- to GNRO-93/00118 Page 1 of 2 i

PROPOSED CHANGE TO THE OPERATING LICENSE SURVElLLANCE REQUIREMENT 4.4.1.2.2, JET PUMP AP MEASUREMENT i

BELOW 25% POWER (GGNS PCOL 93/12) i i

l ph9290308930923 7}

ADDCK 05000426. {#

p PDR g

a REACTOR COOLANT SYSTEM to GNRO-93/00118 Page 2 of 2 JET PUMP 5 LIMITING CONDITION FOR OPERATION 3.4.1.2 All jet pumps shall be OPERABLE.

APPLICABILITY:

OPERATIONAL CONDITIONS 1 and 2.

ACTION:

I With one or more jet pumps inoperable, be in at least HOT SHUTDOWN within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.

i I

l SURVEILLANCE REQUIREMENTS 4.4.1.2.1 Each of the above required jet pumps in an operating loop shall be demonstrated OPERABLE with THERMAL POWER in excess of 25% of RATED THERMAL POWER and at least once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> by detemining recirculation loop flow, total core flow and diffuser-to-lower plenum differential pressure for each jet pump and verifying that no two of the following conditions occur:

I The indicated recirculation loop flow differs by more than 10% from a.

the established flow control valve position-loop flow characteristics.

b.

The indicated total core flow differs by more than 10% from the established total core flow value derived from recirculation loop flow measurements.

c.

The indicated diffuser-to-lower plenum differential pressure of any individual jet pump differs from established piatterns by more than 10%.

=-

~ - -.

4.4.1.2.2 The provisions of Specification 4.0.4 are not applicable provided the diffuser-to-lower plenum differential pressures of the individual jet pumps are determined to be within 50%* of the loop average within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> after entering OPERATIONAL CONDITION 2 and at least once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> thereafter.

pdd

-D 's=:

" Lc pro v;cisM ob S 'O AI** Y' 'Y "' **S "ffldfuIAI' f'** d'0 5 '

T P

de< e,sorveutvee is fe'"* d wi Ak 24 hou's resdoe owc' e

t veeeds z5% cm il hours dit' Oe

  • ssocI*ded tecirculdin /oef p ope e-

" Initial value.

Final value to be determined during startup test program.

Any required changes to the value shall be submitted to the Commission within 90 days of test completion.

u s

GRAND GULF-UNIT 1 3/4 4-2 Amendment No. Mr, _

l r

(-

, '. to GNRO-93/00118 I

Page 1 of 2 l

l l

PROPOSED TECHNICAL SPECIFICATIONS PAGES l

SURVEILLANCE REQUIREMENT 4.4.1.2.2, JET PUMP AP MEASUREMENT BELOW 25% POWER 1

(Information only)

\\

l I

P i

l l

r i

f i

r f

8

, to GNRO-93/00118 Page 2 of 2 REACTOR COOLANT SYSTEM JET PUMPS LIMITING CONDITION FOR OPERATION i

3.4.1.2 All jet pumps shall be OPERABLE.

APPLICABILITY: OPERATIONAL CONDITIONS 1 and 2.

ACTION:

With one or more jet pumps inoperable, be in at least HOT SHUTDOWN within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.

SURVEILLANCE REQUIREMENTS r

4.4.1.2.1 Each of the above required jet pumps in an operating loop shall be demonstrated OPERABLE with THERMAL POWER in excess of 25% of RATED THERMAL POWER and at least once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> by determining recirculation loop flow, total core flow and diffuser-to-lower plenum differential pressure for each jet pump and verifying that no two of the following conditions occur:

a.

The indicated recirculation loop flow differs by more than 10% from the established flow control valve position-loop flow characteristics.

b.

The indicated total core flow differs by more than 10% from the established total core flow value derived from recirculation loop flow measurements.

{

c.

The indicated diffuser-to-lower plenum differential pressure of any individual jet pump differs from established patterns by more than 10%.

The provisions of Specification 4.0.4 are not applicable provided the above l

surveillance is performed within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> after reactor power exceeds 25% or 4 l

hours after the associated recirculation loop is in operation.

l l

t GRAND GULF-UNIT 1 3/4 4-2 Amendment No. 16, i