELEV. 75' MANUFACTURER: GULF TER EQUIPMENT NO.:

61 MODEL: GULF HARMONY 68 TER CATEGORY:

II.A SYSTEM: DH ZONE LOCATION:

7 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL O

QUALIFICATION STATUS:

LUBRICATION ANALYSIS AND DOCUMENTATION IN PROGRESS.

CORRECTIVE ACTION:

INCORPORATE RESULTS INTO PM PROGRAM.

CORRECTIVE ACTION SCHEDULE: REFUEL V, NOVEMBER 1985.

MAR NUMBER: 82-05-24-05 l

JUSTIFICATION FOR CONTINUED OPERATION:

SEE JCO FOR BSP-1A & IB RECORD 16.

l A-74

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS O ID NUMBER: DHV-5/6 RECORD NUMBER: 0044 2

SCEW PAGE NUMBER: 2-56 DESCRIPTION: VALVE MOTOR LOCATION:

OPERATOR AUXILIARY BLDG.

ELEV. 95'-0" MANUFACTURER: LIMITORQUE TER EQUIPMENT NO.:

09 MODEL: SMB-3-100 TER CATEGORY:

II.A SYSTEM: DH ZONE LOCATION:

36 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL
2. EQUIP VS TEST SPECIMEN
3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED
10. RADIATION EXPOSURE

~

QUALIFICATION STATUS:

I NOT QUALIFIED. SEE DISCUSSION ATTACHED.

CORRECTIVE ACTION:

REPLACE MOTOR.

CORRECTIVE ACTION SCHEDULE: REFUEL IV; JULY 1983.

MAR NUMBER: 82-05-24-08 I

l JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

l l

A-75

DISCUSSION ON DHV 5 & 6; 34 & 35 3

Records 0044, 0046 Initial discussiona with the vendor indicated that Test Report FC 3271 (L200-3TR-004) would apply to these actuators. However, during a plant walkdown scheduled for equipment verification, the insulation class of the motor on the actuator was determined to be class H. These motors are located in a zone that receives relatively high total integrated doses during plant life.

Class H insulation is designed for high temperature applications but not high radiation applications. Class RH insulation is designed for both high radiation and high temperature applications and has been tested to radiation exposures in excess of 2 x 10 8 rads. Florida Power Corporation has been unsuccessful in obtaining material breakdowns (composition) of class H insulation to conduct analyses or compare similarities. ,

Florida Power Corporation considers this equipment not qualified due to the insulation class of the motors. (The presence of teflon is suspected.) These motors will be replaced during the l

current outage; no justification for continued operation is required since the plant is currently in an outage.

i l

l O

i l

A-76 l

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS O ID NUMBER: DHV-11/12 RECORD NUMBER: 0045 SCEW PAGE NUMBER: 2-57 DESCRIPTION: VALVE MOTOR LOCATION:

OPERATOR AUXILIARY BLDG.

ELEV. 95' MANUFACTURER: LIMITORQUE TER EQUIPMENT NO.:

MODEL: SMB-000-5 TER CATEGORY:

N/A SYSTEM: DH ZONE LOCATION:

6 TER QUALIFICATION DEFICIENCIES NOTED:

NOT INCLUDED IN EVALUATION O

QUALIFICATION STATUS:

NOT IN SCOPE. SUBSEQUENT REVIEW SHOWS THESE ITEMS ARE LOCATED IN A MILD ENVIRONMENT. (ENVIRONMENTAL ZONE INDICATED ABOVE)

SEE SECTION 2.2 DISCUSSION.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED, O

A-77

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS A

V ID NUMBER: DHV-34/35 RECORD NUMBER: 0046 SCEW PAGE NUMBER: 2-58 DESCRIPTION: VALVE MOTOR LOCATION:

OPERATOR AUXILIARY BLDG.

ELEV. 75'-0" MANUFACTURER: LIMITORQUE TER EQUIPMENT NO.:

02 MODEL: SMB-2-40 TER CATEGORY:

II.A SYSTEM: DH ZONE LOCATION:

7 .

TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL
2. EQUIP VS TEST SPECIMEN
3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED
10. RADIATION EXPOSURE O

QUALIFICATION STATUS:

NOT QUALIFIED. SEE DISCUSSION FOR DHV-5 & 6, RECORD 0044.

CORRECTIVE ACTION:

REPLACE MOTOR.

i I

CORRECTIVE ACTION SCHEDULE: REFUEL IV; JULY 1983.

MAR NUMBER: 82-05-24-08 JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

A-78

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS O ID NUMBER: DHV-110/lll RECORD NUMBET: 0047

^

SCEW PAGE NUMBER: 2-59 DESCRIPTION: VALVE MOTOR LOCATION:

OPERATOR AUXILIARY BLDG.

75'-0" MANUFACTURER: LIMITORQUE TER EQUIPMENT NO.:

03 MODEL: SMB-1-25 TER CATEGORY:

II.A SYSTEM: DH ZONE LOCATION:

7 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL
2. EQUIP VS TEST SPECIMEN
3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED
10. RADIATION EXPOSURE QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

SEE DISCUSSION ATTACHED.

l l

CORRECTIVE ACTION:

REPLACE MOTOR CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER 1985 MAR NUMBER: 82-05-24-06 l

JUSTIFICATION FOR CONTINUED OPERATION:

i SEE ATTACHED.

l A-79

DISCUSSION ON DHV-110/lll 2

Record 0047 Correspondence from Limitorque (L200-3VC-007) indicates that Qualification Report 600198 plus Addendum 1 (L200-3TR-005) apply to the actuators for these valves. A walkdown was conducted and the results (L200-WW-0 01) show these actuators have Reliance motors with insulation class H. These are 3 phase, 220/440 volt motors. Walkdown results were provided to the vendor and they were requested to identify activities required to upgrade these actuators such that Qualification Report B0003 (L200-3TR-003) would apply, thereby ensuring radiation would not be a concern.

The vendor response (L200-3VC-008) indicates motor replacement with Class B (or better) insulated motors will be required.

O o

U A-80 l

) JUSTIFICATION FOR CONTINUED OPERATION for DHV-110 and 111 TER Item 3 References a

1) NRC Technical Evaluation Report, January, 1983.
2) Limitorque Test Report No. 600198, January, 1969, and Addendum 1, April 1969.
3) FPC IE Bulletin 79-OlB Response, November, 1981.
4) Limitorque Letter, FPC #L200-3VC-007
5) Field Inspection Report, L200-WW-001.
6) Limiturque Test Report 600456, Sepctember, 1976.

In the interim between the present and scheduled corrective action, the following justification for continued operation is given:

Operation of this equipment for an interim period can be justified on a functional and equipment basis. The functional reason is valves DHV-110 and 111 are used to align the Decay Heat System with the Makeup System if the Makeup Pumps are required.

In the event of a LOCA, this alignment is not required. Since these valves are normally open and aligned for LOCA conditions, they are not required to move during or subsequent to a LOCA and failure can, therefore, be tolerated.

On an equipment basis, most of the operators parts can be qualified by material similarity.

l l Tests were performed on operators similar to DHV-110 and 111 and l all aspects of the environmental conditions were covered except l radiation and aging (Referencs 4 and 2) . To resolve this issue, j a field inspection (Reference 5) of the installed equipment was V

l A-81

performed to identify materials and parts in the operator that could be compared to materials and parts in similar qualified operators. The materials and parts susceptible to radiation 2 degradation and aging are the torque and limit switches, the motor winding insulation, the seals, and grease.

Based on the field inspection report (Reference 5), the torque and limit switches are the standard Limitorque design and the material (identified by its color) is similar to valve operators which were tested to the conditions described in Test report 600456 (Reference 6). In this test, the operator was exposed to a radiation level of 2.04 x 10 8 rads and aged for an equivalent of 40 years. Therefore, by similarity, it can be concluded that the switches are qualified for the environment.

The other parts, such as the motor winding insulation, seals and grease will be maintained in accordance with with vendor recommendations and replaced as required.

O .

2 g l

I O

A-82

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: DH-43-FIS RECORD NUMBER: 0048 SCEW PAGE NUMBER: 2-60 DESCRIPTION: FLOW INDICATING LOCATION:

SWITCH AUXILIARY BLDG ELEV. 95' MANUFACTURER: BARTON TER EQUIPMENT NO.:

46 MODEL: 288A TER CATEGORY:

II.C SYSTEM: DH ZONE LOCATION:

6 TER QUALIFICATION DEFICIENCIES NOTED:

3. AGING DEGRADA? ION EVAL
4. QUAL LIFE OR REPLACE SKED QUALIFICATION STATUS:

, QUALIFIED FOR CURRENT APPLICATION.

(

SEE DISCUSSION ATTACHED.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: 80-09-03 l

l JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED, O

A-83 l

1

' DISCUSSION ON DH-43-FIS, DH-44-FIS 3

Record 0048, 0049 This equipment is located in environmental zone 6. The only parameter considered harsh is radiation. The 40 year exposure at the equipment is 1 x 10 4R. Total Integrated Dose (TID) dbes not exceed 1x 10 5R until greater than five (5) days after the ac-cident. TID for 40 years plus six (6) months post accident exposure is only 2.6 x 10 5R and is not expected to cause cata-strophic failure of any insulating material. This equipment will be maintained in accordance with vendor recommendations. Any additional aging evaluations are not warranted at this time.

) This equipment is considered qualified for its current applica-tion and location. However, for operational considerations, this switch is being replaced with another qualified switch.

O O

A-84 l

l 1

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS O" ID NUMBER: DH-44-FIS RECORD NUMBER: 0049 SCEW PAGE NUMBER: 2-61 DESCRIPTION: FLOW INDICATING LOCATION:

SWITCH AUXILIARY BLDG.

ELEV. 95' MANUFACTURER: BARTON TER EQUIPMENT NO.:

46 MODEL: 288A TER CATEGORY:

II.C SYSTEM: DH ZONE LOCATION:

6 TER QUALIFICATION DEFICIENCIES NOTED:

3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED O

QUALIFICATION STATUS:

l QUALIFIED FOR CURRENT APPLICATION.

SEE DISCUSSION FOR DH-43-FIS (RECORD NUMBER 0048).

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: 80-09-03 MAR NUMBER: NOT APPLICABLE.

I JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

A-85 l

l

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS

(~)

%/ ID NUMBER: DH-DPT-3,4 RECORD NUMBER: 0050 SCEW PAGE NUMBER: 2-63A DESCRIPTION: DP TRANSMITTER LOCATION:

AUXILIARY BLDG.

ELEV. 98' 4" MANUFACTURER: ROSEMOUNT TER EQUIPMENT NO.:

42 MODEL: ll53B TER CATEGORY:

II.A SYSTEM: DH ZONE LOCATION:

6 TER QUALIFICATION DEFICIENCIES NOTED:

I

2. EQUIP VS TEST SPECIMEN
3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED QUALIFICATION STATUS:

QUALIFIED FOR CURRENT APPLICATION.

SEE DISCUSSION ATTACHED.

l i CORRECTIVE ACTION:

l l NOT APPLICABLE.

i l

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

A-86 l

-- . . , - - - - , - . , _,,_n,., _ . . . , . . , _ _ . . . - , - . - , _ . - _ - - , , ., , , . , _ - , . - , _ . - -

DISCUSSION ON DH-DPT-3, 4 Record 0050 2 References

1) Rosemount Test Report 108025 and 108026, "Rosemount Pressure Transmitter, Model 1153, Series B for Nuclear Service",

dated 2/4/81.

The Rosemount transmitters have been installed. The transmitters are series 1153 B which are qualified to IEEE 323-1974, IEEE 344-1975, and NUREG-0588, Category 1 requirements in accordance with Reference 1. No justification for continued operation is required since the transmitter is qualified. All harsh environ-ments are enveloped by the testing conditions. Walkdown during Refuel IV will verify installation.

O 1

i O

A-87 l

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: DH-DPT-38 RECORD NUMBER: 0051 SCEW PAGE NUMBER: 2-64 DESCRIPTION: DIFFERENTIAL PRESS. LOCATION:

TRANSMITTER AUXILIARY BLDG.

ELEV. 95' MANUFACTURER: BM CO.

TER EQUIPMENT NO.:

47 MODEL: BY8240X-A TER CATEGORY:

II.A SYSTEM: DH ZONE LOCATION:

36 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL O

QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

l CORRECTIVE ACTION:

REPLACE.

l CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER 1985 MAR NUMBER: 82-05-24-04 JUSTIFICATION FOR CONTINUED OPERATION:

SEE ATTACHED.

O~_

A-88

JUSTIFICATION FOR CONTINUED OPERATION for a

DH-DPT-38 Bailey Meter Transmitter TER Item No. 47 The function of the DH-DPT-38 flow transmitters is to detect crossover flow from one decay heat system to the redundant system. The transmitter will be replaced or qualification deficiencies resolved by November, 1985.

In the interim between the present time and corrective action, the following justifications for continued operation are given:

1. The only harsh environment for this transmitter is radiation at a level of 1 x 10 0 rads. Pressure and temperature remain unchanged following an accident; therefore, it is not expected that this component is subject to failure as a result of pressure and temperature conditions.
2. Crossover function may be determined through use of DHS-3-DPT and DHS-4-DPT which are installed and qualified.

i l

l l

l O

A-89

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: DWV-160 RECORD NUMBER: 0052 SCEW PAGE NUMBER: 2-65 DESCRIPTION: VALVE MOTOR LOCATION:

OPERATOR INTERMEDIATE BLDG.

ELEV. 95'-0" MANUFACTURER: LIMITORQUE TER EQUIPMENT NO.:

05 MODEL: SMB-00-2 TER CATEGORY:

II.A SYSTEM: DW ZONE LOCATION:

14 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL
2. EQUIP VS TEST SPECIMEN
3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED 7A. PEAK TEMPERATURE i

QUALIFICATION STATUS:

NOT IN SCOPE, SEE DISCUSSION ATTACHED l

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

l l A-90

O DISCUSSION ON DWV-160 Record 0052 3 Vendor correspondence (L200-3VC-007) indicates Test Report B0003 (L200-3TR-003) is applicable to this valve motor operator.

This valve is located outside containment. Its only safety function is containment isolation in the event of a LOCA or HELB inside containment. While the valve must function during the accident, it is not exposed to accident environment. The environment at the equipment's location does not change during or following the accident for which it must function.

Therefore this equipment is not considered to be within the scope of 10 CFR 50.49. This equipment will be removed from the Master List.

O 1

O A-91

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS O

d ID NUMBER: EFP-1 RECORD NUMBER: 0053

^

SCEW PAGE NUMBER: 2-66 DESCRIPTION: PUMP MOTOR LOCATION:

INTERMEDIATE BLDG.

ELEV. 95'-0" MANUFACTURER: ELECTRIC MACHINERY TER EQUIPMENT NO.:

58 MODEL: 2419-S TER CATEGORY:

II.A SYSTEM: EF ZONE LOCATION:

14 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL

/

QUALIFICATION STATUS:

QUALIFIED FOR CURRENT APPLICATION i

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

O A-92

DISCUSSION ON EFP-1 Record 0053 2 Electric Machinery Pump Motor As previously provided, these motors are totally encased, water-air cooled and designed for a temperature rise of 70 C rise over 40 C ambient. Walkdown results indicate these are Type 1C, continuous duty, 800 H.P., 4KV motors. (The electrical connection is hermetically sealed.) Due to the short duration of the accident temperatures (below 230 F in 16 seconds reaching 0

212 F in 40 seconds) and the relatively large mass of the equipment, motor internals will not sense accident temperatures in excess of 2120 F (within design margin).

Although the motor is not located in a radiologically harsh en-vironment, both the radiological and thermal susceptibilities of

\ motor construction materials, have been investigated. Results do ~

not show risk of failure.

Currently this motor is tested, inspected for abnormalities, cleaned and dried annually (PM 105). In addition, it is functionally tested (SP 349) monthly.

1 In light of the above, FPC considers this motor qualified for its j current application. Further qualification efforts are not j anticipated. Additional surveillances and testing are not deemed i necessary.

i l

O A-93

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS O i ID NUMBER: EFP-1 RECORD NUMBER: 0054 SCEW PAGE NUMBER: 2-66A DESCRIPTION: LUBRICANT LOCATION:

INTERMEDIATE BLDG.

ELEV. 95' MANUFACTURER: GULF TER EQUIPMENT NO.:

58 MODEL: GULF HARMONY 68 TER CATEGORY:

II.A SYSTEM: EF ZONE LOCATION:

14 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL O

QUALIFICATION STATUS:

ADDRESSED GENERICALLY VIA PM PROGRAM (PM-133).

CORRECTIVE ACTION: .

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

A-94 l

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS O ID NUMBER: EFV-3/4 RECORD NUMBER: 0055

^

SCEW PAGE NUMBER: 2-67 DESCRIPTION: VALVE MOTOR LOCATION:

OPERATOR INTERMEDIATE BLDG.

ELEV. 95' MANUFACTURER: LIMITORQUE TER EQUIPMENT NO.:

01 MODEL: SMB-000 TER CATEGORY:

II.A SYSTEM: EF ZONE LOCATION:

14 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL
2. EQUIP VS TEST SPECIMEN
3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED 7A. PEAK TEMPERATURE O

N.)

QUALIFICATION STATUS:

QUALIFIED FOR CURRENT APPLICATION.

SEE DISCUSSION ATTACHED.

l l

CORRECTIVE ACTION:

NOT APPLICABLE.

l CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

l A-95 l

DISCUSSION ON EFV-3/4; EFV-7 & 8 Records 0055; 0056 Vendor correspondence (L200-3VC-005) indicates that Test Report B0003 (L200-3TR-003) applies to the equipment listed. Thus, the only remaining concern is that testing does not completely envelop the required accident profile. The accident profile has an initial temperature spike that returns below the testing profile within 16 seconds. Because of the extremely short duration of this temperature peak, the equipment internals will not realize the higher initial temperatures. Thus the temperature peak is not an actual concern and the equipment is considered qualified for its current application.

O O

A-96

.- . _ _ _ _ _ _ . . , - . - - - - - . . . _ _ _ _ _ - . ~ __ . , .__.

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS A

b ID NUMBER: EFV-7 & 8 RECORD NUMBER: 0056 SCEW PAGE NUMBER: 2-68 DESCRIPTION: VALVE MOTOR LOCATION:

OPERATOR INTERMEDIATE BLDG.

ELEV. 95' MANUFACTURER: LIMITORQUE TER EQUIPMENT NO.:

19 MODEL: SMB-2 TER CATEGORY:

II.A SYSTEM: EF ZONE LOCATION:

14 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL
2. EQUIP VS TEST SPECIMEN
3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED 7A. PEAK TEMPERATURE O

QUALIFICATION STATUS:

QUALIFIED FOR CURRENT APPLICATION.

SEE DISCUSSION FOR EFV-3/4, RECORD 0055.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

A-97

\

FLORIDA POWER CORPORATION , '

x QUALIFICATION STATUS

SUMMARY

SHEETS

)

'ID NUMBER: EFV-11/32 RECORD NUMBER: 0057 ,

) 4 SCEW PAGE NUMBER: 2-69 3. ,

~

DESCRIPTION: VALVE MOTOR LOCATION:

OPERATOR INTERMEDIATE BLDG.

ELEV. 95'-0" MANUFACTURER: LIMITORQUE TER EQUIPMENT NO.:

23 MODEL: SMB-0 TER CATEGORY:

II.A SYSTEM: EF ZONE LOCATION:

14 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL

( ~

QUALIFICATION STATUS:

QUALIFIED FOR CURRENT APPLICATION.

SEE DISCUSSION ATTACHED.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

O A-98

l l

DISCUSSION ON EFV-ll/32, 14/33 Records 0057, 0058 t

This equipment has been walked down to obtain information that would attest to its qualification. These units have 250 volt D.C. motors with Class B insulation. Similar motors have been

, tested in "Limitorque Valve Actuator Qualification Report for Class lE Service Outside Containment", B0003 (L200-3TR-003).

This testing envelopes the environmental requirements for equipment in Zone 14 with the exception of an initial temperature spike. This temperature spike however, returns below the testing profile within ten seconds, hence the equipment internals will not sense temperatures in excess of the tested profile. Since the only real itm of concern is temperature for the current location, FPC considers this equipment qualified for its current application. Walk'down results (L200-WW-001) have been sent to the vendor to confirm our evaluation.

O A-99

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS O

(O ID NUMBER: EFV-14/33 RECORD NUMBER: 0058 SCEW PAGE NUMBER: 2-70 DESCRIPTION: VALVE MOTOR LOCATION:

OPERATOR INTERMEDIATE BLDG.

ELEV. 95' - 0" MANUFACTURER: LIMITORQUE TER EQUIPMENT NO.:

23 MODEL: SMB-0

'fER CATEGORY:

II.A SYSTEM: EF ZONE LOCATION:

14 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL O

QUALIFICATION STATUS:

QUALIFIED FOR CURRENT APPLICATION.

SEE DISCUSSION ATTACHED.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

s NOT REQUIRED.

)

A-100

I l

DISCUSSION ON .

EFV-ll/32, 14/33 Records 0057, 0058 i This equipment has been walked down to obtain information that would attest to its qualification. These units have 250 volt D.C. motors with Class B insulation. Similar motors have been tested in "Limitorque Valve Actuator Qualification Report for Class lE Service Outside Containment", B0003 (L200-3TR-003). .

This testing envelopes the environmental requirements for equipment in Zone 14 with the exception of an initial temperature spike. This temperature spike however, returns below the testing profile within ten seconds, hence the equipment internals will not sense temperatures in excess of the tested profile. Since the only real item of concern is temperature for the current location, FPC considers this equipment qualified for its current application. Walkdown results (L200-WW-001) have been sent to the vendor to confirm our evaluation.

O A-101

FLORIDA POWER CORPORATION QUALIFICATION STATUS SUNMARY SHEETS O ID NUMBER: EFV-ll,14 RECORD NUMBER: 0059 32, & 33 '

SCEW PAGE NUMBER: 2-71 DESCRIPTION: MOTOR STARTER LOCATION:

INTERMEDIATE BLDG, ELEV. 95'-0" MANUFACTURER: ALLEN BRADLEY TER EQUIPMENT NO.:

86 MODEL: BULLETIN 205 TER CATEGORY:

II.A SYSTEM: EF ZONE LOCATION:

14 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL 3

(0 QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

CORRECTIVE ACTION:

RELOCATE TO MILD ENVIRONMENT.

CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER 1985 MAR NUMBER: 82-05-24-02 JUSTIFICATION FOR CONTINUED OPERATION:

SEE JCO FOR ASV-5 (RECORD 012) b I

a A-102

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS O ID NUMBER: EF-3,4 RECORD NUMBER: 0060 4

SCEW PAGE NUMBER: 2-72 DESCRIPTION: LOCAL CONTROL LOCATION:

STATION INTERMEDIATE BLDG.

ELEV. 95'-0" MANUFACTURER: FIELD FABRICATED TER EQUIPMENT NO.:

90 MODEL: G.E. TYPE UA202 SW.

G.E. TYPE UC212 LIGHT TER CATEGORY:

I.B SYSTEM: EF ZONE LOCATION:

14 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL 1 -

QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

CORRECTIVE ACTION:

RELOCATE TO A MILD ENVIRONMENT.

l CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER 1985 MAR NUMBER: 82-05-24-02 JUSTIFICATION FOR CONTINUED OPERATION:

SEE JCO FOR AS-1 (RECORD 013)

A-103

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: EF-3,4 RECORD NUMBER: 0061

^

SCEW PAGE NUMBER: 2-73 DESCRIPTION: TERMINAL BOX LOCATION:

INTERMEDIATE BLDG, ELEV. 95'-0" MANUFACTURER: FIELD FABRICATED TER EQUIPMENT NO.:

75 MODEL: STATES TYPE NT TERMINAL BLOCKS TER CATEGORY:

I.B SYSTEM: EF ZONE LOCATION:

14 TER QUALIFICATION DEFICIENCIES NOTED:

3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED QUALIFICATION STATUS:

QUALIFIED FOR CURRENT APPLICATION.

SEE APPENDIX A.

l l CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

l JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

A-104

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: RECORD NUMBER: 0097 SCEW PAGE NUMBER: 2-122 DESCRIPTION: POWER AND CONTROL LOCATION:

CABLE PLANT WIDE MANUFACTURER: KERITE TER EQUIPMENT NO.:

77 MODEL: FR & HT TER CATEGORY:

II.A SYSTEM: ELECTRICAL DISTRIBUTION ZONE LOCATION:

N/A TER QUALIFICATION DEFICIENCIES NOTED:

2. EQUIP VS TEST SPECIMEN N

QUALIFICATION STATUS:

QUALIFIED FOR CURRENT APPLICATION.

SEE ATTACHED DISCUSSION.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

( JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

A-105

DISCUSSION ON

'Kerite Power and Control Cable Record 0097 The Kerite cable in use at CR3 consists of 5 KV, 1 KV and 600 V power cable with HTK insulation and control cable with FR insulation.

Documentation from vendor exists in the file (K080-3VC-006) that indicates Report F-C4020-1 and F-C4020-2 (K080-3TR-002 and K080-3TR-003, respectively) apply to cable in use at CR3.

Production testing data shows that CR3 uses cables having FR and HTK insulation. This corresponds to samples A through J of FIRL reports F-C4020-1 and F-C4020-2. Conductor sizes and insulation thickness used at CR3 are standard with Kerite and the test samples address standard cables. Note that the FIRL report samples conform to IEEE 383 representative sizes. Kerite insulation is used only for power and control circuits.

Differences between the test specimen and the cables installed at CR3 are in the thickness of insulation and jackets. The CR3 cable primary insulation thickness is three mils less than the 50 mil test specimen and the jacket thickness is 2.5 mils less than the 62.5 mils of the test specimen. IEEE 383 evaluates the materials of construction of cables rather than insulation thickness. A difference of 2.5 mils will not compromise the ability of the cable to perform in an accident environment.

O A-106

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: RECORD NUMBER: 0098 SCEW PAGE NUMBER: 2-123 DESCRIPTION: CONT. & THERMOCOUPLE LOCATION:

EXTENSION CABLE PLANT WIDE MANUFACTURER: ROCKBESTOS TER EQUIPMENT NO.:

78 MODEL: SILICONE RUBBER TER CATEGORY:

II.A SYSTEM: ELECTRICAL DISTRIBUTION ZONE LOCATION:

N/A TER QUALIFICATION DEFICIENCIES NOTED:

2. EQUIP VS TEST SPECIMEN O

QUALIFICATION STATUS:

QUALIFIED BY FOR CURRENT APPLICATION.

SEE ATTACHED DISCUSSION, CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

(g NOT REQUIRED.

V A-107

- - _ .__. .- . . _ - - = - _ - - -. _ _ . - _ . _ . _ . . - . - - - . - . .

DISCUSSION ON j

ROCKBESTOS SILICONE RUBBER i

! Record 0098 i

Cable installed at CR3 is Rockbestos Firewall SR as determined by a review of factory production test records. Documentation from vendor exists in the file (attached to R352-3TR-002) that indicates Rockbestos report " Qualification of Firewall SR Class IE Electric Cables" (R352-3TR-002) applies to cable in use at CR3.

)O l

l 1 0 V

A-108 l

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS O ID NUMBER: RECORD NUMBER: 0099 SCEW PAGE NUMBER: 2-124 DESCRIPTION: INST. CABLE &THERMO- LOCATION:

COUPLE EXTENSION CBL PLANT WIDE MANUFACTURER: CONTINENTAL WIRE

& CABLE COMPANY TER EQUIPMENT NO.:

79 MODEL: SILICONE RUBBER INS.

  1. CC-2193 TER CATEGORY:

II.A SYSTEM: ELECTRICAL DISTRIBUTION ZONE LOCATION:

N/A TER QUALIFICATION DEFICIENCIES NOTED:

2. EQUIP VS TEST SPECIMEN 7A. PEAK TEMPERATURE 7B. PEAK PRESSURE O

QUALIFICATION STATUS:

QUALIFIED FOR CURRENT APPLICATION.

SEE ATTACHED DISCUSSION.

CORRECTIVE ACTION:

NONE REQUIRED.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

lNOT REQUIRED.

A-109

.. - - - - -- - - ~ _ _ _ . _ - _ - _ - . - . . - - - _

i 1

DISCUSSION ON Continental Wire & Cable Co.

i i Instrument and Thermocouple Extension Cables i Record 0099 A review of FPC Purchase Order No. PR3-2178 was conducted, along ,

with referenced bills of materials and their cable descriptions, to identify type and insulation materials of instrument and thermocouple cables; as a result of this review it can be l

summarized that all cables have silicone rubber insulation type CC-2193. The outer jackets are either glass braid or silicone rubber type CC-2193. F-C2935 applies to cables having glass-

^

braid outer coverings. Anaconda Co. No 79118 applies to cables .

with silicone rubber outer jackets. Available qualification test f reports Anaconda Co. No 79118 and Franklin Institute No. F-C2935, and its addendum dated November 1970, provide qualification test data for previously mentioned materials on comparable test samples to specified cables. Individual test reports alone ,

provide only partial qualification data. For this reason, the combination of both reports and their test results was used for f evaluation of cable performance in the CR3 application; this l approach can be justified, since the insulation material is the same for both tested samples and specified cables.

Since the CR3 cables have a specified operability time of six months, it is necessary to compute a post-accident time period, for which the cables are qualified, for comparison to the post-accident operability time required.

The approach used was to calculate from the post-LOCA time / temperature profile, an equivalent time / temperature combination with the temperature being of the postulated, CR3 post-accident environment. The transformation of a given time and temperature to a longer time period at ambient temperature was based on the slope of the Arrhenius plot provided by the A-110 ,

. . . _ . . _ _ _ _ . _ , . _ , _ _ - . _ . - _ . ,~~-_m... , _ . - , , , _ _ . , . . . . , . , _ . . . _ . _ . _ . . _ . - - . . _ - _ _ _ _ _ - _ _ _ _ _ _ _ _ _ _ _ _

l l

l manufacturer; this approach necessitated certain assumptions, namely:

a ,

l 1. The Arrhenius line for the pre-accident thermal aging can be

applied at a post-accident time / temperature combination. It i

is assumed that the slope of the line can be used anywhere on the log t vs. 1/T plot. The calculation of a slope was included.

i 0

I 2. The post-LOCA temperature remains constant at 150 F after 5 seconds for the duration of the operating time of six 10 months; this is a conservative assumption, since some decay i of the temperature below 150 F is expected.

i j 3. The post-accident environmental pressure decays close to j atmospheric and does not affect the calculation.

{ 0 F for less than j The CR3 temperature peak during LOCA is above 280 one hour. The silicone rubber cable was tested to a temperature of 2800 F for a total of three hours in the Anaconda test. A cable insulated with the identical silicone rubber insulation (CC-2193) was tested in F-C2935 to a level of 340 0F for two hours. The only component which can be presumed to fail, therefore, is the outer jacket which was different in the two referenced tests. The jacket provides physical protection cnly l and, therefore, can fail without compromising the safety-related function of the cable. Pressure differences will not affect the

! ability of cables to carry signals or current. In addition, j F-C2935 indicates a pressure transient which is greater than j CR3. The cable is considered qualified since its safety-related function has been demonstrated in environments which exceed LOCA environments at CR3.

1 O

A-lli

- - . - = - -_. -_ - - _ - . _ . . - _ . - _ _ - _ . . _ _ _ _ _ . . , - _ - ._ .-_ _.

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS O ID NUMBER: RECORD NUMBER: 0100 SCEW PAGE NUMBER: 2-124A DESCRIPTION: CONTROL & INSTRUMENT LOCATION:

CABLE PLANT WIDE MANUFACTURER: BOSTON INSULATED WIRE AND CABLE CO. TER EQUIPMENT NO.:

80 MODEL: EPR INSULATION BOS-TRAD 7 CSPE JACKET TER CATEGORY:

II.A SYSTEM: ELECTRICAL DISTRIBUTION ZONE LOCATION:

N/A TER QUALIFICATION DEFICIENCIES NOTED:

2. EQUIP VS TEST SPECIMEN

~

QUALIFICATION STATUS:

QUALIFIED FOR CURRENT APPLICATION.

SEE ATTACHED DISCUSSION.

CORRECTIVE ACTION:

NONE REQUIRED.

1 CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

O A-112

DISCUSSION ON BIW Control and Instrument Cable 3

Record No. 0100 A review of CR3 purchase documents has shown that CR3 cable is Ethylene Propylene Rubber with a Bostrad 7 CSPE jacket. The insulation system was tested in accordance with IEEE 383 test sample requirements using a 7/C and 2/C cable. Differences in conductor size and numbers of conductors do not affect the validity of the testing since it is the insulation system which is being evaluated, not the inorganic materials or structural characteristics of the cables.

O O

l A-ll3 l

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: RECORD NUMBER: 0101 s

SCEW PAGE NUMBER: 2-127 DESCRIPTION: CABLE CONNECTORS LOCATION:

MTBD-2A,2B & 2C MANUFACTURER: T&B TER EQUIPMENT NO.:

85 MODEL: F1 TER CATEGORY:

IV SYSTEM: ELECTRICAL DISTRIBUTION ZONE LOCATION:

39 TER QUALIFICATION DEFICIENCIES NOTED:

O .

QUALIFICATION STATUS:

QUALIFIED FOR CURRENT APPLICATION.

(COMPLETELY METALLIC) l CORRECTIVE ACTION:

NOT APPLICABLE.

i l

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

I JUSTIFICATION FOR CONTINUED OPERATION:

O j NOT REQUIRED.

1 A-ll4

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS O ID NUMBER: RECORD NUMBER: 0102 SCEW PAGE NUMBER: 2-128 DESCRIPTION: TERMINAL BLOCKS LOCATION:

MTBD-8A,B,C & D MTBD-9A,B,C & D MANUFACTURER: KULKA TER EQUIPMENT NO.:

66 MODEL: 7TB & STB TER CATEGORY:

I.B SYSTEM: ELECTRICAL DISTRIBUTION ZONE LOCATION:

39 TER QUALIFICATION DEFICIENCIES NOTED:

2. EQUIP VS TEST SPECIMEN O -

i QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

CORRECTIVE ACTION:

REPLACE.

CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER 1985 MAR NUMBER: 82-05-24-01 JUSTIFICATIOD FOR CONTINUED OPERATION:

SEE ATTACHED.

O A-ll5

[

JUSTIFICATION FOR CONTINUED OPERATION for 2 Kulka Terminal Blocks Inside Containment TER Item No. 66 References

1) Franklin Institute Research Laboratories Test Report QL-C4927, " Quick Look Report for a Steam and Chemical Spray Exposure Test of Electrical Terminal Blocks".
2) Wyle Report 17436-15, " Final Report on Evaluation of Terminal Block Model EB-25", dated 12/1/80.
3) Wyle 58687, " Loss of Coolant Accident Testing of 5 Weidmuller Terminal Blocks", dated 6/29/82.

The terminal block terminations inside containment will be replaced with qualified in-line splices prior to November, 1985.

O _

In the interim between the present and November, 1985, the following justification for continued operation is given:

Kulka terminal blocks are typically composed of metallic com-ponents insulated by phenolic compounds. The test reports noted above have shown that phenolic terminal blocks are capable of surviving harsh environments due to LOCA or HELB.

O O

A-ll6

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS O ID NUMBER: RECORD NUMBER: 0103

^

SCEW PAGE NUMBER: 2-129 DESCRIPTION: TERMINAL LUGS LOCATION:

PLANT WIDE MANUFACTURER: BURNDY TER EQUIPMENT NO.:

83 MODEL: CRIMP TYPE TER CATEGORY:

II.A SYSTEM: ELECTRICAL DISTRIBUTION ZONE LOCATION:

N/A TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL O

QUALIFICATION STATUS:

QUALIFIED FOR CURRENT APPLICATION.

(COMPLETELY METALLIC)

CORRECTIVE ACTION:

NOT APPLICABLE, CORRECTIVE ACTION SCHEDULE: NOT AFPLICABLE.

MAR NUMBER: NOT APPLICABLE.

l l

JUSTIFICATION FOR CONTINUED- OPERATION:

NOT REQUIRED.

l Os l

A-ll7 l

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS

\

ID NUMBER: RECORD NUMBER: 0104 SCEW PAGE NUMBER: 2-130 DESCRIPTION: TERMINATION LOCATION:

PROCEDURE OUTSIDE CONTAINMENT MANUFACTURER: KERITE TER EQUIPMENT NO.:

82 MODEL: T-lNS-HT TER CATEGORY:

I.B SYSTEM: MT ELECTRICAL DISTRIBUTION ZONE LOCATION:

N/A TER QUALIFICATION DEFICIENCIES NOTED:

2. EQUIP VS TEST SPECIMEN C\

V QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

CORRECTIVE ACTION:

REPLACE.

CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER 1985 MAR NUMBER: 82-05-24-01 JUSTIFICATION FOR CONTINUED OPERATION:

SEE ATTACHED.

