l ATTACHMENTI
?
r r
OYSTER CREEK NUCLEAR GENERATING STATION
't F
PROCEDURE 2000-RAP-3024.01 l
i I
d 9
i 9307020327'930628 I
P'.
PDR '
j PDR ADOCK.05000219.
i
f A N N U N C I A T 0 R C
L A Y 0 U T 5 HUT I 5 0 L R8 DN T 0 R U S / 0 R Y W E L L C 0 N D CCU CLS DW PRESS CAPGRMS 1
LOGlc TRAIN I TORUS BULK HI-HI RADIATION POST ACC SMPL 1
ACTUATED TEMP HI-MI RV 46 A/8 HIGH VLV OPEN AC DU PRESS CAPGRMS DW/ TORUS 02 2
LOGIC TRAIN 11 R8 CCW PUMP A TORUS BULK HI-HI TROUBLE ANALYZER ISOL 2
ACTUATED CCW ISOL TRIP TEMP HI RV 46 C/D VLYS BYPASS E
COND A COND 8 TORUS TEMP DW SUMP 3
FLOW HI FLOW HI PUMP 1 1 PUMP 8 MON STS DW PRESS N2 COMPR HI LEAK /
3 POSSIBLE RUPTURE POSSIBLE RUPTURE TRIP TRIP TROUBLE I HI/LO FAIL PWR Fall TORUS TEMP TORUS /DW 4
COND A VLYS COND 8 VLVS PUMP 1 2 PUMP C MON SYS TORUS /DW 1 VENT & PURGE DW SUMP 4
0FF NORM OFF NORM TRIP TRIP TROUBLE 11 VAC BRKR TN HI RAD ISOL VLV CLOSED 5
COND A COND 8
$ URGE TANK TORUS LEVEL TORUS h W 2 DW PURGE DW CNTRL AIR 5
DISABLED DISABLED LVL Hl/LO Hl/LO VAC BRtR OPN VLV OPEN FLOW HI E
6 SHELL A SHELL 8 CHEM ADD TORUS VAC DW VENT DW CNTRL AIR 6
LVL Hl/LO LYL Hl/LO TNK LYL LO HI VLV OPEN ISOLATED 7
ISOL VALVES RB/ TORUS TORUS /DW VENT / PURGE DW CNTRL AIR 7
SHELL TEMP OPEN VAC BRKR OPN 02 HI ISOL BYPASS ISOL BTPASS HI CCW/SD CLG/
8 COND AREA FUEL POOL SD MX PUMP DW H2/02 DW H2/02 8
TEMP HI TEMP HI RM TEMP HI SYS A SYS B DW TEMP HI E
E E TROUBLE E TROUBLE o
b c
d e
f g
h REFERENCE ANNUNCIATOR DWG: 3E-611-17-005, SH. 1 & 2 2000 RAP-3024.01 Rev. 48 Page 1 of 1
~,_
~
l Group Heading
~
ISOL COND C-1-a 1
i L0GIC TRAIN I
ACTUATED j
AND CAUSES:
SETPOINTS:
ACTUATING DEVICES:
Sustained high Rx pressure --
1051 psig 6K9 From: REISA or-1 16K110A or 6K57 or QE i
Lo-Lo Rx water level --
90" above TAF 6K10 From:
RE15C or
'16K110C or 6K57 or Reference Drawings V-14-34 manually opened 6K57 Energized JC 19529 Sh. 1
-l BR 3029 Sh. 1 & 2 CONFIRMATORY ACTIONS:
Verify high Rx pressure or Lo-Lo Rx water level (Panel SF/6F).
-l f
AUTOMATIC ACTIONS:
f IE Logic Train I and Logic Train II are actuated on High Reactor pressure or Low Low Reactor water level.
THEN valves V-14-34 and V-14-35 will open, and all five (5) Recire Pumps will trip.
f MANUAL CORRECTIVE ACTIONS:
t
~
Follow the actions of Procedure EMG-3200.01. RPV Control.
l j
l This alarm indicates that a parameter has exceeded or has the potential to exceed an Emergency Action Level (EAL).
Enter Procedure EPIP-OCP 01, l
" Classification of Emergency Conditions".
EAL - RPV Pressure or RPV Level Subject Procedure No.
1 Page 1 of 1
l NSSS 2000-RAP-3024.01 C-1-a l
-Alarm Response Procedures Revision No:
51 (21bbF/4)
1 Group Heading ISOL COND C-2-a 1
l 1
LOGIC TRAIN II i
ACTUATED j
ll1t.
