  • IfEl}'@

Southern California Edison Company i^ ~

2-.W 2!;

S A N CSOF RE *. v C L C A M G F N E R A Y t 4 G S T A Y C *.

' it

,9.

P.O.MO4 12 8 Sase C L Fut N f t, C A LIF OH NI A dJ 6 72

[.

H8 RAY vettawoNE S f A f 8 0 ** te A *e A G E III i7 4 el 497 7 700 May 19, 1982 U.S. Nuclear Regulatory Corrinission Office of Inspection and Enforcement Region V 1450 f&iria Lane, Sulto 210 Walnut Creek, CA 94596-5368 Attention Mr. R.H. Engelken, Regional Acministrator

Dear Sir:

Subject:

Docket No. 50-206 initial Notification of LER 82-013 San Onofre Nuclear Generating Station, Unit 1 This submittal provides written confirmation of a 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> report made in accordance with Section 5.6.3.a.(1) of Appendix B to Provisional Operating License DPR-13.

On October 2, 1981, a liquid waste release was made from the Reheater Pit Sump as authorized by Liquid Radioactive Release Fermit No. 1096.

The release pathway was through the Oily Waste Sump and thus the liquid did not go through Radwaste Monitor Channel R-1218.

Sample analysis prior to the release identified the following isotopes:

Cs-134 at 3.74 X 10-7/' Ci /ml, Co-144 at t.49 X 10-6/( Ci/ml, Co-60 I.15 X 10-6

/Ci/ml,Cs-137at7.19X10-7/I Ci/mi and H-3 at 3.02 X 10-5 / Ci/ml.

A total of 10,000 gallons was released at a release rate of 150 gpm to the Circulating Water System.

The total activity calculated from this Cs-134, 1.41 X 10-5 Curies; C 5.67 X 10-5 Curles; Co-60, 4.38 X 10-5 Curles;Cs-137,2.72X10g-144, release por isotope is as follows:

Curies; and H-3, 1.14 X 10-3 Curies.

A total activity of 1.28 X 10-3 Curies was discharged under this release permit.

l The discharge of this radioactive waste to the Circulating Water System was maintained below the limits set by 10CFR20 and there was no impact on public health and safety.

App lix B Technical Speci f ication 5.6.3.a(1) requires a prompt report in 1,.at the Limiting Condition for Operation specified by Appendix A Technical Specification 4.5.0.(2) was violated by not taking mid and end point samples during the release in question.

The sampling omission was identifled by QuaIity Assurance audit; subsequent management review of the audit results identified the reporting omission.

g20 6 0 WM y

  • a g

R.ll. Engelkon May 19, 1982 Prompt notification was made by telephone to G.P. Yuhas in the Region V Offices at 1600 hours0.0185 days <br />0.444 hours <br />0.00265 weeks <br />6.088e-4 months <br /> on fray 18, 1982, immediately upon recognition of the reportability of the original incident.

A 14-day written report and Licensee Event Report flo.82-013 will be submltied by June 1, 1982.

Please contact me If you have any questions concerning this matter.

Sincerely,

[

/

cc:

U.S. Nuclear Regulatory Commission Office of Inspection and Enforcement U.S. Nuclear Regulatory Commission Office of Management information and Program Control institute of Nuclear Power Operaticns (INPO)

L. F. Miller (UNSRC Resident inspector - San Onofre Unit 1)