L-OPERATING DATA REPORT

'~

DOCKET NO. 50-266 DATE October 8, 1990 COMPLETED BY K. H.. Nickels TELEPHONE 414/755-2321 OPERATING STATUS

1. UNIT NAME: POINT BEACH NUCLEAR PLANT UNIT 1

. NOTES

2. REPORTING PERIOD: SEPTEMBER 1990
3. LICENSED THERMAL POWER (MWT):

1518.5

4. NAMEPLATE RATING (GROSS MWE):

523.8

5. DESIGN ELECTRICAL RATING (NET MWE): _ 497.
6. MAXIMUM DEPENDABLE CAPACITY (GROSS MWE):

509.

7. MAXIMUM DEPENDABLE CAPACITY (NET MWE):

485.

8.

IF CHANGES OCCUR IN CAPACITY RATINGS (ITEMS NUMBER 3 THROUGH 7) SINCE LAST REPORT, GIVE REASONS:

NOT APPLICABLE 9.

POWER LEVEL.TO WHICH RESTRICTED, IF-ANY (NET MWE): NOT APPLICABLE-

10. REASONS FOR RESTRICTIONS, (IF ANY): NOT APPLICABLE THIS MONTH YR.TO DATE CUMULATIVE
11. HOURS IN REPORTING" PERIOD

-720 6,551 174,455

12. NUMBER.OF. HOURS REACTOR WAS CRITICAL 720.0

.5,214.8 143,558.5

13. REACTOR RESERVE SHUTDOWN HOURS 0.0
0.0 652.7:
14. HOURS GENERATOR ON LINE 720.0 5,155.3 140,694.5

~15. UNIT RESERVE SHUTDOWN HOURS.

0.0 -

0.0 837.9.

16. GROSS' THERMAL' ENERGY GENERATED (MWH) :-

1,084,121

.7,593,071 196,061,463

17. GROSS ELECTRICAL ENERGY GENERATED-(MWH) 362,320 2,561,640 66,168,330.

18.-NET ELECTRICAL ENERGY-GENERATED'(MWH)~

346,222 2,445,857 63,036,548

19. UNIT SERVICE FACTOR-100.0

-- 7 8. 7 80.6

20. UNIT AVAILABILITY FACTOR 100.0

.78.7 -

81.1

21. UNIT CAPACITY FACTOR (USING.MDC NET)-

99.1-77.0 74.1

22. UNIT CAPACITY FACTOR-(USING' DER NET).

96.8-75.1 72.7

23. UNIT FORCED OUTAGE RATE 0.0 0.0

-1.8

24. SHUTDOWNS SCHEDULED OVER NEXT 6 MONTHS'(TYPE,-DATE, FRD DURATION.OF EACH):

'NONE

25. IF) SHUTDOWN AT END OF REPORT PERIOD,. ESTIMATED DATE OF STARTUP:

NOT~ SHUTDOWN e

DATA REPORTED AND FACTORS CALCULATED AS REQUESTED IN NRC LETTER. DATED SEPTEMBER 22,~.1977 9010160083 901009

~

PDR ADOCK 05000266 R

PDC

.m

--_-_a,

. #~

.. ~

.., - -~.. c _. _a m.

u..

.u.

_,u

_g-

.?

POIST BEACII NUCLEAR PLANT DOCKET NO.

50-266 AVERAGE DAILY UNIT POWER LEVEL UNIT NAME.

Point Beach. Unit 1 ' '

MONTil SEPTEMBER DATE October 8.1990 -

COMPLETED BY K. H. N'miels TELEPHONE' 414/755-2321 AVERAGE AVERAGE AVERAGE-DAILY DAILY:

DAILY POWER LEVEL POWER LEVEL POWERIEVEL "-

DAY MWe NET DAY MWe NET '

DAY MWe NET 1

487 11 480 21 -

483 2

483 12 483 22 485

-3 482 13 458 23

'464' 4

488 14 489

24i

'486 "

' 5 486 15 -

459

~

'486 25' m.

- 6

'485 16 433~

26 --

-486 il. -

.7 483

' 17-

'457- ~489-

~

8 482

.-18 483 28 488 9-483

19

'484 29

'487 20' 483

'30 489 0

483 31 PBF-0028a

.(0190J-g.

s.4,>_

=-es

.y

.-cy-

.c g

p,y--*

++.e y n 5-w

-e-..-,--w, ysv ~

s ce e m = -,

o,

c< mwwe,.'-

n,

.,v.#

m.