A-ll8

JUSTIFICATION FOR CONTINUED OPERATION for Kerite Cable Splice Outside Containment TER Item 82 Cable terminations subjected to harsh environments due to MSLB on recirculating fluids after LOCA will be replaced prior to November, 1985. Replacement terminations will be supplied with documented evidence of qualification. New SCEW sheets will be completed for the replacement terminations upon receipt of the terminations and associated test reports.

In the interim between the present time and scheduled replacement, the following justification for continued operation is given:

Cable termination splices are generally provided for personnel protection and do not provide electrical insulation to maintain equipment function. Spacing of terminals for both power and -

control functions is sufficient to maintain the electrical integrity necessary for proper equipment operation. The air f

space between termination points is sufficient to maintain integrity. Failure of the splices, therefore, may result in personnel hazard but will not compromise significantly the ability of the equipment to perform its safety-related function.

Where termination splices are required to maintain electrical l

integrity, the splices should provide adequate insulation if not moved from their original position. Dielectrici strength is not reduced to an unacceptable value even if termination material is

degraded physically. Maintenance activities will monitor the condition of the splices and replacement will be indicated if visible degradation occurs. Common mode failure is not postu-lated since locations of redundant equipment, distances from damage mechanisms, and times of refurbishment vary.

'O A-119

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: RECORD NUMBER: 0105 SCEW PAGE NUMBER: 2-131 DESCRIPTION: TERMINATION LOCATION:

PROCEDURE OUTSIDE CONTAINMENT MANUFACTURER: KERITE TER EQUIPMENT NO.:

82 MODEL: T-5NS-HT TER CATEGORY:

I.B SYSTEM: MT ELECTRICAL DISTRIBUTION ZONE LOCATION:

N/A TER QUALIFICATION DEFICIENCIES NOTED:

2. EQUIP VS TEST SPECIMEN O

QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

I t

CORRECTIVE ACTION:

REPLACE.

l CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER 1985 i

MAR NUMBER: 82-05-24-01 JUSTIFICATION FOR CONTINUED OPERATION:

SEE DISCUSSION FOLLOWING RECORD NO. 0104.

l J A-120

__ . . _ . _ . . _ ,, . . _ _ . _ _ _ _ _ _ _ _ _ . _ __ __ ~ _ _

._ . . . - - _. _ - _ . = ,_ _..

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: RECORD NUMBER: 0106 SCEW PAGE NUMBER: 2-132 DESCRIPTION: TERMINATION LOCATION:

PROCEDURE CONTAINMENT MANUFACTURER: KERITE TER EQUIPMENT NO.:

81 MODEL: 39-69 TER CATEGORY:

II.A SYSTEM: MT ELECTRICAL DISTRIBUTION ZONE LOCATION:

38/39/40 TER QUALIFICATION DEFICIENCIES NOTED:

10. RADIATION EXPOSURE O -

QUALIFICATION STATUS:

QUALIFIED FOR CURRENT APPLICATION.

SEE ATTACHED DISCUSSION.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

i NOT REQUIRED.

l A-121

DISCUSSION ON Kerite Co. Termination Procedure 439-69 Record No. 0106 A letter from the Kerite Co. in the FPC files states that the FIRL Report F-C4020-2 applies to termination procedure #39-69.

According to the vendor:

"Kerite Tape Type Terminals are qualified by comparison with qualified splices using similar designs and identical materials. The 39-69 terminal corresponds to Splice 38-69 covered in FIRL Report F-C4020-2...

"The following is a listing of Kerite Kit materials and corresponding manufacturer designations:

Kerite Kit Manufacturer Designation Bishop Bi-Seal 3 Bishop Bi-Seal 3 (see Section 1 for comments on this tape)

Bishop W962 Bishop W962 Kerite Friction Tape Kerite Friction Tape Glass Electrical Tape Permacel P212 Glass Electrical Tape (not Scotch 27)

I Silicone Rubber Tape Scotch 70 Silicone Tape "The Bishop Bi-Seal 3 tape has been subjected to radiaton and maintains its physical properties up to 0.1 megarads of exposure.

/

U A-122

i "The purpose of both terminals is to provide a lug seal to prevent the cable from breathing during normal thermal cycling allowing moisture to collect in the conductor ' l strands. The Bishop W962 tape will maintain its integrity during 40 years of normal service (both thermal and radiation aging) and a LOCA accident. The Bishop Bi-Seal 3, as stated in earlier conversations, starts to revert at radiation i levels above 1 megarad (0.1 includes safety factor).

Therefore, its performance cannot be guaranteed at levels above this, but our judgement is that it will still adequately seal the end of the cable."

sased on the above information, it is the position of FPC that the subject equipment is qualified for its current application.

i O -

O A-123

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS O ID NUMBER: RECORD NUMBER: 0107 SCEW PAGE NUMBER: 2-138 DESCRIPTION: SPLICE TERMINAL LOCATION:

PLANT WIDE MANUFACTURER: BURNDY TER EQUIPMENT NO.:

84 MODEL: INSULINK TER CATEGORY:

I.B SYSTEM: MT ELECTRICAL DISTRIBUTION ZONE LOCATION:

N/A TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL n

U QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

CORRECTIVE ACTION:

REPLACE.

CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER 1985 MAR NUMBER: 82-05-24-01 JUSTIFICATION FOR CONTINUED OPERATION:

SEE DISCUSSION FOLLOWING RECORD NO. 0104.

O A-124

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS U

ID NUMBER: FWV-14/15 RECORD NUMBER: 0062 2

SCEW PAGE NUMBER: 2-74 DESCRIPTION: VALVE MOTOR LOCATION:

OPERATOR TURBINE BLDG.

ELEV. 119'-0" MANUFACTURER: LIMITORQUE TER EQUIPMENT NO.:

08 MODEL: SMB-1 TER CATEGORY:

II.A SYSTEM: FW ZONE LOCATION:

N/A TER QUALIFICATION DEFICIENCIES NOTED:

2. EQUIP VS TEST SPECIMEN
3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED

~

QUALIFICATION STATUS:

QUALIFIED FOR CURRENT APPLICATION.

SEE DISCUSSION ATTACHED.

I CORRECTIVE ACTION:

l NOT APPLICABLE.

I CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

A-125

i-i DISCUSSION ON- k FWV 14/15 RECORD 0062 s,

'j '

Vendor correspondence (L200-3VC-007) indicates that Test Report B0003 (L200-3TR-003) applies to the equipment listed. As such, all environmental parameters are enveloped by testing and this valve is considered qualified for its current application.

i

o .

4 e

f 4 O

A-126

i t

FLORIDA POWER CORPORATION i

QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: FWV-29/30 RECORD NUMBER: 0063

, SCEW PAGE NUMBER: 2-76 DESCRIPTION: VALVE MOTOR LOCATION:

OPERATOR INTERMEDIATE BLDG.

ELEV. 119'-0" MANUFACTURER: LIMITORQUE TER EQUIPMENT NO.:

05 MODEL: SMB-4T TER CATEGORY:

II.A SYSTEM: FW ZONE LOCATION:

17 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL 2.' EQUIP VS TEST SPECIMEN
3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED 7A. PEAK TEMPERATURE O

QUALIFICATION STATUS:

QUALIFIED FOR CURRENT APPLICATION.

SEE DISCUSSION ATTACHED.

CORRECTIVE ACTION: -

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

l'M

() NOT REQUIRED.

A-127

n DISCUSSION ON FWV-29, 30; FWV-31, 32 RECORD 0063; 0064 Vendor correspondence (L200-3VC-007) indicates that Test Report B0003 (L200-3TR-003) applies to the equipment listed. Thus, the only remaining concern is that testing does not completely envelop the required accident profile. The accident profile has an initial temperature spike that returns below .the testing profile within 16 seconds. Because of the extremely short duration of this temperature peak, the equipment internals will not realize the higher intitial temperatures. Thus the temperature peak is not an actual concern and the equipment is considered qualified for its current application.

O .

A-128

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS O ID NUMBER: FWV-31/32 RECORD NUMBER: 0064 SCEW PAGE NUMBER: 2-77 DESCRIPTION: VALVE MOTOR LOCATION:

OPERATOR INTERMEDIATE BLDG.

ELEV. 119' - 0" MANUFACTURER: LIMITORQUE TER EQUIPMENT NO.:

05 MODEL: SMB-1 TER CATEGORY:

II.A SYSTEM: FW ZONE LOCATION:

17 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL
2. EQUIP VS TEST SPECIMEN
3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED 7A. PEAK TEMPERATURE O -

QUALIFICATION STATUS:

QUALIFIED FOR CURRENT APPLICATION.

SEE DISCUSSION FOR FWV 29 & 30, RECORD 0063.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

A-129

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS O ID NUMBER: FWV-33,34,35 & 36 RECORD NUMBER: 0065 2

SCEW PAGE NUMBER: 2-78 DESCRIPTION: VALVE MOTOR LOCATION:

OPERATOR INTERMEDIATE BLDG.

ELEV. 119'-0" MANUFACTURER: LIMITORQUE TER EQUIPMENT NO.:

25 MODEL: SMB-0 TER CATEGORY:

II.A SYSTEM: FW ZONE LOCATION:

17 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL O -

QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

l l

CORRECTIVE ACTION:

REPLACE MOTOR (34,35)

CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER 1985 MAR NUMBER: 82-05-24-06 JUSTIFICATION FOR CONTINUED OPERATION:

O SEE ATTACHED.

U A-130

JUSTIFICATION FOR CONTINUED OPERATION for 3

FWV-33, 34, 35, & 36 Limitorque Motorized Valve Operators TER Item 25 References

1) NRC Technical Evaluation Report, January, 1983.
2) FPC IE Bulletin 79-01B Response, November, 1981.
3) Field Inspection Report L200-WW-001.
4) Limitorque Test Report B0003.

Although no tests were performed on Limitorque operators with type BG insulation and red limit switches, the following justification for continued operation is provided:

1. A Limitorque Class B operator was tested for operability during HELB. Test conditions were a maximum 250 0F, 25 psig, and 2 x 10 7 rads (Reference 4). This valve operator was similar in construction to the operator on the feedwater valves.
2. Temperature rise calculations have shown that the Class B Limitorque is operable for the one minute requirement after HELB. Radiation is not considered since the total 4

integrated dose is equal to 1 x 10 rads which is considered mild.

3. The auxiliary feedwater inlet valves are required to mitigate the consequences of main steam line break. If the auxiliary feedwater system is inoperable, feed and bleed techniques can be used to remove decay heat from the reactor or main feedwater can be used to remove decay heat, if the main feedwater is available. Therefore, failure of these valves can, in the interim, be tolerated.

A-131

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: FWV-161/162 RECORD NUMBER: 0066 SCEW PAGE NUMBER: 2-79 DESCRIPTION: VALVE MOTOR LOCATION:

OPERATOR INTERMEDIATE BLDG.

ELEV. 95'-0" MANUFACTURER: LIMITORQUE TER EQUIPMENT NO.:

23 MODEL: SMB-00 TER CATEGORY:

II.A SYSTEM: FW ZONE LOCATION:

56 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL O

l QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

CORRECTIVE ACTION:

REPLACE MOTOR.

CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER 1985 MAR NUMBER: 82-05-24-06 JUSTIFICATION FOR CONTINUED OPERATION:

s SEE ATTACHED.

d A-132

JUSTIFICATION FOR CONTINUED OPERATION for i

FWV-161 and FWV-162 TER Item 23 References

1. Technical Specifications for Crystal River Unit 3.
2. Feedwater System Flow Diagram, FPC Drawing Number FD-302-081, Revision 28,
3. Environmental and Seismic Qualification Guide Specifications and Data, Section 4.
4. Limitorque Test Report B0003, "Limitorque Valve Actuator Qualification Report for Class lE Service Outside Containment".

In the interim between the present and the scheduled corrective action, the following justification for continued operation is provided:

1. These units have been walked down to obtain nameplate data and installation orientation. The motors are Reliance, Class B insulated, 125 volt D.C. motors; the electrical connections are hermetically sealed. Similar operators with similar insulation were satisfactorily tested in Reference 4.

i

2. Reference 2 shows there are redundant paths to provide

! secondary feedwater to both steam generators and control level in each.

3. Reference 1, Table 3.6-1 indicates closure time is not I critical for these valves; they are not considered isolation valves.
O A-133

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: FWV-33,34,35,36 RECORD NUMBER: 0067 2

SCEW PAGE NUMBER: 2-80 DESCRIPTION: LOCAL MOTOR LOCATION:

STARTER INTERMEDIATE BLDG.

ELEV. 119'-0" MANUFACTURER: ALLEN BRADLEY TER EQUIPMENT NO.:

86 MODEL: BULLETIN 205 TER CATEGORY:

II.A SYSTEM: FW ZONE LOCATION:

17 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

CORRECTIVE ACTION:

DURING EFIC INSTALLATION REMOVE FWV-33 & 36; RELOCATE FWV-34 & 35.

CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER 1985 MAR NUMBER: 82-05-24-02 JUSTIFICATION FOR CONTINUED OPERATION:

SEE JCO FOR ASV-5 (RECORD 012)

O A-134

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: FWV-161,162 RECORD NUMBER: 0068 SCEW PAGE NUMBER: 2-81 DESCRIPTION: LOCAL MOTOR STARTER LOCATION:

INTERMEDIATE BLDG.

ELEV. 95'-0" MANUFACTURER: ALLEN BRADLEY TER EQUIPMENT NO.:

86 MODEL: BULLETIN 205 TER CATEGORY:

II.A SYSTEM: FW ZONE LOCATION:

56 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL 1

0 -

QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

CORRECTIVE ACTION:

REMOVE DURING EFIC INSTALLATION.

CORRECTIVE ACTION SCHEDULE: REFUEL V, NOVEMBER 1985.

MAR NUMBER: 82-05-24-02 JUSTIFICATION FOR CONTINUED OPERATION:

SEE JCO FOR ASV-5 (RECORD 012).

A-135

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: FW-5,6 RECORD NUMBER: 0069

^

SCEW PAGE NUMBER: 2-82 DESCRIPTION: LOCAL CONTROL LOCATION:

STATION INTERMEDIATE BLDG.

ELEV. 119'-0" MANUFACTURER: FIELD FABRICATED TER EQUIPMENT NO.:

90 MODEL: G.E. TYPE UA202 SW.

G.E. TYPE UC212 LIGHT TER CATEGORY:

I.B SYSTEM: FW ZONE LOCATION:

17 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL O

QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

CORRECTIVE ACTION:

REMOVE.

CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER 1985 MAR NUMBER: 82-05-24-02 JUSTIFICATION FOR CONTINUED OPERATION:

SEE JCO FOR AS-1 (RECORD 013)

A-136

.- -. - --. .=. - .. - - - , . _ - _ ._ - =. _ _. . . _ . _ _ .

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS O ID NUMBER: FW-ll,12 RECORD NUMBER: 0070 SCEW PAGE NUMBER: 2-83 DESCRIPTION: LOCAL CONTROL LOCATION:

STATION INTERMEDIATE BLDG.

ELEV. 95'-0" MANUFACTURER: FIELD FABRICATED TER EQUIPMENT NO.:

90 MODEL: G.E. TYPE UA202 SW.

G.E. TYPE UC212 LIGHT TER CATEGORY:

I.B SYSTEM: FW ZONE LOCATION:

56 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL i ,

QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

CORRECTIVE ACTION:

REMOVE DURING EFIC INSTALLATION.

CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER 1985 MAR NUMBER: 80-10-66 JUSTIFICATION FOR CONTINUED OPERATION:

SEE JCO FOR AS-1 (RECORD 013) i O

l A-137

. ~ - -

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS O ID NUMBER: FW-3 & 4 RECORD NUMBER: 0071 SCEW PAGE NUMBER: 2-84 DESCRIPTION: TERMINAL BOX LOCATION:

INTERMEDIATE BLDG.

ELEV. 119' MANUFACTURER: FIELD FABRICATED TER EQUIPMENT NO.:

72 MODEL: STATES TYPE NT TERMINAL BLOCKS TER CATEGORY:

I.B SYSTEM: FW ZONE LOCATION:

17 TER QUALIFICATION DEFICIENCIES NOTED:

3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED O.

QUALIFICATION STATUS:

QUALIFIED FOR CURRENT APPLICATION.

SEE APPENDIX A.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

(>

A-138

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: FW-ll & 20 RECORD NUMBER: 0072 SCEW PAGE NUMBER: 2-85 DESCRIPTION: TERMINAL BOX LOCATION:

INTERMEDIATE BLDG.

ELEV. 95' MANUFACTURER: FIELD FABRICATED TER EQUIPMENT NO.:

75 MODEL: STATES TYPE NT TERMINAL BLOCKS TER CATEGORY:

I.B SYSTEM: FW ZONE LOCATION:

55 TER QUALIFICATION DEFICIENCIES NOTED:

3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED O

QUALIFICATION STATUS:

NOT IN SCOPE. SUBSEQUENT REVIEW SHOWS THESE ITEMS ARE LOCATED IN A MILD ENVIRONMENT. (ENVIRONMENTAL ZONE INDICATED ABOVE). SEE SECTION 2.2 DISCUSSION.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

A-139

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS O

V FW-22 RECORD NUMBER: 0073 ID NUMBER:

SCEW PAGE NUMBER: 2-86 DESCRIPTION: TERMINAL BOX LOCATION:

INTERMEDIATE BLDG.

ELEV. 119' MANUFACTURER: FIELD FABRICATED TER EQUIPMENT NO.:

72 MODEL: STATES TYPE NT TERMINAL BLOCKS TER CATEGORY:

I.B SYSTEM: FW ZONE LOCATION:

16 TER QUALIFICATION DEFICIENCIES NOTED:

3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED C) -

QUALIFICATION STATUS:

QUALIFIED FOR CURRENT APPLICATION. SEE APPENDIX A.

i i

CORRECTIVE ACTION:

NOT APPLICABLE. -

1 l

i CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

l O

l A-140 l

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: FW-312-FE RECORD NUMBER: 0074 FW-313-FE ,

SCEW PAGE NUMBER: 2-87A DESCRIPTION: FLOW ELEMENT LOCATION:

INTERMEDIATE BLDG.

ELEV. 119' MANUFACTURER: CONTROLATION TER EQUIPMENT NO.:

43 MODEL:

TER CATEGORY:

I.B SYSTEM: FW ZONE LOCATION:

19/20-RESP TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL O

QUALIFICATION STATUS:

(NOT INSTALLED YET. )

CORRECTIVE ACTION:

(INSTALLATION.)

CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER 1985 MAR NUMBER: 80-10-66-05 JUSTIFICATION FOR CONTINUED OPERATIOh.

NOT REQUIRED.

A-141

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS p) t

~~'

ID NUMBER: MSV-55 & 56 RECORD NUMBER: 0075 SCEW PAGE NUMBER: 2-88 DESCRIPTION: VALVE MOTOR LOCATION:

OPERATOR INTERMEDIATE BLDG.

ELEV. 119' MANUFACTURER: LIMITORQUE TER EQUIPMENT NO.:

23 MODEL: SMB-0-15 TER CATEGORY:

II.A SYSTEM: MS ZONE LOCATION:

16 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

CORRECTIVE ACTION:

REPLACE MCTOR.

CORRECTIVE ACTION SCHEDULE: REFUEL V, NOVEMBER 1985 MAR NUMBER: 82-05-24-06 JUSTIFICATION FOR CONTINUED OPERATION:

SEE ATTACHED.

A-142

/7 DISCUSSION ON U MSV 55 & 56 Record 0075 A walkdown was conducted for this valve and the results (L200-WW-001) show this actuator has a D.C. motor with Class B insulation. The vendor was contacted and requested to identify activities required to upgrade this actuator such that I

Qualification Report B0009 (L200-3TR-008) would apply, thereby encompassing the environmental specifications for Zone 14. The vendor response (L200-3vC-008) indicates a motor replacement with a Peerless D.C. motor with Class RH insulation will be required.

L O

i l

l l .

l .

O A-143

. = _ . _ _ . _ . .

JUSTIFICATION FOR CONTINUED OPERATION for MSV-55 & 56 Limitorque Motor Operator TER Item 23 References

1) Limitorque Report No. B0003, dated 5/76.

Qualification deficiencies will be resolved by November, 1985.

In the interim between the present time and corrective action, the following justification for continued operation is given:

1. Walkdown data has shown that these valve operators have Class B, D.C. motors, gray limit switches, and red torque 10 7 switches. Reference 1 indicates qualification of rads. Specified radiation and pressure are below tested values and capability is, therefore, demonstrated.

Equipment temperature rise calculations have shown that the equipment temperature will remain at or below qualification temperature for the required valve operating time.

l t

O y

A-144 I

l

-- - - - - - . + w - - - , . * , .-_.-_,,__,g,, , , , , , , , _ ,

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS O ID NUMBER: MSV-55 & 56 RECORD NUMBER: 0076 SCEW PAGE NUMBER: 2-89 DESCRIPTION: LOCAL MOTOR LOCATION:

STARTER INTERMEDIATE BLDG.

ELEV. 119' MANUFACTURER: ALLEN BRADLEY TER EQUIPMENT NO.:

86 MODEL: BULLETIN 205 TER CATEGORY:

II.A SYSTEM: MS ZONE LOCATION:

16 TER QUALIFICATION DEFICIENCIES NOTED:

! 1. DOCUMENTED EVIDENCE OF QUA".

O QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

[ CORRECTIVE ACTION:

RELOCATE STARTERS TO MILD ENVIRONMENT.

l CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER 1985 MAR NUMBER: 82-05-24-02 JUSTIFICATION FOR CONTINUED OPERATION:

SEE JCO FOR ASV-5 (RECORD 012)

A-145

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: MSV-411,412, RECORD NUMBER: 0077 413,414-SV1,2,3, '

5,6 SCEW PAGE NUMBER: 2-90 DESCRIPTION: SOLENOID VALVE LOCATION:

INTERMEDIATE BLDG.

ELEV. 119' MANUFACTURER: ASCO TER EQUIPMENT NO.:

35 MODEL: HT8320A34V,A20V TER CATEGORY:

I.B SYSTEM: MS ZONE LOCATION:

17/16-RESP TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL

-w QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

CORRECTIVE ACTION:

REPLACE VALVE PARTS CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER 1985 MAR NUMBER: 82-05-24-03 JUSTIFICATION FOR CONTINUED OPERATION:

~g SEE ATTACHED.

u)

A-146

O JUSTIFICATION FOR CONTINUED OPERATION v for MSV-411, 412, 413, 414-SV1, 2, 3 TER Item 35 References

1) FPC Environmental Qualification of Class lE Equipment IE Bulletin 79-OlB Qualification Summary.

In the interim between the present and scheduled corrective action, the following justification for continued operation, as previously provided in Reference 1, is given:

1. Investigations with the manufacturer indicate the solenoid valves are good for 10 5 rads. Accident conditions will not affect the components for the period of operaLility required. Also, due to the location of the component when required to perform its safety function, the accident environment has no impact.
2. Due to the period of operability required as per CR#3 Tech.

Spec. Table 3.6-1 to perform their safety function, and the fact that the total radiation exposure per the SCEW sheets is conservative in regard to the 5-1/2 year operating life of the plant, these valves are not considered to be a restraint to the safe operation of CR#3.

O l

A-147 I

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS O ID NUMBER: MS-5 & 6 RECORD NUMBER: 0078 a

^

SCEW PAGE NUMBER: 2-93 DESCRIPTION: LOCAL CONTROL LOCATION:

STATION INTERMEDIATE BLDG.

ELEV. 119' MANUFACTURER: FIELD FABRICATED TER EQUIPMENT NO.:

90 MODEL: G.E. TYPE UA202 SW.

G.E. TYPE UC212 LIGHT TER CATEGORY:

I.B SYSTEM: MS ZONE LOCATION:

16/17-RESP TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL 1

I QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

CORRECTIVE ACTION:

RELOCATE TO MILD j ENVIRONMENT.

l CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER 1985 l

MAR NUMBER: 82-05-24-02 JUSTIFICATION FOR CONTINUED OPERATION:

SEE JCO FOR AS-1 (RECORD 013)

O A-148

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: MS-5 & 6 RECORD NUMBER: 0079 SCEW PAGE NUMBER: 2-98 DESCRIPTION: TERMINAL BOX LOCATION:

INTERMEDIATE BLDG.

ELEV. 119' MANUFACTURER: FIELD FABRICATED TER EQUIPMENT NO.:

67 MODEL: STATES TYPE NT TERMINAL BLOCKS TER CATEGORY:

I.B SYSTEM: MS ZONE LOCATION:

16 TER QUALIFICATION DEFICIENCIES NOTED:

3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED QUALIFICATION STATUS:

QUALIFIED FOR CURRENT APPLICATION.

SEE APPENDIX A.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

O A-150 r- - , . _ ---, . . - - , , - ,, - , . - - - - - . . - , , - - . , , , , , , - , ., _..,...-_n, , ,

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS n ID NUMBER: MS-7 RECORD NUMBER: 0080 SCEW PAGE NUMBER: 2-99 DESCRIPTION: TERMINAL BOX LOCATION:

INTERMEDIATE BLDG.

ELEV. 95' MANUFACTURER: FIELD FABRICATED TER EQUIPMENT NO.:

72 MODEL: STATES TYPE NT TERMINAL BLOCKS TER CATEGORY:

I.B SYSTEM: MS ZONE LOCATION:

21 TER QUALIFICATION DEFICIENCIES NOTED:

3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED O

U QUALIFICATION STATUS:

NOT IN SCOPE. ASSOCIATED EQUIPMENT (MSV 130) REMOVED FROM MASTER LIST.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

O A- 15 0

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: MS-8 RECORD NUMBER: 0081 a

SCEW PAGE NUMBER: 2-100 DESCRIPTION: TERMINAL BOX LOCATION:

AUXILIARY BLDG.

ELEV. 119' MANUFACTURER: FIELD FABRICATED TER EQUIPMENT NO.:

NA MODEL: STATES TYPE NT TERMINAL BLOCKS TER CATEGORY:

N/A SYSTEM: MS ZONE LOCATION:

21 TER QUALIFICATION DEFICIENCIES NOTED:

NOT INCLUDED IN EVALUATION G

QUALIFICATION STATUS:

QUALIFIED FOR CURRENT APPLICATION.

SEE APPENDIX A.

CORRECTIVE ACTION: ,

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

O A-151

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS O

\~ ID NUMBER: MS-17 RECORD NUMBER: 0082 SCEW PAGE NUMBER: 2-101 DESCRIPTION: TERMINAL BOX LOCATION:

INTERMEDIATE BLDG.

ELEV. 119' MANUFACTURER: FIELD FABRICATED TER EQUIPMENT NO.:

72 MODEL: STATES TYPE NT TERMINAL BLOCKS TER CATEGORY:

I.B SYSTEM: MS ZONE LOCATION:

17 TER QUALIFICATION DEFICIENCIES NOTED:

3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED QUALIFICATION STATUS:

QUALIFIED FOR CURRENT APPLICATION.

SEE APPENDIX A.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

O v

A-152

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: MS-18 RECORD NUMBER: 0083 SCEW PAGE NUMBER: 2-102 DESCRIPTION: TERMINAL BOX LOCATION:

INTERMEDIATE BLDG.

ELEV. 119' MANUFACTURER: FIELD FABRICATED TER EQUIPMENT NO.:

72 MODEL: STATES TYPE NT TERMINAL BLOCKS TER CATEGORY:

I.B SYSTEM: MS ZONE LOCATION:

16 TER QUALIFICATION DEFICIENCIES NOTED:

3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED O -

QUALIFICATION STATUS:

QUALIFIED FOR CURRENT APPLICATION.

SEE APPENDIX A.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

A-153

i FLORIDA POWER CORPORATION '

QUALIFICATION STATUS

SUMMARY

SHEETN O ID NUMBER: MS-92-PS1 & 2 RECORD NUMBER: 0084 (SEE NOTE 3) .

SCEW PAGE NUMBER: 2-103 DESCRIPTION: PRESS SWITCH LOCA? ION:

INTERMEDIATE BLDG.

ELEV. 119' MANUFACTURER: STATIC-O-RING TER EQUIPMENT NO.: -

39 -

MODEL: 9R2YYSNCXJ TER CATEGORY:

1.B SYSTEM: MS '

ZONE LOCATION:

16 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL O

QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

CORRECTIVE ACTION:

REPLACE.

CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER 1985 MAR NUMBER: 80-10-66-05 JUSTIFICATION FOR CONTINUED OPERATION:

SEE ATTACHED.

A-154

JUSTIFICATION FOR CONTINUED OPERATION for ,

MS-92-PS1 & 2 Static-O-Ring Pressure Switches TER Item 39 References

1) FPC 79-OlB Response, pg.'2-103 4
2) .FPC 79-OlB Response, Figure 4-4
3) FPC Crystal River FSAR, Table 14-19a
4) Wyle Test Report No. 44296-2, " Qualification Report for Two (2) Static-O-Ring Pressure Switches Model 7828-100...",

l- dated November, 1978.

5) FPC Crystal River FSAR, Section 10.2.1.4 & 14.2.2.1 The main steam pressure switches will be replaced during the emergency feedwater upgrade prior to November, 1985 or their d function will be performed by qualified equipment which will be installed by November, 1985.

In the interim between the present and November, 1985, the following jus.tifications for continued operation are given:

1. The main steam line pressure switches operate in a rela-tively mild radiation environment during accident

~

4

'cond itions . The 1.0 x 10 radiation level will not contri-l bute to failure of the switches.

2. Refer'ences 3 and 5 indicate main steam stop and isolation i valves closing times of 'a pproximately 7.0 seconds or less.

Main feedwater valves close in 34 seconds. The valves close on receipt of a signal' from the pressure switches. Feed-water isolation is also initiated by reactor trip which

!O A-155

occurs at 6.5 seconds into the transient. The pressure p

r switches must, therefore, operate for a period of less than

(/ 7.0 seconds into the transient.

Temperature (Reference 1) increases to 350 F then decreases to 250 F within 7 seconds following the transient. Maximum pressure is 19.15 psig. Reference 4 indicates operability to 14 seconds at 285 F and 37 psig after the testing tran-sient. Due to the short duration of the transient and the evidence presented in the pressure switch test report, there is reasonable assurance that the pressure switches will perform as specified during a main steam line break.

3. Failure of the pressure switches can be tolerated since tur-bine stop valves will close on reactor trip in addition to low steam line pressure. The accident analysis (Refer-ence 5) is based on turbine stop valve closure to terminate the transient. As mentioned above, feedwater isolation is redundant because a reactor trip signal will also close the

(} feedwater valves in addition to the main steam low pressure signal.

l l

l I

l l

I C-A-156

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS O ID NUMBER: MTMC-3 RECORD NUMBER: >J85 SCEW PAGE NUMBER: 2-104 DESCRIPTION: MOTOR CONTROL CENTER LOCATION:

AUXILIARY BLDG.

ELEV. 95' MANUFACTURER: ALLEN BRADLEY TER EQUIPMENT NO.:

95 MODEL: BULLETIN 798 TER CATEGORY:

I.B SYSTEM: MT ZONE LOCATION:

15/35 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL C\

U QUALIFICATION STATUS:

QUALIFIED FOR CURRENT APPLICATION.

SEE DISCUSSION ATTACHED.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

A-157

DISCUSSION ON MTMC 3; MTMC 7

~

4 Allen Bradley Motor Control Centers Records 0085; 0088 The materials of construction were analyzed to determine their susceptibility to radiation and thermal degradation. This evaluation concluded that various subcomponents were not qualified for the entire plant life. However, these subcomponents are suitable for plant service in their current

! location for a minimum of 20 years. Therefore, the components identified in the evaluation (summarized below) will be replaced or the entire MCC relocated (whichever is most cost effective at the time of modification) prior to the 20th year of plant service. Florida Power Corporation considers this equipment qualified for its current application for a period of 20 years.

The evaluation concluded that nylon materials are not suitable for 40 years in the specified environmental conditions. These

materials under various trade names are

Fosta 523 - Manufacturer's Codes - R, QQ, WW I Nylatron GSHS - Manufacturer's Codes - S Celanese 1000 Manufacturer's Codes - RR l Fosta 512 - Manufacturer's Codes - SS Other material susceptible to the radiation age related degradation are paper and fibre products designated as:

Kraft Paper - Manufacturer's Codes - CC 3M #4 - Manufacturer's Code - EE, DD Fish Paper -

Rag Insulating Paper - Manufacturer's Code - BB "ulcanized Fibre - Manufacturer's Code - A, TT O

A-158

The following is a summary of parts of the motor control centers with a potential to radiation age related degradation:

a e Cover reset assembly, Part No. Z20174 e Sizes 1 & 2 starters operating coils, Part No. 71A86 and 72A86 (if not replaced with the motor starter) e Size 3 starters operating coils, Part No. 73A86 (if not replaced with the motor starter) e 2 pole, open type "C" relay, Part No. 700-C0202A1 8 pole, type "N" relay, Part No. 700-N800Al e

e #84AB86 operating coil for relay - Components 40099-302-02 (if not replaced with the entire relay) l The following is a summary of parts of the motor control centers with a potential to radiation and thermal related degradation:

e size 3 coil cover with interlock, Part No. X230933 e Size 1 motor starter, Part No. X234345 e Size 2 motor starter, Part No. X234516 e Size 3 motor starter, Part No. X234579 ,

a Size 4 motor starter, Part No. X266926 e Motor starters, Part No. X266949 e Adj. overload reset button, Part No. Z20811 e Auxiliary switch operating lever, Part No. F24524 e Operating lever, Part No. F24523 e Operating lever, Part No. F24306 e Bussman fuses, Part No X276124, X276127, X276132, X276126, E276120 i

A-159

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS O ID NUMBER: MTMC-5 RECORD NUMBER: 0086 SCEW PAGE NUMBER: 2-106 DESCRIPTION: MOTOR CONTROL CENTER LOCATION:

AUXILIARY BLDG.

ELEV. 119' MANUFACTURER: ALLEN BRADLEY TER EQUIPMENT NO.:

MODEL: BULLETIN 798 TER CATEGORY:

N/A SYSTEM: MT ZONE LOCATION:

24 TER QUALIFICATION DEFICIENCIES NOTED:

NOT INCLUDED IN EVALUATION QUALIFICATION STATUS:

NOT IN SCOPE. SUBSEQUENT REVIEW SHOWS THESE ITEMS ARE LOCATED IN A MILD ENVIRONMENT. (ENVIRONMENTAL ZONE INDICATED ABOVE.) SEE SECTION 2.2 DISCUSSION.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED, A-160

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS O ID NUMBER: MTMC-6 RECORD NUMBER: 0087 SCEW PAGE NUMBER: 2-107 DESCRIPTION: MOTOR CONTROL CENTER LOCATION:

AUXILIARY BLDG.

ELEV. 95' MANUFACTURER: ALLEN BRADLEY TER EQUIPMENT NO.:

94 MODEL: BULLETIN 798 TER CATEGORY:

I.B SYSTEM: MT ZONE LOCATION:

5 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL O

QUALIFICATION STATUS:

NOT IN SCOPE. SUBSEQUENT REVIEW SHOWS THESE ITEMS ARE LOCATED IN A MT.LD ENVIRONMENT. (ENVIRONMENTAL ZONE INDICATED ABOVE.) SEE SECTION 2.2 DISCUSSION.

CORRECTIVE ACTION:

NOT APPLICABLE.

l CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

p% )

A-161

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SEEETS ID NUMBER: MTMC-7 RECORD NUMBER: 0083 SCEW PAGE NUMBER: 2-108 DESCRIPTION: MOTOR CONTROL CENTER LOCATION:

AUXILIARY BLDG.

ELEV. 119' MANUFACTURER: ALLEN BRADLEY TER EQUIPMENT NO.:

95 MODEL: BULLETIN 798 TER CATEGORY:

I.B SYSTEM: MT ZONE LOCATION:

28 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL

~

QUALIFICATION STATUS:

QUALIFIED FOR CURRENT APPLICATION.

SEE DISCUSSION FOR MTMC-3, RECORD 0085.

CORRECTIVE ACTION: .

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

! MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

A-162

FLORIDA POWER CORPORATION ,

QUALIFICATION STATUS

SUMMARY

SHEETS

( ID NUMBER: MTBD-2A RECORD NUMBER: 0089 a

SCEW PAGE NUMBER: 2-113 DESCRIPTION: ELECTRICAL PENETRA- LOCATION:

TION ASSEMBLY R.B. WALL QUAD 1 ELEV. 136' MANUFACTURER: CONAX TER EQUIPMENT NO.:

76 MODEL: CANISTER TYPE TER CATEGORY:

IV SYSTEM: MT ZONE LOCATION:

39 TER QUALIFICATION DEFICIENCIES NOTED:

i

! QUALIFICATION STATUS:

QUALIFIED FOR CURRENT APPLICATION.

