BEFORE THE UNITED STATES NUCLEAR REGULATORY COMMISSION In the Matter of

)

POWER AUTHORITY OF THE STATE OF NEW YORK

)

Docket No. 50-333 James A. FitzPatrick Nuclear Power Plant

)

APPLICATION MR AMENDEMENT TO OPERATING LICENSE Pursuant to Section 50.90 of the regulations of the Nuclear Regulatory Commission (URC), the Power Authority of the State of New York, as holder of Facility Operating License No. DPR-59, hereby applies for an Amendment of the Technical Specifications contained in Appendix A of this license.

'This proposed amendment to Appendix A of the operating Lice 1se deletes the closure time limit of the High Pressure Coolant Injection (HPCI) pump suction line isolation valves. This closure time limit is given in Table 3.7-1 of the Technical Specifications (page 202).

The proposed change deletes a time limit requirement which was included in the original Technical U

Specifications, but which is not necessary to assure the safe operation of the plant or the health and safety of the public. This change will conform the Technical Specifications to the Final Safety Analysis Report which states that a closure time requirement is not applicable to these valves. This change is l

also consistent with the existing Technical Specification Bases.

l The proposed change to the Technical Specifications is presented in l

Attac hnent I to this Application. The Safety Evaluation is included in Attachment II.

f/.IIC!!CLt'1 WEINSWI (Netary Pubh, SW ?

  • NN ' w POWER AUTHORITY OF THE Th -

STATE OF NEW YORK Qun'md.c ic a CCatY Cemtrssicn E4res t/ar:h 30,1983 State of New York County of New York Subscribed and sworn to before BY

/

d_

s me t his yd day of /7/th 1982 Q'

J.

P. Bay e Senior,s Vi e President 9203190321 020309 q

PDR ADOCK 05000333 g

Nuclear Generation P

PDR

/

Notgp Public /