CAUSES:
SETPOINTS:
ACTUATING DEVICES:
{
Sustained high Rx pressure --
1051 psig 6K11 From: RE15B or 16K110B or 6K58 or OB Lo-Lo Rx water level --
90" above TAF 6K12 From: REISD or 16K110D or 6K58 or..
Reference Drawings:
V-14-35 manually opened 6K58 Energized JC 19529 Sh. 1 l
BR 3029 Sh.~1 & 2 CONFIRMATORY ACTIONS:
.i Verify high Rx pressure or Lo-Lo Rx water level (Panel 5F/6F).
l t
AUTOMATIC ACTIONS:
1E Logic Train I and Logic Train II are actuated on High Reactor pressure or Low Low Reactor water level.
THEN valves V-14-34 and V-14-35 will open and all five (5) Recirc Pumps trip.
MANUAL CORRECTIVE ACTIONS:
g Follow actions of Procedure EMG-3200.01, RPV Control.
l k
1 9
This alarm indicates that a parameter has exceeded or has the potential to exceed I
an Emergency Action Level (EAL).
Enter Procedure EPIP-OC.01, l
7
" Classification of Emergency Conditions".
EAL - RPV Pressure or RPV Level i
Subject Procedure No.
Page 1 of 1 l
NSSS 2000-RAP-3024.01 C-2-a Alarm Response Procedures Revision No:
51 i
(2JbbP/b) l i
5 Group Heading ISOL COND C-3-a COND A
FL0W HI POSSIBLE RUPTURE t
CAUSES:
SETPOINTS:
ACTUATING DEVICES:
Sustained (35 seconds) High Steam Flow 15 psid 6KSA From: IB05A2 or IB11A2
- OR -
- QB -
Sustained (35 seconds) High Condensate 24" H O DP-6K3A From: IB05A1 2
Flow or IB11A1 Reference Drawings:
B&R 3029 i
GE 148F262 CONFIRMATORY ACTIONS:
Annunciator C-8-b COND AREA TEMP HI alarmed Increase in area temperatures at Panel 10R Closure of System A Isolation valves For an Isolation Condenser in the Standby Mode also l
Check for level changes on Panel 2F Check for smell temperature increases on TR IG02 on Panel 2F t
AUTOMATIC ACTIONS:
Closes Isolation Condenser System A Valves V-14-30, V-14-31, V-14-34 and V-14-36.
MANUAL CORRECTIVE ACTIONS:
.i IE Pipe break is verified
~
_l THEN
- Evacuate Reactor Building
}
- Place Control Switches for A ISO COND Isolation and Vent Valves to CLOSE position.
IE No pipe break is indicated j
THEN Return A ISO COND to Service Refer to OPS-3024.18 Isolation Condenser System - Diagnostic and Restoration
_1plions.
Subject Procedure No.
Page 1 of 1 NSSS 2000-RAP-3024.01 C-3-a I
Alarm Responss Procedures Revision No: 52 (2155P/7)
I
l i
Group Heading ISOL COND C-4-a l
i COND A
VLVS i
l OFF NORH
,1 l
l 1
CAUSES:
SETPOINTS:
ACTUATING DEVICES:
l Any of the four (4) isolation valves V-14-30 Not Fully Valve Position in the "A" Isolation Condenser System Open Switches l
not in the normal standby position.
v-14-31 Not Fully Open i
V-14-36 Not Fully Open V-14-34 Not Fully l
Closed Reference Drawings i
B&R 3019 GE 148F262 l
SW 14364.05-EC-01 l
i CONFIRMATORY ACTIONS:
I Verify valve positions on Panel IF/2F and 11F.
l l
AUTOHATIC ACTIONS:
NONE I
1 KANUAL CORRECTIVE ACTIONS:
I Return valves to the normal standby position as plant conditions allow.
I i
Subject Procedure No.
t Page 1 of 1 j
NSSS 2000-RAP-3024.01 C-4-a I
Alarm Response Procedures Revision No:
51
(?l55P/7) t a
. -t
,c Group Heading ISOL C0ND C-5-a.
1
)
)
i COND A
DISABLED I
t CAUS?S SETPOINTS:
ACTUATING DEVICES:
ssntrol switch for any of the four Control switch Valve Control Switch isolation valves in the A Isolation not in OPEN or Contacts for:
Condenser System not in the OPEN or AUTO AUTO position position.
i V-14-30 V-14-31 V-14-34 V-14-36 Reference Drawings:
B&R 3019 GE 148F262' l*
i SW 14364.05 EC-01 t
+
CONFIRMATORY ACTIONS Verify position of valve control switches at Panel 2F.
l' 5'
AUTOMATIC ACTIONS:
1 NONE l
1 M.h > 1 CORRECTIVE ACTIONS:
Return control switches to AUTO position as conditions require.
l f i
Subject Pro';edure No.