SEE DISCUSSION ATTACHED.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

, N_/

l A-163

DISCUSSION ON Conax Canister Type Electric Penetration Assemblies References

1) Conax Report IPS-769, " Feasibility Study Electric

' Penetration Qualification Crystal River - Unit 3".

2) Conax Report, IPS-499.2, " Design Qualification Report for Kulka Terminal Blocks, Type 7TB, Glass Fiber Filled Alkyd Materials".
3) Conax Report, IPS-585.1, " Test Report -

Qualification of Medium Voltage Power Service Classification Electric Penetration (BF-ll) " .

4) Conax Report, IPS-16, "Specificatien for Type Qualification of Electric Penetration Sub-Assemblies for Crystal River Plant - Unit No. 3, Florida Power Corporation".

[ 5) Conax Report, IPS-353.2, " Design Qualification Report for a Conax Low Voltage Control Feedthrough Assembly".

FPC has reviewed the references indicated and concludes that the electric penetration assemblies in use at Crystal River Unit 3 are qualified for their current application.

Walkdowns are being completed to confirm compliance with recommendations listed in Reference 1.

O A-164

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS U-~ ID NUMBER: MTBD-2B RECORD NUMBER: 0090 SCEW PAGE NUMBER: 2-114 DESCRIPTION: ELECTRICAL PENETRA- LOCATION:

TION ASSEMBLY R.B. WALL QUAD 4 ELEV. 137' MANUFACTURER: CONAX TER EQUIPMENT NO.:

76 MODEL: CANISTER TYPE TER CATEGORY:

IV SYSTEM: MT ZONE LOCATION:

39 TER QUALIFICATION DEFICIENCIES NOTED:

O QUALIFICATION STATUS:

QUALIFIED FOR CURRENT APPLICATION.

SEE DISCUSSION FOR MTBD-2A, RECORD 0089.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

A-165

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: NTBD-2C RECORD NUMBER: 0091 SCEW PAGE NUMBER: 2-115 DESCRIPTION: ELECTRICAL PENETRA- LOCATION:

TION ASSEMBLY R.B. WALL QUAD 3 ELEV. 146' MANUFACTURER: CONAX TER EQUIPMENT NO.:

76 MODEL: CANISTER TYPE TER CATEGORY:

IV SYSTEM: MT ZONE LOCATION:

39 TER QUALIFICATION DEFICIENCIES NOTED:

O QUALIFICATION STATUS:

SEE DISCUSSION FOR MTBD-2A, RECORD 0089.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

A-166

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS

~

ID NUMBER: MTBD-8A RECORD NUMBER: 0092 SCEW PAGE NUMBER: 2-116 DESCRIPTION: ELECTRICAL PENETRA- LOCATION:

TION ASSEMBLY R.B. WALL QUAD 1 ELEV. 136' MANUFACTURER: CONAX TER EQUIPMENT NO.:

76 MODEL: CANISTER TYPE TER CATEGORY:

IV SYSTEM: MT ZONE LOCATION:

39 TER QUALIFICATION DEFICIENCIES NOTED:

O -

QUALIFICATION STATUS:

SEE DISCUSSION FOR MTBD-2A, RECORD 0089.

l CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED, A-167

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS

~2D NUMBER: MTBD-8B RECORD NUMBER: 0093 SCEW PAGE NUMBER: 2-117 DESCRIPTION: ELECTRICAL PENETRA- LOCATION:

TION ASSEMBLY R.B. WALL QUAD 3 ELEV. 146' MANUFACTURER: CONAX TER EQUIPMENT NO.:

76 MODEL: CANISTER TYPE

!, TER CATEGORY:

IV SYSTEM: MT ZONE LOCATION:

39 TER QUALIFICATION DEFICIENCIES NOTED:

)

CJ QUALIFICATION STATUS:

SEE DISCUSSION FOR MTBD-2A, RECORD 0089.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

A-168

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS O ID NUMBER: MTBD-8C & 8D RECORD NUMBER: 0094 SCEW PAGE NUMBER: 2-118 DESCRIPTION: ELECTRICAL PENETRA- LOCATION:

TION ASSEMBLY R.B. WALL QUAD 4 ELEV. 137' MANUFACTURER: CONAX TER EQUIPMENT NO.:

76 MODEL: CANISTER TYPE TER CATEGORY:

IV SYSTEM: MT ZONE LOCATION:

39 TER QUALIFICATION DEFICIENCIES NOTED:

QUALIFICATION STATUS:

SEE DISCUSSION FOR MTBD-2A, RECORD 0089.

-CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

A-169

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS O ID NUMBER: MTBD-9A & 9B RECORD NUMBER: 0095 SCEW PAGE NUMBER: 2-119 DESCRIPTION: ELECTRICAL PENETRA- LOCATION:

TION ASSEMBLY R.B. WALL QUAD 1 ELEV. 133' MANUFACTURER: CONAX '

TER EQUIPMENT NO.:

76 MODEL: CANISTER TYPE TER CATEGORY:

IV SYSTEM: MT ZONE LOCATION:

39 TER QUALIFICATION DEFICIENCIES NOTED:

O QUALIFICATION STATUS:

SEE DISCUSSION FOR MTBD-2A, RECORD 0089.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

A-170

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: MTBD-9C & 9D RECORD NUMBER: 0096 SCEW PAGE NUMBER: 2-120 DESCRIPTION: ELECTRICAL PENETRA- LOCATION:

TION ASSEMBLY R.B. WALL QUAD 1 ELEV. 129' MANUFACTURER: CONAX TER EQUIPMENT NO.:

76 MODEL: CANISTER TYPE TER CATEGORY:

IV SYSTEM: MT ZONE LOCATION:

39 TER QUALIFICATION DEFICIENCIES NOTED:

n (v) l QUALIFICATION STATUS:

SEE DISCUSSION FOR MTBD-2A, RECORD 0089.

CORRECTIVE ACTION:

l NOT APPLICABLE.

1 CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

l A-171

.-__.__z . __ _ . -- . - . . . - ._ - _ _ - . _ _ _ _ _ . - - - _ - _ _ _ _ _ _ _ , . - - .

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS O ID NUMBER: MUP-1A,lB,1C RECORD NUMBER: 0108 SCEW PAGE NUMBER: 2-141 DESCRIPTION: PUMP MOTOR LOCATION:

AUXILIARY BLDG.

ELEV. 95' MANUFACTURER: WESTINGHOUSE TER EQUIPMENT NO.:

59 MODEL: 688.5"S" " CSP" TER CATEGORY:

II.A SYSTEM: MU ZONE LOCATION:

1 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDEFCE OF QUAL O

i QUALIFICATION STATUS:

I QUALIFIED FOR CURRENT APPLICATION.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

A-172

DISCUSSION ON MUP 1A, 18, 1C 3

Westinghouse Motors Record 0108 References

1) WCAP 8754 " Environmental Qualification of Class lE Motors for Nuclear Out-of-Containment Use" dated June, 1976.

Although these motors were purchased prior to the issuance of IEEE 323 1971, they are similar in design to motors tested in the reference indicated.

The harsh environment is limited to radiation since the motor need only operate for conditions inside containment, and its location is outside containment.

The total integrated dose for these motors is 1.2 x 10 6 R (40 year TID of 1.2 x 10 6R plus five day post accident exposure of 3.7 x 104 R). Since the integrated dose for lifetime is significantly greater than the dose received during the accident, the radiation i

susceptibility of motor components if any, should be detectable via periodic surveillances.

l Currently, the motors are tested and inspected annually (PM-105 )

for abnormalities. This equipment is also tested quarterly in the ISI program (SP-340) and is periodically (18 month intervals) functionally tested.

FPC feels there are adequate surveillances on this equipment and considers it qualified for its current application.

1 l

O C

A-173 l

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS O ID NUMBER: MUP-1A,lB & 1C RECORD NUMBER: 0109 SCEW PAGE NUMBER: 2-141A DESCRIPTION: LUBRICANT LOCATION:

AUXILIARY BLDG, ELEV. 95' MANUFACTURER: GULF TER EQUIPMENT NO.:

59 MODEL: GULF CREST 32 TER CATEGORY:

II.A SYSTEM: MU ZONE LOCATION:

1 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL O

QUALIFICATION STATUS:

ADDRESSED GENERICALLY VIA PM PROGRAM l

(PM-133). SEE APPENDIX A.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

1 l A-174 l

l

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS O

V ID NUMBER: MUV-18 RECORD NUMBER: 0110 SCEW PAGE NUMBER: 2-142 DESCRIPTION: VALVE MOTOR LOCATION:

OPERATOR AUXILIARY BLDG.

ELEV. 119' MANUFACTURER: LIMITORQUE TER EQUIPMENT NO.:

21 MODEL: SMB-00 TER CATEGORY:

II.A SYSTEM: MU ZONE LOCATION:

22 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL
2. EQUIP VS TEST SPECIMEN
3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED
10. RADIATION EXPOSURE O .

QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS. SEE DISCUSSION ATTACHED.

CORRECTIVE ACTION:

REPLACE MOTOR.

CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER, 1985.

MAR NUMBER: 82-05-24-06 JUSTIFICATION FOR CONTINUED OPERATION:

SEE ATTACHED.

A-175

DISCUSSION ON MUV 18 Record 0110 '

Vendor correspondence (L200-3VC-005) indicates that Test Report 600198 plus Addendum 1 are applicable to this valve motor operator. A walkdown was conducted and the results (L200-WW-001) show these actuators have Reliance motors with Class H insulation. The vendor was contacted with walkdown results and regtested to identify activities required to upgrade these actuators such that Qualification Report B0003 (L200-3TR-003) would apply, thereby ensuring radiation would not be a concern.

The vendor response (L200-3VC-008) indicates it would be necessary to replace the motors with Class RH insulated motors.

O

. O A-176

JUSTIFICATION FOR CONTINUED OPERATION

, for MUV 18 4 TER Item 21 References

1) Technical Specifications for Crystal River Unit 3.
2) Make up and Purification Flow Diagram, FPC Drawing Number FD-302-661, Revision 33.
3) Environmental and Seismic Qualification Guide Specifications and Data, Section 4 (draft).

In the interim between the present and scheduled upgrades, the following justification for continued operation is given.

This valve isolates Reactor Coolant Pump seal injection. There are manually operated valves upstream that can be used to serve the same function. Reference 1 indicates that closure time is not critical. Therefore, the safe operation of CR3 is not jeopardized in the interim.

l l

l i

l O

A-177

FLO2IDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS O

"' 0111 ID NUMBER: MUV-23 & 24 RECORD NUMBER:

SCEW PAGE NUMBER: 2-143 DESCRIPTION: VALVE MOTOR LOCATION:

OPERATOR AUXILIARY BLDG.

ELEV. 95' MANUFACTURER: LIMITORQUE TER EQUIPMENT NO.: ,

20 MODEL: SMB-00-25 TER CATEGORY:

II.A SYSTEM: MU ZONE LOCATION:

3 TER QUALIFICATION DEFICIENCIES NOTED:

2. EQUIP VS TEST SPECIMEN
3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED O

QUALIFICATION STATUS:

QUALIFIED FOR CURRENT APPLICATION.

SEE DISCUSSION ATTACHED.

l l

CORRECTIVE ACTION

1 NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

A-178

i DISCUSSION ON MUV 23 & 24 4

Record 0111 Correspondence from Limitorque (L200-3vC-007) indicates that l Qualification Report 80003 (L200-3TR-003) applies to these

actuators. Review of this report indicates all environmental i parameters for Zone 3 are encompassed by testing. This equipment is considered qualified for its current application.

O i

I l

t

!O l

A-179

FLO3IDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS O ID NUMBER: MUV-25 & 26 RECORD NUMBER: 0112 SCEW PAGE NUMBER: 2-144 DESCRIPTION: VALVE MOTOR LOCATION:

OPERATOR AUXILIARY BLDG.

ELEV. 95' MANUFACTURER: LIMITORQUE TER EQUIPMENT NO.:

20 MODEL: SMB-00-25 TER CATEGORY:

II.A SYSTEM: MU ZONE LOCATION:

3 TER QUALIFICATION DEFICIENCIES NOTED:

2. EQUIP VS TEST SPECIMEN
3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED O -

QUALIFICATION STATUS:

QUALIFIED FOR CURRENT APPLICATION.

SEE DISCUSSION ATTACHED.

l CORRECTIVE ACTION:

NOT APPLICABLE.

l CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

l JUSTIFICATION FOR CONTINUED OPERATION:

( NOT REQUIRED.

l A-180 l - _ _ . . . _ . _ __

DISCUSSION ON MUV 25 & 26 Record 0112 2 Correspondence from Limitorque (L200-3VC-007) indicates that Qualification Report B0003 (L200-3TR-003) applies to these actuators. Review of this report indicates all environmental parameters for Zone 3 are encompassed by testing. This equipment is considered qualified for its current application.

O i

l l

O

A-181

\

FLORIDA POWER CORPORATION ,

QUALIFICATION STATUS

SUMMARY

SHEETS O ID NUMBER: MUV-27 RECORD NUMBER: 0113 SCEW PAGE NUMBER: 2-145 DESCRIPTION: VALVE MOTOR LOCATION:

OPERATOR AUXILIARY BL'DG.

ELEV. 95' '

MANUFACTURER: LIMITORQUE TER EQUIPMENT NO.:

20 MODEL: SMB-00-10 TER CATEGORY:

II.A i SYSTEM: MU ZONE LOCATION:

3 TER QUALIFICATION DEFICIENCIES NOTED:

2. EQUIP VS TEST SPECIMEN
3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED O -

QUALIFICATION STATUS:

QUALIFIED FOR CURRENT APPLICATION.

SEE DISCUSSION ATTACHED. ,

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

A-182

DISCUSSION ON MUV 27 ,,

Record 0113 e i

1

}' , s a Correspondence from Limitorque (L200-3VC-007) indicates that Qualification Report 80003 (L200-3TR-003) applies to these actuators. Review of this report , indicates all environmental parameters for Zone 3 are encompassed by testing. This equipment 4< is considered qualified for its current application.

(

4 I

o j 4

' 1 ;

s

~

' t.

's 5

E e i

\

l'

\

7

^

1 a

O A-183

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEET 9 ID NUMBER: MUV-40 & 41 RECORD NUMBER: 0114 SCEW PAGE NUMBER: 2-147 '

DESCRIPTION: VALVE MOTOR LOCATION:

OPERATOR CONTAINMENT ELEV.

102.3' MANUFACTURER: LIMITORQUE TER EQUIPMENT NO.:

13 MODEL: SMB-00-5 TER CATEGORY:

II.A SYSTEM: MU ZONE LOCATION:

38 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL
2. EQUIP VS TEST SPECIMEN
3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED
10. RADIATION EXPOSURE O

QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS. SEE DISCUSSION ATTACHED.

CORRECTIVE ACTION:

REPLACE MOTOR.

CORRECTIVE ACTION SCHEDULE: REFUEL V, NOVEMBER 1985.

MAR NUMBER: 82-05-24-06 JUSTIFICATION FOR CONTINUED OPERATION:

SEE ATTACHED.

A-184

DISCUSSION ON V MUV 40 & 41 Record 0114 2 A walkdown was conducted for this equipment to obtain nameplate data and shop order data to attest to the equipments' qualification. The vendor was contacted with walkdown results and requested to identify activities required to upgrade these actuators such that Qualification Report 600456 (L200-3TR-001) would apply, thereby ensuring all environmental parameters for Zo,ne 38 are encompassed by testing. The vendor response (L200-3VC-008) indicates it would be necessary to replace the motors with Class RH motors and add a grease relief valve.

O l

O A-185

,- . . , - - , . -.,,r_ . - . , - - ~ - - . - ~ , , - _ , , , - , , , , . . . - , - - - ~ , . . - . . . , . - . - -

JUSTIFICATION FOR CONTINUED OPERATION O for MUV 40 & 41 2 TER Item 13 References _

1) Technical Specifications for Crystal River Unit 3.
2) Makeup and Purification Flow Diagram, FPC Drawing Number FD-302-661, Revision 33.
3) Environmental and Seismic Qualification Guide Specifications and Data, Section 4 (draft).

In the interim between the present and scheduled upgrade, the following justification for continued operation is given.

MUV 40 and 41 are isolation valves for letdown coolers 3A and 3B, respectively. They are located inside containment and their s function is containmen,t isolation. The letdown lines join downstream of MUV 40 and 41 and penetrate containment via penetration #333. Outside containment the line is isolable via MUV 49.

Since there is a redundant means of isolation for this line, interim operation does not jeopardize the safe operation of Crystal River Unit 3.

I A-186

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS  ;

ID NUMBER: MUV-53 & 257 RECORD NUMBER: 0115 SCEW PAGE NUMBER: 2-148 DESCRIPTION: VALVE MOTOR LOCATION:

OPERATOR AUXILIARY BLDG.

ELEV. 95' MANUFACTURER: LIMITORQUE TER EQUIPMENT NO.:

22 MODEL: SMB-00-15 TER CATEGORY:

II.A SYSTEM: MU ZONE LOCATION:

15 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL
2. EQUIP VS TEST SPECIMEN
3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED
10. RADIATION EXPOSURE QUALIFICATION STATUS:

NOT IN SCOPE. SUBSEQUENT REVIEW SHOWS THESE ITEMS ARE LOCATED IN A MILD l

ENVIRONMENT. (ENVIRONMENTAL ZONE INDICATED ABOVE) SEE SECTION 2.2 DISCUSSION.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

t

('~)T A-187 l

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS b

d ID NUMBER: MUV-58 RECORD NUMBER: 0116 SCEW PAGE NUMBER: 2-149 DESCRIPTION: VALVE MOTOR LOCATION:

OPERATOR AUXILIARY BLDG.

ELEV. 95' MANUFACTURER: LIMITORQUE TER EQUIPMENT NO.:

MODEL: SMB-000-10 TER CATEGORY:

N/A SYSTEM: MU ZONE LOCATION:

6 TER QUALIFICATION DEFICIENCIES NOTED:

NOT INCLUDED IN EVALUATION U)

QUALIFICATION STATUS:

NOT IN SCOPE. SUBSEQUENT REVIEW SHOWS THESE ITEMS ARE LOCATED IN A MILD ENVIRONMENT. (ENVIRONMENTAL ZONE INDICATED ABOVE) SEE SECTION 2.2 DISCUSSION.

CORRECTIVE ACTION:

NOT APPLICABLE.

l CORRECTIVE ACTION 3CHEDULE: NOT APPLICABLE.

l MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

A-188 l

l l

1-.- - .- .=_ ._ _ . . . . . .. .. -___. . _ _ . -_ __ - - _ - _ .

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS O ID NUMBER: MUV-73 RECORD NUMBER: 0117 SCEW PAGE NUMBER: 2-150 DESCRIPTION: VALVE MOTOR LOCATION:

OPERATOR AUXILIARY BLDG.

ELEV. 95' MANUFACTURER: LIMITORQUE TER EQUIPMENT NO.:

MODEL: SMB-000-10 TER CATEGORY:

N/A i SYSTEM: MU ZONE LOCATION:

6 l

l TER QUALIFICATION DEFICIENCIES NOTED:

! NOT INCLUDED IN EVALUATION QUALIFICATION STATUS:

NOT IN SCOPE. SUBSEQUENT REVIEW SHOWS THESE ITEMS ARE LOCATED IN A MILD ENVIRONMENT. (ENVIRONMENTAL ZONE INDICATED ABOVE) SEE SECTION 2.2 DISCUSSION.

l l CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

O v

A-189

FLORIDA PONER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: MUV-258 & 259 RECORD NUMBER: 0118 MUV-260 & 261 '

SCEW PAGE NUMBER: 2-152 DESCRIPTION: VALVE MOTOR LOCATION:

OPERATOR CONTAINMENT ELEV..

119' MANUFACTURER: LIMITORQUE TER EQUIPMENT NO.:

06 MODEL: SMB-000 TER CATEGORY:

II.A SYSTEM: MU ZONE LOCATION:

39 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL
2. EQUIP VS TEST SPECIMEN
3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED
10. RADIATION EXPOSURE O

v QUALIFICATION STATUS:

QUALIFIED FOR CURRENT APPLICATION.

SEE DISCUSSION ATTACHED.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

n v

NOT REQUIRED.

A-190

i DISCUSSION ON O MUV 258, 259, 260 & 261 2

Record 0118 Vendor correspondence (L200-3VC-008) indicates that Test Report 600456 (L200-3TR-001) would apply if the motors were replaced ,

with Class RH insulated motors. Walkdown results (L 200-WW-001) indicate these units have Reliance motors with HR insulation.

These motors are 3 phase, 230/460 volt Reliance motors. Although the walkdown worksheets indicate HR insulation, it is believed there was an error in data collection since we are not familiar with any HR insulation in existence. Another walkdown is scheduled for the current outage to confirm our belief that the motors have Class RH insulation. This equipment is considered qualified for its current application.

O l

t i O

A-191

FLORIDA POWER CORPORATION l

QUALIFICATION STA3'US

SUMMARY

SHEETS l ID NUMBER: MUV-49-SV RECORD NUMBER: 0119 SCEW PAGE NUMBER: 2-153 2 DESCRIPTION: SOLENOID VALVE LOCATION:

AUXILIARY BLDG.

ELEV. 95' MANUFACTURER: ASCO TER EQUIPMENT NO.:

MODEL: 831657 TER CATEGORY:

N/A SYSTEM: MU ZONE LOCATION:

3 TER QUALIFICATION DEFICIENCIES NOTED:

NOT INCLUDED IN EVALUATION O

QUALIFICATION STATUS:

NOT IN SCOPE. SUBSEQUENT REVIEW SHOWS THESE ITEMS ARE LOCATED IN A MILD ENVIRONMENT. (ENVIRONMENTAL ZONE INDICATED ABOVE) SEE SECTION 2.2 DISCUSSION.

CORRECTIVE ACTION:

i NOT APPLICABLE.

l I

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

i NOT REQUIRED.

i l A-192

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS b

v ID NUMBER: MUV-64-SV1,2,3,4,5,6 RECORD NUMBER: 0120 SCEW PAGE NUMBER: 2-154 DESCRIPTION: SOLENOID VALVE LOCATION:

AUXILIARY BLDG.

ELEV. 95' MANUFACTURER: ASCO TER EQUIPMENT NO.:

31 MODEL: HT831657,HT8211B54 FT8211B33 TER CATEGORY:

I.B SYSTEM: MU ZONE LOCATION:

15 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL O _

U QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

CORRECTIVE ACTION:

REPLACE.

CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER 1985 MAR NUMBER: 82-05-24-03 JUSTIFICATION FOR CONTINUED OPERATION:

SEE ATTACHED.

A-193

JUSTIFICATION FOR CONTINUED OPERATION for MUV-64-SV1, 2, 3, 4, 5, 6 TER Item 31 References

1) FPC Environmental Qualification of Class lE Equipment IE Bulletin 79-01B Qualification Summary.

In the interim between the present and scheduled corrective action, the following justification for continued operation, as previously provided in Reference 1, is given:

1. Investigations with the manufacturer indicate the solenoid valves are good for 10 5 rads. Accident conditions will not affect the components for the period of operability O' required. Also, due to the location of the component when required to perform its safety function, the accident environment has no impact.
2. Due to the period of operability required as per CRf3 Tech.

Spec. Table 3.6-1 to perform their safety function, and the fact that the total radiation exposure per the SCEW sheets is conservative in regard to the 5-1/2 year operating life of the plant, these valves are not considered to be a restraint to the safe operation of CRf3.

A-194

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: MUV-253-SVl/SV2 RECORD NUMBER: 0121 SCEW PAGE NUMBER: 2-155 l DESCRIPTION: SOLENOID VALVE LOCATION:

AUXILIARY BLDG. '

ELEV. 119' MANUFACTURER: ASCC TER EQUIPMENT NO.:

30 MODEL: HT831655 FOR SV1 8320A38 FOR SV2 TER CATEGORY:

I.B SYSTEM: MU ZONE LOCATION:

22 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL

~

QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

CORRECTIVE ACTION:

REPLACE.

CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER 1985 MAR NUMBER: 82-05-24-03 JUSTIFICATION FOR CONTINUED OPERATION:

SEE ATTACHED.

A-195

JUSTIFICATION FOR CONTINUED OPERATION for MUV-253/SVl/SV2 4 TER Item 30 References

1) FPC Environmental Qualification of Class lE Equipment IE Bulletin 79-01B Qualification Summary.

In the interim between the present and scheduled corrective action, the following justification for continued operation, as previously provided in Reference 1, is given:

1. Investigations with the manufacturer indicate the solenoid valves are good for 10 5 rads. Accident conditions will not affect the components for the period of operability required. Also, due to the location of the component when required to perform its safety function, the accident environment has no impact.
2. Due to the period of operability required as per CR3 Tech.

Spec. Table 3.6-1 to perform their safety function, and the fact that the total radiation exposure per the SCEW sheets is conservative in regard to the 5-1/2 year operating life of the plant, these valves are not considered to be a restraint to the safe operation of CR3.

A-196

FLORIDA POWER CORPORATION QUALIFICATION STATUS SIDetARY SHEETS O ID NUMBER: MU-25-SV RECORD NUMBER: 0122 2

SCEW PAGE NUMBER: 2-156 DESCRIPTION: SOLENOID VALVE LOCATION:

AUXILIARY BLDG.

ELEV. 95' MANUFACTURER: ASCO TER EQUIPMENT NO.:

,12 MODEL: 8320 A 92 TER CATEGORY:

I.B SYSTEM: MU ZONE LOCATION:

2 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

CORRECTIVE ACTION:

REPLACE.

CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER 1985 MAR NUMBER: 82-05-24-03 JUSTIFICATION FOR CONTINUED OPERATION:

SEE ATTACHED.

A-197

JUSTIFICATION FOR CONTINUED OPERATION for MU-25-SV TER Item 32 References

1) FPC Environmenial Qualification of Class lE Equipment IE Bulletin 79-OlB Qualification Summary.

In the interim between the present and scheduled corrective action, the following justification for continued operation, as previously provided in Reference 1, is given:

1. Investigations with the manufacturer indicate the solenoid valves are good for 10 5 rads. Accident conditions will not affect the components for the period of operability required. Also, due to the location of the component when required to perform its safety function, the accident environment has no impact.
2. Due to the period of operability required as per CR#3 Tech.

Spec. Table 3.6-1 to perform their safety function, and the fact that the total radiation exposure per the SCEW sheets is conservative in regard to the 5-1/2 year operating life of the plant, these valves are not considered to be a restraint to the safe operation of CRt3.

l O A-198 I - -- . . - .

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: MU-23/24 RECORD NUMBER: 0123 MU-25/26 ^

SCEW PAGE NUMBER: 2-157 DESCRIPTION: MOTOR STARTER LOCATION:

AUXILIARY BLDG.

ELEV. 95' MANUFACTURER: GOULD I-T-E TER EQUIPMENT NO.:

93 MODEL: GERIES 5600 TER CATEGORY:

II.C SYSTEM: MU ZONE LOCATION:

3 TER QUALIFICATION DEFICIENCIES NOTED:

3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED O

QUALIFICATION STATUS:

QUALIFIED FOR CURRENT APPLICATION.

SEE DISCUSSION ATTACHED.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

A-199

DISCUSSION ON MU 23, 24, 25 & 26 Gould Motor Starters 2 RECORD 0123 Reference

1) Qualification Summary Report for Class lE Equipment, Revision 1 Gould SO #84-66702 (FPC I212-3TR-001) .

The reference indicated above demonstrates qualified life for equipment components for both 40 C and 50 C environments.

Surveillance and maintenance recommendations are also identified therein. Florida Power Corporation considers this equipment to be qualified for its current application.

O O

A-200

FLORIDA POWER CORPORATIOJ QUALIFICATION STATUS

SUMMARY

SHEETS O ID NUMBER: MU-4 & MU-5 RECORD NUMBER: 0124 SCEW PAGE NUMBER: 2-158 DESCRIPTION: LOCAL CONTROL LOCATION:

STATION AUXILIARY BLDG.

ELEV. 95' MANUFACTURER: FIELD FABRICATED TER EQUIPMENT NO.:

87 MODEL: G.E. TYPE UE202 SW.

G.E. TYPE UC212 LIGHT TER CATEGORY:

I.B SYSTEM: MU ZONE LOCATION:

15 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL

^

QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

CORRECTIVE ACTION:

REPLACE.

CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER 1985 MAR NUMBER: 82-05-24-02 JUSTIFICATION FOR CONTINUED OPERATION:

SEE JCO FOR AS-1 (RECORD 013)

A-201

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: MU-7 RECORD NUMBER: 0125 a

SCEW PAGE NUMBER: 2-159 DESCRIPTION: LOCAL CONTROL LOCATION:

STATION AUXILIARY BLDG.

ELEV. 95' MANUFACTURER: FIELD FABRICATED TER EQUIPMENT NO.:

MODEL: G.E. TYPE UA202 SW.

G.E. TYPE UC212 LIGHT TER CATEGORY:

N/A SYSTEM: MU ZONE LOCATION:

3 TER QUALIFICATION DEFICIENCIES NOTED:

NOT INCLUDED IN EVALUATION O -

QUALIFICATION STATUS:

NOT IN SCOPE. SUBSEQUENT REVIEW SHOWS THESE ITEMS ARE LOCATED IN A MILD ENVIRONMENT. (ENVIRONMENTAL ZONE INDICATED ABOVE) SEE SECTION 2.2 DISCUSSION.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

A-202

FLORIDA POWER CORPORATION QUALIFICATION STATUS SUM 8ARY SHEETS O ID NUMBER: MU-16 RECORD NUMBER: 0126 SCEW PAGE NUMBER: 2-160 DESCRIPTION: LOCAL CONTROL LOCATION:

STATION AUXILIARY BLDG.

ELEV. 119' MANUFACTURER: FIELD FABRICATED TER EQUIPMENT NO.:

88 MODEL: G.E. TYPE UA202 SW.

G.E. TYPE UC212 LIGHT TER CATEGORY:

I.B SYSTEM: MU ZONE LOCATION:

22 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL O

QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

CORRECTIVE ACTION:

REMOVE.

CORRECTIVE ACTION SCHEDULE: REFUEL V, NOVEMBER 1985 l

MAR NUMBER: 82-05-24-02 l

i JUSTIFICATION FOR CONTINUED OPERATION:

I SEE ATTACHED.

l A-204 i

A I _) JUSTIFICATION FOR CONTINUED OPERATION for ,

MU-16 GE Switches and Lights TER Item 88 References

1) FPC IE Bulletin 79-OlB Response, Figure 4-4.

(The motor starters will be relocated in a mild environment prior to November, 1985.)

In the interim between the present time and scheduled relocation, the following justifications for continued operation are given:

1. Specification environment radiation values were compared to radiation values for the typical materials from the DOR

() Guidelines Appendix C for motor control centers.

parison revealed that the specification This com-environment radiation is at or below radiation susceptibility acceptance levels; thereby indicating radiation is not a restraint to the safety-related operation of the motor control centers.

2. The motor starters are used to position valves immediately after the occurrence of a HELB in the intermediate building.

Although a failure analysis has shown that if repositioning of the valves is postulated, repositioning will occur sub-sequent to the maximum thermal and pressure conditions, l

allowing operator access to correct the repositioning should it occur.

l l

A-204

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS O ID NUMBER: MU-4 & 5 RECORD NUMBER: 0127 SCEW PAGE NUMBER: 2-161 DESCRIPTION: TERMINAL BOX LOCATION:

AUXILIARY BLDG.

ELEV. 95' MANUFACTURER: FIELD FABRICATED TER EQUIPMENT NO.:

70 MODEL: STATES TYPE NT TERMINAL BLOCKS TER CATEGORY:

I.B SYSTEM: MU ZONE LOCATION:

15 TER QUALIFICATION DEFICIENCIES NOTED:

3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED QUALIFICATION STATUS:

NOT IN SCOPE. SUBSEQUENT REVIEW SHOWS THESE ITEMS ARE LOCATED IN A MILD ENVIRONMENT. (ENVIRONMENTAL ZONE INDICATED ABOVE) SEE SECTION 2.2 DISCUSSION.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

A-205

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS O

V ID NUMBER: MU-ll RECORD NUMBER: 0128 SCEW PAGE NUMBER: 2-162 DESCRIPTION: TERMINAL BOX LOCATION:

AUXILIARY BLDG.

ELEV. 95' MANUFACTURER: FIELD FABRICATED TER EQUIPMENT NO.:

NA MODEL: STATES TYPE NT TERMINAL BLOCKS TER CATEGORY:

N/A SYSTEM: MU ZONE LOCATION:

3 TER QUALIFICATION DEFICIENCIES NOTED:

NOT INCLUDED IN EVALUATION O -

QUALIFICATION STATUS:

NOT IN SCOPE. SUBSEQUENT REVIEW SHOWS THESE ITEMS ARE LOCATED IN A MILD ENVIRONMENT. (ENVIRONMENTAL ZONE INDICATED ABOVE) SEE SECTION 2.2 DISCUSSION.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

A-206

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS O ID NUMBER: MU-21 RECORD NUMBER: 0129 SCEW PAGE NUMBER: 2-163 DESCRIPTION: TERMINAL BOX LOCATION:

AUXILIARY BLDG.

ELEV. 119 MANUFACTURER: FIELD FABRICATED TER EQUIPMENT NO.:

68 MODEL: STATES TYPE NT TERMINAL BLOCKS TER CATEGORY:

I.B SYSTEM: MU ZONE LOCATION:

22 TER QUALIFICATION DEFICIENCIES NOTED:

3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED O -

QUALIFICATION STATUS:

QUALIFIED FOR CURRENT APPLICATION.

SEE APPENDIX A,.

CORRECTIVE ACTION:

.NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

J A-207 i

l

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: MU-22 RECORD NUMBER: 0130 SCEW PAGE NUMBER: 2-164 '

DESCRIPTION: TERMINAL BOX LOCATION:

AUXILIARY BLDG.

ELEV. 95' MANUFACTURER: FIELD FABRICATED TER EQUIPMENT NO.:

71 MODEL: STATES TYPE NT TERMINAL BLOCKS TER CATEGORY:

I.B SYSTEM: MU ZONE LOCATION:

2 TER QUALIFICATION DEFICIENCIES NOTED:

3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED O

QUALIFICATION STATUS:

QUALIFIED FOR CURRENT APPLICATION.

SEE APPENDIX A.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

A-208

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS \

ID NUMBER: MU-23-DPT-5,6,7,8 RECORD NUMBER: 0131 2

SCEW PAGE NUMBER: 2-166A DESCRIPTION: DP TRANSMITTER LOCATION:

E AUXILIARY BLDG.

ELEV. 95' MANUFACTURER: ROSEMOUNT TER EQUIPMENT NO.:

41 MODEL: ll53B TER CATEGORY:

II.A SYSTEM: MU ZONE LOCATION:

2 TER QUALIFICATION DEFICIENCIES NOTED:

2. EQUIP VS TEST SPECIMEN
3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED QUALIFICATION STATUS:

QUALIFIED FOR CURRENT APPLICATION.

SEE DISCUSSION ATTACHED.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

O A-209

b f

I t

3

() DISCUSSION ON Rosemount Transmitters ,

9 i

Record 0131 4 f' 7s s s

t l "

Reference .

1) Rosemount Test Report 108025 and 108026, "Rosemount. Pressure Transmitter Model 1153 Series B for Nuclear Service", dated February 4, 1981.

)

The Rosemount transmitters have been installed. The transmitters I are Series 1153B which are qualified to IEEE 323-1974, IEEE 344- l 1975, and NUREG-0588, Category I requirements in accordance with, Reference 1. No justification for continued operation !is -1 required since the transmitter is qualified. All harsh enviro 6-[

J a

ments are enveloped by the testing conditions.

v.

I a

5 I

3-I

\

l O

A-210 I t

~

/

,- . - - , . ~ - . . - - , , . _ _ _ . . . , _ .,---.- _,,--.- _,.._-_ _ _.._,-, --- .-- - m _ _ -,--- _ . _ , - - . - _

t y

x .

a 3 FLORIDA POWER CORPORATION QUALIFICATION STATUS SUMM/AY SHEETS O ID NUMBER: s RCV-ll RECORD NUMBER: 0132 SCEW PAGE NUMBER: 2-168 DESCRIPTION: VALVE MOTOR LOCATION:

OPERATOR CONTAINMENT ELEV.

160' MANUFACTURER: LIMITORQUE TER EQUIPMENT NO.:

17 MODEL:

TER CATEGORY:

II.A SYSTEM: RC s ZONE LOCATION:

40 i

TER QUALIFICATION DEFICIENCIES NOTED:

2. EQUIP VS TEST SPECIMEN '
3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED f

i QUALIFICATION STATUS:

QUALIFIED FOR CURRENT APPLICATION.-

8 CORRECTIVE ACTION:

t{OT APPLICABLE.

l

,4 CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER
NOT APPLICABLE.

t

{,,

, JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

t A-211

DISCUSSION ON RCV-ll Limitorque Motor Operator 2 Record 0132 This equipment (PORV block valve) was replaced in October, 1982 via Work Request 036866 (FCA 04 3376 00). The associated QA package indicates the replacement is qualified to the environmental parameters specified in Test Report 600456.

