ML20062B727

From kanterella
Jump to navigation Jump to search

Forwards Safety Evaluation Identifying Three Open Items Re App J Containment Leak Testing Review.Nrc Review Put on Hold Pending Receipt of Licensee Info.Response Due in 30 Days. Supplemental SER Will Be Issued Upon Review Completion
ML20062B727
Person / Time
Site: Fort Calhoun 
Issue date: 07/23/1982
From: Clark R
Office of Nuclear Reactor Regulation
To: William Jones
OMAHA PUBLIC POWER DISTRICT
Shared Package
ML20062B728 List:
References
TAC-8910, NUDOCS 8208050012
Download: ML20062B727 (3)


Text

1 P

f

).

r (TGEDIU JUL 2 3 1982 Docket No. 50-285 Mr. W. C. Jones Division Manager, Production Operations Omaha Public Power District 1623 Harney Street Omaha, Nebraska 68102

Dear Mr. Jones:

SUBJECT:

APPENDIX J CONTAINMENT LEAK TESTING REVIEW We have cor pleted our Appendix J Containnent Leak Testing Review in response to your submittals dated September 10, 1975, March 30, 1977, and May 15, 1980. Our Safety Evaluation Report, which is enclosed, identifies three open items as follows:

(1) OPPD's correlation to extrapolate leakage rates at 5 psig to 60 psig for containment airlocks is not sufficiently conservative, (2) The valve or valves associated with penetration M-3 should be testad in accordance with Appendix J. and (3) The valve or valves associated with penetration M-44 should be tested in accordance with Appendix J.

Regarding open item 1, we do not believe that your correlation to extrapo-late leakage rates at 5 psig to 60 psig for containment airlocks is suffi-cien':ly conservative. The basis for not approving this correlation can be found on page 8 of the enclosed NRC contractor report. He agree with our contractor on this, and the method contained in Appendix A of the enclosed contractor report is one method that is acceptable to us.

Regarding open items 2 and 3, we concluded that you did not provide suffi-cient justification for not testing the valves associated with these pene-trations in accordance with Appendix J, thus we conclude at this time that they should be tested.

8208050012 020723 PDR ADOCK 05000285 p

PDR OFFICE )

  • .**a.

suRuime>

o4re >

NRC FORM 318 (10-80) NRCM 0240 OFFiCI AL RECORD COPY usom mi-us-se

e4 Mr. W. C. Jones,

In order to resolve these open items, we propose the following.

(1) We request that the District review the methodology contained in Appendix A of our contractor report and determine if this method is acceptable to the District.

If the method is acceptable, your response should document your planned use of this method.

If the method is not acceptable to tSe District, please propope a method that you believe will resolve our concerns on this issue.

(2) We request that the District either agree to test the valves as-sociated with penetrations M-3 and M-44 in accordance with Appendix J or submit a detailed. justification for not doing so.

If you agree to Type C test the valves associated with penetrations M-3 and M-44, please please update your proposed technical specifications under item 3.5(4)f entitled " Penetrations to be Tested".

If you believe that you need not Type C test the valves associated with penetrations M-3 and M-44, please provide detailed justification for not doing so.

We have put your proposed Appendix.J technical specifications in a held status until these items are resolved. We plan to issue a Supplemental SER based upon the resolution of these open items, and issue your proposed technical specifications as an amendment to your license at that time.

Please provide your response to these open items within 30 days from your receipt of this letter.

The information requested in this letter affects f ewar than 10 respondents; therefore GMB clearance is rot required under P.L.96-511.

Please contact your NRC Project Panager if you have any questions regarding this matter.

Sincerely, Original signed by Robert A. Clark Robert A. Clark, Chief <

Operating Reactors Dranch #3 l

Division of Licensing

Enclosures:

. DISTRIBUTION:

i As stated

/ Docket File ETourigny i

NRC PDR 0 ELD cc w/ enclosures:

Local PDR I&E See next page ORB #3 Rdg NSIC D. Eisenhut ACRS-10 J. Heltemes J. Pulsipher PMKreutzer-3 RAClark

... ORB #3:DL ORB #3:D OR IDL...

0 orrice >

.9

.f.d.. j.g,,....teV.t.7.et..

FJ.

.lep...W,..

aulson..

...YAtlar.k..... h.................

sua = <>

... 7/.f.3./.87...

....Z93/.68........Z/.9./.82....

..Z/4.?/.62......

l mn>

OFFICIAL RECORD COPY uso n.ini-an e

, Nac ronu ste oo-sci nacu oaa

v k

l l,

i Omaha Public Power District cc:

j Marilyn T. Shaw, Esq.

I LeBoeuf, Lamb, Leiby & MacRae 1333 New Hampshire Avenue, N.W.

Washington, D. C.

20036 Mr. Jack Jensen Chairman, Washington County Board of Supervisors Blair, Nebraska 68023 U.S. Environmental Protection Agency Region VII ATTN: Regional Radiation.

Representative 324 East lith Street Kansas City, Missouri 64106 Mr. Frank Gibson W. Dale Clark Library 215 South 15th Street Omaha, Nebraska 68102 Alan H. Kirshen, Esq.

Fe11 man, Ramsey & Kirshen 1166 Woodmen Tower Omaha, Nebraska 68102 Mr. Larry Yandel.1 U.S.N.R.C. Resident Inspector P. O. Box 309 Fort Calhoun, Nebraska 68023

~

Mr. Charles B. Brinkman Manager - Washington Nuclear Operations C-E Power Systems Combustion Engineering, Inc.

4853 Cordell Avenue, Suite A-1 Bethesda, Maryland 20014

/

Regional Administrator Nuclear Regulatory Commission, Region IV Office of Executive-Director for Ophrations 611 Ryan Plaza Drive Suite 1000 Arlington, Texas 76011 i

..