Page 1 of 1
NSSS 2000-RAP-3024.01 C-5-a Alarm Response Procedures Revision No:
51
( 2.155P/8 )
i
.y
.. ~.
a,
I 1
I Group Heading 5
ISOL COND C-6-a l
SHELL A
LVL HI / L0 t
CAUSES:
SETPOINTS:
ACTUATING DEVICES:
i High or low water level in Isolation
-High 7.7 ft.
LS 1GO3A Trip Unit (10R)
Condenser A.
Low 7.2 ft.
From LT IG06A i
Reference Drawings:
GE 148F912 Sheet'l GE J8F262 l-CONFIRMATORY ACTIONS:
i Verify level indication at Panel 1F/2F l:
AUTOMATIC ACTIONS:
i NONE
+
MANUAL CORRECTIVE ACTIONS:
i E4 4 trmine cause of High/ Low level.
Restore level in accordance with Procedure 307, Isolation Condenser System.'
l 3
l l
l Subject Procedure No.
j Page 1 of 1
~
NSSS 2000-RAP-3024.01 C-6-a
-1
. Alarm Response Procedures Revision No: 51 I
(2155P/9)-
1
i Group Heading i
ISOL C0ND
.C b' l
COND B
FLOW HI POSSIBLE RUPTURE CAUSES:
SETPOINTS:
ACTUATING DEVICES:
l Sustained (35-seconds) High Steam Flow 15 psid 6K4A From: IB05B1
)
flow ewitch - IB05, or IB11B1 j
-OR-
- OB -
- OR -
I Sustained (35 seconds) High Condensate 24" H O DP 6K6A From: IB05B2
+
2 Flow or IB11B2 Reference Drawings:
1 B&R 3029 GE 148F262 CONFIRMATORY ACTIONS:
f Annunicator C-8-b COND AREA TEMP HI alarmed j
Increase in area temperature at Panel 10R Closure of System B Isolation Valves
-3 For an Isolation Condenser in the Standby Mode Check for level changes on Panel 2F Check for shell temperature increases on TR It02 on Panel 2F
[
e AUTOMATIC ACTIONS:
Closes Isolation Condenser System B Valves V-14-32, V-14-33, V-14-35 and V-14-37.
1 I
MANUAL CORRECTIVE ACTIONS:
'~
If Pipe break is verified IHEH
- Evacuate Reactor Building
- Place Control Switches for B ISO COND Isolation and Vent Valves to CLOSE
'i position.
i if No pipe break is indicated THEN Return B ISO COND to Service Refer to OPS-3024.18 Isolation Condenser System - Diagnostic and Restoration Actions.
Subject Procedure No.
Page 1 of 1 NSSS 2000-RAP-3024.01 C - b l
i Alarm Response Procedures-Revision No:.El (zJddP/10)
.g 4,
4 t
Group Heading.
ISOL COND
'C b.
i i
COND B
VLVS OFF NORH e
f CAUSES:
SETPOINTS:
ACTUATING DEVICES:
.[
Any of the four (4) isolation valves V-14-32 Not Fully Valve position switches in the "B" Isolation Condenser System Open not in the normal standby position.
V-14-33 Not Fully Open V-14-37 Not' Fully open i
V-14-35 Not Fully closed l'
Reference Drawings:
f B&R.3019.
GE'_148F262 l-
[
SW 14364.05-EC-01 CONFIRMATORY ACTIONS:
l l
l Verify valve positions on Panel IF/2F and 11F.
1 P
l t
a
.t AUTOHATIC ACTIONS:
[
t
.i NONE
.r i
MANUAL CORRECTIVE ACTIONS:
i Return valves to normal standby positions as plant conditions permit.
6 i
9 6
1 Subject l
Procedure No.
- i Page l'
of 1 i
NSSS 2000-RAP-3024.01 C-4-b l
I Alarm Response 1
Procedures Revision No:
51 I
(2155P/11)
'E I
~-
,j i'
Gr'oup Heading ISOL COND C -'S - b l
l l
COND B
DISAB,ED CAUSES:
SETPOINTS:
ACTUATING DEVICES:
t control switch for... y or ti four Control switch Valve control Switch isolation valves in ' solation Condenser not in OPEN.
, Contacts for j
System B not in the OPEN or AUTO or AUTO V-14-32, V-14-33, i
V-14-35 and V-14-37 position.
l i
Reference Drawings:
.j B&R 3019 l
GE 148F262 SW 14364.05-EC-Ol' CONFIRMATORY ACTIONS:
]
Verify position of valve control switches at Panel 2F.