Florida Power Corporation considers this equipment qualified for its current application.

O -

O A-212

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS O ID NUMBER: RC-3A-PT2,RC-3A-FTl RECORD NUMBER: 0133 RC-3B-PT1,RC-3B-PT2 .

SCEW PAGE NUMBER: 2-170 DESCRIPTION: PRESSURE TRANSMITTER LOCATION:

CONTAINMENT ELEV.

99'-11" MANUFACTURER: ROSEMOUNT TER EQUIPMENT NO.:

37 MODEL: 1152 GP TER CATEGORY:

II.A SYSTEM: RC ZONE LOCATION:

38 TER QUALIFICATION DEFICIENCIES NOTED:

2. EQUIP VS TEST SPECIMEN
3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED
5. PROGRAM FOR AGE DEGRAD
6. AGING SIMULATION
10. RADIATION EXPOSURE O .

QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

CORRECTIVE ACTION:

REPLACE.

CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER 1985 MAR NUMBER: 82-05-24-04 JUSTIFICATION FOR CONTINUED OPERATION:

SEE ATTACHED.

O A-213

l JUSTIFICATION FOR CONTINUED OPERATION

for
RC-3A-PT 1 & 2 and RC-3B-PT-1 & 2 Rosemount Transmitter TER Item 37 i

References i

1) FPC IE Bulletin 79-OlB Response, Figure 4-6.
2) B&W Proprietary Document 58-0261-001, " Qualification Report for Pressure Transmitter, Rosemount Model ll52GP9A92PB for Reactor Coolant Pressure Measurement", dated 2/17/77, FPC File R369-3TR-001.
3) B&W Proprietary Document 58-0157-014, " Qualification Test Report, Rosemount, Inc., Model 1152 Alphaline, Pressure Transmitter", Rev. 1, dated 2/10/77, FPC File R369-3TR-001. i
4) B&W Topical Report BAW 10082, Rev. 1, " Environmental Qualification of Class lE Control and Instrumentation Equipment", Table 3-9, FPC File B014-3TR-001.
5) FPC IE Bulletin 79-OlB Response, Figure 4-5, " Reactor Building Pressure vs. Time".
6) FPC IE Bulletin 79-OlB Response, Tables 4-1 and 4-2.

The RC-3A-PT 1 & 2 and RC-3B-PT 1 & 2 Rosemount transmitters will

. be replaced with new Rosemount transmitters prior to November, 1985. The replacement Rosemount transmitters will be provided

) with documented evidence of qualification. New SCEW sheets will be completed for the replacement transmitters upon receipt of the transmitters and associated test reports.

In the interim between the present time and scheduled replacement, the following justifications for continued operation is provided:

O i

A-214 r- - ---- -- ,- -,p., v -

,.n.,,.nnw - , , . . , - . . . - - - . , . ..n-_..,..,,,.,-------. , - , . . , - , - , - - , , , , , - - , - .,.---_.._-----------r- - - - - - , - - - -

1. FPC 79-OlB Response, Figure 4-6 (test conditions) has been

[ developed from Reference 3. FPC Report F-C4432-6, Figure 4 (included in Reference 3) is the test condition figure used to develop Figure 4-6. Output deviation was incorporated into FPC Figure 4 to produce Figure 4-6. The test condi-i tions envelope the high temperature and pressure conditions for the first five (5) minutes of the LOCA test conditions.

During this time, accuracy deviation was equal to or less than 3.3%. Output deviation in the test performed in Refer- ,

ence 3 was 10% of span during subsequent DBE exposure.

During the tests performed in Reference 2, a maximum accuracy deviation of less than 4% occurred.

The function of the RC-3A-PT 1 & 2 and RC-3B-PTl & 2 pres-sure transmitters is to sense reactor coolant pressure and actuate safety systems on low pressure. Low pressure sensing occurs during the first few seconds after LOCA during which the transmitters will remain within the required accuracy deviation bounds.

p O

A-215

FLORIDA PONER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: RC-3A-PT3,RC-3A-PT4 RECORD NUMBER: 0134 RC-3B-PT3

  • SCEW PAGE NUMBER: 2-171 DESCRIPTION: PRESSURE TRANSMITTER LOCATION:

CONTAINMENT ELEV.

99'-11" MANUFACTURER: FOXBORO TER EQUIPMENT NO.:

38 MODEL: EllGHINM2 TER CATEGORY:

II.A SYSTEM: RC ZONE LOCATION:

38 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL
10. RADIATION EXPOSURE

^

QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

CORRECTIVE ACTION:

REPLACE.

l l CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER 1985 MAR NUMBER: 82-05-24-04 JUSTIFICATION FOR CONTINUED OPERATION:

SEE ATTACHED.

A-216

JUSTIFICATION FOR CONTINUED OPERATION for 4

RC-3A-PT3,4 and RC-3B-PT3 Foxboro Pressure Transmitters TER Item 38 References

1) FPC 79-OlB Response, Figure 4-8.
2) B&W Proprietary Document 58-0079-001, " Test Data for Nuclear Transmitters" (Foxboro) FPC File F180-3TR-002.
3) Foxboro Test Report T2-1057, " Radiation Test of E-10 Series Differential Pressure Transmitter" (August, 1973).
4) Foxboro Test Report T3-1097, " Radiation Test of E-10 Series Amplifiers - StanCard and Radiation Resistant Types".
5) FPC IE Bulletin 79-OlB Response, Figure 4-5, " Reactor Building Pressure vs. Time".

() RC-3A-PT3,4 and RC-3B-PT3 will be replaced prior to November, 1985. The replacement transmitters will be provided with documented evidence of qualification. New SCEW sheets will be completed for the replacement transmitters upon receipt of the transmitters and associated test reports.

In the interim between the present and scheduled replacement, the following justifications for continued operation are given:

1. Figure 4-8 of the FPC 79-OlB Response (Reference 1) has been reproduced from Reference 2, " Test Data for Nuclear Trans-mitters". The test conditions shown in Figure 4-8 completely envelope the conditions specified (Reference 5) for Crystal River for high temperature and pressure condi-tions. Radiation conditions are discussed below.

O V

A-217

2. Subsequent to the qualification tests performed for B&W (Reference 2) , Foxboro performed tests on E10 Series Trans-mitters and Amplifiers (Reference 3 and 4) to levels of 1.0 x 10 7 rads or greater. Maximum error was 5.7% in zero shift for an amplifier irradiated to 2.2 x 10 8 rads (a factor of 37 above the 5.9 x 10 6 rads specified for Crystal River) .

Maximum error at 1 x 10 7 rads was 4.2%. Due to the fact that accuracy was better than specified for Crystal River (5%)

for transmitters and amplifiers at 1.0 x 10 7 rads and the fact that maximum error at 2.2 x 10 8 was only 0.7% greater than specified, the transmitters should operate at the Crystal River specified radiation dose of 5.9 x 10 6 rads including margin. .

O O

A-218

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: RC-PT-132 RECORD NUMBER: 0135 a

SCEW PAGE NUMBER: 2-172 DESCRIPTION: PRESSURE TRANSMITTER LOCATION:

CONTAINMENT ELEV.

99'-9.75" MANUFACTURER: ROSEMOUNT TER EQUIPMENT NO.:

37 MODEL: 1152 GP TER CATEGORY:

II.A SYSTEM: RC ZONE LOCATION:

38 TER QUALIFICATION DEFICIENCIES NOTED:

2. EQUIP VS TEST SPECIMEN
3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED
5. PROGRAM FOR AGE DEGRAD lb. DAI SURE QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

CORRECTIVE ACTION:

REPLACE.

CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER 1985 MAR NUMBER: 82-05-24-04 JUSTIFICATION FOR CONTINUED OPERATION:

SEE ATTACHED, A-219

r

( JUSTIFICATION FOR CONTINUED OPERATION for i RC-PT-132 Rosemount Transmitter TER Item 37 References

1) FPC IE Bulletin 79-01B Response, Figure 4-6.
2) B&W Proprietary Document 58-0261-001, " Qualification Report for Pressure Transmitter, Rosemount Model ll52GP9A92PB for Reactor Coolant Pressure Measurement", dated 2/17/77, FPC File R369-3TR-001.
3) B&W Proprietary Document 58-0157-014, " Qualification Test Report, Rosemount, Inc., Model 1152 Alphaline, Pressure Transmitter", Rev. 1, dated 2/10/77, FPC File R369-3TR-001.
4) B&W Topical Report BAW 10082, Rev. 1, " Environmental Qualification of Class lE Control and Instrumentation

() 5)

Equipment", Table 3-9, FPC File B014-3TR-001.

FPC IE Bulletin 79-OlB Response, Figure 4-5, " Reactor Building Pressure vs. Time".

6) FPC IE Bulletin 79-OlB Response, Tables 4-1 and 4-2.

The RC-PT-132 Rosemount transmitter will be replaced with new Rosemount transmitters prior to November, 1985. The replacement Rosemount transmitters will be provided with documented evidence of qualification. New SCEW sheets will be completed for the replacement transmitters upon receipt of the transmitters and associated test reports.

In the interim between the present time and scheduled replacement, the following justifications for continued operation are provided:

1. FPC 79-OlB Response, Figure 4-6 (test conditions) has been developed from Reference 3. FPC Report F-C4432-6, Figure 4 A-220

(included in Reference 3) is the test condition figure used to develop Figure 4-6. Output deviation was incorporated into FPC Figure 4 to produce Figure 4-6. The test condi-2 tions envelope the high temperature and pressure conditions for the first five (5) minutes of the LOCA test conditions.

During this time, accuracy deviation was equal to or less than 3.3%. Output deviation in the test performed in Refer-ence 3 was 10% of span during subsequent DBE exposure.

During the tests performed in Reference 2, a maximum accuracy deviation of less than 4% occurred.

The function of the RC-PT-132 pressure transmitter is to prevent opening of the DH letdown valve when reactor coolant system pressure is too high. Deviation from a specified value of 10% or less can be tolerated since there are more than four (4) redundant pressure measurements on the same reactor coolant loops which can be used to cross check the reactor coolant system pressure.

2. The total dose to the transmitters is dependent on the amount of time 'needed for the depressurization of the reactor coolant system. For the 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> operating time required, total integrated dose at the transmitter is the sum of a ten (10) year plant life plus the accident dose.

The transmitters may receive a total dose of 3.5 x 10 6 rads (ten (10) year operating dose) plus 9.2 x 10 7 rads (accident dose). Since the transmitters have been tested to less than total postulated dose, long-term operation is not assured subsequent to LOCA. Other RC pressure transmitters may be used (see above) to ensure that the RC system pressure is low enough to allow decay heat removal in the long term.

f O

A-221

l FLORIDA POWER CORPORATION l QUALIFICATION STATUS

SUMMARY

SHEETS O

N' ID NUMBER: RC-14A-DPT-1, DPT-2 RECORD NUMBER: 0136 RC-14B-DPT-1, DPT-2 SCEW PAGE NUMBER: 2-173 '

DESCRIPTION: FLOW TRANSMITTER LOCATION:

CONTAINMENT ELEV.

100'-4.5" MANUFACTURER: BM CO.

TER EQUIPMENT NO.:

44 MODEL: BY 3241-A TER CATEGORY:

II.A SYSTEM: RC ZONE LOCATION:

38 TER QUALIFICATION DEFICIENCIES NOTED:

2. EQUIP VS TEST SPECIMEN
3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED
5. PROGRAM FOR AGE DEGRAD
6. AGING SIMULATION

() b.RADATIONEXPOSURE _

QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

CORRECTIVE AdTION:

REPLACE.

CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER 1985 MAR NUMBER: 82-05-24-04 JUSTIFICATION FOR CONTINUED OPERATION:

SEE ATTACHED, A-222

JUSTIFICATION FOR CONTINUED OPERATION for RC-14A-DPT1 & 2 and RC-14B-DPTl & 2 Bailey Transmitters TER Item 44 References

1) FPC IE Bulletin 79-01B Response, Figure 4-7.
2) B&W Proprietary Document 58-0081-00, " Type Test Report of Bailey Meter BY Differential Pressure Transmitter", dated 3/12/73.

RC-14A-DPT 1&2 and RC-14B-DPT 1&2 will be replaced prior to November, 1985. The replacement transmitters will be supplied with documented evidence of qualification. New SCEW sheets will be completed for the replacement transmitters upon receipt of the transmitters and associated test reports.

O In the interim between the present time and scheduled transmitter replacement, the following justification for continued operation is given:

1. The function of the transmitters is to provide indication of reactor coolant flow to plant operators. The transmitters have no other safety functions. Reactor coolant flow measurement is not needed by the operators to perform any safety functions. Although flow measurements mdy not be directly available to the operators, flow can be inferred from rasctor pressure and temperature measurements as well as from RC pump running indications. Therefore, failure of these transmitters can be tolerated.

O A-223

% w -.-. , . - . - - , --.,,,_,--,m- - _y- . - , . _ , _ , _ , _ - , , - -

,,,y- - _ , , , , - - _ - y ,,-- - , - . -- -- r , .,-w

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS O EID NUMBER: RC-4A-TE4 RECORD NUMBER: 0137 RC-4A-TEl,4;RC-4B-TEl,4 RC-5A-TEl,2,3,4 SCEW PAGE NUMBER: 2-174 RC-58-TEl,2,3,4 DESCRIPTION: TEMP. ELEMENT LOCATION:

CONTAINMENT ELEV.

119' MANUFACTURER: ROSEMOUNT TER EQUIPMENT NO.:

96 MODEL: RTD-177HW TER CATEGORY:

II.A SYSTEM: RC ZONE LOCATION:

40 TER QUALIFICATION DEFICIENCIES NOTED:

3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED
6. AGING SIMULATION 7D. ENVELOP REQUIRED PROFILE 7E. STEAM EXPOSURE
8. SPRAY O 13. FUNCTIONAL TESTING QUALIFICATION STATUS:

QUALIFIED FOR CURRENT APPLICATION.

SEE DISCUSSION ATTACHED.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: 82-05-24-04 JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

O A-224

i DISCUSSION ON RC-4A-TEl & 4; RC-4B-TE1 & 4; RC-5A-TEl, 2, 3& 4; RC-5B-TEl, 2, 3& 4 Rosemount RTDs References

1) B&W Report Number 58-0372-01, " Qualification Test Report -

Rosemount 177HW Sensor, Temperature, Resistance Type",

dated January 19, 1978.

2) FPC IE Bulletin 79-OlB Response, Figure 4-6.

Florida Power Corporation disagrees with the Franklin Research Center (FRC) evaluation of the Rosemount RTD reactor coolant temperature sensors.

The sensor, thermowell, mounting nuts and gaskets are subjected to temperature and pressure conditions during normal operation which exceed harsh environment parameters. Reactor coolant -

temperature exceeds 500 F and pressure exceeds 2000 psi during normal operation. Testing of these components at levels of approximately 300 F and 65 psig is unnecessary, since normal operating conditions far exceed accident conditions. It should be noted that pressure testing to 3750 psig was performed on the thermowell, and calibration at 610 F was performed on the sensor as pre-qualification for the RTD showing capability at environments which are more severe than accident environments.

Two RTDs with connection heads attached were subjected to 3.8 x 10 8 rads and 3.0 x 10 8 rads without failure. Connection head capability during LOCA conditions was demonstrated by similarity to a unit tested to a maximum 350 F, 67 psia environment. The tested unit had a painted outer surface versus a bare surface for the analyzed Model 177 series. Although the qualification tests 1

A-225

4 d

, were performed on the 177 HW model, the differences between the 177 HW and 177 GY were analyzed to show applicability of the test reports to the 177 HW model used at Crystal River.

l 1 4 i Based on the above evidence of qualification, FPC has concluded that the Rosemount RTDs are qualified for their current applica-  !

tion.

O I

f J

l e

!O

'l i

i i

e 1

O A-226

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: RC-1-LT 1,2,3 RECORD NUMBER: 0138 SCEW PAGE NUMBER: 2-175 DESCRIPTION: LEVEL TRANSMITTER LOCATION:

CONTAINMENT ELEV.

99'-9.5" MANUFACTURER: ROSEMOUNT TER EQUIPMENT NO.:

53 MODEL: 1152 DP TER CATEGORY:

II.A SYSTEM: RC ZONE LOCATION:

38 TER QUALIFICATION DEFICIENCIES NOTED:

2. EQUIP VS TEST SPECIMEN
3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED
5. PROGRAM FOR AGE DEGRAD
b. A N URE QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

l l

CORRECTIVE ACTION:

REPLACE.

, CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER 1985 i

MAR NUMBER: 82-05-24-04 l JUSTIFICATION FOR CONTINUED OPERATION:

l SEE ATTACHED.

O A-227

l JUSTIFICATION FOR CONTINUED OPERATION for RC-LT-1,2,3 Rosemount Level Transmitter TER Item No. 53 The reactor coolant level transi::itters will be replaced prior to November, 1985. Replacement transmitters will be provided with documented evidence of qualification.

In the interim between the present time and scheduled replacement, the following justification for continued operation is provided:

, The function of the reactor coolant level transmitters is to provide indication to plant operators of the amount of water in the pressurizer. No other safety function is performed by these level transmitters. The level of water in the pressurizer may also be inferred from other reactor coolant system parameters, such as pressurizer level and reactor coolant temperature / pres-sure. Failure of these transmitters, therefore, can be tolerated.

1 O

A-228

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: RECORD NUMBER: 0139 SCEW PAGE NUMBER: 2-175A DESCRIPTION: ACCELEROMETER LOCATION:

CONTAINMENT ELEV. 168' MANUFACTURER: ENDEVCO TER EQUIPMENT NO.:

54 MODEL: 2273AM20 TER CATEGORY:

II.A SYSTEM: RC ZONE LOCATION:

40 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL 0

QUALIFICATION STATUS:

NOT IN SCOPE. SEE DISCUSSION ATTACHED.

CORRECTIVE ACTION:

REMOVE EMERGENCY PROCEDURE REFERENCE CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

r k-}

A-229 l

'q DISCUSSION ON

%J Endevco Accelerometer Record 0139 The Endevco accelerometer is placed on the PORV piping to sense flow acoustically.

Since the system is presently undergoing qualification, its function has been removed from emergency procedures.

Since NUREG 0737 Item II.D.3 requires a 'ect indication of flow in the discharge pipe, the function of the accelerometer 5. 'l be mair.tained. The system is not Class 1E and is not presently sa.fety related.

The B & W Owner's Group is presantly working on a fully qualified method of providing the direct indication of flow or a positive indication of valve position.

This fully qualified modification will be installed during Refuel V prior to November,1985. This system will be classified as ha environmentally qualified

? important to safety system.

O

FLO21DA POWER CORPORATION QUALIFICATION STATUS CUMMARY SHEETS ID NUMBER: RWP-2A,2B RECORD NUMBER: 0140 SCEW PAGE NUMBER: 2-181 ,

DESCRIPTION: PUMP MOTOR LOCATION:

AUXILIARY BLDG.

ELEV. 95' MANUFACTURER: ELECTRIC MACHINERY TER EQUIPMENT NO.:

57 MODEL: FRAME SIZE 3317-V TER CATEGORY:

II.A SYSTEM: RW ZONE LOCATION:

11 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL O

QUALIFICATION STATUS:

NOT IN SCOPE. SUBSEQUENT REVIEW SHOWS THESE ITEMS ARE LOCATED IN A MILD ENVIRONMENT. (ENVIRONMENTAL ZONE INDICATED ABOVE) SEE SECTION 2.2 DISCUSSION.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

P O

A-230

FLORIDA POWER CORPORATION QUALIFICATION CTATU3 CUMMARY SHEETS ID NUMBER: RWP-2A & 2B RECORD NUMBER: 0141 SCEW PAGE NUMBER: 2-181A ,

DESCRIPTION: LUBRICANT LOCATION:

AUXILIARY BLDG.

ELEV. 95' MANUFACTURER: GULF TER EQUIPMENT NO.:

57 MODEL: GULF HARMONY 46 TER CATEGORY:

II.A SYSTEM: RW ZONE LOCATION:

11 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL 1

QUALIFICATION STATUS:

NOT IN SCOPE. SUBSEQUENT REVIEW SHOWS THESE ITEMS ARE LOCATED IN A MILD ENVIRONMENT. (ENVIRONMENTAL ZONE INDICATED ABOVE) SEE SECTION 2.2 DISCUSSION.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

A U

A-231 l

l

FLORIDA POWER CORPORATION QUALIFICATION STATUS CUMMARY SHEETS

() ID NUMBER: RWP-3A,3B RECORD NUMBER: 0142 SCEW PAGE NUMBER: 2-182 s DESCRIPTION: PUMP MOTOR LOCATION:

AUXILIARY BLDG.

ELEV. 95' MANUFACTURER: ELECTRIC MACHINERY TER EQUIPMENT NO.:

56 MODEL: FRAME SIZE 2315-V TER CATEGORY:

II.A SYSTEM: RW ZONE LOCATION:

11 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL QUALIFICATION STATUS:

NOT IN SCOPE. SUBSEQUENT REVIEW SHOWS THESE ITEMS ARE LOCATED IN A MILD ENVIRONMENT. (ENVIRONMENTAL ZONE INDICATED ABOVE) SEE SECTION 2.2 DISCUSSION.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

O A-232

FLORIDA POWER CORPORATION QUALIFICATION STATUS CUMMARY SBEETS C\

's_/

ID NUMBER: RWP-3A & 3B RECORD NUMBER: 0143 2

SCEW PAGE NUMBER: 2-182A DESCRIPTION: LUBRICANT LOCATION.

AUXILIARY BLDG, ELEV. 95' MANUFACTURER: GULF TER EQUIPMENT NO.:

56 MODEL: GULF HARMONY 46 TER CATEGORY:

II.A SYSTEM: RW ZONE LOCATION:

11 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL QUALIFICATION STATUS:

NOT IN SCOPE. SUBSEQUENT REVIEW SHOWS THESE ITEMS ARE LOCATED IN A MILD ENVIRONMENT. (ENVIRONMENTAL ZONE INDICATED ABOVE) SEE SECTION 2.2 DISCUSSION.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

( NOT REQUIRED.

A-233

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS

) ID NUMBER: SPlA-LTl SPlB-LTl RECORD NUMBER: 0144 SCEW PAGE NUMBER: 2-183 ,

DESCRIPTION: LEVEL TRANSMITTERS LOCATION:

CONTAINMENT ELEV.

99'-11.5" MANUFACTURER: BM CO.

TER EQUIPMENT NO.:

51 MODEL: BY8B41X-A TER CATEGORY:

I.B SYSTEM: SP ZONE LOCATION:

38 TER QUALIFICATION DEFICIENCIES NOTED:

2. EQUIP VS TEST SPECIMEN
3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED
5. PROGRAM FOR AGE DEGRAD
6. AGING SIMULATION
8. SPRAY
10. RADIATION EXPOSURE O

QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

CORRECTIVE ACTION:

  • REPLACE.

CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER 1985 MAR NUMBER: 80-10-66-05 JUSTIFICATION FOR CONTINUED OPERATION:

SEE ATTACHED.

A-234

JUSTIFICATION FOR CONTINUED OPERATION for ,

SPlA-LT 1, 2, 3, 4 & 5 Bailey Transmitters TER Item No. 51 References

1) FPC IE Bulletin 79-OlB Response, Figure 4-7.
2) B&W Proprietary Document 58-0081-00, " Type Test Report of Bailey Meter BY Differential Pressure Transmitter", dated 3/12/73.
3) B&W Topical Report BAW-10082, Rev. 2, " Environmental Qualification of Class lE Control and Instrumentation",

dated 10/80.

SP-1A-LT 1, 2, 3, 4 & 5 will be replaced prior to November, 1985, by qualified equipment.

O In the interim between the present and November, 1985, the following justification for continued operation is given:

1. The function of the steam generator level tranr:aitters is to start auxiliary feedwater flow and to give indication of reactor heat removal to the plant operator. The transmit-ters will function within a few seconds after MSLB to supply auxiliary feedwater. During the first few seconds of required operation, temperature, pressure, radiation and other MSLB-caused harsh environments will be less severe than the environments during testing of the transmitters.

Steam generator level, in the long term, may be inferred by the operator from other instruments such as steam generator pressure, auxiliary feedwater flow and pressure, etc.

A-235

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: SPlA-LT2,3 RECORD NUMBER. 0145 SPlB-LT2,3 SCEW PAGE NUMBER: 2-184 2 DESCRIPTION: LEVEL TRANSMITTERS LOCATION:

CONTAINMENT ELEV.

100'-4" MANUFACTURER: BM CO.

TER EQUIPMENT NO.:

51 MODEL: BY8B41X-A TER CATEGORY:

I.B SYSTEM: SP ZONE LOCATION:

38 TER QUALIFICATION DEFICIENCIES NOTED: <

2. EQUIP VS TEST SPECIMEN
3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED
5. PROGRAM FOR AGE DEGRAD
6. AGING SIMULATION
10. ATION EXPOSURE QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

CORRECTIVE ACTION:

REPLACE.

1 CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER 1985 MAR NUMBER: 80-10-66-05 i

l l JUSTIFICATION FOR CONTINUED OPERATION:

l i

SEE JCO FOR SPlA-LTl (RECORD 144)

A-236

FLORIDA POWER CORPORATION ,

)

QUALIFICATION STATUS

SUMMARY

SHZETS g i

ID NUMBER: SP-17,18,21,22 RECORD NUMBER: 0146

(

2-184A SCEW PAGE NUMBER:

DESCRIPTION: LEVEL TRANSMITTERS LOCATION:

CONTAINMENT ELEV.

100.5' MANUFACTURER: ROSEMOUNT TER EQUIPMENT NO.:

52 MODEL: 1153 TER CATEGORY:

II.A SYSTEM: SP '

ZONE LOCATION:

  • 38

\ .

TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL l-O QUALIFICATION STATUS: -

NOT INSTALLED YET (REPLACEMENTS FOR SP-1A-LT2,3 AND SP-1B-LT2,3).

(TAG NUMBERS CHANGED SINCE PREVIOUS SUBMITTAL.)

CORRECTIVE ACTION:

(INSTALLATION) l

~

l

, CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER, 1985 MAR NUMBER: 80-10-66-05 JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

A-237

;4 3
  • lt

d' '

FLORIDA POWER CORPORATION

.s QUALIFICATION STATUS

SUMMARY

SHEETS

's -

O <[.ID NUMBER:

SPlA-LT4,5 SPlB-LT4,5 RECORD NUMBER:

SCEW PAGE NUMBER:

0147 2-185 1 -

DESCRIPTION:;I LEVEL. TRANSMITTER LOCATION:

/' CONTAINMENT ELEV.

,  ; 99'-9.5"

, MANUFA01tRER:t BM CO.. '

/

TER EQUIPMENT NO.:

( >

\ .

51 MODEL': BY8B41X-A

' TER CATEGORY:

I.B SYSTEM: g SP ZONE LOCATION:

38 c- ,

TER QUALIFICATION DEFICIENCIES NOTED:

2. EQUIP VS TEST SPECIMEN
3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED
5. PROGRAM FOR AGE DEGRAD
6. AGING SIMULATION
b. RAD ATION EXPOSURE QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS INI PROGRESS.

CORRECTIVE ACTION:

REPLACE.

CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER 1985 MAR NUMBER: 80-10-66-05 JUSTIFICATION FOR CONTINUED OPERATION:

SEE JCO FOR SPlA-LTl (RECORD 144) t 3

A-238

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS

( ID NUMBER: SP-25,26,29,30 RECORD NUMBER: 014R SCEW PAGE NUMBER: 2-185A ,

DESCRIPTION: LEVEL TRANSMITTERS LOCATION:

CONTAINMENT ELEV.

100.5' MANUFACTURER: ROSEMOUNT TER EQUIPMENT NO.:

52 MODEL: 1153 TER CATEGORY:

II.A SYSTEM: SP ZONE LOCATION:

38 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL O

QUALIFICATION STATUS:

NOT INSTALLED YET (REPLACEMENTS FOR SP-1A-LT4,5 AND SP-1B-LT4,5).

(TAG NUMBERS CHANGED SINCE PREVIOUS SUBMITTAL.)

CORRECTIVE ACTION:

(INSTALLATION) l CORRECTIVE ACTION SCHEDULE
REFUEL V; NOVEMBER 1985 MAR NUMBER: 80-10-66-05 l

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

A-239

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS

( ID NUMBER: SP-6A-PT3,4 SP-6B-PT3,4 RECORD NUMBER: 0149 SCEW PAGE NUMBER: 2-186A 2 DESCRIPTION: PRESSURE TRANSMITTER LOCATION:

CONTAINMENT ELEV.

119' MANUFACTURER: FOXBORO TER EQUIPMENT NO.:

36 MODEL: EllGH TER CATEGORY:

II.A SYSTEM: SP ZONE LOCATION:

39 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL O

QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

CORRECTIVE ACTION:

REPLACE.

CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER 1985 MAR NUMBER: 80-10-66-05 JUSTIFICATION FOR CONTINUED OPERATION:

SEE ATTACHED.

O V

A-240

.. . - - ..--~ - . -- - , .

JUSTIFICATION FOR CONTINUED OPERATION for SP-6A-PT3, 4 and SP-6B-PT3, 4 2 Foxboro Transmitter TER Item 36 References

1) FPC 79-OlB Response, Figure 4-8.
2) B&W Proprietary Document 58-0079-001, " Test Data for Nuclear Transmitters" (Foxboro) FPC File F180-3TR-002.
3) Foxboro Test Report T2-1057, " Radiation Test of E-10 Series Differential Pressure Transmitter" (August, 1973).
4) Foxboro Test Report T3-1097, " Radiation Test of E-10 Series Amplifiers - Standard and Radiation Resistant Types".
5) FPC IE Bulletin 79-OlB Response, Figure 4-5, " Reactor Building Pressure vs. Time".

{} SP-6A-PT3, replaced prior to November, 1985.

4 and SP-6B-PT3, 4 Foxboro transmitters will be The units will be replaced with Rosemount transmitters, and will have documented evidence of qualification. The safety function of providing post accident monitoring information will be accomplished by pressure transmit-ters installed for the emrgency feedwater change.

In the interim between the present and scheduled replacement, the following justifications for continued operation are given:

4

1. Figure 4-8 of the FPC 79-01B Response (Reference 1) has been

)! reproduced from Reference 2, " Test Data for Nuclear Trans-

! mitters". The test conditions shown in Figure 4-8 completely envelope the conditions specified (Reference 5) for Crystal River for high temperature and pressure condi-tions. Radiation conditions are discussed below.

O A-241

2. Subsequent to the qualification tests performed for B&W (Reference 2) , Foxboro performed tests on E10 Series Trans-mitters and Amplifiers (Reference 3 and 4) to levels of 1.0 ,

^

x 10' rads or greater. Maximum error was 5.7% in zero shift for an amplifier irradiated to 2.2 x 10 8 rads (a factor of 37 above the 5.9 x 10 6 rads specified for Crystal River) .

Maximum error at 1 x 10 7 rads was 4.2%. Due to the fact that accuracy was better than specified for Crystal River (5%)

for transmitters and amplifiers at 1.0 x 10 7 rads and the fact that maximum error at 2.2 x 10 8 was only 0.7% greater than specified, the transmitters should operate at the Crystal River specified radiation dose of 5.9 x 10 6 rads including margin.

O -

O A-242

. . . - - - - . - ~ - - __ - .- - - - ._.

FLORIDA POWER CORPORATION QUALIFICATION STATUS CUMMARY SHEETS O ID NUMBER: SP-8A-DPT1, 2, & 3 SP-8B-DPT1, 2, & 3 RECORD NUMBER: 0150 SCEW PAGE NUMBER: 2-187 ,

DESCRIPTION: DIFFERENTIAL LOCATION:

PRESSURE TRANSMITTER TURBINE BLDG.

ELEV. 100' MANUFACTURER: BM CO.

TER EQUIPMENT NO.:

48 MODEL: BY 6241-A TER CATEGORY:

I.B SYSTEM: SP ZONE LOCATION:

N/A TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

CORRECTIVE ACTION:

REPLACE.

CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER 1985 MAR NUMBER: 82-05-24-04 JUSTIFICATION FOR CONTINUED OPERATION:

SEE ATTACHED.

O A-243

l 1

l 1

JUSTIFICATION FOR CONTINUED OPERATION for SP-8A-DPT 1,2,3 and SP-8B-DPT 1,2,3 Bailey Transmitters TER Item No. 48 References

1) FPC I&E Bulletin 79-OlB Response, p. 2-187.

The feedwater flow pressure transmitters will be replaced by qualified equipment which will be installed by November, 1985.

In the interim between the present and November, 1985, the following justifications for continued operation are given:

1. The feedwater flow pressure transmitters have no radiation qualification requirement since their location is in the turbine building.
2. The function of the flow transmitters is to determine the availability of the main feedwater system to provide reactor heat removal for LOCA or MSLB. The availability of main feedwater can be determined by alternate means such as steam generator level and main feedwater system pressure. Also j the auxiliary feedwater system will provide the same func-tion during accident conditions and can be relied on to remove heat from the reactor upon main feedwater unavaila-bility.

l O

l A-244 l ... . -- . - _ _ , - - . _ _ . . . . _ _ - . . .

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: SWP-1A RECORD NUMBER: 0151 SWP-1B SCEW PAGE NUMBER: 2-188 2

DESCRIPTION: PUMP MOTOR LOCATION:

AUXILIARY BLDG.

ELEV. 95' MANUFACTURER: ELECTRIC MACHINERY TER EQUIPMENT NO.:

55 MODEL: FRAME SIZE 2525-S TER CATEGORY:

II.A SYSTEM: SW ZONE LOCATION:

11 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL O

QUALIFICATION STATUS:

NOT IN SCOPE. SUBSEQUENT REVIEW SHOWS THESE ITEMS ARE LOCATED IN A MILD ENVIRONMENT. (ENVIRONMENTAL ZONE INDICATED ABOVE) SEE SECTION 2.2 DISCUSSION.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

A-245

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS

() ID NUMBER: SWP-1A & 1B RECORD NUMBER:

SCEW PAGE NUMBER:

0152 2-188A 2

DESCRIPTION: LUBRICANT LOCATION:

AUXILIARY BLDG.

ELEV. 95' MANUFACTURER: GULF TER EQUIPMENT NO.:

MODEL: GULF HARMONY 46 TER CATEGORY:

N/A SYSTEM: SW ZONE LOCATION:

11 TER QUALIFICATION DEFICIENCIES NOTED:

NOT INCLUDED IN EVALUATION C) -

QUALIFICATION STATUS:

NOT IN SCOPE. SUBSEQUENT REVIEW SHOWS THESE ITEMS ARE LOCATED IN A MILD ENVIRONMENT. (ENVIRONMENTAL ZONE INDICATED ABOVE) SEE SECTION 2.2 DISCUSSION.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

() .

A-246 t-

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: SWV-12 RECORD NUMBER: 0153 SCEW PAGE NUMBER: 2-189 2 DESCRIPTION: SOLENOID VALVE LOCATION:

AUXILIARY BLDG.

ELEV. 119' MANUFACTURER: ASCO TER EQUIPMENT NO.:

MODEL: LB8321A8 TER CATEGORY:

N/A SYSTEM: SW ZONE LOCATION:

28 TER QUALIFICATION DEFICIENCIES NOTED:

NOT INCLUDED IN EVALUATION h

(b QUALIFICATION STATUS:

NOT IN SCOPE. SUBSEQUENT REVIEW SHOWS THESF ITEMS ARE LOCATED IN A MILD ENVIRONMEN'. . (ENVIRONMENTAL ZONE INDICATED ABOVE) SEE SECTION 2.2 DISCUSSION.

CORRECTIVE ACTION:

1 NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

A-247 i

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS

() ID NUMBER: SWV-35,37,39 41,43,45 RECORD NUMBER: 0154 SCEW PAGE NUMBIR: 2-190 ,

DESCRIPTION: SOLENOID VALVE LOCATION:

AUXILIARY BLDG.

ELEV. 95' MANUFACTURER: ASCO TER EQUIPMENT NO.:

MODEL: LB8344A5 TER CATEGORY:

N/A SYSTEM: SW ZONE LOCATION:

36 TER QUALIFICATION DEFICIENCIES NOTED:

NOT INCLUDED IN EVALUATION QUALIFICATION STATUS:

NOT IN SCOPE. SUBSEQUENT REVIEW SHOWS THESE ITEMS ARE LOCATED IN A MILD ENVIRONMENT. (ENVIRONMENTAL ZONE INDICATED ABOVE) SEE SECTION 2.2 DISCUSSION.

