j ULNRC-2824 i
PROPOSED TECHNICAL SPECIFICATION CHANGES Specifications 3/4.8.1.1 Markup.
3/4.8.1.2 Markup Specifications 3/4.8.1.1 Retyped-3/4.8.1.2 Retyped i
L
=
9307260089 930716 m
PDR ADOCK 050004g3 fi'sh P
.~
i 3/4.8 ELECTRICAL POWER SYSTEMS 3/4.8.1 A.C. SOURCES OPERATING LIMITING CONDITION FOR OPERATION
- 3. 8.1.1 As a minimum, the following A.C. electrical power sources shall be OPERABLE:
a.
Two physically independent circuits between the offsite transmission network and the Onsite Class 1E Distribution System, and b.
Two separate and independent diesel generators, each ith: 5m 7
1)
A separate day tank containing a minimum volume of-399 gallo s of fuel 2) separa Fuel Oil Storage System containing ? m Himum volume of g5,j0ggallnsoffuel,and 3)
A separat fuel transfer pump.
APPLICABILITY:
DES, 2, 3, and 4.
ACTION:
a.
One Offsite Circuit Inoperable:
l With an offsite circuit of the above required A.C. electrical power i
sources inoperable, demonstrate the OPERABILITY of the remaining offsite A.C. source by performing Specification 4.8.1.1.1 within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and'at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter. If either diesel generator of the above required A.C. electrical power sources has not been successfully tested within the past 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, demonstrate OPERABILITY by performing Specification 4.8.1.1.2a.4) ## for that dfesel generator within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />. Restore at least two offsite circuits and two diesel generators to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least HOT STANOBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />, b.
One Diesel Generator Inoperable:
l With one diesel generator of the above required A.C. electrical power sources inoperable, demonstrate the OPERABILITY of the offsite A.C. sources by performing Specification 4.8.1.1.1 within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter. Demonstrate the OPERABILITY of the remaining OPERABLE diesel generator by performing Specifica-tion 4.8.1.1.2a.4) within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />
- and restore the inoperable diesel generator to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the fol-lowing 30 hou,s. In addition, perform ACTION d.
- The automatic start and sequence loading of a diesel generator satisfies the testing requirements of Specification 4.8.1.1.2a.4) for this Action Statement.
- This test is required to be completed regardless of when the inoperable diesel generator is restored to OPERABLE status unless the diesel was declared inoper-able to do preplanned preventive maintenance, testing, or maint.enance to cor-rect a condition which,Jif left uncorrected, would not affect the OPERABILITY of the diesel generator.
CALLAWAY - UNIT 1 3/4 8-1 Amendment No. 21
_i_.
.~,
~.
REvig,0N I
ELECTRICAL POWER SYSTEMS A C. SOURCES SHUT 00WN i
7 LIMITING CON 0! TION FOR OPERATION 3.8.1.2 As a minimum, the following A.C. electrical power sources shall be OPERABLE:
a.
One circuit between the offsite transmission network and the Onsite Class IE Distribution System, and b.
One diesel generator with:
51()
1)
A da tank containing a minimum.vol of-190 ga ns of fuel, j
2)
A fuel st age system containing a min volume f 35,000 g lons of fuel, and 80,400
})
A fuel ansfer pump.
l APPLICABILITY: MODES 5 and 6.
\\
ACTION:
With less than the above minimum required A.C. electrical power sources
)'
OPERABLE, immediately suspend all operations involving CORE ALTERATIONS, positive reactivity changes, movement of irradiated fuel. or crane operation with loads over the spent fuel pool. In addition, Gher i.1 MODE 5 with the reactor coolant loops not filled, or in MODE 6 with the water level less than 23 feet above the reactor vessel flange, immediately initiate corrective action to restore the required sources to OPERABLE status as soon as possible.
