i t~

i MAR 2 51982

.~

z G

9 S

RECEIVED Duke Power Company ATTN: Mr. W. O. Parker, Jr.

gp Vice President, Steam Production p} Q bj P.O. Box 2178 acam mess, ff Charlotte, llc 28242 nos Gentlemen:

g

Subject:

Confimation of Action - Docket No. 50-369 This letter refers to the telephone conversation on March 24, 1982, between Mr. J. Olshinski of this office and Mr. N. Rutherford of your office concerning corrective actions on your repnrtable occurrence report No. 82-15.

This pertains to the loss of both centrifugal charging pumps due to hydrogen entrainment when restoring the positive displacement (PD) pump to service at your ficGuire Unit 1 facility.

Based upon the natter discussed, it is our understanding that the following actions were or will be pronptly initiated:

1.

Remove the PD pump from service and isolate from the charging system, the hydrogen controlled suction dampener.

2.

Evaluate system design changes to prevent recurrence of this type of event.

3.

Following any design changes and prior to returning the PD pump and suction dampener system to service, submit your evaluation to this office for our review.

Please note that the reporting requirements identified above are not subject to Office of Management and Budget clearance as required by P. L.96-511.

If your understanding of our discussion is different from that stated above, please inform this office promptly.

Sincerely, 8

James P. O'Reilly Regional Administrator cc: it. D. ficIntosh, Plant itanager f

J. T. floore, Project flanager

/rk j

h N l0Y

$20423oy,c, A3k L

S 2*ESI GE!

i i

I Carolina Power and Light Company 2

1 bec: NRC Resident Inspector i

Document Management Branch State of North Carolina E. Jordan, Director DE&QA J. Lieberman, Director, Enforcement Staff R. Birkel, NRR J

i i

1 i

i 4

i RII RII RIl R

R1 RII I

Algnatonis:ejw FJa AR dt shinski FJLong CConer CAlderson 3/JS/82 3

/82 3/

2

/2f/82-3A 1782 3/tf/82 3/35/82

..-. -