CORRECTIVE ACTION:

i NOT APPLICABLE.

  • l l

l CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

I

MAR NUMBER
NOT APPLICABLE.

l l

l JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

A-248

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: SWV-47,48,49 & 50 RECORD NUMBER: 0155 SCEW PAGE NUMBER: 2-191 ,

DESCRIPTION: SOLENOID VALVE LOCATION:

AUXILIARY BLDG.

ELEV. 95' MANUFACTURER: ASCO TER EQUIPMENT NO.:

26 MODEL: LB8321A8 TER CATEGORY:

I.B SYSTEM: SW ZONE LOCATION:

36 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

CORRECTIVE ACTION:

REPLACE.

l CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER 1985 MAR NUMBER: 82-05-24-03

(

JUSTIFICATION FOR CONTINUED OPERATION:

SEE ATTACHED.

O

, A-249 l

JUSTIFICATION FOR CONTINUED OPERATION for SWV-47, 48, 49 & 50 TER Item 26 References

1) FPC Environmental Qualification of Class lE Equipment IE Bulletin 79-01B Qualification Summary.

In the interim between the present and scheduled corrective action, the following justification for continued operation, as previously provided in Reference 1, is given:

1. Investigations with the manufacturer indicate the solenoid valves are good for 10 5 rads. Accident conditions will not affect the components for the period of operability required. Also, due to the location of the component when required to perform its safety function, the accident environment has no impact.
2. Due to the period of operability required as per CRf3 Tech.

, Spec. Table 3.6-1 to perform their safety function, and the fact that the total radiation exposure per the SCEW sheets is conservative in regard to the 5-1/2 year operating life of the plant, these valves are not considered to be a restraint to the safe operation of CR#3.

O A-250

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS O

U ID NUMBER: SWV-79,80,81,82,83 84,85 & 86 RECORD NUMBER: 0156 SCEW PAGE NUMBER: 2-19:2 2

DESCRIPTION: SOLENOID VALVE LOCATION:

AUXILIARY BLDG.

ELEV. 119' MANUFACTURER: ASCO TER EQUIPMENT NO.:

27 MODEL: LB8321A8 TER CATEGORY:

I.B SYSTEM: SW ZONE LOCATION:

22 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL

%)

QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

CORRECTIVE ACTION:

REPLACE.

CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER 1985 MAR NUMBER: 82-05-24-03 JUSTIFICATION FOR CONTINUED OPERATION:

SEE ATTACHED.

O V

A-251

JUSTIFICATION FOR CONTINUED OPERATION for SWV-79, 80, 81, 82, 83, 84, 85 & 86 2 TER Item 27 References

1) FPC Environmental Qualification of Class lE Equipment IE Bulletin 79-018 Qualification Summary.

In the interim between the present and scheduled corrective action, the following justification for continued operation, as previously provided in Reference 1, is given:

1. Investigations with the manufacturer indicate the solenoid valves are good for 105 rads. Accident conditions will not p affect the components for the period of operability required. Also, due to the location of the component when required to perform its safety function, the accident environment has no impact.
2. Due to the period of operability required as per CRf3 Tech.

Spec. Table 3.6-1 to perform their safety function, and the fact that the total radiation exposure per the SCEW sheets is conservative in regard to the 5-1/2 year operating life of the plant, these valves are not considered to be a restraint to the safe operation of CR#3.

O A-252

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: SWV-109 & RECORD NUMBER: 0157 110-SV-3/4 SCEW PAGE NUMBER: 2-193 ,

DESCRIPTION: SOLENOID VALVE LOCATION:

AUXILIhRY BLDG.

ELEV. 119' MANUFACTURER: ASCO TER EQUIPMENT NO.:

30 MODEL: HT831655 TER CATEGORY:

I.B SYSTEM: SW ZONE LOCATION:

22 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

CORRECTIVE ACTION:

REPLACE.

CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER 1985 l MAR NUMBER: 82-05-24-03 l

l l JUSTIFICATION FOR CONTINUED OPERATION:

SEE ATTACHED.

O A-253

JUSTIFICATION FOR CONTINUED OPERATION for SWV-109 & 110-SV3/4 2 TER Item 30 References

1) FPC Environmental Qualification of Class lE Equipment IE Bulletin 79-01B Qualification Summary.

In the interim between the present and scheduled corrective action, the following justification for continued operation, as previously provided in Reference 1, is given:

1. Investigations with the manufacturer indicate the solenoid valves are good for 105 rads. Accident conditions will not affect the components for the period of operability required. Also, due to the location of the component when required to perform its safety function, the accident environment has no impact.
2. Due to the period of operability required as per CR3 Tech.

Spec. Table 3.6-1 to perform their safety function, and the fact that the total radiation exposure per the SCEW sheets is conservative in regard to the 5-1/2 year operating life of the plant, these valves are not considered to be a restraint l to the safe operation of CR3.

i l

O A-254

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: SWV-151,152,353 RECORD NUMBER: 0158

{~'}/

s- 354,355 SCEW PAGE NUMBER: 2-194 a DESCRIPTION: SOLENOID VALVE LOCATION:

AUXILIARY BLDG.

ELEV. 95' MANUFACTURER: ASCO TER EQUIPMENT NO.:

MODEL: LB8321A6 TER CATEGORY:

N/A SYSTEM: SW ZONE LOCATION:

64 TER QUALIFICATION DEFICIENCIES NOTED:

NOT INCLUDED IN EVALUATION O -

QUALIFICATION STATUS:

NOT IN SCOPE. SUBSEQUENT REVIEW SHOWS THESE ITEMS ARE LOCATED IN A MILD ENVIRONMENT. (ENVIRONMENTAL ZONE INDICATED ABOVE) SEE SECTION 2.2 l DISCUSSION.

l CORRECTIVE ACTION:

NOT APPLICABLE.

i CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

l A-255

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS

/~N ID NUMBER: SW-3 RECORD NUMBER: 0159 U

SCEW PAGE NUMBER: 2-195 a

DESCRIPTION: LOCAL CONTROL LOCATION:

STATION AUXILIARY BLDG.

ELEV. 119' MANUFACTURER: FIELD FABRICATED TER EQUIPMENT NO.:

MODEL: G.E. TYPE UA202 SW.

G.E. TYPE UC212 LIGHT TER CATEGORY:

N/A SYSTEM: SW ZONE LOCATION:

28 TER QUALIFICATION DEFICIENCIES NOTED:

NOT INCLUDED IN EVALUATION O

QUALIFICATION STATU3:

NOT IN SCOPE. SUBSEQUENT REVIEW SHOWS THESE ITEMS ARE LOCATED IN A MILD ENVIRONMENT. (ENVIRONMENTAL ZONE INDICATED ABOVE) SEE SECTION 2.2 DISCUSSION.

CORRECTIVE ACTION:

NOT APPLICABLE. .

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

O A-256

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS fN

%Y ID NUMBER: SW-6 RECORD NUMBER: 0190 SCEW PAGE NUMBER: 2-197 s

DESCRIPTION: LOCAL CONTROL LOCATION:

STATION AUXILIARY BLDG.

ELEV. 95'-0" MANUFACTURER: FIELD FABRICATED TER EQUIPMENT NO.:

MODEL: G.E. TYPE UA202 SW.

G.E. TYPE UC212 LIGHT TER CATEGORY:

I.B-A SYSTEM: SW ZONE LOCATION:

TER QUALIFICATION DEFICIENCIES NOTED:

NOT INCLUDED IN EVALUATION.

(~

U)

QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

CORRECTIVE ACTION:

. RELOCATE.

CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER 1985 MAR NUMBER: 82-05-24-02 JUSTIFICATION FOR CONTINUED OPERATION:

SEE JCO FOR AS-1, RECORD 0013.

O\

V A-257 l

FLORIDA POWER CORPORATION QUALIFICATION ST%TUS CUMMARY SHEETS

( ID NUMBER: SW-7 RECORD NUMBER: 0160 SCEW PAGE NUMBER: 2-198 2 DESCRIPTION: LOCAL CONTROL LOCATION:

STATION AUXILIARY BLDG.

ELEV. 119' MANUFACTURER: FIELD FABRICATED TER EQUIPMENT NO.:

89 MODEL: G.E. TYPE UA202 SW.

G.E. TYPE UC212 LIGHT TER CATEGORY:

I.B SYSTEM: SW ZONE LOCATION:

22 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL O

v QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

CORRECTIVE ACTION:

RELOCATE TO MILD ENVIRONMENT.

CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER 1985 MAR NUMBER: 82-05-24-02 JUSTIFICATION FOR CONTINUED OPERATION:

SEE JCO FOR AS-1 (RECORD 013) l A-258 l

l

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: SW-8 RECORD NUMBER: 0191

(

SCEW PAGE NUMBER: 2-199 2

DESCRIPTION: LOCAL CONTROL LOCATION:

STATION AUXILIARY BLDG.

ELEV. 119'-0" MANUFACTURER: FIELD FABRICATED TER EQUIPMENT NO.:

90 MODEL: G.E. TYPE UA202 SW.

G.E. TYPE UC212 LIGHT TER CATEGORY:

I.B SYSTEM: SW ZONE LOCATION:

14 TER QUALIFICATION DEFICIENCIES NOTED:

NOT INCLUDED IN EVALUATION.

O QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

CORRECTIVE ACTION:

RELOCATE TO MILD ENVIRONMENT.

CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER 1985 MAR NUMBER: 82-05-24-02 i

l JUSTIFICATION FOR CONTINUED OPERATION:

SEE JCO FOR AS-1, RECORD 0013.

l A-259

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS

() ID NUMBER: SW-9 RECORD NUMBER:

SCEW PAGE NUMBER:

0161 2-200 ,

DESCRIPTION: LOCAL CONTROL LOCATION:

STATION AUXILIARY BLDG.

ELEV. 119' MANUFACTURER: FIELD FABRICATED TER EQUIPMENT NO.:

89 MODEL: G.E. TYPE UA202 SW.

G.E. TYPE UC212 LIGHT TER CATEGORY:

I.B SYSTEM: SW ZONE LOCATION:

22 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL A)

(_

QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

CORRECTIVE ACTION:

RELOCATE TO A MILD ENVIRONMENT.

CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER 1985 MAR NUMBER: 82-05-24-02 JUSTIFICATION FOR CONTINUED OPERATION:

SEE JCO FOR AS-1 (RECORD 013)

O A-260

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS Q

D ID NUMBER: SW-10 RECORD NUMBER: 0162 SCEW PAGE NUMBER: 2-201 a

DESCRIPTION: LOCAL CONTROL LOCATION:

STATION AUXILIARY BLDG.

ELEV. 95' MANUFACTURER: FIELD FABRICATED TER EQUIPMENT NO.:

MODEL: G.E. TYPE UA202 SW.

G.E. TYPE UC212 LIGHT TER CATEGORY:

N/A SYSTEM: SW ZONE LOCATION:

11 TER QUALIFICATION DEFICIENCIES NOTED:

NOT INCLUDED IN EVALUATION O

QUALIFICATION STATUS:

NOT IN SCOPE. SUBSEQUENT REVIEW SHOWS THESE ITEMS ARE LOCATED IN A MILD ENVIRONMENT. (ENVIRONMENTAL ZONE INDICATED ABOVE) SEE SECTION 2.2 DISCUSSION.

CORRECTIVE ACTION:

NOT APPLICABLE.

I CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

l.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

O A-261

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: SW-11,13 & 14 RECORD NUMBER: 0163 SCEW PAGE NUMBER: 2-202 a

DESCRIPTION: LOCAL CONTROL LOCATION:

STATION AUXILIARY BLDG.

ELEV. 95' MANUFACTURER: FIELD FABRICATED TER EQUIPMENT NO.:

MODEL: G.E. TYPE UA202 SW.

G.E. TYPE UC212 LIGHT TER CATEGORY:

N/A SYSTEM: SW ZONE LOCATION:

11 TER QUALIFICATION DEFICIENCIES NOTED:

NOT INCLUDED IN EVALUATION O

QUALIFICATION STATUS:

NOT IN SCOPE. SUBSEQUENT REVIEW SHOWS THESE ITEMS ARE LOCATED IN A MILD ENVIRONMENT. (ENVIRONMENTAL ZONE INDICATED ABOVE) SEE SECTION 2.2 DISCUSSION.

CORRECTIVE ACTION:

NOT APPLICABLE.

l CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

A-262 i l

FLORIDA POWER CORPORATION +

QUALIFICATION STATUS

SUMMARY

SHEETS

! ID NUMBER: SW-3 RECORD NUMBER: 0164 SCEW PAGE NUMBER: 2-203 a '

DESCRIPTION: TERMINAL BOX LOCATION:

AUXILIARY BLDG.

ELEV. 119' MANUFACTURER: FIELD FABRICATED '

TER EQUIPMENT NO : s NA MODEL: STATES TYPE NT TERMINAL BLOCKS TER CATEGORY:

N/A SYSTEM: SW ZONE LOCATION:

28 TER QUALIFICATION DEFICIENCIES NOTED:

NOT INCLUDED IN EVALUATION i '~

1

,c

\ i

}. . , . .

QUALIFICATION STATUS: ')  ;

NOT IN SCOPE. SUBSEQUENT REVIEW SHOWS THESE ITEMS ARE LOCATED IN A MILD ENVIRONMENT. (ENVIRONMENTAL ZONE INDICATED ABOVE) SEE SECTION 2.2 DISCUSSION.

CORRECTIVE ACTION:

NOT APPLICABLE. -

< l CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE. , , ,

's n'-

g ,

MAR NUMBER: NOT APPLICABLE. -

c i4 s_, .-

JUSTIFICATION FOR CONTINUED OPERATION: 1 ,

, l'

  • NOT REQUIRED. ,, , w

' *1, t

A-263 y

. . . _ . . _ . _ . _ . _ . _ _ _ _, _ ju.%, . _ _ _ . __ _ _ . _

(3,

PLORIDA POWER CORPORATION .

QUALIFICATION STATUS

SUMMARY

SHEETS ,

ID NUMBER: SW-4,5,19 RECORD NUMBER: 0165 SCEW PAGE NUMBER: 2-204 1

DESCRIPTION: TERMINAL BOX LOCATION:

AUXILIARY BLDG. -

_* ~

ELEV. 95'" ,

MANUFACTURER: FIELD FABRICATED

% s ,, -

TER EQUIPMENT NO.: ~

. NA MODEL: STATES TYPE NT

TERMINAL BLOCKS ^

TER CATEGORY:

, g . ,-

N/A.

'SYSTEMd '

Sh' A

\'

D '

~N ZONE LOCATION:

, i -

N 64 i

g i.

TER QUALIFICATION DEFIC,iNNCIES NOTED:

...s, NOT , INCLUDED IN EVALITA' TION 3_ ..-

N pr Ox \

.f N

\ ,_

QUALIFICATION STATUS: .

s NOT IN UCOPE. SUBSEQUENT REVIEi6 g ~ b

' \' k. s SHOWS THESE ITEMS ARE LOCATED IN MA MILD't '

ENVIRONMENT. (ENVIRONMENTAL 2ONE i INDICATED'4BOVE) SEE SECTION 2.2 ",, -

..'.__ N

'_,('s " fi ,

DISCUSSION. C ,,' ' 9 u it,, d_ ; <

CORRE[.TIVE ACTION: s' i

. i,. m i NOT ' APPLICABLE . "' "' '

t , Q i .'. ,

34v , \

s

)

s.

i .Ii

~. . .

\, ,. 4 .

s CORRECTIVE ACTION SCHEDULE: NOT APPLIQ.BLE.

x s' ~,Q* w MAR NU G ER:  ; NOT APPL'LCABL3'h ; ' '

r m ,  ; , ~. . .-

~

~~>%y

~

z ,;. , c-  %

^

JUSTIFIC5TTC$ EOECON'5NUED GPERATI,b

, - - . M' , '

s NOT REQt1IESD. it

, ;,' M, _ '

i ' , s. , \

  • g- ' g-E  ;--

s s- s_ ..(

t g

st -

g4- , r., -

.s.

A. -2 n; \ 'l'+ - -

t'~sc -

N'*' ~x ' #

s.i oj

, ', t 3* "

1.t

., N

\ = ys

's N,Ni

~; 3. . ,

l' s

-% s , ,

l FLORIDA POWER CLRPORATION '

i QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: SW-6 RECORD NUMBER: 0166 SCEW PAGE NUMBER: 2-205 ,

DESCRIPTION: TERMINAL BOX LOCATION:

AUXILIARY BLDG.

ELEV. 95' '

MANUFACTURER: FIELD FABRICATED TER EQUIPMENT NO.:

MODEL: STATES TYPE NT TERMINAL BLOCKS TER CATEGORY:

I.B SYSTEM: SW

  • ZONE LOCATION:

36 '

TER QUALIFICATION DEFICIENCIES NOTED: ,

I h

  • }
3. AGING DEGRADATION EVAL .
4. QUAL LIFE OR REPLACE SKED
10. RADIATION EXPOSURE ,

i b

O '

QUALIFICATION STATUS:

\

QUALIFICATION MODIFICATIONS IN l PROGRESS.

I t

CORRECTIVE ACTION:

s RELOCATE.

I CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER,<1985.

MAR NUMBER: 82-05-24-07 i

JUSTIFICATION FOR CONTINUED OPERATION:

l SEE ATTACHED.

O -

f A-265 ,

h

. i t

>k~ JUSTIFICATION FOR CONTINUED OPERATION for SW 6 & 14, WD-3 i

States Terminal Blocks in Auxiliary Building TER Item 73 n

References l

1) Franklin Institute Research Laboratories Test Report QL-C4927, " Quick Look Report for a Steam and Chemical Spray '

Exposure Test of Elect.rical Terminal Blocks".

2) Wyle ' Report 17436-15, " Final Report on Evaluation of Terminal Block Model EB-25", dated 12/1/80.
3) Wyle 58687, " Loss of Coolant Accident Testing of 5 Weidmuller Terminal Blocks", dated 6/29/82.
4) Fink, D. G. and Beaty, H. W., " Standard Handbook for i Electrical Enginee\rs", Eleventh Edition, '"able 4-71.

?

In the interim between the present time and scheduled ,

qualification completion and installation, the following justifications for continued operation are given:

1. The above referenced test reports indicate that phenolic terminal blocks can survive the relatively mild environment in the auxiliary building.
2. Reference 4 indicates that the maximum use temperature for phenolics is 350 F, which is greater than the maximum tem-perature during normal environments in tih'e auxiliary

\

building. Radiation, pressure'and moisture' conditions were

.i addressed in the othM referenced test reports.

s ja 4

3. The mos$ sensitive organic material, Polypropylene, is used

/A for terminal barriehs'tand their failure is not expected to

/ affect the Class lE function of the terminal block.

.O 4

u A-266 s  !

N

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: SW-7 RECORD NUMBER: 0167 SCEW PAGE NUMBER: 2-206 ,

DESCRIPTION: TERMINAL BOX LOCATION:

AUXILIARY BLDG.

ELEV. 119' MANUFACTURER: FIELD FABRICATED TER EQUIPMENT NO.:

69 MODEL: STATES TYPE NT TERMINAL BLOCKS TER CATEGORY:

I.B SYSTEM: SW ZONE LOCATION:

22 TER QUALIFICATION DEFICIENCIES NOTED:

3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED O

QUALIFICATION STATUS:

QUALIFIED FOR CURRENT APPLICATION.

SEE APPENDIX A.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

A-267

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS 4 ID NUMBER: SW-8 RECORD NUMBER: 0168 SCEW PAGE NUMBER: 2-207 ,

DESCRIPTION: TERMINAL BOX LOCATION:

AUXILIARY BLDG.

ELEV. 119' MANUFACTURER: FIELD FABRICATED TER EQUIPMENT NO.:

69 MODEL: STATES TYPE NT TERMINAL BLOCKS TER CATEGORY:

I.B SYSTEM: SW ZONE LOCATION:

22 TER QUALIFICATION DEFICIENCIES NOTED:

3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED QUALIFICATION STATUS:

QUALIFIED FOR CURRENT APPLICATION.

SEE APPENDIX A.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

A-268

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: SW-9 RECORD NUMBER: 0169 SCEW PAGE NUMBER: 2-208 4 DESCRIPTION: TERMINAL BOX LOCATION:

AUXILIARY BLDG.

ELEV. 119' MANUFACTURER: FIELD FABRICATED TER EQUIPMENT NO.:

69 MODEL: STATES TYPE NT TERMINAL BLOCKS TER CATEGORY:

I.B SYSTEM: SW ZONE LOCATION:

22 TER QUALIFICATION. DEFICIENCIES NOTED:

3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED O

QUALIFICATION STATUS:

QUALIFIED FOR CURRENT APPLICATION.

SEE APPENDIX A.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

A-269

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: SW-10 RECORD NUMBER: 0170 SCEW PAGE NUMBER: 2-209 ,

DESCRIPTION: TERMINAL BOX LOCATION:

AUXILIARY BLDG.

ELEV. 95' MANUFACTURER: FIELD FABRICATED TER EQUIPMENT NO.:

NA MODEL: STATES TYPE NT TERMINAL BLOCKS TER CATEGORY:

N/A SYSTEM: SW ZONE LOCATION:

11 TER QUALIFICATION DEFICIENCIES NOTED:

NOT INCLUDED IN EVALUATION O .

QUALIFICATION STATUS:

NOT IN SCOPE. SUBSEQUENT REVIEW SHOWS THESE ITEMS ARE LOCATED IN A MILD ENVIRONMENT. (ENVIRONMENTAL ZONE INDICATED ABOVE) SEE SECTION 2.2 DISCUSSION.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NO'" APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

O A-270

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS s

ID NUMBER: SW-11,12 & 13 RECORD NUMBER: 0171 SCEW PAGE NUMBER: 2-210 2 DESCRIPTION: TERMINAL BOX LOCATION:

AUXILIARY BLDG.

ELEV. 95' MANUFACTURER: FIELD FABRICATED TER EQUIPMENT NO.:

NA MODEL: STATES TYPE NT TERMINAL BLOCKS TER CATEGORY:

N/A SYSTEM: SW ZONE LOCATION:

11 TER QUALIFICATION DEFICIENCIES NOTED:

NOT INCLUDED IN EVALUATION O

QUALIFICATION STATUS:

NOT IN SCOPE. SUBSEQUENT REVIEW SHOWS THESE ITEMS ARE LOCATED IN A MILD ENVIRONMENT. (ENVIRONMENTAL ZONE INDICATED ABOVE) SEE SECTION 2.2 DISCUSSION.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

O A-271

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: SW-14 RECORD NUMBER: 0172 SCEW PAGE NUMBER: 2-211 2 DESCRIPTION: TERMINAL BOX LOCATION:

AUXILIARY BLDG.

ELEV. 95' MANUFACTURER: FIELD FABRICATED TER EQUIPMENT NO.:

73 MODEL: STATES TYPE NT TERMINAL BLOCKS TER CATEGORY:

I.B SYSTEM: SW ZONE LOCATION:

36 TER QUALIFICATION DEFICIENCIES NOTED:

3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED
10. RADIATION EXPOSURE QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

CORRECTIVE ACTION:

1 RELOCATE.

i l

CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER, 1985.

MAR NUMBER: 82-05-24-07

{

JUSTIFICATION FOR CONTINUED OPERATION:

SEE JCO FOR SW-6 (RECORD 166).

p)g

\-

A-272 l

l

FLORIDA PON3R CORPORATION QUALIFICATION STATUS SUDGEARY SHEETS ID NUMBER: SW-15 RECORD NUMBER: 0173 SCEW PAGE NUMBER: 2-212 ,

DESCRIPTION: TERMINAL BOX LOCATION:

AUXILIARY BLDG.

ELEV. 119' MANUFACTURER: FIELD FABRICATED TER EQUIPMENT NO.:

69 MODEL: STATES TYPE NT TERMINAL BLOCKS TER CATEGORY:

I.B SYSTEM: SW ZONE LOCATION:

22 TER QUALIFICATION DEFICIENCIES NOTED:

3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED O

QUALIFICATION STATUS:

QUALIFIED FOR CURRENT APPLICATION.

SEE APPENDIX A.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

A-273

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS O)

N/

ID NUMBER: SW-18 RECORD NUMBER: 0174 SCEW PAGE NUMBER: 2-213 ,

DESCRIPTION: TERMINAL BOX LOCATION:

AUXILIARY BLDG.

ELEV. 95' MANUFACTURER: FIELD FABRICATED TER EQUIPMENT NO.:

NA MODEL: STATES TYPE NT TERMINAL BLOCKS TER CATEGORY:

N/A SYSTEM: SW ZONE LOCATION:

11 TER QUALIFICATION DEFICIENCIES NOTED:

NOT INCLUDED IN EVALUATION QUALIFICATION STATUS:

NOT IN SCOPE. SUBSEQUENT REVIEW SHOWS THESE ITEMS ARE LOCATED IN A MILD ENVIRONMENT. (ENVIRONMENTAL ZONE INDICATED ABOVE) SEE SECTION 2.2 DISCUSSION.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMEER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

l A-274

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: WDV-3 RECORD NUMBER: 0175 SCEW PAGE NUMBER: 2-214 s

DESCRIPTION: VALVE MOTOR LOCATION:

OPERATOR INSIDE CONTAINMENT ELEV. 112' MANUFACTURER: LIMITORQUE TER EQUIPMENT NO.:

12 MODEL: SMB-000-2 TER CATEGORY:

II.A SYSTEM: WD ZONE LOCATION:

38 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL
2. EQUIP VS TEST SPECIMEN
3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED
10. RADIATION EXPOSURE O

O QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

SEE DISCUSSION ATTACHED.

CORRECTIVE ACTION:

REPLACE MOTOR.

CORRECTIVE ACTION SCHEDULE: REFUEL V, NOVEMBER 1985.

MAR NUMBER: 82-05-24-06 JUSTIFICATION FOR CONTINUED OPERATION:

SEE ATTACHED.

O A-275

DISCUSSION ON O WDV 3 Record 0175 ,

Correspondence from Limitorque (L200-3VC-007) indicates that Test Report 600198 plus Addendum 1 apply to this actuator. A walkdown was conducted and the results (L200-WW-001) were discussed with the vendor. The vendor was requested to identify activities required to upgrade this actuator such that Qualification Report 600456 (L200-3TR-001) would apply, thereby ensuring all environ-mental parameters for Zone 38 would be encompassed by testing.

The vendor response (L200-3VC-008) indicates motor replacement with a Class RH insulated motor will be required.

O A-276

4 JUSTIFICATION FOR CONTINUED OPERATION 2 for 3 '

WDV-3 Limitorque Motor Operator TER Item 12

! In the interim between the present and corrective action, the

, following justification for continued operation is given:

1. WDV-3 is a normally closed valve which is used to drain the RB sump. During an accident, the valve has no active function to perform and will fail as is. Therefore, failure of the valve operator can be tolerated.
O .

r i o

'O A-277 l

FLORIDA PONER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: WDV-60 RECORD NUMBER: 0176 SCEW PAGE NUMBER: 2-215 ,

DESCRIPTION: VALVE MOTOR OPERATOR LOCATION:

INSIDE CONTAINMENT ELEV. 112' MANUFACTURER: LIMITORQUE TER EQUIPMENT NO.:

04 MODEL: SMB-000-5 TER CATEGORY:

II.A SYSTEM: WD ZONE LOCATION:

38 TER QUALIFICATION DEFICIENCIES NOTED:

2. EQUIP VS TEST SPECIMEN
3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED f~h V

QUALIFICATION STATUS:

QUALIFIED FOR CURRENT APPLICATION.

SEE DISCUSSION ATTACHED.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCI!EDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

O A-278

i l l

DISCUSSION ON WDV-60; 94; 406 Limitorque Motor Operators Records 0176, 0177, 0179 Initial discussions with the vendor using shop order numbers and serial numbers of originally installed equipment indicates Test Report 600456 (L200-3TR-001) applies to this equipment. This report encompasses all environmental parameters for the required operating time of this equipment. Walkdowns are scheduled during the current outage to confirm and document qualification. From the current information available, Florida Power Corporation

considers this equipment qualified for its current application.

1 O -

4 9

'T 1

1 O

A-279

~ - _ - . ~ . _ - . - _ - . . . . . , . - . - - . - . . - - , . . - . . . . . - _ . - - _ . - -. - -.

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS

(} ID NUMBER: WDV-94 RECORD NUMBER:

SCEW PAGE NUMBER:

0177 2-216 ,

DESCRIPTION: VALVE MOTOR nDERATOR LOCATION:

INSIDE CONTAINMENT ELEV. 112' MANUFACTURER: LIMITORQUE TER EQUIPMENT NO.:

04 MODEL: SMB-000-2 4 TER CATEGORY:

II.A SYSTEM: WD ZONE LOCATION:

38 TER QUALIFICATION DEFICIENCIES NOTED:

2. EQUIP VS TEST SPECIMEN
3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED m

QUALIFICATION STATUS:

QUALIFIED FOR CURRENT APPLICATION.

SEE DISCUSSION FOR WDV-60, RECORD 0176.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

v A-280

\.-. _ _ _ . . _ , - -_ _

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: WDV-405 RECORD NUMBER: 0178 SCEW PAGE NUMBER: 2-217 2 DESCRIPTION: VALVE PTOR OPERATOR LOCATION:

AUXILIARY BLDG.

ELEV. 119' -0" MANUFACTURER: LIMITORQUE TER EQUIPMENT NO.:

18 MODEL: SMB000 TER CATEGORY:

II.A SYSTEM: WD ZONE LOCATION:

22 TER QUALIFICATION DEFICIENCIES NOTED:

2. EQUIP VS TEST SPECIMEN
3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED O

QUALIFICATION STATUS:

QUALIFIED FOR CURRENT APPLICATION.

SEE DISCUSSION ATTACHED.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

p NOT REQITIRED.

's )

A-281 i

l - - - - - -

DISCUSSION ON WDV 407 e

Record 0178 Vendor correspondence (L200-3VC-005) indicates Test Report 600456 (L200-3TR-001) applies to this actuator. Hence, all environ-mental parameters for Zone 38 are encompassed by testing and this equipment is considered qualified for its current application.

i I

J

O h

O A-282  ;

f l

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS

) ID NUMBER: WDV-406 RfCORD NUMBER: 0179 SCEW PAGE NUMBER: 2-218 2 DESCRIPTION: VALVE MOTOR OPERATOR LOCATION:

IN CONT.ELEV. 119' OUTSIDE SHIELD WALL MANUFACTURER: LIMITORQUE TER EQUIPMENT NO.:

14 MODEL: SMB-000 TER CATEGORY:

II.A SYSTEM: WD ZONE LOCATION:

39 TER QUALIFICATION DEFICIENCIES NOTED:

2. EQUIP VS TEST SPECIMEN
3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED l'

V) .

QUALIFICATION STATUS:

QUALIFIED FOR CURRENT APPLICATION.

SEE DISCUSSION FOR WDV-60, RECORD 0176.

-CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

A-283

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS

[ ID NUMBER: WDV-407 RECORD NUMBER: 0180 SCEW PAGE NUMBER: 2-219 ,

DESCRIPTION: VALVE MOTOR OPERATOR LOCATION:

CONTAINMENT ELEV.

112' MANUFACTURER: LIMITORQUE TER EQUIPMENT NO.:

15 MODEL: SMB-000 TER CATEGORY:

II.A SYSTEM: WD ZONE LOCATION:

38 TER QUALIFICATION DEFICIENCIES NOTED:

2. EQUIP VS TEST SPECIMEN
3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED
8. SPRAY O

QUALIFICATION STATUS:

QUALIFIED FOR CURRENT APPLICATION.

SEE DISCUSSION ATTACHED.

I i CORRECTIVE ACTION:

NOT APPLICABLE.

l l

l CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

A-284

i DISCUCSION ON WDV 407 2

Record 0180 Vendor correspondence (L200-3VC-012) indicates Test Report 80003 (L200-3TR-001) applies to this actuator. Review of this report indicates all environmental parameters from Zone 22 are encompassed. This equipment is considered qualified for its current application.

1

.t O

[

O A-285

_ _ . _ __ . ._.~ . - . . . _ . . . - _ _ _ . . . _ _ . . _ _ . . . _ . _ . - - . . _ . - _ . - . _ _ - - - _ _ _ _ . - - . . - . - -

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: WDV-4 RECORD NUMBER: 0181 SCEW PAGE NUMBER: 2-220 ,

DESCRIPTION: SOLENOID VALVE LOCATION:

AUXILIARY BLDG.

ELEV. 95' MANUFACTURER: ASCO TER EQUIPMENT NO.:

35 MODEL: 8320A20 TER CATEGORY:

I.B SYSTEM: WD ZONE LOCATION:

36 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

CORRECTIVE ACTION:

REPLACE.

CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER 1985 MAR NUMBER: 82-05-24-03 JUSTIFICATION FOR CONTINUED OPERATION:

SEE ATTACHED.

O A-286

fs JUSTIFICATION FOR CONTINUED OPERATION for WDV-4 3 TER Item 35 References

1) FPC Environmental Qualification of Class lE Equipment IE Bulletin 79-OlB Qualification Summary.

In the interim between the present and scheduled corrective action, the following justification for continued operation, as previously provided in Reference 1, is given:

1. Investigations with the manuf acturer indicate the solenoid valves are good for 10 5 rads. Accident conditions will not affect the components for the period of operability required. Also, due to the location of the component when required to perform its safety function, the accident environment has no impact.
2. Due to the period of operability required as per CR43 Tech.

Spec. Table 3.6-1 to perform their safety function, and the fact that the total radiation exposure per the SCEW sheets is conservative in regard to the 5-1/2 year operating life of the plant, these valves are not considered to be a restraint to the safe operation of CR#3.

A-287

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: WDV-61 & 62 RECORD NUMBER: 0182 SCEW PAGE NUMBER: 2-221 2 DESCRIPTION: SOLENOID VALVE LOCATION:

AUXILIARY BLDG.

ELEV. 95' MANUFACTURER: ASCO TER EQUIPMENT NO.:

35 MODEL: 8320A20 TER CATEGORY:

I.B SYSTEM: WD ZONE LOCATION:

36 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL m

U QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

CORRECTIVE ACTION:

REPLACE.

CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER 1985 MAR NUMBER: 82-05-24-03 i

JUSTIFICATION FOR CONTINUED OPERATION:

SI:E ATTACHED.

A-288 l

l

l i

JUSTIFICATION FOR CONTINUED OPERATION
for WDV-61 & 62 2 TER Item 35 References 4
1) FPC Environmental Qualification of Class lE Equipment IE Bulletin 79-01B Qualification Summary.

In the interim between the present and scheduled corrective action, the following justification for continued operation, as previously provided in Reference 1, is given:

1. Investigations with the manufacturer indicate the solenoid valves are good for 10 5 rads. Accident conditions will not affect the components for the period of operability _

. required. Also,.due to the location of the component when required to perform its safety function, the accident

! environment has no impact.

1

2. Due to the period of operability required as per CR93 Tech.

Spec. Table 3.6-1 to perform their safety function, and the fact that the total radiation exposure per the SCEW sheets is conservative in regard to the 5-1/2 year operating life of the plant, these valves are not considered to be a

! restraint to the safe operation of CRf3.

O i

A-289

..,.---._,.-.,-.-....-_.__..--,-,-.--,m-----.,---. .

,.r.-- -.m__.-.-..-,--.,.,,---n ,_,--.---,w....,,-. ,.m..-.,,-.,, .,, - r--

FLORIDA POWER CORPORATION QUALIFICATION STATUS CUMMARY SHEETS ID NUMBER: WD-1 RECORD NUMBER: 0192

(

SCEW PAGE NUMBER: 2-222 ,

DESCRIPTION: LOCAL CONTROL LOCATION:

STATION AUXILIARY BLDG.

ELEV. 95'-0" MANUFACTURER: FIELD FABRICATED TER EQUIPMENT NO.:

MODEL: G.E. TYPE UA202 SW.

G.E. TYPE UC212 LIGHT TER CATEGORY:

I.B-A SYSTEM: WD ZONE LOCATION:

~'

TER QUALIFICATION DEFICIENCIES NOTED:

NOT INCLUDED IN EVALUATION.

t O

v QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

CORRECTIVE ACTION:

RELOCATE TO A MILD ENVIRONMENT.

CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER 1985 MAR NUMBER: 82-05-24-02 JUSTIFICATION FOR CONTINUED OPERATION:

SEE JCO FOR AS-1, RECORD 0013.