SURVEILLANCE REQUIREMENTS 4.8.1.2 The above required A.C. electrical power sources shall be demonstrated OPERABLE by the performance of each of the requirements of Specifications l
4.8.1.1.1, 4.8.1.1.2 (except for Specification 4.8.1.1.2a.5)), and 4.8.1.1.3.
l v
J CALLAWAY - UNIT 1 3/4 6-8 i
s._.
r l
i e
3/4.8 ELECTRICAL POWER SYSTEMS 3/4.8.1 A.C. SOURCES OPERATING LIMITING CONDITION FOR OPERATION 3.8.1.1 As a minimum, the following A.C. electrical power sources shall be j
OPERABLE:
a.
Two physically independent circuits between the offsite transmission network and the Onsite Class 1E Distribution System, and i
l b.
Two separate and independent diesel generators, each with:
- 1) A separate day tank containing a minimum volume of S10 gallons of fuel,
- 2) A separate Fuel Oil Storage System containing a minimum volume of 80,400 gallons of fuel, and
- 3) A separate fuel transfer pump.
APPLICABILITY: MODES 1, 2,3, AND 4.
ACTION:
i a.
One Offsite Circuit inoperable:
With an offsite circuit of the above required A.C. electrical power sources inoperable, demonstrate the OPERABILITY of the remaining offsite A.C.
source by performing Specification 4.8.1.1.1 within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter. If either diesel generator of the above required A.C.
electrical power sources has not been successfully tested within the past 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, demonstrate OPERABILITY by performing Specification 4.8.1.1.2a.4)
- for that diesel generator within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />. Restore at least two offsite l
circuits and two diesel generators to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.
b.
One Diesel Generator Inoperable:
l With one diesel generator of the above required A.C. electrical power sources inoperable, demonstrate the OPERABILITY of the offsite A.C. sources by performing Specification 4.8.1.1.1 within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter. Demonstrate the OPERABILITY of the remaining OPERABLE l
diesel generator by performing Specification 4.8.1.1.2a.4) within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />' L
and restore the inoperable diesel generator to OPERABLE status within 72 l
hours or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />, in addition, perform ACTION d.
- The automatic start and sequence loading of a diesel generator satisfies the testing requirements of Specification 4.8.1.1.2a.4) for this Action Statement.
- This test is required to be completed regardless of when the inoperable diesel generator is restored to OPERABLE status unless the diesel was declared inoper-able to do preplanned preventive mainienance, testing, or maintenance to correct a condition which,if left uncorrected, would not affect the OPERABILITY of the diesel generator.
CALLAWAY - UNIT 1 3/4 8-1 Amendment No. 21 t
O ELECTRICAL POWER SYSTEMS A.C. SOURCES
- SHUTDOWN LIMITING CONDITION FOR OPERATION 3.8.1.2 As a minimum, the following A.C. electrical power sources shall be OPERABLE:
a.
One circuit between the offsite transmission network and the Onsite Class 1E Distribution System, and b.
One diesel generator with:
- 1) A day tank containing a minimum volume of 510 gallons of fuel,
- 2) A fuel storage system containing a minimum volume of 80,400 gallons of fuel, and
- 3) A fuel transfer pump.
APPLICABILITY: MODES 5 and 6.
ACTION:
With less than the above minimum required A.C. electrical power sources OPERABLE, immediately suspend all operations involving CORE ALTERATIONS, positive reactivity changes, movement of irradiated fuel, or crane operation with loads over the spent fuel pool. In addition, when in MODE 5 with the reactor coolant loops not filled, or in MODE 6 with the water level less than 23 feet above the a
reactor vessel flange, immediately initiate corrective action to restore the required sources to OPERABLE status as soon as possible.
SURVEILLANCE REQUIREMENTS
(
4.8.1.2 The above required A.C. electrical power sources shall be demonstrated l
OPERABLE by the performance of each of the requirements of Specifications l
4.8.1.1.1, 4.8.1.1.2 (except for Specification 4.8.1.1.2a.5)), and 4.8.1.1.3.
l CALLAWAY - UNIT 1 3/4 8-8
.