Text
_ - - _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
OPE?0 TING DATA LEPORT =Jk T
^
39020928101
~
DOCMET NO. 50 - 352
- u_
5 33 j[j _
DATE JULY 1.1990 hh LOMPLETED BY PHILADELPHIA ELECTRIC COMPANY 3>$
MARL MECK C5 C)
REPORTS SUPERVISOR O --
EUSINESS UNIT h{h-(
LIMERICK GENEPATING STATION TELEPHONE (215) 327-1200 EXTENSION 3320-04 M C)
ODERATING-STATUS Oo 1 UNIT NAME: LIMERICK UNIT 1 NOTES: THERE WERE TWO LOAD REDUCTIONS l qgff hhjh
- 2. REPORTING PERIOD:
JUNE. 1990 GREATER THAN 20% SEFORE THE
- 3. LICENSED THERMAL POWER (MwT):
3293 UNIT WAS SHUTDOWN. THERE WAS 4 NAMEPLATE RATING (GROSS MWE):
1138
- SECOND SHUTDOWN AT THE END
- 5. DESIGN ELECTRICAL RATING (NET MWE):
1055 OF THE MONTH.
. )
- 6. MAXIMUM DEPENDABLE CAPACITY (GROSS MwE): 1092 7.
MAXIMUM DEPENDABLE CAPACITY (NET MWE):
1055 8.
IF CHANGES OCCUR IN CAPACITV RATINGS (ITEMS NUMBER 3 THROUGH 7) SINCE LAST REPORT GIVE REASONS:
- 9. POWER LEVEL TO WV'"
'ESTRICTED. IF ANY (NET MWE):
- 10. REASONS FOR RESTRICTIONS. IF ANY:
THIS MONTH VR-TO-DATE CUMULATIVE 11 HOURS'IN REPORTING PERIOD 720 4.343 38.663
- 12. NUMBER OF HOURS REACTOR WAS CRITICAL 232.9.
3.855.9-30.984.7.
- 13. REACTOR RESERVE SHUTDOWN HOURS 0.0 0.0 0.0
'14 HOURS GENERATOR ON-LINE' 148.0 3.771.0 30.442 6
- 15. UNIT RESERVE SHUTDOWN HOURS
- 0. 0 '
O.0 0.0-
-16.
GROSS THE9 MAL ENERGY GENERATER (MWH) 366.490 12.033.766 89.897,206
- 17. GROSS ELECTRICAL ENERGY GENERATED (MWH) 106.550 3.885.30 29.071.700
- 18. NET ELECTRICAL ENERGY GENERATED (MWH) 96.961 3.740.678 27.797.074 PAGE'1 GF.22
=
2.
OPECATING DQTO REPORT (CONTINUED)
' DOCKET NO. 50'- 353.'
'3902092810l DATE JULY 1.1990 THIS MONTH
'YR-TO-DATE CL9tULATIVE
- 19. UNIT SERVICE FACTOR 20.6 86.8
'78.7
- 20. UNIT AVAILABILITY FACTOR 20.6 86.8
-78.7
- 21. UNIT CAPACITY FACTOR (USING MDC NET) 12.3 81.6 68
- 22. UNIT CAPACITY FACTOR (USING DER NET) 12.8 81.6 68.1
- 23. UNIT FORCED OUTAGE RATE..
60.1d
-- S. 6d..
3.3d 24 SHUTDOWNS SCHEDULED OVER NEXT 6 MONTHS (TYPE, DATE..AND DURATION OF EACH): ~
~
REFUELING OUTAGE:' SEPTEMBER 07.1990: 75 DAYS
- 25. IF SHUTDOWN AT END OF REPORT PERIOD. ESTIMATED DATE OF STARTUP: 07/03/90
- 26. UNITS IN. TEST STATUS (PRIOR TO COMMERCIAL OPERATION):
FORECAST ACHIEVED _
INITIAL'CRITICALITV c12/19/04 12/22/84 INITIAL'ELECTRICITV MID APRIL 05 4/13/85 COMMERCIAL OPERATION 1ST OTR 86-2/01/86 eJe CORRECTION TO REFLECT MANAGEMENT DECISION TO SHUTDOWN TO CORRECT FROBLEM RATHER THAN OPERATE DERATED.