O A-290

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ,\ s,

~,t ID NUMBER: WD-3 RECORD NUMBER: 0164  ;

SCEW PAGE NUMBER: 2-223 DESCRIPTION: TERMINAL BOX LOCATION: 1 AUXILIARY BLDG. ',1 ELEV. 95' ~

MANUFACTURER: FIELD FABRICATED TER EQUIPMENT NO.: , 3,

\ \

73 MODEL: STATES TYPE NT .

TERMINAL BLOCKS TER CATEGORY:

'I .B' SYSTEM: WD ZONE LOCATION:

36 s t

TER QUALIFICATION DEFICIENCIES NOTED:

3. AGING DEGRADATION EVAL 3 N
4. QUAL LIFE OR REPLACE SKED __
10. RADIATION EXPOSURE

('\

b)-

QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

CORRECTIVE ACTION: t RELOCATE.

, t x s.

CORRECTIVE ACTION SCHEDULE: REFUEL V, NOVEMBER, 1985. ,

~

s MAR NUMBER: 82-05-24-07 JUSTIFICATION FOR CONTINUED OPERATION:

SEE JCO FOR SW-6 (RECORD 166).

A-291

, t w  ;

3

(, s ,

s v ,

N ,

5- s '

FLORIDA POWER CORPORATION ,,

s ~s , s .

3

( g, ..t* QUALIFICATION STATU3'SUB9tARI SHEETS '1%

t *-

\'_.---

g s

s

,T s'\\.,'

g

. ,q -

_1 N \ 's s

( .ID PUMBER: WD-300-LT, WD-301-LT RELCRD 11UMBElu 0184 (

' \j ' WD-302-LT, WD-303-LT '$

.N s

..J , SCFM.PAGE NUMBER: 2 4B g+r, - Q N , *

- t , ,s LOCATJ.0F . g<! (.. , w. '

DESCRIPT"3N: ' TRANSMITTER T 1 '

y ' \l ' - C047.It.PL ' SUMP ELEV.

T- 91.' g B.WTR' OL.115' MANUFACTURER: DELAVAL (GEMS) AND d

  • s y ,

CABLE CO.

TIR MPUIPMEiT M'. : ** I MODEL: XM-54854

[, \ ' 50 ' !

\ .'

p 'LI ,,, ~

t

[\, '

XM-54852 '

TER CAT /' GOR'l I.L, \

DA T'd ;s SYSTEM: WD \ '

b '

' TONE LOCATION: I ~* M ',

' t ' '^

y ' R 37 \

-s

~:.< Q" ,

s 7

m s, 3. , c ..

'l , s ,

%' ' .lN TER QUALIFTCAI'23N > DEFICIENCIES NOTED: t,.' '

4 3-q w, q ,'L ,

.s.

g

... , g _. .

'g "

1. DOCUMEN?EDJ3VIDENCE OF QUAL ... k . tw

, .t

i. ;i 5

,  ; c,. \ - 1, . sT  %,'

s a s ,s

,i

  • s  % i .i

\ x* .

N ,

s ,t -

ss j ,, T , --

3,

\ v', \ .s , T---

\ 3

'

  • T/

N(, % , A , .

.. p 4 .> ,

s

\_, \. i ,s s

.I-

's

% 1 y g-

\ .. ..a s

t ,"

i; QUALIFICATION STATUS: s  ;

i .- \ C, \ ,s (NOT INSTALLED YET. ) w,'w i s '

'sw s

\, N N.1 -

N1 ,1 '

(,

's } ' x w

CORRECTIVE ACTION: ,

- N y

\

(INSTALLATION) 4

% - x1 s

a .

i s

s, s '

' , (, i

-t

. . . ) ,,

i_\n .

CORRECTIVE ACTION SCHEDULE: il0'TElm2R 1985 REFUEL V;f T s N- -

\ , * ' '

^

MAR NUMDERi 79-11'-69 'ss. s is., -

\

~ ~ ~

JUSTIFICATION FOR CONTINUED OPERATION: ,

%. s NOT REQUIRED.

  • s -

7' -

O m

,N A-292 s _ _?'

'.e

~- m . i s

i FLORIDA POWER CORPORATION QUAI.IFICATION STATUS

SUMMARY

SHEETS ID NUMBER: WSV-3,4,5, & 6 RECORD NUMBER: 0185 SCEW PAGE NUMBER: 2-225 a DESCRIPTION: SOLENOID VALVE LOCATION:

AUXILIARY BLDG.

ELEV. 119' MANUFACTURER: ASCO TER EQUIPMENT NO.:

33 MODEL: 8317A29 TER CATEGORY:

I.B SYSTEM: WS ZONE LOCATION:

22 TER QUALIFICATION DEFICIENCIES NOTED:

1. DOCUMENTED EVIDENCE OF QUAL t]

C l QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

CORRECTIVE ACTION:

REPLACE.

CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMBER 1985 MAR NUMBER: 82-05-24-03 JUSTIFICATION FOR CONTINUED OPERATION:

SEE ATTACHBD.

O ul i

A-293

e i ,

JUSTIFICATION FOR CONTINUED OPERATION q for .

\ WSV-3, 4, 5 & 6 2 v ,i 1 TER Item 33 References

1) FPC Environmental Qualification of Class lE Equipment IE

~

Bulletin 79-OlB Qualification Summary.

In the interim between the present and scheduled corrective action, the following justification for continued operation, as previously provided in Reference 1, is given:

1. Investigations with the manufacturer indicate the solenoid valves are good for 10 5 rads. Accident conditions will not p affect the components for the period of operability required. Also, due to the location of the component when required to perform its safety function, the accident environment has no impact.
2. Due to the period of operability required as per CRf3 Tech.

Spec. Table 3.6-1 to perform their safety function, and the fact that the total radiation exposure per the SCEW sheets is conservative in regard to the 5-1/2 year operating life of the plant, these valves are not considered to be a restraint to the safe operation of CR#3.

i l \

A-294

FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS ID NUMBER: WS-1,2,3, & 4 RECORD NUMBER: 0193 SCEW PAGE NUMBER: 2-226 2 DESCRIPTION: LOCAL CONTROL LOCATION:

STATION AUXILIARY BLDG.

ELEV. 119'-0" MANUFACTURER: FIELD FABRICATED TER EQUIPMENT NO.:

MODEL: G.E. TYPE UA202 SW.

G.E. TYPE UC212 LIGHT TER CATEGORY:

I.B-A SYSTEM: WS ZONE LOCATION:

TER QUALIFICATION DEFICIENCIES NOTED:

NOT INCLUDED IN EVALUATION.

O QUALIFICATION STATUS:

QUALIFICATION MODIFICATIONS IN PROGRESS.

CORRECTIVE ACTION:

REMOVE.

CORRECTIVE ACTION SCHEDULE: REFUEL V; NOVEMoER 1985 MAR NUMBER: 82-05-24-02 JUSTIFICATION FOR CONTINUED OPERATION:

SEE JCO FOR AS-1, RECORD 0013.

A-295

FLORIDA PONER CORPORATION QUALIFICATION STATUS CUMMARY SHEETS ID NUMBER: WS-2 RECORD NUMBER: 0186 SCEW PAGE NUMBER: 2-227 ,

i DESCRIFTION: TERMINAL BOX LOCATION:

AUXILIARY BLDG.

ELEV. 119' MANUFACTURER: FIELD FABRICATED TER EQUIPMENT NO.:

69 MODEL: STATES TYPE NT TERMINAL BLOCKS TER CATEGORY:

I.B SYSTEM: WS ZONE LOCATION:

22 TER QUALIFICATION DEFICIENCIES NOTED:

3. AGING DEGRADATION EVAL
4. QUAL LIFE OR REPLACE SKED

. rm QUALIFICATION STATUS:

QUALIFIED FOR CURRENT APPLICATION.

SEE APPENDIX A.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

A-296

- _ . _ . . . __ _ . _ _ . . _ _- - _ . - _ . . . _ - . . , . . _ - _ , _ _ _ _ . _ _ ~ . . - - _ - - - - . _ _ - _ . . . , _ _ . . . - _ - _ _

I FLORIDA POWER CORPORATION QUALIFICATION STATUS

SUMMARY

SHEETS F ID NUMBER: WS-3 RECORD NUMBER: 0187

(

SCEW PAGE NUMBER: 2-228 ,

DESCRIPTION: TERMINAL BOX LOCATION:

AUXILIARY BLDG.

ELEV. 119' MANUFACTURER: FIELD FABRICATED TER EQUIPMENT NO.:

NA MODEL: STATES TYPE NT TERMINAL BLOCKS TER CATEGORY:

I.B-A SYSTEM: WS ZONE LOCATION:

22 TER QUALIFICATION DEFICIENCIES NOTED:

NOT INCLUDED IN EVALUATION r

QUALIFICATION STATUS:

QUALIFIED FOR CURRENT APPLICATION.

SEE APPENDIX A.

CORRECTIVE ACTION:

NOT APPLICABLE.

CORRECTIVE ACTION SCHEDULE: NOT APPLICABLE.

MAR NUMBER: NOT APPLICABLE.

JUSTIFICATION FOR CONTINUED OPERATION:

NOT REQUIRED.

A-297

FLORIDA POWER CORPORATION Crystal River Unit 3 ZONE # 1 Zone Environmental Data Revision 1

~ Date 4/83 DESCRIPTION: Elev. 95'- Auxiliary Building, Makeup and Purification Pump Room Pabmeters Normal Environment Environment For Loss Environment For High Energy Of Coolant Accident line Break (Inside AB & IB)

Tcmp';rature Hours / Year Temp. Time Temo. Time Temo.

(oF) 189 93 to 97 N/A N/A 4959 85 to 92 3464 70 to 84 148 55 to 69 Note 1 Pr;ssure (PS1G) Atmospheric Time Press. Time Press.

N/A N/A tive 20 to 90 N/A N/A ,

riumidity (%)

Ch:mical Spray N/A N/A N/A (pH)

Radiation (Rads) 40 Year Dose Time Post N/A Accident Dose 1.2 x 106 1 Hr 5.6 x 103 1 Day 2.0 x 104 5 Days 3.7 x 104 30 Days 7.4 x 104 6 Months 1.5 x 105 40 Yr. Total + 6 Mo, =

1.4 x 106 Total Submcrgence N/A N/A N/A (Flood Level)

LEGEND: N/A = Not Aaplicable, N/C = Not Calculated NOTES: (1) Allow 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> per year at 1150F for postulated HVAC system failures.

FLORIDA POWER CORPORATION Crystal River Unit 3 ZONED 2 Zone Environmental Data Revision 1 W DESCRIPTION: Elev. 95* - Auxiliary Building, Hall Outside Makeup Pump Room Date 4/83 Par: meters Normal Environment Environment For loss Environment For High Energy Of Coolant Accident Line Break (Inside AB & 18)

Temp;rature Hours / Year Tem o. Time Temo. Time Temo.

189 93 to 97 N/A N/A (oF) 4959 85 to 92 3464 70 to 84 148 55 to 69 Note 1 Pr;ssure (PSIG) Atmospheric Time, Press. Time Press.

N/A N/A tive 20 to 90 N/A N/A .

Humidity (%)

Chimical Spray N/A N/A N/A (pH)

Radiation (Rads) 40 Year Ocse Time Post N/A Accident Dose 1.2 x 106 1 Hr 1.5 x 105 1 Day 4.9 x 105 5 Days 8.8 x 105 30 Days 1.7 x 106 6 Months 3.2 x 106 40 Yr. Total + 6 Mo. =

4.4 x 106 Total Submtrgence N/A N/A N/A (Flood Level)

I I

LEGEND: N/A = Not Applicable, N/C = Not Calculated NOTES: (1) Allow 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> per year at 115cF for postulated HVAC system failures.

FLORIDA POWER CORPORATION Crystal River Unit 3 ZONE # 3 Zone Environmental Data Revision 1 Date 4/83 DESCRIPTION: Elev. 95'- Auxiliary 3uilding, Hall Outside Reactor Building Paramr,ters Normal Environment Environment For Loss Environment For High Energy Of Coolant Accident Line Break (Inside AB & 18)

Temperature Hours / Year Temo. Time Temo. Time Temo.

189 93 to 97 N/A N/A (oF) 4959 85 to 92 3464 70 to 84 148 55 to 69 Note 1 Pressure (PSIG) Atmospheric Time Press. Time Press.

N/A N/A l 20 to 90 N/A N/A ltive F umidity (%)

Chimical Spray N/A N/A N/A (pH)

Radiation (Rads) 40 Year Dose Time Post N/A Accident Dose 1.0 x 10' 1 Hr 1.8 x 104 1 Day 5.8 x 104 5 Days 1.0 x 105 30 Days 2.0 x 105 6 Months 3.9 x 10s 40 Yr. Total + 6 Mo. =

4.0 x 105 Total Submergence N/A N/A N/A (Flood Level)

,k I LEGEND: N/A = Not Applicable, N/C = Not Calculated NOTES: (1) Allow 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> per year at 115cF for postulated HVAC system failures

FLORIDA POWER CORPORATION Crystal River Unit 3 ZONE # 4

- Zone Environmental Data Revision 1 Date 4/83 DESCRIPTION: Elev. 95* Auxiliary Building, Equipment Hatch Area Outside Rad Waste Tank Room Normal Environment Environment For Les Environment For High Energy Par meters Of Coolant Accident Line Break (Inside A8 & 18)

Temo. Time Temo. Time Tem o.

Tcmperature Hours / Year 189 93 to 97 N/A N/A (oF) 4959 85 to 92 3464 70 to 84 148 55 to 69 Note 1 Atmospheric Time Press. Time Press.

Pr ssure(PSiG)

N/A N/A 20 to 90 N/A N/A l htive -

r .midity(%)

Chtmical Spray N/A N/A N/A (pH) 40 Year Oose Time Post N/A Radiation (Rads)

Accident Dose 1.0 x 104 1 Hr 2.5 x 104 1 Day 8.0 x 104

~ Oays 1.5 x 105 30 Days 2.8 x 105 6 Months 5.5 x 105 40 Yr. Total + 6 Mo. =

5.6 x 105 Total Submergence N/A N/A N/A (Flood Level)

\

LEGEND: N/A = Not Acolicable, N/C x Not Calculated NOTES: (1) Allow 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> peryear at 1150F for postulated HVAC system failures

FLORIDA POWER CORPORATION Crystal Rivar Unit 3 ZONE # 5 Zone Environmental Data Revision 1 Date 4/83 DESCRIPTION: Elev. 95'- Auxiliary Building, Waste Removal System Control Board Area Partm;ters Normal Environment Environment For Loss Environment For High Energy Of Coolant Accident Line Break (Inside AB & IB)

TcmpIrature Hours / Year Temo. Time Temo. Time Temp.

(oF) 189 90 to 97 N/A N/A 4253 85 to 89 4489 70 to 84 148 55 to 69 Note 1 Pressure (PSIG) Atmospheric Time Press. Time Press.

N/A N/A l )tive ~

r . midity (%) 20 to 90 N/A N/A Chimical Spray N/A N/A N/A (pH)

Radiation (Rads) 40 Year Dose Time Post N/A Accide at Dose 1.0 x 104 1 Hr 2.3 x 103 1 Day 7.5 x 103 5 Days 1.4 x 104 30 Days 2.6 x 104 6 Months 5.1 x 104 40 Yr. Total + 6 Mo. =

6.1 x 104 Total Submergence N/A N/A N/A (Flood Level)

LEGEND: N/A = Not Acolicable N/C = Not Calculated NOTES: (1) Allow 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> per year at 115cF for postulated HVAC system failures

FLORIDA POWER CORPORATION Crystal River Unit 3 ZONE # 6 Zone Environmental Cata Revision 1 Date 4/83 DESCRIPTION: Elev. 95* - Auxiliary Building, Nuclear Services Booster Pump Area PIrameters Normal Environment Environment For Loss Environment For High Energy Of Coolant Accident Line Break (Inside A8 & IB)

Temperature Hours / Year Temo. Time Temo. Time Temo.

(oF) 189 93 to 97 N/A N/A 4959 85 to 92 3464 70 to 84 148 55 to 69 Note 1 Pressure (PSIG) Atmospheric Time Press. Time Press.

N/A N/A tive 20 to 90 N/A N/A Humidity (%)

Chimical Spray N/A N/A N/A (pH)

Radiation (Rads) 40 Year Dose Time Post N/A Accident Oose 1.0 x 104 1 Hr 1.1 x 104 1 Day 3.5 x 104 5 Days 6.4 x 104 30 Days 1.3 x 105 6 Months 2.5 x 105 40 Yr. Total + 6 Mo. =

2.6 x 105 Total Submergence N/A N/A N/A (Flcod Level)

I LEGEND: N/A = Not Acolicable. N/C = Not Calculated NOTES; (1) Allow 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> per year at 115cF for postulated HVAC system failures

FLORIDA POWER CORPORATION Crystal River Unit 3 ZONE # 7 Zone Environmental Data Revision 1 Date 4/83 DESCRIPTION: Elev. 95'- Auxiliary Building, Decay Heat Pump Room Paramsters Normal Environment Environment For Loss Environment For High Er ergy Of Coolant Accident Line Break (Inside AB & 18)

Tamp;rature Hours / Year Temo. Time Temo. Time Temo.

189 93 to 97 N/A N/A (oF) 4959 85 to 92 3464 70 to 84 148 55 to 69 Note 1 Pressure (PSIG) Atmospheric Time Press. Time Press.

N/A N/A Itive 20 to 90 N/A N/A ,

Humidity (%)

Chtmical Spray N/A N/A N/A (pH)

Radiation (Rads) 40 Year Dose Tirbe Post N/A Accident Dose 4.9 x 106 1 Hr 5.5 x 1 F 1 Day 1.7 x 105 l

5 Days 3.2 x 105 l

l 30 Days 6.1 x 105 l

6 Months 1.2 x 106 1

40 Yr. Total + 6 Mo. =

6.1 x 106 Total l

Submsrgence N/A N/A N/A (Flood Level)

LEGEND: N/A = Not Acolicable, N/C = Not Calculated NOTES: (1) Allow 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> per year at 1150F for postulated HVAC system failures

FLORIDA POWER CORPORATION Crystal River Unit 3 ZONE # 8 Zone Environmental Data Revision 1 Date 4/83 DESCRIPTION: Elev.119' . Auxiliary Building, Hallway Outside Deborating Demineralizer Pir meters Normal Environment Environment For Loss Environment For High Energy Of Coolant Accident Line Break (Inside AB & 18)

Hours' Year Temo. Time Tem o. Time Temp.

Tempirature 189 90 to 100 N/A N/A (oF) 6041 80 to 89 2382 70 to 79 148 65 to 69 Note 1 Pressure (PSIG) Atmospheric Time Press. Time Press.

N/A N/A tive 20 to 90 N/A N/A Humidity (%)

Chimical Spray N/A N/A N/A (pH)

Radiation (Rads) 40 Year Dose Time Post N/A Accident Dose 1.0 x 104 1 Hr 3.5 x 104 1 Day 1.1 x 105 5 Days 2.0 x 105 30 Days 4.0 x 105 6 Months 7.8 x 105 40 Yr. Total + 6 Mo. =

7.9 x 105 Total Submirgence N/A N/A N/A (Flood Level) ll' l

\ n LEGEND: N/A = Not Acolicable, N/C = Not Calcu!ated NOTES: (1) Allow 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> per year at 115cF for postulated HVAC system failures

FLORIDA POWER CORPORATION Crystal River Unit 3 ZONE # 9 Zone Environmental Data Revision 1 Date 4/83 DESCRIPTION: Elev.119'- Auxiliary Building, Hallway Outside Demineralizer Room PirJmeters Normal Environment Environment For Loss Environment For High Energy Of Coolant Accident Line Break (Inside A8 & IB)

Titmpirature Hours / Year Temo. Time Tem p. Time Temo.

(oF) 189 90 to 100 N/A N/A 6041 80 to 89 2382 70 to 79 148 65 to 69 Note 1 Pressure (PSIG) Atmospheric Time Press. Time Press.

N/A N/A ktive 20 to 90 N/A N/A Humidity (%)

Chtmical Soray N/A N/A N/A (pH)

Radiation (Rads) 40 Year Dose Time Post N/A Accident Dose 1.0 x 104 1 Hr 7.5 x 104 1 Day 2.5 x 105 5 Days 4.5 x 105 30 Days 8.8 x 105 6 Months 1.7 x 106 40 Yr. Total + 6 Mo. =

1.7 x 106 Total Submergence N/A N/A N/A (Flood Level) l I I

LEGEND: N/A = Not Applicable, N/C = Not Calcu!ated NOTES: (1) Allow 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> per year at 115cF for postulated HVAC system failures

FLORIDA POWER CORPORATION ZONE 77 10 Crystal River Unit 3 Zone Environmental Data Revision 1 Date 4/83 DESCRIPTION: Elev. 95'-Intermediate Building, Nuclear Sample Room PIr:m'ters Normal Environment Environment For Loss Environment For High Energy Of Coolant Accident Line Break (Inside AB & IB)

Tcmpirature Hours / Year Temo. Time Temo. Time Temo.

189 90 to 97 N/A N/A (oF) 4959 85 to 89 3464 70 to 84 148 55 to 69 Note 1 Pressure (PSIG) Atmospheric Time Press. Time Press.

N/A N/A tive 20 to 90 N/A N/A Humidity (%)

Ch".mical Spray N/A N/A N/A (pH)

Radiation (Rads) 40 Year Dose Time Post N/A Accident Dose 1.0 x 104 1 Hr 1.6 x 102 1 Day 5.2 x 102 5 Days 9.5 x 102 30 Days 1.8 x 103 6 Months 3.5 x 103 40 Yr. Total + 6 Mo. =

1.4 x 104 Total Submtrgence N/A N/A N/A (Flood Level) f f

LEGEND: N/A = Not Acolicable, N/C = Not Calculated NOTES: (1) Allow 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> per year at 1100F for postulated HVAC system failures

FLORIDA POWER CORPORATION Crystal Riv:r Unit 3 ZONE # 11 Zone Environmental Data Revision 1 Date 4/83 DESCRIPTION: Elev. 95'- Auxiliary Building, Emergency Pump Room P: rim;ters Normal Environment Environment For Loss Environment For High Energy Of Coolant Accident Line Break (Inside AB & IB)

Temp ^rature Hours / Year Temo. Time Temo. Time Tem o.

(oF) 189 90 to 97 N/A N/A 4959 85 to 89 -

3464 70 to 84 148 55 to 69 Note 1 Pressure (PSIG) Atmospheric Time Press. Time Press.

N/A N/A N/A N/A Stive i humidity (%)

20 to 90 -

Ch:mical Spray N/A N/A N/A (pH)

Radiation (Rads) 40 Year Dose Time PCst N/A Accident Dose 1.0 x 104 1 Hr 2.2 x 103 1 Day 7.0 x 103 5 Days 1.3 x 104 30 Days 2.4 x 104 6 Months 4.6 x 104 40 Yr. Total + 6 Mo. =

5.6 x 104 Total Submsrgence N/A N/A N/A (Flood Level)

LEGEND: N/A = Not Acolicable, N/C = Not Calculated NOTES: (1) Allow 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> per year at 1150F for postulated HVAC system failures

FLORIDA POWER CORPORATION Crystal Riv: r Unit 3 ZONE # 12 Zone Environrnental Data Revision 1 Date 4/83 DESCRIPTION: Elev. 95* - Auxiliary Building, Heat Exchanger Room Parameters Normal Environment Environment For loss Environment For High Energy Of Coolant Accident Line Break (Inside A8 & 18)

Tcmp;rature Hours / Year Temo. Time Temo. Time Tem o.

(oF) 189 93 to 97 N/A N/A 1817 85 to 92 4224 75 to 84 2382 70 to 75 148 65 to 69 Note 1 Pressure (PSIG) Atmosphenc Time Press. Time Press.

N/A N/A tive 20 to 90 N/A N/A ,

Humidity (%)

Chimical Spray N/A N/A N/A (pH)

Radiation (Rads) 40 Year Dose Time Post N/A Accident Dose 1.0 x 104 1 Hr 1 Day N/A 5 Days 30 Days 6 Months 40 Yr. Total + 6 Mo. =

1.0 x 104 Total Submtrgence N/A N/A N/A (Flood Level)

I I

LEGEND: N/A = Not Acolicable, N/C = Not Calculated NOTES: (1) Allow 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> per year at 115cF for postulated HVAC system failures

FLORIDA POWER CORPORATION Crystal Riv::r Unit 3 ZONE # 13 Zone Environmental Data Revision 1 _

Date 4/83 DESCRIPTION: Elev.145'-Control Complex, Between Columns 301 and 303 Parameters Normal Environment Environment For Loss Environment For High Energy Of Coolant Accident Line Break (Inside AB & IB)

Tem o. Time Temo. Time Tem o.

Tcmp;rature Hours / Year 8760 70 to 80 N/A N/A (oF)

Atmospheric Time Press. Time Press.

Pr:ssure (PSIG)

N/A N/A tive N/A N/A Humidity (%) ,

Chemical Spray N/A N/A N/A (pH) l Radiation (Rads) 40 Year Oose Time Post N/A Accident Dose 1.0 x 104 1 Hr 1 Day N/A 5 Days 30 Days 6 Months 40 Yr. Total + 6 Mo. =

1.0 x 104 Total Submergence N/A N/A N/A l (Flood Level) 1 1! ( -.  !

.~/

l LEGEND: N/A = Not Acolicable. N/C = Not Calculated l NOTES:

FLORIDA POWER CORPORATION Crystal River Unit 3 ZONE # 14 Zone Environmental Data Revision 1 Date 4/83 DESCRIPTION: Elev. 95'-Intermediate Building , Motor Driven Emergency Feedwater Pump Room P:ramiters Normal Environment Environment For Loss Environment For High Energy Of Coolant Accident Line Break (Inside A8 & IB)

Tcmparature Hours / Year Temo. Time Temo. Time Temo.

5 95 to 99 N/A 0-2 Sec 345 (oF) 890 90 to 94 2-4 Sec 345-287 4253 80 to 89 4-10 Sec 287-240 3464 70 to 79 10-40 Sec 240-212 148 55 to 69 40-1000 Sec 212 Note 1 1000-3600 Sec 212 - Amb.

1 Hr-6 Mo Ambient Pressure (PSIG) Atmospheric Time Press. Time Press.

N/A 0-2 Sec 2.43 2-40 Sec 2.43-0.5 40-1000 Sec 0.5 1000-3600 Sec 0.5-0 1 Hr-6 Mo O 20 to 90 N/A Time  %

Rtlative idity (%) 0-1 Hr 100 j ,I 1 1-2 Hr 100-90 .

2 Hr-6 Mo 90 Chtmical Spray N/A N/A N/A (pH)

Radiation (Rads) 40 Year Dose Time Post N/A Accident Dose 1.0 x 104 1 Hr 1 Day N/A 5 Days 30 Days 6 Months 40 Yr. Total + 6 Mo. =

1.0 x 104 Total Submergence N/A N/A N/A (Flood Level) l I l

LEGEND: N/A = Not Acolicable. N/C = Not Calculated NOTES: (1) A!!ow 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> per year at 1100F for postulated HVAC system failures

__m l

^w LNTERMEDLATE BUILDNG 400 TEMPERATURE VER5U5 TIME FOR HELS OR M5LS 350

-7 300 TEMPERATURE \

F w 250 g

~~- '

  • %g,

=eum-200 -s

' w k

' u 150 \,

,N 3

100 a v

10 20 30 40 50 1000 2000 2000 4000 TIME ($fC)

~ ,

6

~~~~

, INTERMEDIATE butLDNG g0 PRES $UREVERSUSTIME FOR lifLa OR M5LR -_

50 4.0 PRESSURE iP54 3.0

-~

\

2.0 N N 1.0 Nm'%.'N

's

's* ,-.

~~

,g ~-_

0 v M 40 50 1000 2000 3M M to 20 ThE(SEC)

FLORIDA POWER CORPORATION Crystal River Unit 3 ZONE # 15 Zone Environmental Data Revision 1 CRIPTION: Elev. 95' Auxiliary Building, Hall Between Make up Pump Room and Neutralizer Date 4/83 Pump Room Pir:m;ters Normal Environment Environment For Loss Environment For High Energy Of Coolant Accident Une Break (Inside AB & IB)

Temp;rature Hours / Year Temo. Time Tem o. Time Temo.

(or) 895 85 to 97 N/A N/A 7243 75 to 84 474 70 to 74 148 65 to 69 Note 1 Pressure (PSIG) Atmospheric Time Press. Time Press.

N/A N/A etive humidity (%)

20 to 90 N/A N/A Ch:mical Spray N/A N/A N/A (pH)

Radiation (Rads) 40 Year Dose Time Post N/A Accident Dose 1.0 x 104 1 Hr 2.2 x 104 1 Day 7.0 x 104 5 Days 1.3 x 105 30 Days 2.4 x 105 6 Months 4.6 x 105 40 Yr. Total + 6 Mo. =

4.7 x 105 Total Submergence N/A N/A N/A (Flood Level)

LEGEND: N/A = Not Applicable, N/C = Not Calculated NOTES: (1) Allow 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> per year at 115cF for postulated HVAC system failures

FLORIDA POWER CORPORATION Crystal River Unit 3 ZONE # 16 Zone Environmental Data Revision 1 Date 4/83 DESCRIPTION: Elev.119'-Intermediate Building, Leak Rate Test Area Param;ters Normal Environment Environment For Loss Environment For High Energy Of Coolant Accident Line Break (Inside A8 & 18)

Tcmpirature Hours / Year Temo. Time Tem o. Time Temo.

5 129 to 135 N/A 0-2 Sec 345 (oF) 890 125 to 128 2-4 Sec 345-287 2828 120 to 124 4-10 Sec 287-240 1425 100 to 119 10-40 Sec 240-212 2990 95 to 99 40-1000 Sec 212 474 90 to 94 1000-3600 Sec 212 - Amb.

148 80 to 89 1 Hr-6 Mo Ambient Pressure (PSIG) Atmospheric Time Press. Time Press N/A 0-2 Sec 2.85 2-40 Sec 2.85-0.5 40-1000 Sec 0.5 1000-3600 Sec 0.5-0 1 Hr-6 Mo O R:latF.e 20 to 80 Time  %

N/A 0-1 Hr 100 Widity(%) 1-2 Hr 100-90 -

2 Hr-6 Mo 90 Ch mical Spray N/A N/A N/A (pH)

Radiation (Rads) 40 Year Dose Time Post N/A Accident Dose 1.0 x 108 1 Hr Note 1 1 Day 5 Days 30 Days 6 Months 40 Yr. Total + 6 Mo. =

1.0 x 104 Total Submcrgence N/A N/A N/A (Flood Level)

, ~

.,I LEGEND: N/A = Not Acolicable, N/C = Not Calculated NOTES: (1) Total 6 Month Integrated Accident Dose < 100 RADS.

^v INTERMEDLATE BUILDING 400 TEMPERATURE VER$USTIME FOR HELS OR M5LS 350

-\

~

1 300 TEMPERATURE N

  • F k T

250 g N

200  %

' t N

^

w'N 150 ' '

s T

100 v 10 20 30 40 50 1000 2000 3M M TIME (5EC.)

y

\ii i e

INTERMEDIATE 8DtLDING 60 PRE 550RE VER$US TIME FOR l

HEL8 OR MSLA

[ 5.0 40 PRES $URE P54 3.0 _,

N

'N e

'\ . -----

N's .

l Nm's i 1.0 x'N --

, ;ii ig il  ! I I 6 e ~*C 0 v to 20 30 40 50 1000 2000 3000 M i

TIME (SEC.)

l l

FLORIDA POWER CORPORATION Crystal River Unit 3 ZONE # 17 Zone Environmental Data Revision 1 Date 4/83 DESCRIPTION: Elev.119'-Intermediate Building, Pressurizer Cabinet Area, To Column 308 Parameters Normal Environment Environment For Loss Environment For High Energy Of Coolant Accident Line Break (Inside AB & 18)

Tem o. Time Temo. Time Tem o.

Tcmp;rature Hours / Year 3723 100 to 140 N/A 0-2 Sec 345 (oF) 3368 85 to 99 2-4 Sec 345-287 1521 85 to 94 4-10 Sec 287-240 148 70 to 84 10-40 Sec 240-212 40-1000 Sec 212 1000-3600 Sec 212 - Amb.

1 Hr-6 Mo Ambient Atmospheric Time Press. Time Press.

Prcssure(PSIG)

N/A 0-2 Sec 2.85 2-40 Sec 2.85-0.5 40-1000 Sec 0.5 1000-3600 Sec 0.5-0 1 Hr-6 Mo O R:lative 20 to 80 N/A Time  %

u idity (%) 0-1 Hr 100 1-2 Hr 100-90 2 Hr-6 Mo 90 Ch mical Scray N/A N/A N/A (pH)

Radiation (Rads) 40 Year Oose Time Post N/A Accident Oose 1.0 x 104 1 Hr 1.1 x 101 1 Day 3.5 x 101 5 Days 6.4 x 101 30 Days 1.3 x 102 6 Months 2.5 x 102 40 Yr. Total + 6 Mo. =

1.0 x 104 Total Submergence N/A N/A N/A (Flood Level)

LEGEND: N/A = Not Acolicable, N/C = Not Calculated NOTES:

Iv.

INTERMEDIATE BUILDING 400 TEMPERATURE VER5U$ TIME FOR HELS OR M5LB 350 -5 300 TEMPERATURE \

of (

250 g

--..'~%umag

""4.sup _

' w l

l g 1 T l

! i a '

100 v 10 20 30 40 50 1000 2000 3000 4000 l

( TIME ($f C.)

1 4 { l 4 i 6)

C INTERMEDIATE BUILDING 6.0 PRE 55URE VER5US TIME FOR

~~~

HEL.8 OR M5LB i 5.0 l

40 --"

PRES 5URE (Me 3.0 ,

1 l N'N '

