_ _. - _ _ _

4 1

TABLE 3.3.5.2-1 REMOTE SHUTDOWN MONITORINC INSTRUMENTATION MINIMUM READOUT CllANNELS FUNCTIONAL UNIT LOCATION OPERABLE I8)

1. Reactor Vessel Pressure RSP 1
2. Reactor Vessel Water Level RSP(a) g
3. Suppression Chamber Water Level RSP(a) g
4. Suppression Chamber Water Temperature RSP(a) 3
5. Drywell Pressure RSP(a) g I8)
6. Drywell Temperature RSP 1
7. Residual Heat Removal System Flow RSP ")

1 I

(a) Remote Shutdown Panel, Reactor Building 20' Elevation BRUNSWICK - UNIT 2 3/4 3-57 Amendment No.

9101070171 901227 PDR ADOCK 05000324 P

PDR

.1 TABLE 4.3.5.2-1 REMOTE SHUTDOVN MONITORING INSTRUMENTATION SURVEILLANCE REQUIREMENTS CHANNEL CilANNEL FUNCTIONAL UNIT CHECK 9ALIBRATION

1. Reactor Vessel Pressure H

Q

2. Reactor Vessel Water Level N017 Instrument Loopt NA Q

Remaining Instruments:

M Q

3. Suppression Chamber Water Level H

R

4. Suppression Chamber Water Temperature H

R

5. Drywell Pressure M

Q

6. Drywell Temperature M

R

7. Residual Heat Removal System flow H

Q i

l l

i BRUNSWICK - UNIT 2 3/4 3-58 Amendment No.

l.

. -