BRUNSWICK STEAM ELECTRIC PLANT, UNIT NO. 1 DPR-71 OPERATING LICENSE CONDITION Operating License Paragraph 2.C.(2)(b)
Effective July 1, 1982, and until July 8, 1982, Action statement "a" of Technical Specification 3.8.1.1 shall read as follows:
ACTION:
a.
With either one offsite circuit or one diesel generator of the above required A.C. electrical power sources inoperable, demonstrate the OPERABILITY of the remaining A.C. sources by performing Surveillance Requirements 4.8.1.1.1.a and 4.8.1.1.2.a.4 within two hours and at least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> thereafter; restore at least two offsite circuits and four diesel generators to OPERABLE status within 7 days or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SRUTDOWN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.
.1 BRUNSWICK STEAM ELECTRIC PLANT, UNIT NO. 2 DPR-62 OPERATING LICENSE CONDITION s
Operating License Paragraph 2.c. (2)(c)
Effective July 1, 1982, and until July 8, 1982, Action statement "a" of Technical Specification 3.8.1.1 shall read as follows:
1-l ACTION:
l a.
With either one offsite circuit or one diesel generator of the above required A.C. electrical power sources inoperable, demonstrate the OPERABILITY of the remaining A.C. sources by performing Surveillance l
Requirements 4.8.1.1.1.a and 4.8.1.1.2.a.4 within two hours and at least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> thereafter; restore at least two offsite circuits and four diesel generators to OPERABLE status within 7 days or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, l
8207090029 820703 l