3.w.

gw,--,

n.--

+

~

h_

POINT BEACH NUCLEAR PIANT

' Docket No.

50-266

^

.:m Uni 3 Name Point Beach: Unit 1 - -

  • UNIT SHUTDOWNS AND POWER REDUCTIONS Date. _

October 8.1990

. ;g _

Completed By -

K. H. Nickels '

REPORT MONTH SEPTEMBER Telephone No. ' 414/755-2321 Method of

~

Shutting No.

Date Type' Duration Reason Down Licensee Sent System Component Cause and Correctne Action 2

(Ifours)

Reactor 3 Report No.

Code Code 8 d

To Present Recurrence 4

4 6

a v'

q i

l

'F: Forced

' Reason:

8Method:.

' Exhibit G - Instructions S: Scheduled A - Equipment Failure (explain) :

.1 - Manual

, for preparation of :

B - Maintenance or Testing' ~ ~

2 - Manual Scram data entry sheets

. C - Refueling :.

3 - Autonsatic Scram IER file (NUREG-0161) -

. D - Regulatory Restriction

4 - Continuation of 2 E - Operator Training &

' Previous Shutdown Ur*==ia-Exam 5 - Reduced load :

F - Adminierative :,

6 - Other (explain) -'

' Exhibit I - Same Source i 1..

. G - Operational Error (explain).

H - Other (explain).

PBF-0028b' (OW)

- i '

_ _ _ _ _ _ _ _ _ - _ _ - _ - _ - - ~ - - - - - -, - -, -. -

~ - -

- - ~

t t

o.

DOCKET Nd.

50-266-UNIT NAME Point Beach Unit 1.

DATE Cktober 8,1990 COMPLETED BY K. H. Nickels.

TELEPilONE 414/755 2321
Unit 1 operated at approximately 486 MWe net throughout the period with no ma,ior load reductions.

Safety related maintenance included the P 32C service water pump motor.

ay 2

=

1 J

k

-:j l

l 3

L 1

r q

OPERATING DATA REPORT DOCKET NO. 50-301

?-

DATE October 8, 1990 COMPLETED BY

~ K. H. Nickels TELEPHONE-414/755-2321 OPERATING STATUS

1. UNIT NAME:

POINT BEACH NUCLEAR PLANT. UNIT 2

. NOTES-

2. REPORTING PERIOD: SEPTEMBER 1990
3. LICENSED THERMAL POWER (MWT):

1518.5

4. NAMEPLATE RATING (GROSS MWE}:

523.8

5. DESIGN ELECTRICAL RATING (NET MWE):

497.

6. MAXIMUM DEPENDABLE CAPACITY (GROSS MWE):

509.

7. MAXIMUM DEPENDABLE CAPACITY (NET MWE):

485.

8.

IF CHANGES OCCUR IN' CAPACITY RATINGS (ITEMS NUMBER 3 THROUGH 7) SINCE LAST REPORT, GIVE REASONS:

NOT APPLICABLE 9.

POWER LEVEL TO WHICH. RESTRICTED, IF ANY (NET MWE): NOT APPLICABLE

10. REASONS FOR RESTRICTIONS,,(IF'ANY):.NOT APPLICABLE

.. THIS MONTH YR TO DATE.

CUMULATIVE 11.' HOURS IN REPORTING' PERIOD 720

. 6,551-159,240

12. NUMBER OF HOURS REACTOR WAS CRITICAL

.720.0 6,551.0 139,896.8

-13. REACTOR RESERVE SHUTDOWN HOURS 0.O

'O.O-216.7-

14. HOURS GENERATOR ON LINE 720.0-

' 6,551.0^

137,756.3

15. UNIT RESERVE SHUTDOWN HOURS 0.0 0.0

.302.2

16. GROSS THERMAL ENERGY GENERATED (MWH).

1,068,375

.9,889,260 196,472,796

17. GROSS ELECTRICAL ENERGY GENERATED (MWH)
360,960 3,389,910

-66,715,1~D

18. NET ELECTRICAL ENERGY GENERATED (MWH)

.344,495 3,241,989 63,580,599

19. UNIT. SERVICE FACTOR

~100.0 100.0 86.5

20. UNIT AVAILABILITY-FACTOR-

-100.0 100.0 86.7

- 21. UNIT CAPACITY FACTOR (USING'MDC NET) 98.7 102.0

81. 6.-
22. UNIT CAPACITY FACTOR (USING DER NET)'

96.3 99.6-80.3

23. UNIT FORCED OUTAGE RATE O.0.

0.0 1.1

24. SHUTDOWNS SCHEDULED OVER NEXT 6 MONTHS-(TYPE,'DATE, AND. DURATION OF EACH):

. Forty-two day refueling and maintenance outage scheduled to begin October-5, 1990.