P AUTOHATIC ACTIONS:
NONE
~
MANUAL' CORRECTIVE ACTIONS:
Return control switches to. AUTO position as conditions require.
l l
I l
Subject Procedure No.
Page 1 of 3 l
NSSS 2OOO-RAP-3024.01 C-5-b-Alarm Response j
Procedures Revision No:
51 (2155P/12) i l
yN 3k $
f Gr'oup Heading I SOL COND C-6-b SHELL B
LVL HI /LO CAUSES:
SETPOINTS:
ACTUATING DEVICES:
High or low water level in Isolation High 7.7 ft.
LS IG03B Trip Unit (10R)
Condenser B.
Low 7.2 ft.
From LT IG06B Reference Drawings:
GE 148F912 Sheet 1 GE 148F262 l
CONFIRMATORY ACTIONS:
Check level indication at Panel 1F/2F.
AUTOMATIC ACTIONS:
NONE HANUAL CORRECTIVE ACTIONS:
- Determine cause of High/ Low level.
- Restore level in accordance with Procedure 307, Isolation Condenser System.
Subject Procedure No.
Page 1 of 1
NS SS 2OOO-RAP-3024.01 C-6-b Alarm Response Procedures Revision No: 51 l
(2155P/13)
t i
Group Heading ISOL C0ND C-7-b' i
I
<t t
f SHELL TEMP HI I
CAUSES:
SETPOINTS:
ACTUATING DEVICES:
High temperatures in shell side of 225' T.R.
IG02.
isolation condensers.
-?
+
Reference Drawings:
GE 148F965
[
CONFIRMATORY ACTIONS:
l Check temperature recorder IG02 Panel 1F/2F for location of high-temperature.
AUTOMATIC ACTIONS:
-t NONE
[
i v
MANUAL CORRECTIVE ACTIONS:
Check position of valves V-14-34 and V-14-35 for system initiation or leakage past valve.
Refer to OPS-3024.18 Isolation Condenser System - Diagnostic and Restoration Actions.
Subject Procedure No.
Page 1 of 1 NS SS 2OOO-RAP-3024.01 C-7-b i
i
. Alarm Response Procedures Revision No:
51
'l
'(2155P/14) 1
- fo:
-i
_i Grbup Heading ISOL COND C-8-b l
C-0 N D AREA TEMP HI I
CAUSESI' SETPOINTS:
ACTUATING DEVICES:
High temperature in the Isolation 160*F
'T.S.
IB06 A, B,
C, D Condenser Area indicating possible pipe
{
rupture.
l t
1 Reference Drawings:
GU-3E-611-17-005
_i t
)
CONFIRMATORY ACTIONS:
Check for system isolation at Panel IF/2F.
check local alarm indicator on' Panel 10R for affected grea.
Check radiation levels of isolation condenser area on panel 1R/2R.
t i
AUTOKATIC ACTIONS:
NONE 1
i MANUAL CORRECTIVE ACTIONS:
Enter EMG-3200.11, Secondary Containment Control.
l II a leak or pipe break exists within the Isolation condenser System THEN
- Evacuate the Reactor Building
- Isolate the affected system by placing the control switches for the Isolation and Vent Valves to the CLOSE position.
Subject Procedure No.
Page 1-of 1
NSSS 2000-RAP-3024.01 C-8-b Alarm Response Procedures Revision No:
51 i
i i
.{2155P/15)_
i
I b
w ANNUNCIATOR 10F LAYOUT NSSS RADIATION M0 NIT 0RS O F F,
PR0 CESS A R E A G A S
~
S Y S T E M OFF STACK
! SOL RX WTR TUR8 119 FT GA5 EFFLUENi C0ND 8LDG BLDG ELEV 1
0FF GAS OFF GAS OFF GAS STACK EFFLUENT A VENT YENT ESW AREA MON CRii MON 1
ISOL ACT I PRESS HI Hl-MI Hi-HI HI HI A/B Hi HI C5 HI
- AND 2
OFF GAS OFF GAS OFF GAS STACK EFFLUENT B YE*li ESW FUEL POOL FLTR NORTH WALL 2
43 ISOL ACT I!
TEMP HI Hi HI HI C/D HI AREA HI C10 HI E
E STACK /;URS BLOG SVC WTR NORTH WALL 3
SJAE INLET OFF GAS DISCH RAGEMS STS RBCCW Hl/
CU SYS AREA C9 HI 3
VLV CLOSED VLV OPIN TROUBLE RAD HI TROU8tE HI VENT TRIP E
E CPER FLOOR 4
ISOL SIG OFF GAS OFF GAS SAMPLE VLV POS/SYS STPI OFF GAS /MN STM LIQUID AREA /YENT/
HI RANGE RAD.
