ML20055H921
| ML20055H921 | |
| Person / Time | |
|---|---|
| Site: | Oyster Creek |
| Issue date: | 07/24/1990 |
| From: | GENERAL PUBLIC UTILITIES CORP. |
| To: | |
| Shared Package | |
| ML20055H901 | List: |
| References | |
| NUDOCS 9007310137 | |
| Download: ML20055H921 (3) | |
Text
9 b, n
.( [t s ; n;.
g[
V-
~!
+x
+
v w
i
.' L. ' M c.
. Th3 cpecific' gecvity, ' fer c ch coll, 10 ' gr:ct:r th:n '
.or equal;to 1.'190 whenLeorrectedito 77'F..The 1
electrolyte temperature of.every fifth cell:
j (Diesel; every fourth cell) sha.11 be recorded'for-j surveillance review.
- )
1 3.
At least.once per 12 months, the diesel generator l, 1
battery capacity shall be. demonstrated to be ableitoi il supply the design duty. loads'(diesel start) during a
,J
[
battery service test.
y J
[
4.
At least once per 24 months (during shutdown, the-d W
ifo11owing tests will be' performed to verify battery e(
,L capacity.
m, I
,.. <_[<
a..
Battery capacity.shall-.be demonstrated.to Li
.n n
be at least'80% of the manufacturers'
'i
[
rating when subjected to a battery-1 capacity, discharge = test to be considered:
- lz o
f operable..
R O
l' b.
Any battery which is demonstrated to have less than 85% of manufacturers ratingsL during a capacity discharge test _shallbe,
[
replaced during the subsequent refueling-i,,-
outage.,
~~
j j
- 's ;
c.
. Station battery capacity shall be, 5
mt demonstrated to be able to supply the design duty. cycle' loads-during a battery m
,7 service test.
<,q
~'
d.
Battery low = voltage annunciatorsfare j
verifled.to pick-up at--115 volts-1:1. volt?
L!
and:to reset at 125 volts't 1: volt-d y,
(Diesel; 112 volta i 1 volt)..
"I
&'i Basis:
The' biweekly tests of the diesel-generators are primarily~to check y"
' for failures and deterioration:in the system since'last use..The E
- manufacturer has recommended the-two week test interval, based on-i experience with many of their engines. One factor in. determining 4
1 this test interval (besides checking whether or.not the engine l-I starts and runs).is that the lubricating oil should be circulated =
through the engine approximately'every two weeks. The diesels
,j (D
. should be loaded to at least-20% of rated power until engine and l
m
[J>
~ generator temperatures have stabilized (about one. hour). The 1
W s
minimum 20%' load will prevent soot formation its the cylinders and 6h injection nozzles. Operation up.to-an equilibrium' temperature 4
- ensures that there is no over-heat problem., The tests also provide an engine and generator operating history to be compared with' subsequent engine-generator test data to identify and correct any 1
g.
mechanical or electrical deficiency before it can result in a system failure.
j OYSTER CREEK 4.7-2 Amendment No.: 15,55,60 i
i o007310137 900724 ADOCK0500g PDR At d
P i
i '
i
s g - -
~ -
i, ; :sf l
?
_1y
,1 Ji.,
e
+
lpt
-l S T:..
.h.4 b
('
f I
~ Uj,
d:
t!
Theltest during refueling outages is more comprehensive,.
I iil f i L
~ including procedures thatiare most offactively conducted at that-
+-
! time.-~These-include' automatic actuation and functional capability' tests,4to verify that the_ generators can start'and' assume 1oad in-less.than 20 seconds and testing of~the diesel
~
.i generator load sequence timers which provide protection from'a F(,
possible diesel generator' overload during LOCA conditions.-
Thorough-inspections will detect any signs of. wear long before failure.
i n
h,'
LThe manufacturer's instructions for_ battery care and, maintenance:
j I
, with regard to the floating charge, the= equalizing ~ charge,-_and y
U
-the addition of water will be'followed.
In addition, written-4
~ records will belmaintained-of the battery performance.. station /
batteries w'.11 deteriorate with time, but precipitous. failure is=
j Q
unlikely. The: attation'aurveillance procedures' follow'the recommei*ed' maintenance and-testing practices of IEEE STD. 450.
which have demonstrated, through experience,. tho' ability to provide positive indications of cell deterioration tendencies long before such tendencies cause cell irregularity or improper-9 d
1 cell performance.'
s The battery service test is a special capacity test to
, demonstrate th's capability'of the battery to meet the system design. requirements. The Oyster Creek design duty cycle loads lare determined by a LOC 7 subsequent to a loss of AC power. ' Thel 1 battery performance test is a, capacity test on the. battery to
[
' check it:against the manufacturer's specified capacity and.is used to determine when the battery has arrived at.the end of its' I1ife.
l A
e
).
,w-
'l 9
.IEEE Standard 450-1975: recommends battery-performance testing g
once.per fiveLyears.
IEEE Standard :308-1974 recommendu. battery 3
E-Performance testing'once per three_ years.=lThe_ Oyster-Creek "t
N
, Technical 1 Specifications-re_ quire a periortance test ence per two 0
years.
Both IEEE. Standards recommend decrsasing.the, L>
^
' surveillance interval to annually when battery service life.
- p l
exceeds 854.
i-t The diesel generator batteries are challenged every two weeks to Li J
perform the 20% load test. This effectively performs.an
.uninstrumented battery service test.- The: biweekly! diesel start, when combined with the1 annual _ battery service test, provides'an-
-l extensive amount of data on battery performance-characteristics.
This test-data negates the nased'to-lower the e
battery performance test interval from biennially to annually.
/
l o.
LI The station batteries are required for plant operation, and
-performing the station battery performance test requires the
,[
reactor to be in COLD SHUTDOWN. The guidance in IEEE 450-1975 would-result in 3 performance tests to reach 85% service life, jl,
- OYSTER CREEK 4.7.3 AMENDMENT NO.'s 1
('
ji; V lh%
l:
lb.
i l
} '-
1 e
MX ' (.
followed by 3 performanes tecto'to comploto bottory lifo..< The a
- guidance in IEEE'308-1974 would. result in 5 performance tests to
?
reach 85%: service-11fe;1followed by 3 performance tests, toc
' complete battery life. The Oyster Creek Technical ~
specifications l require 8 performance tests to reach 854 service L iil
+ 11fe, followed by 2 performance tests ta) complete battery-life.
~
'[f
-The requirement which would resultLin a reactor shutdown for the j.
' solo purpose of' performing a battery performance testiduring the f'
last 15% of-battery life cannot be' justified to11ncrease battery-.
is, "
Additionally, the increase'in battery performance' year period.
test performance.from 2 to 3 in'a 3-testing during the first 85%
Jt1 ffJ of battery service life would result in a, greater: level of g
battery, reliability by identifying, and causing to be corrected, small anomalies in cell performance thereby reducing battery-
'j.,
= failure probability.
e,y The requirement to' replace any battery'in the next refueling:
outage which: demonstrates less than 85% of manufacturers-
- j _
. capacity during-a capacity discharge test provides additional
-assurance of continued battery operability.
nj i
- l L (if l l,i I!l f[
.i-
+
i.
i 1
4
(;
l ;. ' 4,
1 OYSTER CREEK-4.7-4 AMENDMENT NO.:
c' 8 -. i eli
-. - -._..-__ _ _ -_