PAGE 2 OF. 2
~
-39020928101L UNIT SHUTDOWN 3 AND POWER GEDUCTIONS DOCKET NO.' 50"- 352 UNIT NAME LIME ICM UNIT 1 DATE JULY 1.1990 REPORT MONTH JUNE. 1990 rOMPLETED BV PHILADELPHIA ELECTRIC COMPANV.
KARL'MECM REPOnTS-SUPERVISOR BUSINESS UNIT ~
LIMERICK GENERATING STATION.
TELEPHONE (215).327-1200 EXTENSION 3320 TYPE DURATION] REASON SHUTTING DOWN EVENT CODE C00E ACTION TO NO.
DATE (1);
(HOURS){
(2)
REACTOR (3)
REPORT s.
(4)
(5)
PREVENT RECURRENCE
.I 17 900601 S
000.0 l
B 4
N/A ZZ ZZZZZZ LOAD WAS REDUCED 38% TO PERFORM CONTROL I
ROD PATTERH ADJUSTMENT AND MAIN TURBINE CONTROL VALVE TESTING.
18 900604 F.
000.0 A
i 4
N/A ZZ ZZZZZZ LOAD WAS REDUCED 82% DUE TO LOSS OF CONDENSER VACUUM. STEAM JET AIR EJECTOR l.
I RECIRC VALVE FAILED OPEN.
L I
i 19 900604 S
177.6 B l 2
N/A
} ZZ ZZZZZZ SEVERAL EQUIPMENT DEFICIENCIES PROMPTED 1
MANAGEMENT DECISION TO SHUTDOWN FOR l
1 SHORT MAINTENANCE OUTAGE TO IMPROVE PERFORMANCE AND RELIABILITY FOR l
REMAINDER OF FUEL CVCLE.
I
'900612d 222.9(.
A 4
1-90-013 ZZ l ZZZZZZ UNDERRATED FUSES IN DC CIRCUITS AND F
20 I
- BROKEN MOTOR-GENERATOR SCOOP TUBE i
I j
l LINKAGE RESTRAINED STARTUP.
21 900623 Whg 5 171.4 A
2 N/A ZZ ZZZZZZ MAINSTEAM ISOLATION VALVE CLOSURE DUE TO LEAMING AIR SOLENIOD FITTING. ALSO A CONDENSATE FILTER DEMINERALIZER INLET l
ISOLATION VALVE LEAKAGE PROMOTED (1)
(2)
(3)
'(4)
F - FORCED REASON METHOD EXHIBIT G - INSTRUCTIONS S - SCHEDULED.
A-EQUIPMENT FAILURE (EXPLAIN) 1 - MANUAL FOR PREPARATION OF DATA B - MAINTENANCE OR TEST-2 - MANUAL SCRAM.
ENTRY SHEETS FOR LICENSEE C - REFUELING 3 - AUTOMATIC SCRAM.
EVENT REPORT (LER)
D - REGULATORY RESTRICTION 4 - OTHER (EXPLAIN)
FILE (NUREG-0161)
E - OPERATOR TRAINING + LICENSE EXAMINATION F - ADMINISTRATIVE (5)
G - OPERATIONAL ERROR'(EXPLAIN) 44 - UTHER(EKPLAIN)
. EXHIBIT I - SAME SOURCE
[ CORRECTION TO REFLECT MMMIEMENT DECISION TO SMUTDOM TO CORRECT PROBLEM MTHER TMN OPERATE DEMTED. ALSO CORRECTS DATE AND HOURS FOR ACTUAL FORCED OUTAGE HOURS.
=
. - ~.
, ~.
_39020928!;01' 2 NIT SHUTDOWN 3 CDD POWEN CEDUCTION3 DOCKET..NO.' 50 - 352 UNIT NAME LINEDICK UNIT ~1 DATE JULY 1.1990 REPORT MONTH JUNE. 1990 COMPLETED'BY PHILADELPHIA ELECTRIC COMPANV, KARL MECK REPORTS SUPERVISOR BUSINESS UNIT LIMERICK GENERATING STATION TELEPHONE (215) 327-1200 EXTENSION 3320-METHOD OF LICENSEE l SYSTEM COMPONENT
'CAUSE AND CORRECTIVE TYPE DURATION REASON SHUTTING DOWN EVENT l CODE.