89 HI 4
N3 V-24-29/30 STK 5'*DL F LU. LO/
BYPASS FliR A P HI FLOW LO OFF NRM / MON DNSC DNSCL/INOP DOWNSCALE EFFL DNSCL MON. ABNORM.
VENT TRIP E
a b
c d
e f
g h
k m
REFERENCE ANNUNCIATOR DWG:
3E-611-17-003 2000-RAP-3024.01 (2163P/2)
Rev. 43 Page 1 of 1
o e
Group Heading RADIATION MONITORS PROCESS lOF e ISOL C0ND A
VENT HI CAUSES:
SETPOINTS:
ACTUATING DEVICES:
Upscale trip of Isolation Condenser A 30 mr/hr RN07A - 3 Vent radiation monitor.
RN07A --4 Reference Drawings:
GE 706E841
[
CONFIRMATORY ACTIONS:
i Verify the high radiation level on redundant indicators (Panel 2R).
AUTOMATIC ACTIONS:
-NONE z
MANUAL CORRECTIVE ACTIONS:
NOTE: Because of the closeness of the radiation monitor,to the Isolation condensers, which contain reactor water, this alarm is not positive indication of a leak.
check the isolation condenser temperature and level for indications of, tube leakage.
Sample the shell of the isolation condenser for activity as soon as practicable.
Isolate the affected isolation condenser as necessary. If the isolation condenser is isolated, place all "A" isolation condenser isolation valve control switches to the CLOSE position prior to depressing the ISOL COND RESET button (4F).
Perform actions defined in Procedure OPS-3024.18, Isolation. condenser.
This alarm indicates that a parameter has exceeded or has the potential to exceed an Emergency Action Level (EAL). Enter Procedure IMP-1300.01, Classification of Emergency conditions. EAL - Radiolocical Effluent.
FoTE: offsite radiological release rates above that resulting in an ALERT Emergency Action Level being decleared, require entry into procedure EMG-3200.12, Radioactivity Release Control.
Subject Procedure No.
Page 1 of 1 NSSS 2000-RAP-3024.01 10F e-Alarm Response Procedures Revision No:
52 i
(3163P2/13)
b,
e Group Heading RADIATION MONITORS PROCESS 10F e ISOL C0ND B
VENT HI
'CAUSES:
SETPOINTS:
ACTUATING DEVICES:
Upscale trip of Isolation Condenser B 30 mr/hr RN07A - 5 Vent radiation monitor.
RN07A - 6
' Reference Drawings
- GE 706E841 CONFIRMATORY ACTIONS:
Verify the high radiation level on redundant indicators (Panel 2R).
AUTOMATIC ACTIONS:
NONE MANUAL CORRECTIVE ACTIONS:
NOTE: Because of the closeness of the radiation monitor to the Isolation Condensers, wr.ich contain reactor water, this alarm is not positive indication of a leak.
Check the isolation condenser temperature and level for indications of' tube leakage'.
Sample the shell of the isolation condenser for activity as socn as practicable.
Inolate the affected isolation condenser as necessary.
If the isolation condenser is isolated, place all "B" isolation condenser isolation valve control switches to the CLOSE position prior to depressing the ISOL COND RESET button (4F).
Perform actions defined in Procedure OPS-3024.18, Isolation. Condenser.
This alarm indicates that a parameter has exceeded or has the potential to exceed an Emergency Action Level (EAL).
Enter Procedure-IMP-1300.01, Classification of Emergency Conditions.
EAL - Radioloaical Effluent.
WOTE: Offsite radiological release rates above that resulting in an ALERT Emergency Action Level being decleared, require entry into procedure EMG-3200.12, Radioactivity Release Control.
Subject Procedure No.
Page 1 of 1 NSSS 2OOO-RAP-3024.01 IOP - 2.- e Alarm Response Procedures Revision No:
52 (2163P2/14)
.1
a a
a
.A s
o i
ATTACHMENT II i
i t
3 9
i 8
OYSTER CREEK l
I NUCLEAR GENERATING STATION ia 1-o t
'i t
l
{
CONTROL ROOM LAYOUT DIAGRAM 3
i b
h i
)
asLd e
k e
i FRONT o
e e
e ejeje a
y
/f, l
L
\\ej$
e e
e eje e
g,.
/
/
9 4
e
=
l i
.h
'=
com m en k
A60M FRONT T
FRONT 15 1
e e l e le 1
..s.
- E
~
,