~'

t l

l 2.0 ---

N 1.0

~~~

\ l

. l l j i

'N~ _

i

,iii ig i i i i iI e .m  % 6

==

G v 10 20 30 40 50 1000 2000 3000 AM TIME (SEC.)

FLORIDA POWER CORPORATION Crystal River Unit 3 ZONE # 18 Zone Environmental Data Revision 1 Date 4/83 DESCRIPTION: Elev. 95* -Intermediate Building, Area Adjacent To Nuclear Sample Room Par maters Normal Environment Environment For loss Environment For High Energy Of Coolant Accident Line Break (Inside A8 & 18)

Temo. Time Tem p. Time Tem o.

Tcmp;rature Hours / Year 189 90 to 95 N/A N/A (oF) 4959 80 to 89 3464 70 to 79 148 65 to 69 Note 1 Time Press. Time Press.

Prtssure (P5lG) Atmospheric N/A N/A ive 20 to 90 N/A N/A Humidity (%)

Chsmical Spray N/A N/A N/A (pH) 1 40 Year Oose Time Post N/A

( Rad lation (Rads)

Accident Dose 1.9 x 104 1 Hr 2.2 x 103 l

1 Day 7.0 x 103 l

l 5 Days 1.3 x 104 30 Days 2.4 x 104 6 Months 4.6 x 104 l

l 40 Yr. Total + 6 Mo. =

l 5.6 x 104 Total Submsrgence N/A N/A N/A l

(Flood Level) i LEGEND: N/A = Not Acolicable, NiC = Not Calculated NOTES: (1) Allow 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> per year at 1100F for postulated HVAC system failures

FLORf DA POWER CORPORATION Crystal River Unit 3 ZONE # 19 Zone Environmental Data Revision 1 Date 4/83 DESCRIPTION: Elev.95'-Intermediate Building,5upply Fan Area Partmsters Normal Environment Environment For Loss Environment For High Energy Of Coolant Accident Line Break (Inside A8 & IB)

Temp;rature Hours / Year Tem o. Time Tem o. Time Tem p.

189 90 to 99 N/A 0-2 Sec 345 (oF) 4959 80 to 89 24 Sec 345-287 3464 70 to 79 4-10 Sec 287-240 148 55 to 69 10-40 Sec 240-212 Note 1 40-1000 Sec 212 1000-3600 Sec 212 - Amb.

1 Hr-6 Mo Ambient Pressure (PSIG) Atmospheric Time Press. Time Press.

N/A 0-2 Sec 2.43 2-40 Sec 2.43-0.5 40-1000 Sec 0.5 1000-3600 Sec 0.5-0 1 Hr-6 Mo 0 R:lative 20 to 90 N/A Time  %

0-1 Hr 100 Widity(%) 1-2 Hr 100-90 ,

2 Hr-6 Mo 90 Chtmical Spray N/A N/A N/A (pH)

I Radiation (Rads) 40 Year Oose Time Post N/A Accident Oose 1.0 x 104 1 Hr 1.2 x 102 1 Day 3.8 x 102 5 Days 6.9 x 102 30 Days 1.3 x 103 6 Months 2.6 x 103 40 Yr. Total + 6 Mo. =

1.3 x 104 Total Submcrgence N/A N/A N/A (Flood Level)

LEGEND: N/A = Not Acolicable, N/C = Not Calculated NOTES: (1) Allow 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> per year at 1100F for postulated HVAC system failures

\

l INTERMEDIATE BUILDING 400 TEMPERATURE VER5US TIME FOR HELS OR M5LS 350

-l 300 TEMPERATURE \

W (

250 g

--- ~  %

200 s N

N N

150 x'N T Sy 100 10 20 30 40 50 1000 2000 3000 4000 TIME (SEC.)

1 v

. INTERMEDIATE BUILDNG 60 PRE 55UREVER$U5 TIME FOR HELS DA M5LS 50 i

40 PRE 55URE IPM 30 l n 2.0 \ N N'N 1.0 ,s s

  1. l l 1 0

IIf hv 10 20 30 40 50 1000 2000 3000 m TIME l5EC.)

FLORIDA POWER CORPORATION Crystal River Unit 3 ZONE # 20 Zone Environmental Data Revision 1 Date 4/83 DESCRIPTION: Elev. 95'-Intermediate Building, Adjacent To Column 306 Param',ters Normal Environment Environment For Loss Environment For High Energy Of Coolant Accident Line Break (Inside AB & IB)

Hours / Year Tem o. Time Temo. Time Tem o.

TGmpirature 5 95 to 99 N/A 0-2 Sec 345 (oF) 890 85 to 94 2-4 Sec 345-287 4253 80 to 84 4-10 Sec 287-240 3464 70 to 79 10-40 Sec 240-212 148 55 to 69 40-1000 Sec 212 Note 1 1000-3600 Sec 212 - Amb.

1 Hr-6 Mo Ambient Atmospheric Time Press. Time Press.

Prtssure (PSIG)

N/A 0-2 Sec 2.43 2-40 Sec 2.43-0.5 40-1000 Sec 0.5 1000-3600 Sec 0.5-0 1 Hr-6 Mo 0 Relative 20 to 90 N/A Time  %

0-1 Hr 100 W' idity(%) 1-2 Hr 100-90 ,

2 Hr-6 Mo 90 Ch:mical Spray N/A N/A N/A (pH) 40 Year Oose Time Post N/A Radiation (Rads)

Accident Dose 3.5 x 103 1 Hr 3.0 x 102 1 Day 6.3 x 102 5 Days 1.8 x 103 30 Days 3.5 x 103 6 Months 6.5 x 103 40 Yr. Total + 6 Mo. =

1.0 x 104 Total Submergence N/A N/A N/A (Flood Level)

  1. 1 LEGEND: N/A = Not Acolicable, N/C = Not Calculated NOTES: (1) Allow 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> per year at 110cF for postulated HVAC system failures

1 l

v INTERMEDIATE BUILD 6NG e

400 TEMPERATURE VER5U5 TIME FOR HELB OR Mitt 350 -

300 TEMPERATURE 's of (

250 g

%hm.

'* %m- e

' m N

^ w

\

150 m .

N T

100 Oy 10 20 30 40 50 1000 2000 3000 4000 TIME (SEC)

O INTERMEDtATE ButtDING EO PRES $UREVER$USTIME FOR 1

, HELB OR M5LB

$0 40 PRES 5URE (P54 3.0 l __Zs s t' 2.0

\ %m N.'N 1.0 's

\ +

j , ,I g %m~* .%_

0 v 10 20 30 40 50 1000 2000 3000 # 00 TIME (SEC)

l FLORIDA POWER CORPORATION l Crystal River Unit 3 ZONE # 21 l 1

Zone Environmental Data Revision 1 l Date 4/83 DESCRIPTION: Elev.119'-Intermediate Building, H & V MCC Area, Adjacent To Column 306 Paramsters Normal Environment Environment For Loss Environment For High Energy Of Coolant Accident Line Break (Inside AB & IB)

Temp;rature Hours / Year Tem o. Time Tem o. Time Temo .

(oF) 5 105 to 115 N/A 0-2 Sec 345 3718 95 to 104 2-4 Sec 345-287 4415 85 to 94 4-10 Sec 287-240 622 75 to 84 10-40 Sec 240-212 40-1000 Sec 212 1000-3600 Sec 2 i 2 - Amb.

1 Hr-6 Mo Ambient Prissure (PSIG) Atmospheric Time Press. Time Press.

N/A 0-2 Sec 3.18 2-40 Sec 3.18-0.5 40-1000 Sec 0.5 1000-3600 Sec 0.5-0 1 Hr-6 Mo O Rtlative 20 to 80 N/A Time _ g

- 0-1 Hr 100 Widity(%) 1-2 Hr 100-90 .

2 Hr-6 Mo 90 Chrmical Spray N/A N/A N/A (pH)

Radiation (Rads) 40 Year Dose Time Post N/A Accident Dose 1.0 x 104 1 Hr Note 1 1 Day 5 Days 30 Days

6 Months 40 Yr. Total + 6 Mo. =

1.0 x 104 Total Submcrgence N/A N/A N/A (Flood Level) l l I

LEGEND: N/A = Nct Acolicable. N/C = Not Calculated NOTES: (1) Total 6 Month Integrated Accident Dose < 100 RADS

  • v INTERMEDIATE ButtDiNG 400 TEMPERATURE VER$US TIME FOR HELS OR M5LB 350 q 1

300 TEMPERATURE g

( *F (

250 g l  % __

200 g g

' m 150 ,

T 100 og l 10 20 30 40 50 1000 2000 3000 4000 TIME ($EC.)

v

. INTERMEDIATE BUltDING g0 PRE 15UREVER505 TIME FOR HEL3 OR MitB 50 1

40 PRE 55URE (P54 30 s

2.0 x 5m 1.0 ,s s~

1iil l -'.-

l I

-u 166I i 3 t --

0 v to 20 30 40 50 1000 2000 3000 m TIME ($EC.)

l i

FLORIDA POWER CORPORATION Crystal River Unit 3 ZONE # 22 Zone Environmental Data Revision 1 Date 4/83 DESCRIPTION: Elev.119'- Auxiliary Building, Penetration Area Parameters Normal Environment Environment For Loss Environment For High Energy Of Coolant Accident Line Break (Inside AB & IB)

Temp;rature Hours / Year Temo. Time Temo. Time Temo.

(oF) 189 90 to 100 N/A N/A 4959 85 to 89 1943 75 to 84 1521 70 to 75 148 65 to 70 Note 1 Pressure (PSIG) Atmospheric Time Press. Time Press.

N/A N/A Stive humidity (%)

20 to 90 N/A N/A Chtmical Spray N/A N/A N/A (pH)

Radiation (Rads) 40 Year Dose Time Post N/A Accident Dose 1.2 x 106 1 Hr 5.5 x 104 1 Day 1.7 x 10s 5 Days 3.2 x 10s 30 Days 6.1 x 10s 6 Months 1.2 x 106 40 Yr. Total + 6 Mo. =

2.4 x 106 Total Submtrgence N/A N/A N/A (Flood Level) l LEGEND: N/A = Not Acolicable, N/C = Not Calculated NOTES: (1) Allow 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> per year at 115cF for postulated HVAC system failures

1 l

FLORIDA POWER CORPORATION Crystal River Unit 3 ZONE # 23 Zone Environmental Data Revision 1 Date 4/83 4 DESCRIPTION: Elev.119'- Auxiliary Building, Boric Acid Storage Tank Room Parzm;ters Normal Environment Environment For Loss Environment For High Energy Of Coolant Accident Line Break (Inside AB & 18)

Temp;rature Hours / Year Temo. Time Temo. Time Tem o. .

(oF) 189 90 to 95 N/A N/A 3535 80 to 89 4415 70 to 79 622 65 to 70 Note 1 Pressure (PSIG) Atmospheric Time Press. Time Press.

N/A N/A tive 20 to 80 N/A N/A Humidity (%)

Ch:mical Soray N/A N/A N/A (pH)

Radiation (Rads) 40 Year Dose Time Post N/A Accident Oose 1.0 x 10' 1 Hr 5.5 x 102

1 Day 1.9 x 103 l 5 Days 3.4 x 103 30 Days 6.8 x 103 6 Months 1.4 x 104 l

40 Yr. Total + 6 Mo. =

2.4 x 104 Total Subm:rgence N/A N/A N/A (Flood Level)

I l

l l LEGEND: N/A = Not Acolicable N/C = Not Calculated l NOTES: (1) Allow 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> per year at 115cF for postulated HVAC system failures l

l

FLORIDA POWER CORPORATION Crystal Riv:r Unit 3 ZONE # 24 Zone Environmental Data Revision 1 Date 4/83 DESCRIPTION: Elev.119'- Auxiliary Building, Boric Acid Storage Tank Room (East of Column 302)

Parameters Normal Environment Environment For Loss Environment For High Energy Of Coolant Accident Line Break (Inside A8 & IB)

Temp rature Hours / Year Temo. Time Temo. Time Temo.

(oF) 189 90 to 95 N/A N/A 3534 80 to 89 4415 70 to 79 622 65 to 70 Note 1 Prcssure (PSIG) Atmospheric Time Press. Time Press.

N/A N/A tive 20 to 90 N/A N/A ,

Humidity (%)

Chtmical Spray N/A N/A N/A (pH)

Radiation (Rads) 40 Year Dose Time Post N/A Accident Dose 1

1.0 x 104 1 Hr 7.8 x 102 l 1 Day 2.4 x 103 5 Days 4.3 x 103 l

8.3 x 103 30 Days 6 Months 1.6 x 104 40 Yr. Total + 6 Mo. =

2.6 x 104 Total l

Submergence N/A N/A N/A (Flood Level) il l,

l I

l l LEGEND: N/A = Not Acolicable. N/C = Not Calculated NOTES: (1) Allow 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> per year at 115cF for postulated HVAC system failures

FLORIDA POWER CORPORATION Crystal Riv:r Unit 3 ZONE # 25 Zone Environmental Data Revision 1 Date 4/83 DESCRIPTION: Elev.119'- Auxiliary Building, Hallway Outside Make-up Tank Room Parameters Normal Environment Environment For loss Environment For High Energy Of Coolant Accident Line Break (Inside AB & IB)

Titmparature Hours / Year Temo. Time Temo. Time Temo.

(cF) 189 90 to 95 N/A N/A 3534 80 to 89 4415 70 to 79 622 65 to 70 Note 1 Pressure (PSIG) Atmospheric Time Press. Time Press.

N/A N/A tive 20 to 90 N/A N/A Humidity (%)

Ch:mical Spray N/A N/A N/A (pH)

Radi stion (Rads) 40 Year Oose Time Post N/A

, Accident Oose 1.0 x 104 1 Hr 6.8 x 100 1 Day 2.2 x 101 5 Days 3.9 x 101 30 Days 7.6 x 101 6 Months 1.5 x 102 40 Yr. Total + 6 Mo. =

1.0 x 104 Total Submergence N/A N/A N/A (Flood Level) 9 i

LEGEND: N/A = Not Acoliceble, N/C = Not Calculated NOTES: (1) Allow 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> per year at 115cF for postulated HVAC system failures

FLORIDA POWER CORPORAT!ON Crystal Riv:r Unit 3 ZONE # 26 Zone Environmental Data Revision 1 Date 4/83 DESCRIPTION: Elev.119'- Auxiliary Building, Boric Acid Storage Tank Room By Waste Press Parameters Normal Environment Environment For Loss Environment For High Energy Of Coolant Accident Line Break (Inside AB & IB)

T4mperature Hours / Year Tem o. Time Temo. Time Temo.

(oF) 189 90 to 99 N/A N/A 3534 80 to 89 4415 70 to 79 622 65 to 70 Note 1 Pr:ssure (PSIG) Atmospheric Time Press. Time Press.

N/A N/A ative 20 to 90 N/A N/A ,

Humidity (%)

Chimical Spray N/A N/A N/A (pH)

Radiation (Rads) 40 Year Dose Time Post N/A Accident Dose 1.0 x 104 1 Hr 1.8 x 101 1 Day 5.8 x 101 5 Days 1.0 x 102 30 Days 2.0 x 102 6 Months 3.9 x 102 40 Yr. Total + 6 Mo. =

1.0 x 104 Total Submergence N/A N/A N/A (Flood Level)

^

LEGEND: N/A = Not Acolicable, N/C = Not Calculated NOTES: (1) Allow 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> per year at 115cF for postulated HVAC system failures

FLORIDA POWER CORPORATION Crystal River Unit 3 ZONE # 27 Zone Environmental Data Revision 1 Date 4/83 DESCRI. N: Elev.119'- Diesel Generator Building Partmaters Normal Environment Environment For Loss Envircnment For High Energy Of Coolant Accident Line Break (Inside AB & IB)

Temperature Hours / Year Tem o. Time Temo. Time Temo.

(oF) 189 100 to 105 N/A N/A 6041 90 to 99 1908 80 to 89 622 70 to 79 Prtssure (PSIG) Atmospheric Time Press. Time Press.

N/A N/A tive 20 to 90 N/A N/A humidity (%)

Ch:mical Spray N/A N/A N/A (pH)

Radiation (Rads) 40 Year Dose Time Post N/A Accident Dose 1.0 x 104 1 Hr N/A 1 Day 5 Days 30 Days 6 Months 40 Yr. Total + 6 Mo. =

1.0 x 104 Total Submergence N/A N/A N/A (Flood Level)

LEGEND: N/A = Not Aco'icable, N/C = Not Calculated NOTES:

FLORIDA POWER CORPORATION I Crystal Riv:r Unit 3 ZONE # 28 Zone Environmental Data Revision 1 Date 4/83 DESCRIPTION: Elev.119'- Auxiliary Building, Makeup And Purification Prefilter Area l PartmT,ters Normal Environment Environment For Loss Environment For High Energy Of Coolant Accident Line Break (Inside A8 & IB)

Tcmpirature Hours / Year Temo. Time Temo. Time Temo.

(oF) 189 90 to 99 N/A N/A 4959 80 to 89 2990 70 to 79 622 65 to 70 Note 1 Pressure (PSIG) Atmospheric Time Press. Time Press.

N/A N/A tive 20 to 90 N/A N/A -

Humidity (%)

Chrmical Spray N/A N/A N/A (pH)

Radiation (Rads) 40 Year Oose Time Post N/A Accident Oose 1.0 x 10' 1 Hr 5.8 x 103

( 1 Day 2.2 x '04 5 Days 3.9 x 104 30 Days 7.6 x 104 6 Months 1.5 x 105 l 40 Yr. Total + 6 Mo. =

1.6 x 10s Total Submsrgence N/A N/A N/A (Flood Level) l I I '

l LEGEND: N/A = Not Acolicable, N/C = Not Calculated NOTES: (1) Allow 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> per year at 1150F for postulated HVAC system f.3! lures l

FLORIDA POWER CORPORATION Crystal River Unit 3 ZONE # 29 Zone Environmental Data Revision 1 CRIPTION: Elev.119'- Auxiliary Building, Beric Acid Recirc Pump Room & Date 4/83 RadioactiveWaste Packaging Area Parameters Normal Environment Environment For Loss Environment For High Energy Of Coolant Accident Line Break (Inside AB & 18)

T(mpirature Hours / Year Temo. Time Temo. Time Tem o.

189 90 to 99 N/A N/A (oF) 4959 80 to 89 1943 70 to 79 1047 65 to 69 622 60 to 65 Note 2 Prissure (PSIG) Atmospheric Time Press. Time Press.

N/A N/A tive 20 to 90 N/A N/A idity(%)

Chimical Spray N/A N/A N/A (pH)

Radiation (Rads) '40 Year Dose Time Post N/A Accident Dose 1.0 x 104 1 Hr Note 1 1 Day 5 Days 30 Days 6 Months 40 Yr. Total + 6 Mo. =

1.0 x 104 Total Submtrgence N/A N/A N/A (Flood Level)

~

LEGEND: N/A = Not Acolicable, N/C = Not Calculated NOTES: (1) Total 6 MonthsIntegrated Accidev. Dose < 100 RADS .

(2) Allow 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> per year at 1150F for postulated HVAC system failures

FLORIDA POWER CORPORATION Crystal River Unit 3 ZONE # 30 Zone Environmental Data Revision 1 Date 4/83 DESCRIPTION: Elev.119'- Auxiliary Building, Makeup Annd Purification Filter Area Parameters Normal Environment Environment For Loss Environment For High Energy Of Coolant Accident Line Break (Inside A8 & IB)

Ttmp:;rature Hours / Year Temo. Time Temo. Time Temo.

(oF) 189 90 to 99 N/A N/A 4959 80 to 89 2990 71 to 79 622 65 to 70 Note 2 Pressure (PSiG) Atmospheric Time Press. Time Press.

N/A N/A l btive 20 to 90 N/A N/A ,

Humidity (%)

Chimical Spray N/A N/A N/A (pH)

Radiation (Rads) 40 Year Oose Time Post N/A Accident Oose 3.5 x 108 1 Hr Note 1 1 Day 5 Days 30 Days 6 Months 40 Yr. Total + 6 Mo. =

3.5 x 108 Total Submergence N/A N/A N/A (Ficod Level) g-

\~ i LEGEND: N/A = Not Acolicable, N/C = Not Calculated NOTES: (1) Totai 6 Month Integrated Accident Dose < 100 RADS.

(2) Ailow 24 nours per year at 115cF for postulated HVAC system failures

FLORIDA POWER CORPORATION Crystal Rivtr Unit 3 ZONE # 31 Zone Environmental Data Revision 1 Date 4/83 DESCRIPTION: Elev.143'- Auxiliary Building, Exhaust Fan Room PartmIters Normal Environment Environment For Loss Environment For High Energy Of Coolant Accident Line Break (Inside AB & IB)

T(mpIrature Hours / Year Temo. Time Tem o. Time Temo.

(oF) 895 85 to 95 N/A N/A 2828 75 to 84 4889 60 to 74 148 55 to 59 Note 2 Pr;ssure (PSIG) Atmospheric Time Press. Time Press.

N/A N/A etive 20 to 90 N/A N/A .

Humidity (%)

Chamical Spray N/A N/A N/A (pH)

Radiation (Rads) 40 Year Dose Time Post N/A Accident Dose 1.0 x 104 1 Hr Note 1 1 Day t

5 Days 30 Days l

l 6 Months 1

40 Yr. Total + 6 Mo. =

1.0 x 104 Total Submergence N/A N/A N/A (Flood Level)

[i )

t

! LEGEND: N/A - Not Apolicable, N/C = Not Calculated l NOTES: (1) Total 6 Month Integrated Accident Dose < 100 RADS.

(2) Allow 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> per year at 115cF for postulated HVAC system failures l

FLORIDA POWER CORPORATION Crystal RivCr Unit 3 ZONE # 32 Zone Environmental Data Revision 1 CRIPTION: Elev.143'- Auxiliary Building, Demin. Water Pump Date 4/83 And Evap. Condensate Tank Room Param:;ters Normal Environment Environment For Loss Environment For High Energy Of Coolant Accident Line Break (Inside AB & 18)

Tsmp;rature Hours / Year Temo. Time Temo. Time Tem o.

(oF) 189 95 to 99 N/A N/A 1817 80 to 94 5085 70 to 79 1669 55 to 69 Note 2 Prcssure (PSIG) Atmospheric Time Press. Time Press.

N/A N/A tive 20 to 90 N/A N/A ,

Humidity (%) ,

Ch;mical Spray N/A N/A N/A (pH)

Radiation (Rads) 40 Year Dose Time Post N/A Accident Dose 1.0 x 104 1 Hr Note 1 1 Day 5 Days 30 Days 6 Months 40 Yr. Total + 6 Mo. =

1.0 x 104 Total Submcrgence N/A N/A N/A (Flood Level) l I i

LEGEND: N/A = Not Acolicable, N/C = Not Calculated NOTES: (1) Total 6 Month Integrated Accident Dose < 100 RADS.

(2) Allow 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> per year at 115cF for postulated HVAC system failures

FLORIDA POWER CORPORATION Crystal River Unit 3 ZONE # 33 Zone Environmental Data Revision 1 Date 4/83 DESCRIPTION: Elev.143'- Auxiliary Building,5 pent Fuel Cooler Area Par meters Normal Environment Environment For Loss Environment For High Energy Of Coolant Accident Line Break (Inside AB & IB)

Tcmp;rature Hours / Year Tem o. Time Temo. Time Temo.

(oF) 189 95 to 99 N/A N/A 1817 85 to 94 5085 70 to 84 1669 55 to 69 Note 2 Pressure (PSIG) Atmospheric Time Press. Time Press.

N/A N/A Rilative 20 to 90 N/A N/A Humidity (%)

Chimical Spray N/A N/A N/A (pH)

Radiation (Rads) 40 Year Oose Time Post N/A Accident Dose 1.0 x 104 1 Hr Note 1 1 Day 5 Days 30 Days 6 Months 40 Yr. Total + 6 Mo. =

1.0 x 104 Total Submergence N/A N/A N/A (Flood Level) l I LEGEND: N/A = Not Acolicable. N/C = Not Calculated NOTES: (1) Total 6 Month integrated Accident Dose < 100 RADS.

(2) Allow 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> per year at 1150F for postulated HVAC system failures

FLORIDA POWER CORPORATION Crystal River Unit 3 ZONE # 34 Zone Environmental Data Revision 1 DESCRIPTION: Elev. 95'- Auxiliary Building, Hallway Outside Make-up Pump Rooms, Date 4/83 Between Columns J and K Pararneters Normal Environment Environment For Loss Environment For High Energy Of Coolant Accident Line Break (Inside A8 & IB)

Temp;rature Hours / Year Temo. Time Temo. Time Temo.

(oF) 189 90 to 97 N/A N/A 7517 75 to 89 906 70 to 75 148 65 to 69 Note 1 Pressure (PSIG) Atmospheric Time Press. Time Press.

N/A N/A Gative 20 to 90 N/A N/A -

Humidity (%)

Chimical Spray N/A N/A N/A (pH)

Radiation (Rads) 40 Year Dese Time Post N/A Accident Dose 1.0 x 104 1 Hr 1.5 x 103 1 Day 5.0 x 103 5 Days 9.0 x 103 30 Days 1.8 x 104 6 Months 3.4 x 104 40 Yr. Total + 6 Mo. =

4.4 x 104 Total Submergence N/A N/A N/A (Flood Level) l I I

LEGEND: N/A = Not Acolicable, N/C = Not Calculated NOTES: (1) Allow 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> per year at 115cF for Postulated HVAC system failures

FLORIDA POWER CORPORATION Crystal River Unit 3 ZONE # 35 Zone Environrnental Data Revision 1 Date 4/83 DESCRIPT;ON: Elev. 95'- Auxiliary Building, Hall Outside Waste Evaporator Room Parameters Normal Environment Environment For Loss Environment For High Energy Of Coolant Accident Line Break (Inside AB & 18)

Tamperature Hours / Year Temo. Time Temo. Time Temo.

(oF) 189 90 to 95 N/A N/A 6902 75 to 89 1521 70 to 74 148 65 to 69 Note 1 Pressure (PSIG) Atmospheric Time Press. Time Press.

N/A N/A

( ~.

( )

~w/ tive 20 to 90 N/A N/A -

Humidity (%)

Chimical Spray N/A N/A N/A (pH)

Radiation (Rads) 40 Year Dose Time Post N/A Accident Den 1.0 x 104 1 Hr 5.1 x 103 10ay 17 x 104 l 5 Days 3.0 x 104 30 Days 5.9 x 104 6 Months 1.1 x 105 40 Yr. Total + 6 Mo. =

1.2 x 105 Total Subm:rgence N/A N/A N/A j (Flood Level)

(M, l . . ,

l l l

l LEGEND: N/A = Not Acolicable, N/C = Not Calculated l NOTES: (1) Allow 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> peryear at 115cF for Postulated HVAC system failures l

FLORIDA POWER CORPORATION Crystal River Unit 3 ZONE # 36 Zone Environmental Data Revision 1 Date 4/83 DESCRIPTION: Elev. 95'- Auxiliary Building, RC Coolant Pump Seal injection Filter Area Parameters Normal Environment Environment For loss Environment For High Energy Of Coolant Accident Line Break (Inside A8 & IB)

Tcmp:.rature Hours / Year Tem o. Time Temo. Time Temo.

(cF) 189 90 to 95 N/A N/A 6902 75 to 89 1521 70 to 74 148 65 to 69 Note 1 Prcssure(PSIG) Atmospheric Time Press. Time Press.

N/A N/A I

R;fative 20 to 90 N/A N/A Humidity (%)

Chimical Spray N/A N/A N/A (pH)

Ridiation (Rads) 40 Year Oose Time Post N/A Accident Oose 1.0 x 10s 1 Hr 8.3 x 103 1 Day 2.6 x 104 5 Days 4.7 x 104 30 Days 8.9 x 104 6 Months 1.7 x 105 40 Yr. Total + 6 Mo. =

1.0 x 108 Total Subm;rgence N/A N/A N/A (Flood Level) e i

LEGEND: N/A = Not Acolicable, N/C = Not Calculated NOTES: (1) Allow 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> per year at 1150F for Postulated HVAC system failures

FLORIDA POWER CORPORATION Crystal River Unit 3 ZONE # 37 Zone Environmental Data Revision 1 Date 4/83 DESCRIPTION: Elev.143'- Auxiliary Building, Containment Penetration Area Parameters Normal Environment Environment For Loss Environment For High Energy Of Coolant Accident Line Break (Inside A8 & IB)

Temperature Hours / Year Temo. Time Tem o. Time Temo.

(oF) 189 95 to 99 .N/A N/A 1817 85 to 94 5085 70 to 84 1669 55 to 69 Note 1 Pr'assure (PSIG) Atmospheric Time Press. Time Fress.

N/A N/A tive 20 to 90 N/A N/A Humidity (%) ,

ChImical Spray N/A N/A N/A (pH)

Radiation (Rads) 40 Year Dose Time Post N/A Accident Dose 1.0 x 104 1 Hr 7.4 x 100 1 Day 2.4 x 101 5 Days 4.3 x 101 30 Days 8.2 x 101 6 Months 1.6 x 102 40 Yr. Total + 6 Mo. =

1.0 x 104 Total l

1 Submtrgence N/A N/A N/A (Flood Level)

,~-

NJ LEGEND: N/A = Not Acolicable, N/C = Not Calculated NOTES: (1) Allow 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> per year at 115cF for postulated HVAC system failures

FLORIDA POWER CORPORATION Crystal River Unit 3 ZONE # 38 Zone Environmental Data Revision 1 Date 4/83 DESCRIPTION: Elev. 95* - Reactor Building Param:ters Normal Environmer.t Environment For Loss Environment For High Energy Of Coolant Accident Line Break (Inside AB & IB)

Tcmpirature Hours / Year Tem o. Time Temo. Time Temo.

(oF) 5129 100 to 109 0-10 sec 110-298 N/A 2663 90 to 99 10-150 sec 298 424 80 to 89 150-400 sec 298-294 30 70 to 79 400-5000 sec 294-171 60 Below 70 5000-8000 sec 171 8000 sec - 24 hr 171-110 Pressure (PSIG) Atmospheric Time Press. Time Press.

0-10 sec 0-49.6 N/A 10-150 sec 49.6 150-400 sec 49.6-46.5 400-5000 sec d6.5-7.7 5000-8000 sec 7.7 8000 sec-24 hr 7.7-0 Ratative (Data not available) 100 N/A Humidity (%)

ChP 1ical Spray N/A 2200 to 2450 ppm boron, N/A (pH) 105,000 to 120,000 ppm NaOH, pH 7.4 to 11.0 Radiation (Rads) 40 Year Dose Time Post N/A Accident Dose 1.4 x 107 1 Hr 1.4 x 107 1 Day 5.5 x 107 5 Days 7 3 x 107 30 Days 9.2 x 107 6 Months 1.8 x 108 40 Yr. Total + 6 Mo. =

1.9 x 108 Tota.

Submtrgence N/A Below 100' elevation N/A (Flood level) immersed in water containing boron and NaOH. pH 8.0 to 11.0 i

LEGEND: N/A = Not Acolicable, N/C = Not Calculated NOTES:

4 (3:54) Innssn a 3 ': 2  % ._

. t! i ii ei .i .t - i ii i  ! .

lill l': lI I!! I ll l.ll l l

.- E *

'Ii llll i . lll.

-4 l'lI it i i

l i o Eg a e,- a '

g'. E*g5=g g9.; _ , e i! / iii i lll ~$ B lI i

{l i l. . 'it i!iI ll h  !

! ) .

i l 6 e i 't. I e is ii , i /: :l

!'l l1l1  :  : >

5/ !  !  !.!/'

.li,/.il j.'  !

Il i

11 . . . . .= j /. .

. =

t , l

-B

.\\

i , , , i i i t g i i / . . 6  ?>

e i e 6  % If i1 '

t/l t lilil /~ i! II / 'll 1- -

y t

l y/ -

ag

, s -

~

/ / i -

~

,, .o / ,

i e i f. *

/ i . i i i

  • li!ll)'I )i* I i ti
  • i8 i I l l  ! l'

!  ! llll g i

i

'. 5 i

.i6 ii) i e ; }/ i i

/*

/-

~. s. . 6 I

~ _2 s N

\ 7x ,

i , , , i 3 . ,

x . .

i i,i! : i . 1 i i i i .

N i i llllt l13 ii ii !lI ! N I'Il

                                                             ~

x , N \ ,

     ! .     .       .       .                        +

N s j l l l l l l } l l il I th 3 I l II . llll ll l1 ll1l ll1i  ! l l) Il!l lll l llll llll ll l l l 2

                                                                                '     . l    l 2
                                                                                                  . l     l     l (4.) lun1Yv3dn31

FLORIDA POWER CORPORATION Crystal River Unit 3 ZONE # 39 Zone Environmental Data Revision 1 Date 4/83 DESCRIPTION: Elev.119' & 143 - Reactor Building Outside "D* Rings

                                             ~

Paramtters Normal Environment Environment For Loss Environment For High Energy Of Coolant Accident Line Break (Inside AB & IB) TcmpIrature Hours / Year Tem o. Time Tem o. Time Temo. (oF) 72 135 to 139 0-10 see 110-298 N/A 29 130 to 134 10-150 sec 298 29 125 to 129 150-400 sec 298-294 666 120 to 124 400-5000 sec 294-171 101 115 to 119 5000-8000 sec 171 1984 110 to 114 8000 sec-24 hr 171-110 4561 100 to 109 608 90 to 99 29 80 to 89 43 70 to 79 116 Below 69 Pr'ssure

        ;      (PSiG)  Atmospheric                       Time                  Press. Time                    Press.

0-10 sec 0-49.6 N/A 10-150 sec 49.6 150-400 sec 49.6-46.5 400-5000 sec 46.5-7.7

 #                                                      5000-8000 sec 8000 sec-24 hr 7.7
                                                                             ".7-0 i

Rilative (Data not available) N/A N/A Humidity (%) ChImical Soray N/A 2200 to 2450 ppm boron, N/A (pH) 105,000 to 120,000 ppm NaOH, pH 7.4 to 11.0 Radiation (Rads) 40 Year Dose Time Post N/A Accident Dose 2.8 x 104 1 Hr 1.5 x 106 1 Day 5.9 x 106 5 Days 7.9 x 106 30 Days 9.9 x 106 6 Months 2.0 x 107 40 Yr. Total + 6 Mo. = 2.0 x 107 Total Submtrgence N/A N/A N/A fFlood Level) l k ~ LEGEND: N/A = Not Acolicable, N/C = Not Calculated NOTES:

6 (sisa) anssna

2  : = ._

p j1 4 5 . 4 i I tt i i i i i . . i- i ,6i i ,, lli i +

                                                   !       I          i       i ll              Illi          I.ll l

e . li lIl lli

                                                              .i-                .-

f i lll1 'lI i l . t i

            ,   O. =
                =3 M
                .....=
                                -=s                                           ,,.,                 ,,,                  ,

lll 5 3,. E.  ;! ! i I ll- . 'II llll Ill"! ! - Hi: 1! !ij lii!j 1

                                                                                    /                       i             ;

i . i i .

/ /

( e i i e i i/' :l

    ' i            lili                    :                                  t/     -
                                                                                                        !     i .1/

i i, ll 1

                                       ;l
                                           -               l l ' ;j/. ; l l'                                   .'

s'; j/.  ;

                       .                                                                           2 i                        =                               i                                                       ,
                       =
                                                                 /
                                                                                                    \          ,

t i\ 1 e i e I k / I I i

                                                                                                      % /l          8 l

l!iil /' l! II' [' I I - l'lli

                                       /           .

I!' V  :  : l liii !

   =

f'i

                                                                                                                                    =

E O

             .  .  ,f l    lilll l' i !                         )' i *               !       '
                                                                              !'        f
                                                                                                '     I'      lli litt lii: (j!
!'!!i' ii!I!I; ,
l. . .

e . s * . 1 . l- ee i f f ef i /4 e ie 8i e Illi lli;l

                                          /I                'l                 '
                                                                                  !I:                   i      ill

, Ill 4 i, 1

                                         &            ~

N i ;

                                                                               '!!! l' ! lll!                                   .-

s s

                              \                                             +A                              .
     ......4,                                                               , . x                           ,  .    .

ie i iii\l .. Ii . .. N l

                                                                                                               '    , i llll           ll lIM                 i        6       ii                 ' Ii!               N           I'II llll Ill W i II:                                                          I      l!        il N I                           _

I B { \ i N i ! . . . . ~ . . 4 l I l l il i i l l i I lh 6 l l l4 l l llll ll!I 11i  ! I ll Il! lll l l

               =

Illl llil = = Ili

                                                                          =

i l lI

                                                                                          =                =

li - g n n n - - l (J.) 3un11nt3dn31

FLORIDA POWER CORPORATION Crystal River Unit 3 ZONE # 40 ( Zone Environmental Data Revision 1 Date 4/83 DESCRIPTION: Elev.119 & 143'- Reactor Building Inside "D" Rings ParamIters Normal Environment Environment For Loss Environment For High Energy Of Coolant Accident Line Break (Inside A8 & IB) TGmpirature Hours / Year Temo. Time Tem o. Time Temp. (oF) (Data not available) 0-10 sec 110-298 N/A 10-150 sec 298 150-400 sec 298-294 400-5000 sec 294-171 5000-8000 sec 171 8000 sec-24 hr 171-110 Prf.ssure (PSIG) Atmospheric Time Press. Time Press. 0-10 sec 0-49.6 N/A 10-150 sec 49.6 150-400 sec 49.6-46.5 400-5000 sec 46.5-7.7 5000-8000 sec 7.7 8000 sec-24 hr 7.7-0 RLlative (Data not available) 100 N/A Humidity (%) Chemical Spray N/A 2200 to 2450 ppn1 boron, N/A

.(pH)                                                105,000 to 120,000 ppm NaOH, pH 7.4 to 11.0 R:diation (Rads) 401' ear Oose                    Time Post                      N/A Accident              Oose 3.3 x 107                       1 Hr                 2.6 x 106 1 Day                1.0 x 107 5 Days               1.4 x 107 30 Days              1.7 x 107 6 Months             3.4 x 107 40 Yr. Total + 6 Mo. =

6.7 x 107 Total Submtrgence N/A N/A N/A (Flood Level) .9 I LEGEND: N/A = Not Acolicable, N/C = Not Calculated NOTES:

l (3154) 33nss334

                                                               "
  • 2 E E E o_
       . ,                 . . . .             .                                                        .                      .i
       .                                                                              i           , i-                iiii                  i+,

ii; i , ie i i lill I : I 'i i ll lIll li!! ll l , , I' llli ! Ili. llll  ! l . E~

                    !E3
       ,.           '65
  • 2 ..

ii, 5TE$ i / . ii i l}l $g$$ '

                                                                                      !           l ' il,                   '

Il lIil

                                   !                                    I!!l                      ! l 'fl                       ll          IlI!)             ._,

i i i. i i ! e e ie I l' 'l i l  ! l l1Ii  :

                                                                                                       /i                          !        i i/'

l!,  ! l iA l,  !  !! !- tas l . I f

                              -                                                    _.                                                        i m                                                  /            e                                             i

( e t l

                                                                    '/                        l t i'                               /I               I I!i'l                                             /             s!             -

Il /' I I ll fIll g lllll ==