CODE ACTION TO NO.
DATE (1);: (HOURS)
(2)
REACTOR (3)
REPORT
- 1 (4)
(5) l PREVENT RECURRENCE MANAGEMENT DECISION'TO SHUTDOWN.
S71.9 1
l (1)
(2)
(3)
(4)'
F - FORCED REASON METHOD EXHIBIT G - INSTRUCTIONS S'-
SCHEDULED A - EOUIPMENT FAILURE (EXPLAIN) 1 - MANUAL FOR PREPARATION OF DATA-B - MAINTENANCE OR TEST 2 - MANUAL SCRAM.
ENTRY SHEETS FOR LICENSEE C - REFUELING AUTOMATIC SCRAM.
EVENT REPORT (LER)-
D - REGULATORY RESTRICTION 4 - OTHER (EXPLAIN).
FILE (NUREG-0161)
E - OPERATOR TRAINING + LICENSE EXAMINATION F - ADMINISTRATIVE (5)
G - OPERATIONAL ERROR (EXPLAIN)
H - OTHER(EXPLAIN)
EXHIBIT I - SAME SOURCE
.m
UNIT SHUTDOWNS AND POWER REDUCTIONS DOCKET NO. 50 - 353
]
UNIT NAME LINE :ICK UNIT 2 DATE JULY 1.1990 REPORT MONTH JUNE. 1990 COMPLETED BY PHILADELPHIA ELECTRIC COMPANY KARL MECK REPORTS SUPERVISOR-BUSINESS UNIT LINERICK GENERATIhG STATION
' TELEPHONE (215) 327-1200 EXTENSION 3320 METHOD OF I LICENSEE
. SYSTEM COMPOMENT1 CAUSE AND CORRECTIVE TYPE DURATION REASON SHUTTING DOWN!
EVENT CODE CODE ACTION TO' NO.
DATE (1)L (HOURS)l (2)'
REACTOR (3).I REPORT a (4)
(5)
PREVENT RECURRENCE I
I I
1.
11 900604 F
000.0 A
4.
N/A ZZ ZZZZZZ
' LOAD WAS REDUCED 54% DUE TO AN ELECTRO-HYDRAULIC CONTROL SYSTEM LEAK.
I 12 900613 S
000.0 F
I 4
N/A ZZ ZZZZZZ LOAD WAS REDUCED BRIEFLV 20% TO PERFORM CONTROL ROD PATTERN ADJUSTMENT.
I I
13 l 900621 F
000.0 A
I 4
N/A e ZZ l ZZZZZZ l LOAD WAS REDUCED 76% DUE TO A CONTENSATE l
l l
l FILTER DEMINERALIZER (CFD) HEAD LEAK.
N/A
.ZZ ZZZZZZ CFD HEAD LEAK PROMPTED MANAGEMENT j (
14 900621 F
O24.0 A
2
'l DECISION TO SHUTDOWN FOR REPAIR.
15 900622 S
200.3 8
4 N/A ZZ ZZZZZZ MAINTENANCE ON THE REACTOR WATER CLEANUP l TO FEEDWATER CHECM VALVE EXTENDED THE l OUTAGE.
l-
-l l
l 224.3 l
1 (1)
(2)
(3)
(4)
F - FORCED REASON METHOD EXHIBIT G-INSTRUCTIONS S - SCHEDULED A - EQUIPMENT FAILURE (EXPLAIN) 1 - MANUAL FOR PREPARATION OF DATA B - MAINTENANCE OR TEST 2 - MANUAL SCRAM.'
ENTRV SHEETS FOR LICENSEE C - REFUELING 3
AUTOMATIC SCRAM.
EVENT REPORT'(LER)
D - REGULATORV RESTRICTION 4 - OTHER (EXPLAIN)
FILE (NUREG-0161)
E - OPERATOR TRAINING + LICENSE EXAMINATION F - ADMINISTRATIVE (5)'
G - OPERATIONAL ERROR (EXPLAIN)
H - OTHER(EXPLAIN)
EXH2ti" I - SAME SOURCE CORRECTION TO IDENTIFY SHUTDOWN METHOD.
.