25. IF SHUTDOWN AT END OF REPORT PERIOD,LESTIMATED-DATE OF STARTUP:- NOT SHUTDOWN DATA REPORTED AND FACTORS CALCULATED AS REQUESTED IN NRC LETTER DATED SEPTEMBER 22, 1977 4

n

+

e.-

.-e.

., _., -,-i,.-

-e-r wl<

.,,-w-

~-m.-

-+~mv e

-w--',-+,,,,w

,e, e

~. -...

4-

.n-.

~'

-c POINT BEACH NUCLEAR PIANT '

DOCKET NO.

50-301 AVERAGE DAILY UNIT POWER LEVEL' UNIT NAMEL

' Point Beadi. Unit 2 MONTH SEPTEMBER DATE Odober 8.1990

~ COMPLETED BY-K. H. N~ckels TELEPHONE ~-

414/755-2321 AVERAGE AVERAGE' AVERAGE' -

DAILY DAILY DAILY POWER LEVEL POWER LEVEL POWER LEVEL -

DAY MWe NET DAY MWe NET DAY

' MWe NET '

1 491 11 485 21 473' 2

488 12 487

. 22 471 3

485 13 492 23 471 4

492 14 494 24 467

~

5

'490 15 488

- 25..

~ 466-6 489 16

-486 26

' 464 7

465 17

'485'

~ 27

'- 468-8 486

.. 18 481

- 28 L

-456 9

492 19.

478'

~29

' 456' 10 483-20 -

'474

- 30.

- 455 31-

'w iPDF-002Sa (03-90)

, i M et

,,,.p

=-h-.,-tw-aa

,=pwn 4

,;7.irh,'Me.-

cM'9--p. Map t:

SrerA=

v{

.'"d'P-

  • g.

"V'r.rrTm--pv

.-a*g"'e'

=*N***Y d "e

-~ * ' * -'O m2' TM'-+#M' '

i=1-m'--"N5*2.-

e a

POINT BEACH NUCLEAR PLA?fr Docket No.

'50-301-

~

'c

~

Unit Name -

Point Beach. Unit 2 - 1 UNIT SHUTDOWNS AND POWER REDUCTIONS Date.

Odober 8.1990 -

Completed By. ' K. H. Nickels

~

REPORT MONTH SEPTEMBER Telephooc No.

414/755-2321 Method of

- H Shutting No.

Date Type' Duration Reason 2 Down 1xensee & cat System Component

~ Cause and Correctm Action -

3 S

Olours) -

Reactor Report No.

Code

  • Code

' To Prevent Recurrence

~..

i.

l I

g r

Reason:

' Method:

'F Fo ced 2

'F hen G Instradions u

.S: Scheduled

'A - Equipment Failure (explain)

~ 1 - Manual for preparation of -

.B Maintenance or Testing ~

12 - Manual Scram

~ data entry sheets

. C - Refueling 3 - Automatic Scram

) LER file (NUREG-0161) '

D ~- Regulatory Restriction 4 - Continuation of.

E - Operator Training &.

. Previous Shutdown :

i-

- hm*mg Fum=

f 5 - Reduced load

F-Administrative 6 - Other (explain) -

'Fuhihet I'- Same Source G - Operational Error (explain)l

~

H - Other (explain)

N l

(N) y-,e m.

.e y

7,

.,_99 n.

.%-n

.g w

id'

.' deer'd-'g' 9

-6 pm.rpr-g'J-

.,g c

p

.,q,'w-w%*,-y.g.p'We%.-p gy.,

y

.;p.

,-_gisa w

--g.,qa y,.w g 7..

y y.

'%g e pg.rW m

'*S h@

w

'7*#'"WT

-'tdt to-e-e o

a*

ar 9 y q

4

,pi

.[

l}

' DOCKET NO

.50-301 UNIT NAME

' Point Beach Unit 2 DATE October 8,1990 COMPLETED BY K. H. Nickels TELEPHONE 414D55 2321 1

Unit 2 operated at approximately 487 MWe net until September 18 when the unit was placed in end-of core life -

~!

coastdown operation.

4 i

Safety related maintenance included installing pump casing drains and repairing oil and seal leaks on P-11 A -

l{

component _ cooling water pump.

. i

-s

-t e

h I

I

[

l-:

I