                         . j
                             ,7                      /
                                                             /     .                                                                                .

i i i ' e i e if i

                                                  /                                                 e                  e t
                                                                                         '                                       l'          ilI l i l l l ):          I I
                                                  )i                          !                     !i            :

il8i l l. ll ' l'I (lli lli !

i i /~ l;iI.

i- . I!I l l IIl. Il i - l \

                           \                             i
  • e i i) / I ia i e , i i / . l. i 8

l l l l l l 't l l1 /! i l'lll l ll! llll k l! I Il  !

                                                                                                                                     ! ll                       -
                                .                                         ~
                                  's       i                         .                     Dx                                           d '            '

e i e .ie .N6 I i '\ l l 1 ei l 8 i k 1 I ' \' I I i Iiilll l IN , i e i4 ' II i N: I'II

                                                                                                                                                  ~
                                                                                  \

N

            . , i            . .                               ii                                   N                                                    Y l l       l      l i i                ;i           l           i e                        i iN i             e            i        I>I\

ll t i I!I ll!I 11; ' l 11 ll!l Ill'

                                                                                              =                     =                     =
                                                                                                                                                                  -   m,
                        -                 o                       -                           -                     -                                                 W  i (J.) 3M0lVB3dR31 l

t l l l

FLORIDA POWER CORPORATION Crystal River Unit 3 ZONE # 41 h Zone Environmental Data Revision 1 Date 4/83 DESCRIPTION: Elev. 95*. Auxiliary Builoing, Neutralizer Tank Room Parameters Normal Environment Environment For loss Environment For High Energy Of Coolant Accident Line Break (Inside AB & IB) TCmp;rature Hours / Year Tem o. Time Temo. Time Temo. (oF) 189 90 to 97 N/A N/A 7949 75 to 89 474 70 to 74 148 65 to 69 Note 2 Pr;ssure (PSIG) Atmospheric Time Press. Time Press. N/A N/A I R;lative 20 to 90 N/A N/A Humidity (%) ChImical Spray N/A N/A, N/A (pH) Radiation (Rads) 40 Year Dose Time Post N/A Accident Dose 1.0 x 108 1 Hr Note 1 1 Day 5 Days 30 Day 5 6 Months 40 Yr. Total + 6 Mo. = 1.0 x 104 Total Submergence N/A N/A N/A (Flood Level) l I LEGEND: N/A = Not Acolicable. N/C = Not Calculated NOTES: (1) Total 6 Month Integrated Accident Dose < 100 RADS (2) Allow 24 hours per year at 1150F for Postulated HVAC system failures

FLORIDA POWER CORPORATION Crystal River Unit 3 ZONE # 42 Zone Environmental Data Revision 1 Date 4/83 DESCRIPTION: Elev. 95' . Auxiliary Building, Neutralizer Pump Room Parim:;ters Normal Environment Environment For Loss Environment For High Energy Of Coolant Accident Line Break (Inside AB & IB) T6mp;rature Hours / Year Tem o. Time Temo. Time Tem o. (oF) 189 90 to 99 N/A N/A 6902 75 to 89 1521 70 to 74 148 65 to 69 Note 2 Pr;ssure (PSIG) Atmospheric Time Press. Time Press. N/A N/A tive 20 to 90 N/A N/A Humidity (%) Chimical Spray N/A N/A, N/A (pH) Radiation (Rads) 40 Year Oose Time Post N/A Accident Oose 1.0 x 104 1 Hr Note 1 1 Day

5. Days 30 Days 6 Months 40 Yr. Total + 6 Mo. =

1.0 x 104 Total Subm;rgence N/A N/A N/A (Flood Level) l I I LEGEND: N/A = Not Acolicable, N/C = Not Calculated NOTES: (1) Total 6 Month Integrated Accident Oose < 100RAOS (2) Allow 24 hours per year at 1150F for Postulated HVAC system failures

FLORIDA POWER CORPORATION Crystal River Unit 3 ZONE # 43 g Zone Environmental Data Revision 1 Date 4/83 DESCRIPTION: Elev. 95' and 108'- Control Complex Parameters Normal Environment Environment For Loss Environment For High Energy Of Coolant Accident Line Break (Inside A8 & IB) Tcmp;rature Hours / Year Temo. Time Tem o. Time Temo. (oF) 8760 70 to 80 N/A N/A Pressure (P5lG) Atmospheric Time Press. Time Press. N/A N/A

                                      /

9etitive 40 to 60 N/A N/A Humidity (%) Chxmical Spray N/A N/A, N/A (pH) Radiation (Rads) 40 Year Oose Time Post N/A Accident Oose 1.0 x 104 1 Hr Note 1 1 Day 5 Days j 30 Days 6 Months 40 Yr. Total + 6 Mo. = 1.0 x 104 Total Submergence N/A N/A N/A (Flood Level) l_ 'w/ l LEGEND: N/A = Not Acolicable, N/C = Not Calculated i NOTES: (1) Total 6 Month integrated Accident Dose < 100 RADS

FLORIDA POWER CORPORATION Crystal River Unit 3 ZONE # 44 g Zone Environmental Data Revision 1 Date 4/83 DESCRIPTION: Elev.145'-Control Complex, Between Columns 304 And 303 Parameters Normal Environment Environment For Loss Environment For High Energy Of Coolant Accident Line Break (Inside AB & 18) Tcmp;rature Hours / Year Temo. Time Temo. Time .Te m o. (oF) 8760 70 to 80 N/A N/A Pressure (PSIG) Atmospheric Time Press. Time Press. N/A N/A ( ) h,.lative 40 to 60 N/A N/A Humidity (%) ChImical Spray N/A N/A, N/A (pH) Radiation (Rads) 40 Year Dose Time Post N/A Accident Oose 1.0 x 104 1 Hr N/A 1 Day 5 Days 30 0ays 6 Months 40 Yr. Total + 6 Mo. = 1.0 x 104 Total Submergence N/A N/A N/A (Flood Level) l w ,' LEGEND: N/A = Not Acolicable, N/C = Not Calculated NOTES:

FLORIDA POWER CORPORATION Crystal Riv:r Unit 3 ZONE # 45 Zone Environmental Data Revision 1 Date 4/83 DESCRIPTION: Elev.143' Auxiliary Building, Exhaust Fan Area From Columns M To O. Parameters Normal Environment Environment For Loss Environment For High Energy Of Coolant Accident Line Break (Inside AB & 18) Tempirature Hours / Year Temo. Time Temo. Time Tem o. (oF) 5 95 to 99 N/A N/A 3723 85 to 94 4889 65 to 84 148 55 to 64 Note 1 Prissure (PSIG) Atmospheric Time Press. Time Press. N/A N/A tive 20 to 90 N/A N/A . Humidity (%) , Chtmical Spray N/A N/A, N/A (pH) Radiation (Rads) 40 Year Dose Time Post N/A Accident Dose 1.0 x 104 1 Hr N/C 1 Day 5 Days 30 Days 6 Months 40 Yr. Total + 6 Mo. = 1.0 x 104 Total Submergence N/A N/A N/A (Flood Level) l h LEGEND: N/A = Not Acolicable N/C = Not Calculated NOTES: (1) Allow 24 hours per year at 1150F for Postulated HVAC system failures

FLORIDA POWER CORPORATION Crystal River Unit 3 ZONE # 46 g Zone Environmental Data Revision 1 Date 4/83 DESCRIPTION: Elev.143'- Auxiliary Building, New Fuel Storage Rack Parameters Normal Environment Environment For Loss Environment For High Energy Of Coolant Accident Line Break (Inside AB & 18) Temp:;rature Hours / Year Tem o. Time Temo. Time Temo. (oF) 189 90 to 95 N/A N/A 7517 75 to 89 906 70 to 74 148 65 to 69 Note 1 Pressure (PSIG) Atmospheric Time Press. Time Press. N/A N/A

  -s.

! ) ~

 " ful'ative          20 to 90                          N/A                         N/A Humidity (%)

Ch mical Spray N/A N/A, N/A (pH) Radiation (Rads) 40 Year Dose Time Post N/A Accident Oose 1.0 x 104 1 Hr N/A 1 Day 5 Days 30 Days 6 Months 40 Yr. Total + 6 Mo. :. 1.0 x 104 Total Submergence N/A N/A N/A (Flood Level) l I I LEGEND: N/A = Not Acolicable, N/C = Not Calculated NOTES: (1) Allow 24 hours per year at 115cF for Postulated HVAC system failures

FLORID A POWER CORPORATION Crystal River Unit 3 ZONE # 47 Zone Environmental Data Revision 1 Date 4/83 DESCRIPTION: Elev,143'- Auxiliary Building, Spent Fuel Supply Fan Area Parameters Normal Environment Environment For Loss Environment For High Energy Of Coolant Accident Line Break (Inside AB & IB) Tcmp;rature Hours / Year Temo. Time Tem p. Time Tem o. (oF) 5 95 to 99 N/A N/A 890 85 to 94 7717 65 to 84 148 55 to 64 Note 1 Pressure (PSIG) Atmospheric Time Press. Time Press. N/A N/A k Rrlative 20 to 90 N/A N/A Humidity (%) Chimical Spray N/A N/A, N/A (PH) l l Radiation (Rads) 40 Year Dose Time Post N/A i Accident Dose ! 1.0 x 10' 1 Hr N/A 1 Day 5 Days 30 Days 6 Months 40 Yr. Total + 6 Mo. = 1.0 x 104 Total Submergence N/A N/A N/A j ! Flood Level) L.,) LEGEND: N/A = Not Acolicable, N/C = Not Calculated NOTES: (1) Allow 24 hours per year at 1150F for Postulated HVAC system failures

FLORIDA POWER CORPORATION Crystal River Unit 3 ZONE # 48 g Zone Environmental Data Revision 1 Date 4/83 DESCRIPTION: Elev.143'- Auxiliary Building, Hall Setween Columns 303 & 304 And I & J Parameters Normal Environment Environment For Loss Environment For High Energy Of Coolant Accident Line Break (Inside A8 & 18) Tcmperature Hours / Year Temo. Time Tem o. Time Temo. (oF) 895 90 to 95 N/A N/A 2828 80 to 89 3983 70 to 79 1054 55 to 69 Note 1 Pressure (PSIG) Atmospheric Time Press. Time Press. N/A N/A

,r    +-

I )

      'hflative           20 to 90                         N/A                          N/A Humidity (%)

Chemical Spray N/A N/A, N/A (pH) Radiation (Rads) 40 Year Oose Time Post N/A Accident Dose 1.0 x 104 1 Hr N/A 1 Day 5 Days 30 Days 6 Months 40 Yr. Total + 6 Mo. = 1.0 x 104 Total Submergence N/A N/A N/A (Flood Level)

     ~~-

LEGEND: N/A = Not Acolicable, N/C = Not Calculated NOTES: (1) Allow 24 hours per year at 1150F for Postulated HVAC system failures

FLORIDA POWER CORPORATION Crystal River Unit 3 ZONE # 49 g Zone Environmental Data Revision 1 Date 4/83 DESCRIPTION: Elev.119'- Auxiliary Building, Stairway By RC Bleed Tanks Parameters Normal Environment Environment For Loss Environment For High Energy Of Coolant Accident Line Break (Inside AB & IB) T(mpIrature Hours / Year Tem o. Time Temo. Time Temo. (oF) 189 90 to 99 N/A N/A 4959 80 to 89 3464 70 to 79 148 65 to 69 Note 1 Pr:ssure (PSIG) Atmospheric Time Press. Time Press. N/A N/A

  .lative          20 to 90                         N/A                        N/A Humidity (%)

ChImical Spray N/A N/A, N/A (pH) Radiation (Rads) 40 Year Dose Time Post N/A Accident Dose 1.0 x 105 1 Hr N/A 1 Day 5 Days 30 Days 6 Months 40 vr. Total + 6 Mo = 1.0 x 105 Total Submergence N/A N/A N/A (Flood Level) 9 LEGEND: N/A = Not Acolicable N/C = Not Calculated NOTES: (1) Allow 24 hours peryear at 1150F for Postulated HVAC system failures

FLORIDA POWER CORPORATION Crystal River Unit 3 ZONE # 50 Zone Environmental Data Revision 1 Date 4/83 DESCRIPTION: Elev.119'- Auxiliary Building, Valve Gallery By Cation Demineralizer Parameters Normal Environment Environment For Loss Environment For High Energy Of Coolant Accident Line Break (Inside AB & IB) Temp;rature Hours / Year Tem o. Time Tem o. Time Temo. (oF) 189 90 to 95 N/A N/A 6902 75 to 89 1521 70 to 74 148 65 to 70 Note 1 Pressure (PSIG) Atmospheric Time Press. Time Press. N/A N/A 7- .. j is' ' Jative

    ..                 20 to 90                         N/A                          N/A Humidity (%)

Chemical Spray N/A N/A, N/A (pH) Radiation (Rads) 40 Year Dose Time Post N/A Accident Dose 1.6 x 104 1 Hr N/A 1 Day 5 Days 30 Days 6 Months 40 Yr. Total + 6 Mo. = 1.6 x 104 Total Submergence N/A N/A N/A (Flood Level) l I LEGEND: ',/A = Not Aco;icable N/C = Not Calculated NOTES: (1) Allow 24 hours per year at 1150F for Postulated HVAC system failures

FLORIDA POWER CORPORATION Crystal River Unit 3 ZONE # 51 Zone Environmental Data Revision 1 Date 4/83 DESCRIPTION: Elev.119'- Auxiliar/ Building, Hall Outside Control Complex Par:mtters Normal Environment Environment For Loss Environment For High Energy Of Coolant Accident Line Break (Inside AB & IB) Tcmp;rature Hours / Year Tem o. Time Temo. Time Tem o. (oF) 189 90 to 99 N/A N/A 6041 80 to 89 2382 70 to 79 148 65 to 69 Note 1 Prissure (PSIG) Atmospheric Time Press. Time Press. N/A N/A Itive 20 to 90 N/A N/A _ Humidity (%) , ChImical Soray N/A N/A, N/A (pH) Radiation (Rads) 40 Year Dose Time Post N/A Accident Dose 1.0 x 104 1 Hr N/A 1 Day 5 Days 30 Days 6 Months 40 Yr. Total + 6 Mo. = 1.0 x 104 Total Submtrgence N/A N/A N/A (Flood Level) LEGEND: N/A = Not Acolicable, N/C = Not Calculated NOTES: (1) Allow 24 hours per year at 1150F for Postulated HVAC system failures

FLORIDA POWER CORPORATION Crystal River Unit 3 ZONE # 52 g Zone Environmental Data Revision 1 DESCRIPTION: Elev.119'- Aur.iliary Building, Hall Between Columns L & I Date 4/83 And Adjacent to Column 301 Param;ters Normal Environment Environment For loss Environment For High Energy Of Coolant Accident Line Break (Inside AB & IB) Tcmptrature ' Hours / Year Temo. Time Temo. Time Temo. (oF) 189 90 to 99 N/A N/A 3534 80 to 89 4415 65 to 79 622 55 to 64 Note 1 Pressure (PSIG) Atmospheric Time Press. Time Press. N/A N/A R. ative 20 to 90 N/A N/A Humidity (%) Chrmical Spray N/A N/A, N/A (pH) Radiation (Rads) 40 Year Dose Time Post N/A Accident Oose 1.0 x 104 1 Hr N/A 1 Day 5 Days 30 Days 6 Months 40 Yr. Total + 6 Mo. = 1.0 x 104 Total SubmIrgence N/A N/A N/A (Flood Level) sl I LEGEND: N/A = Not Acolicable N/C = Not Calculated NOTES: (1) Allow 24 hours per year at 1150F for Postulated HVAC system failures

FLORIDA POWER CORPORATION Crystal River Unit 3 ZONE # 53 Zone Environmental Data Revision 1 Date 4/83 DESCRIPTION: Elev.119'-Intermediate Building, West Penetration Area PartmIters Normal Environment Environment For Loss Environment For High Energy Of Coolant Accident Line Break (Inside A8 & IB) TcmpIrature Hours / Year Temo. Time Temo. Time Temo. (oF) 5 129 to 135 N/A 0-2 Sec 345 890 125 to 128 2-4 Sec 345-287 2828 120 to 124 4-10 Sec 287-240 1425 100 to 119 10-40 Sec 240-212 2990 95 to 99 40-1000 Sec 212 474 90 to 94 1000-3600 Sec 212 - Amb. 148 80 to 89 1 Hr-6 Mo Ambient Pressure (PSIG) Atmospheric Time Press. Time Press. N/A 0-2 Sec 4.45 2-40 Sec 4.45-0.5 40-1000 Sec 0.5 1000 3600 Sec 0.5 0 1 Hr-6 Mo 0 Hiative 20 to 90 N/A Time  %, 0-1Hr 100 tidity(%) 1-2 Hr 100-90

  -                                                                                 2 Hr-6 Mo                90 Chimical Spray    N/A                            N/A                              N/A (pH)

Radiation (Rads) 40 Year Dose Time Post N/A Accident Dose 1.0 x 104 1 Hr 1.1 x 101 1 Day 3.5 x 101 5 Days 6.4 x 101 30 Days 1.3 x 102 6 Months 2.5 x 102 40 Yr. Total + 6 Mo. = 1.0 x 104 Total Submsfgence N/A N/A N/A (Flood Level) k )

  ~.~s i

LEGEND: N/A = Not Apolicable. N/C = Not Calculated NOTES:

INTERMEGATE BUILDING 400 TEMPERATURE VER5U5 TIME

                                                    -----                   FOR HELB OR M5LB
                   ]

300 TEMPERATURE 's

          *F           A 250 g'-    -

200 g N N

                                                                                                      ^  w N

150 ' m

 .                                                                                                                N 3
                                                                   '              O 100                                                                   w 10        20         30             40       50         1000       2000        3000     4000 TIME (5EC.)

INTERMEDIATE BUILDNG 60 -- PRE 55URE VER5US TIME FOR HELB OR MSLB 50 ( 40 , PR ESSURE (M4 5 3 l 3.0 3 N N 2.0 \ \ ( ( 10 , N' ,-. IffI I

                                                                                               '*  w iiei      i 3

i . -*% 0 v to 20 30 40 50 1000 2000 m 4000 TIME (SEC.) , 1 1 l l 1 l l i

Fl.ORIDA POWER CORPORATION Crystal River Unit 3 ZONE # 54 g Zone Environmental Data Revision 1 Date 4/83 DESCRlPTION: Elev.119'-Intermediate Building, Between Columns G & H And 310 & 311 Parameters Normal Environment Environment For Loss Environment For High Energy Of Coolant Accident Line Break (Inside AB & IB) Tcmperature - Hours / Year Temo. Time Temo. Time Tem o. (oF) 189 123 to 128 N/A 0-2 Sec 345 4959 95 to 122 2-4 Sec 345-287 2990 85 to 94 4-10 Sec 287-240 622 70 to 84 10-40 Sec 240-212 40-1000 Sec 212 1000-3600 Sec 212 - Amb. 1 Hr-6 Mo Ambient Pr;ssure (PSIG) Atmospheric Time Press. Time Press. N/A 0-2 Sec 2.85 2-40 Sec 2.85-0.5 40-1000 Sec 0.5 1000-3600 Sec 0.5-0 1 Hr-6 Mo 0 R lative 20 to 90 N/A Time  % idity (%) 0-1 Hr 100 1-2 Hr 100-90 2 Hr-6 Mo 90 Ch:mical Spray N/A N/A N/A (pH) R diation (Rads) 40 Year Dose Time Post N/A Accident Dose 1.0 x 104 1 Hr N/A 1 Day 5 Days 30 Days 6 Months 40 Yr. Total + 6 Mo. = 1.0 x 104 Total Submergence N/A N/A N/A (Flood Level) l I ~ l LEGEND: N/A = Not Acolicable, N/C = Not Calculated NOTES:

s g INTERMEDIATE BUILDING 400 TEMPERATUR E VER5U5 TIME FOR HELS OR M5tB 350 - i 300 TEMPfA,ATURE

                --k    L 250            g
                                         %%mm
                                                 '4%   me  -

L 200 s

                                                                                               ' u k

N

                                                                                                           \

150 w m'N T 1M V 10 20 30 40 50 1000 2000 3W M TIME (SEC.)

                                                      ,.                       ~,

i l INTERMEDIATE BUILDING 60 PRE 55URE VER5US TIME FOR HELS OR M5LS I I e i 50 i l l l 40 l PRESSURE (Pio 3.0 ,, , xi ..- - g .

                                                                                                                                ~

. 20 ,

                                       \

s l N u s 10 mm l '%, p g ii  ; i ii i * w 10 20 30 40 50 1000 2000 3000 4000 TIME (5ECJ

FLORIDA POWER CORPORATION Crystal River Unit 3 ZONE # 55 Zone Environmental Data Revision 1 Date 4/83 DESCRIPTION: Elev.119'-Intermediate Building, Pressurizer Cabinet Area, Columns 307 to 308 Parameters Normal Environment Environment For loss Environment For High Energy Of Coolant Accident Line Break (Inside AB & 18) Temptrature Hours / Year Tem o. Time Tem o. Time Temo. (cF) 5 105 to 110 N/A 0-2 Sec 345 5143 90 to 104 2-4 Sec 345-287 2990 80 to 89 4-10 Sec 287-240 622 70 to 79 10-40 Sec 240-212 40-1000 Sec 212 1000-3600 Sec 212 - Amb. 1 Hr-6 Mo Ambient Prr ssure (PSIG) Atmospheric Time Press. Time Press. N/A 02 Sec 2.85 2-40 Sec 2.85-0.5 40-1000 Sec 0.5 1000-3600 Sec 0.5-0 1 Hr-6 Mo O Rtlative 20 to 80 N/A Time j6, 0-1 Hr 100 emidity(%) 1-2 Hr 100-90

              .                                                                 2 Hr-6 Mo             90 Chtmical Spray   N/A                             N/A                             N/A (pH)

Radiction (Rads) 4_0_ Year Dose Time Post N/A Accident Dose 1.0 x 104 1 Hr N/A 1 Day 5 Days 30 Days 6 Months 40 Yr. Total + 6 Mo. = 1.0 x 104 Total Submergence N/A N/A N/A (Flood Level) LEGEND: N/A = Not Acolicable. N/C = Not Calculated NOTES:

g II INIiRMEDIATE SUILDLNG 400 T!MPERATURE VER5U5 TIME FOR HELS OR MSLR I 350 7 300 TEMPERATURE \ 250 \ '

                                       %g
                                              'N     %,
                                                                                          ' w
                                                                                              \

X 150 , N T 100  % 10 20 30 40 50 1000 2000 3000 4000 TIMf(SECJ I ( l INTERMEDIATE SulLDING 60 PRE 550RE VER5U5 TIME FOR HELS OR MSLB I 50 40 PRES 5URE (PM 30 ., X h N A 2.0 ,(

                                      %m'A N&

1.0 4 x

               ~~'

IIiiiIi6I Th_ - l iil f i } } ii 0 - 10 20 30 40 50 1000 2000 3000 4000 TIMf (5EC.)

FLORIDA POWER CORPORATION Crystal River Unit 3 ZONE # 56 Zone Environmental Data Revision 1 Date 4/83 DESCRIPTION: Elev.119'-Intermediate Building, H & V MCC Area, Adjacent to Column 307 Paramsters Normal Environment Environment For Loss Environment For High Energy Of Coolant Accident Line Break (Inside AB & 13) Temp;rature Hours / Year Temo. Time Temo. Time Temo. (oF) 5 105 to 110 N/A 0-2 Sec 345 5143 90 to 104 2-4 Sec 345-287 2990 80 to 89 4-10 Sec 287-240 622 70 to 79 10-40 Sec 240-212 40-1000 Sec 212 1000-3600 Sec 212 - Amb. 1 Hr-6 Mo Ambient Pressure (PSIG) Atmospheric Time Press. Time Press. , N/A 0-2 Sec 2.85 2-40 Sec 2.85-0.5 40-1000 Sec 0.5 1000-3600 Sec 0.5-0 1 Hr-6 Mo 0 Rr,htive 20 to 90 N/A Time jd 0-1 Hr 100 Widity(%) 1-2 Hr 100-90 2 Hr-6 Mo 90 Chimical Spray N/A , N/A N/A (pH) Radiction (Rads) 40 Year Dose Time Post N/A Accident Dose 1.0 x 104 1 Hr N/A 1 Day 5 Days 30 Days 6 Months 40 Yr. Total + 6 Mo. = 1.0 x 104 Total i Submtrgence N/A N/A N/A l (Flood Level) I 'I LEGEND: N/A = Not Acolicable, N/C = Not Calculated i NOTES:

                                                                                ^

v INTERMED(ATE BUILD 4NG 400 TEMPERATURE VER5U5 TIME

                     '                                                     FOR HELS OR M5LO 350   -

I e l -. . 1 M TEMPERATURE 's I W L 250 g w --

                                                        -  a__
                                                                                           ' e 200                                                                                  s N

N N N 150

                                                                                                                      '.'N 3 100
                                                                                ^

v 10 20 30 40 50 1000 2000 3000 4000 TIME (SECJ g ] t i i I l 6 i I 4 9 o INTERMEDIATE SUILDING 60 PRES 5URE VER5US TIME FOR HELE OR M5LS I' i 50 4.0 PRES 5URE (P54 30 _, N b

                                   '  t 2.0                          x N'A Nu'N 1.0                                         N hhl                                          -

l I 1 ! 6 I I I & *'C 10 20 30 40 50 1000 2000 3000 4000 1 TIME (SEC)

FLORIDA POWER CORPORATION Crystal River Unit 3 ZONE # 57 Zone Environmental Data Revision 1 Date 4/83 DESCRIPTION: Elev.119'-Intermediate Building, By Personnel Access Hatch Paramsters Normal Environment Environment For loss Environment For High Energy Of Coolant Accident Line Break (Inside A8 & IB) Ttmpirature Hours / Year Temo. Time Temo. Time Temo. (oF) 895 90 to 99 N/A 0-2 Sec 345 2828 80 to 89 2-4 Sec 345-287 4889 65 to 79 4-10 Sec 287-240 148 55 to 64 10-40 Sec 240-212 40-1000 Sec 212 1000-3600 Sec 212 . Amb. 1 Hr-6 Mo Ambient Prtssure (PSIG) Atmospheric Time Press. Time Press. N/A 0-2 Sec 3.18 2-40 Sec 3.18-0.5 40-1000 Sec 0.5 1000-3600 Sec 0.5-0 1 Hr-6 Mo O R.lative 20 to 80 N/A Time  % 0-1 Hr 100 Widity(%) 12 Hr 100-90 2 Hr-6 Mo 90 Ch:mical Spray N/A N/A N/A (pH) ., 4 ., Radiation (Rads) 40 Year Dose Time Post N/A Accident Dose 1.0 x 104 1 Hr Note 1 1 Day 5 Days 30 Days 6 Months 40 Yr. Total + 6 Mo. = 1.0 x 104 Total Submergence N/A N/A N/A (Flood Level) l I I LEGEND: N/A = Not Acolicable. N/C = Not Calculated NOTES: (1) Total 6 Month Integrated Accident Dose < 100 RADS

                                                                           *v INTERMEDIATE BU6LDING 400                                        TEMPERATURE VER$US TIME FOR HELS OR M5LS 350  -

300 TEMPERATURE 's W L 250 g

                          ==-
                                     %gungm num-.

L

                                                                                          \
                                                                                            ' t
                                                                                                \
  • m
                                                                                                       \

150 ^ m

                                                                                                             \

iOO

                                                                            ^

v 10 20 30 40 50 1000 2000 M M TIME (SEC.) ( , s l \ INTERMEDIATE suiLDING 60 PRES 5URE VERSUS Tietf FOR HELS OR MSLB l 5.0 l 4.0 PRE 55URE (PM 3.0 s

                       '  m k

N 2.0 g X

                                        'A b
                                              ^ w 1.0                                   x i            g    t bh'*     w      I 0                                                                  v 10      20          30           40         50           1000         2000       M     4M TIME ($f C.)

FLORIDA POWER CORPORATION Crystal River Unit 3 ZONE # 58 Zone Environrelental Data Revision 1 Date 4/83 DESCRIPTION: Elev.124' & 134'- Control complex Parameters Normal Environment Environment For Loss Environment For High Energy Of Coolant Accident Line Break (Inside AB & IB) Temp;rature Hours / Year Tem o. Time Temo. Time Temo. (oF) 8760 70 to 80 N/A N/A Pressure (PSIG) Atmospheric Time Press. Time Press. N/A N/A tive 40 to 60 N/A N/A , Humidity (?p) Chromica! Spray N/A N/A, N/A (pH) Radiation (Rads) 40 Year Dose Time Post N/A Accident Dose 1.0 x 104 1 Hr N/A 1 Day 5 Days 30 Days 6 Months 40 Yr. Total + 6 Mo. = 1.0 x 104 Total Submtrgence N/A N/A N/A (Flood Level) l I LEGEND: N/A = Not Aoplicable, N/C = Not Calculated NOTES:

FLORIDA POWER CORPORATION Crystal Riv :r Unit 3 ZONE # 59 Zone Environmental Data Revision 1 CRIPTION: Elev. 95* - Auxiliary Building, Adjacent To Control Complex Date 4/83 Between Columns 301 and 303 ParamIters Normal Environment Environment For Loss Environment For High Energy Of Coolant Accident Line Break (Inside AB & IB) TGmp'irature Hours / Year Temo. Time Tem o. Time Tem o. (oF) 189 90 to 95 N/A N/A 6902 75 to 89 1521 70 to 74 148 65 to 70 Note 1 Prtssure (PSIG) Atmospheric Time Press. Time Press. N/A N/A l Itive 20 to 90 N/A N/A Humidity (%) Ch:mical Spray N/A N/A, N/A (pH) Radiation (Rads) 40 Year Dose Time Post N/A Accident Dose 1.0 x 104 1 Hr N/A 1 Day 5 Days 30 Days 6 Months 40 Yr. Total + 6 Mo. = 1.0 x 104 Total l Submtrgence N/A N/A N/A (Flood Level)

  /        i l\,_~J LEGEND: N/A = Not Applicable, N/C = Not Calculated NOTES: (1) Allow 24 hours per year at 115cF for Postulated HVAC system failures l

FLORIDA POWER CORPORATION Crystal Riv:r Unit 3 ZONE # 60 Zone Environmental Data Revision 1 CRIPTION: Elev. 95* - Auixiliary Building, Hall Adjacent to Control Complex Date 4/83 Between Columns 303 And 304 Parameters Normal Environment Environment For Loss Environment For High Energy Of Coolant Accident Line Break (Inside AB & 18) Temperature Hours / Year Temo. Time Temo. Time Tem o. (oF) 189 90 to 95 N/A N/A 6902 75 to 89 1521 70 to 74 148 65 to 69 Note 1 Prtssure (PSIG) Atmospheric Time Press. Time Press. N/A N/A Itive 20 to 90 N/A N/A Humidity (%) Chtmical Spray N/A N/A, N/A (pH) Radiction (Rads) 40 Year Dose Time Post N/A l Accident Dose 1.0 x 104 1 Hr N/A 1 Day 5 Days 30 Days 6 Months l l 40 Yr. Total + 6 Mo. = l 1.0 x 104 Total l l Subm;rgence N/A N/A N/A (Flood Level) )

 \      ,i
   . .a LEGEND: N/A = Not Acolicable, N/C = Not Calculated NOTES: (1) Allow 24 hours per year at 1150F for Postulated HVAC system failures

FLORIDA POWER CORPORATION Crystal River Unit 3 ZONE # 61 Zone Environmental Data Revision 1 Date 4/83 DESCRIPTION: Elev. 95'- Auxiliary Building, Hall Between Columns 1 & K Adjacent to Column 301 Parameters Normal Environment Environment For Loss Environment For High Energy Of Coolant Accident Line Break (Inside AB & IB) Tcmp'.rature Hours / Year Temo. Time Temo. Time Temo. (oF) 189 90 to 95 N/A N/A 3534 80 to 89 4889 70 to 79 148 65 to 69 Note 1 Pri.ssure (PSIG) Atmospheric Time Press. Time Press. N/A N/A 9 Rtistive 20 to 90 N/A N/A Humidity (5/a ) Ch:mical Spray N/A N/A, N/A (pH) Radiction (Rads) 40 Year Dose Time Post N/A Accident Dose 1.0 x 104 1 Hr N/A 1 Day 5 Days 30 Days 6 Months 40 Yr. Total + 6 Mo. = 1.0 x 104 Total Submergence N/A N/A N/A (Flood Level) I k \ J LEGEND: N/A = Not Acolicable, N/C = Not Calculated NOTES: (1) Allow 24 hours per year at 1150F for Postulated HVAC system failures

FLORIDA POWER CORPORATION Crystal River Unit 3 ZONE # 62 Zone Environmental Data Revision 1 Date 4/83 DESCRIPTION: Elev. 95* - Auxiliary Building, Area Below Equipment Hatch Param&ters Normal Environment Environment For loss Environment For High Energy Of Coolant Accident Line Break (Inside AB & IB) T6mptrature Hours / Year Tem o. Time Temo. Time Tem p. (oF) 189 90 to 99 N/A N/A 3534 80 to 89 4889 70 to 79 148 65 to 69 Note 1 Pressure (PSIG) Atmospheric Time Press. Time Press. N/A N/A tive 20 to 90 N/A N/A . Humidity (%) Chrmical Spray N/A N/A, N/A (pH) Radiation (Rads) 40 Year Dose Time Post N/A Accident Dose 1.0 x 104 1 Hr N/A ' 1 Day 5 Days 30 Days 6 Months 40 Yr. Total + 6 Mo. = 1.0 x 104 Total Submtrgence N/A N/A N/A (Flood Level) . 9 l l LEGEND: N/A = Not Acolicable, N/C = Not Calculated NOTES: (1) Allow 24 hours per year at 115cF for Postulated HVAC system failures

                                                                                                                      '1

l 1 FLORIDA POWER CORPORATION l Crystal River Unit 3 ZONE # 63 Zone Environmental Data Revision 1 S DESCRIPTION: Elev.164'- Control Complex Date 4/83 i l Parameters Normal Environment Environment For loss Environment For High Energy , Of Coolant Accident Line Break (Inside A8 & IB) l T(mp",rature Hours / Year Tem o. Time Temo. Time Tem o. (oF) 8760 70 to 80 N/A , N/A Pressure (PSIG) Atmospheric Time Press. Time Press.

                                                       'N/A                          N/A tive '     40'to 60                        N/A                          N/A                            _

Humidity (%) , Chimical Spray N/A N/A, - N/A (pH) Radiation (Rads) 40 Year Dose Time Post N/A Accident Dose 1.0 x 104 1 Hr N/A 1 Day

 '~

5 Days 30 Days 6 Months 40 Yr. Total + 6 Mo. = 1.0 x 104 Total Subidtrgence N/A N/A N/A (Flood Level) - ^ l I l LEGEND: N/A = Not ADolicable, N/C = Not Calculated NOTES:

                                               /

FLORIDA POWER CORPORATION Crystal River Unit 3 ZONE #- 64 Zone Environmental Data Revision 1 Date 4/83 DESCRIPTION: Elev. 95* - Auxiliary Building, Penetration Area, North of Emergency Pump Room Parameters Normal Environment Environment For Loss Environment For High Energy Of Coolant Accident Line Break (Inside A8 & IB) Temperature Hours / Year Temo. Time Temo. Time Temo. (oF) 189 90 to 99 N/A N/A 4959 80 to 89 3464 70 to 79 148 55 to 69 Note 1 Pressure (PSIG) Atmospheric Time Press. Time Press. N/A N/A I btive 20 to 90 N/A N/A . Humidity (%) Ch:mical Spray N/A N/A N/A (pH) R diation(Rads) 40 Year Dose Time Post N/A Accident Oose 4.5 x 104 1 Hr 8.3 x 103 1 Day 2.6 x 108 l 5 Days 4.7 x 104 l 30 Days 8.9 x 104 6 Months 1.7 x 105 40 Yr. Total + 6 Mo. = 2.2 x 10s Total Submergence N/A N/A N/A l (Flood Level) ,l I LEGEND: N/A = Not Apolicable, N/C = Not Calculated l NOTES: (1) Allow 24 hours per year at 115cF for postulated HVAC system failuces l

FLORIDA POWER CORPORATION Crystal River Unit 3 ZONE # 65 Zone Environmental Data Revision 1 Date 4/83 DESCRIPTION: Elev. 95* -Intermediate Building, Penetration and Sample Cooler Area Parameters Normal Environment Environment For loss Environment For High Energy Of Coolant Accident Line Break (Inside AB & IB) Tempirature Hours / Year Tem p. Time Tem o. Time Temo. (oF) 189 90 to 99 N/A 0-2 Sec 345 4959 85 to 89 2-4 Sec 345-287 3464 70 to 84 4-10 Sec 287-240 148 55 to 69 10-40 Sec 240-212 Note 1 40-1000 Sec 212 1000-3600 Sec 212 - Amb. 1 Hr-6 Mo Ambient Pressure (PSIG) Atmaspheric Time Press. Time Press. N/A 0-2 Sec 2.43 2-40 Sec 2.43-0.5 40-1000 Sec 0.5 1000-3600 Sec 0.5-0 1 Hr-6 Mo O R*lative 20 to 90 N/A Time & tidity (%) 0-1 Hr 100 1-2 Hr 100-90 2 Hr-6 Mo 90 Chtmical Spray N/A N/A N/A (pH) R diation(Rads) 40 Year Dose Time Post N/A

                                                       ~ Accident            Dose 1.62 x 104                    1 Hr                 4.1 x 103 1 Day                1.4 x 104 5 Days               2.5 x 104 30 Days              4.9 x 104 6 Months             9.0 x 104 40 Yr. Total + 6 Mo. =

1.1 x 105 Total Submergence N/A N/A N/A (Flood Level) I LEGEND: N/A = Not Acolicable, N/C = Not Calculated NOTES: (1) Allow 24 hours per year at 1100F for postulated HVAC system failures _ _ . .}}