8 [ykB E80Q*'o,,
UNITED STATES
<?
NUCLEAR REGULATORY COMMISSION e
5 t
WASHINGTON D. C. 20666
?,
8 SYSTEM ENERGY RESOURCES, INC., et al.
. DOCKET NO. 50-416 GRAND GULF NUCLEAR STATION. UNIT 1 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 68-Li cen se No.. NPF-29 1.
The Nuclear Regulatory Commission:(the Commission)~ has found that A.
The application for_ amendment by; System Energy Resources, Inc.,
I (the licensee), dated February 9,L 1990,! complies with the standards d
and requirements of the' Atomic Energy Act of 1954, as amended (the j
Act), and the Commission's rules and regulations set forth in 10 CFR 4
Chapter I; B.
The facility will operate in conformity with.the application, the provisions of the Act, and the rules and regulations of the Commi ssion; 1
C.
There is reasonable assurance (i) that the activities authorized by-this anendment can be-conducted without endangering -the~ health and safety:of the public,-and (ii) that-such activities _will be conducted in compliance with the Commission's regulations; D.
The issuance of this amendnent will not be inimical to the common defense and security or to the healthLand safety of-the-public; and E.
The issuance of this anendment is in accordance with 10 CFR Part 51 o
of the Commission's regulations and all' applicable requirements have j
been satisfied.
i 1
.I i -
P l
l
- 2~.
2.
Accordingly, the license is amended by changes to the-Technical Specifications, as indicated in the attachment.to this license amendment; and paragraph 2.C.(2) of Facility Operating License No. NPF.29 is hereby amended to read as follows:
(2) Technical Specifications-The Technical Specifications contained in Appendix A and the.
Environmental' Protection Plan contained in Appendix B, as revised through Amendment No.- 68, are hereby ' incorporated into this W
license.
System Energy Resources, Inc. shall operate the facility in accordance with the Technical Specifications and-the Environmental Protection Plan.
3.
This license amendment is effective as of.its date of issuance and shall be implemented by June 1,.1991.
FOR THE NUCLEAR REGULATORY _ COMMISSION Original Signed By:
Elinor_.G. Adens'am Director Project Directorate II.1--
Division of Reactor Projects - I/II Office of Nuclear Reactor. Regulation-
Attachment:
Changes to the Technical-Specifications Date of Issuance: May 9, 1990
- SEE PREVIOUS CONCURRENCES OFC :LA: i 5 R:PM:P DRPR:*SPLB: DEST
- D:
1:D PR :
NAME : P
- LK r:sw:CMcCracken :LDewey
- E am
~ :
DATE:5/9/90
- 5/}/90
- 5/12/90
- 4/30/90
- 5/@/90 OFFICIAL RECORD COPY-
l l
0 f.-
ATTACHMENT TO LICENSE AMENDMENT'NO. 68 FACILITY OPERATING' LICENSE NO. NPF-29
?
DOCKET NO. 50-416 e
Replace the following pages of.the Appendix "A" Technical Specifications with-the attached pages. :The revised pages are identified by Amendment number and contain vertical-lines ~ indicating the area of change.
Remove-Insert 3/4 3 3/4 3-81 3/4 3-86 3/4 3-86 i
l' k
i
. 4 v
I-l
_ _. ~
9 s-l-
TABLE 3.3.7.9-1 FIRE DETECTION INSTRUMENTATION MINIMUM INSTRUMENTS OPERABLE
- ll)
'MOKE(1)
INSTRUMENT LOCATION HEAT FLAME S
.(X/Y).
(X/Y)
(X/Y)
-a.
CONTAINMENT BUILDING #
- 1.. Return Duct Mounted Detectors
-3/0-ROOM ELEV' ROOM NAME-b.
CONTROL _B_UILDING i
1.
Zone 1-3 12/0 00103-93' H. P. Checkout-l.
~ 00109 93' Decontamination Area 00115' 93' Corridor 0C116 93' Hot Machine Shop' 00117 93' Corridor 00128 93' Hot Water Heater Rm.
2.
Zone 1-4 12/0 0C201-111' Stairwell 0C202 111' Div. I Swgr. Rm.
0/13(CO )
t 2
0C207 111' Div. I Battery Rm.
(X/Y):
X - is n' umber.of Function A.(early warning fire detection and' notification only) instruments.
Y - is number of Function B (actuation of fire suppression systems and early warning and notification) instruments.
l The fire detection instruments located within the primary containment are L
not required to_be OPERABLE during the performance of Type A Containment
-Leakage Rate Tests.
(1) Smoke and flame detectors provide only early warning capability with the exception of:
(a) Zone 1-27 detectors trip closed the door between the OC208/00208A Remote Shutdown panel rooms.
(b) Containment building return duct mounted detectors trip the containment cooler fans.
[
(c) Zone 1-11 and 1-13 detectors initiate the control building purge fan system.
(d) Control Room HVAC Intake Plenum Detectors trip the' control room A/C units unless a control room emergency filtration system isolation mode automatic actuation signal is present.
GRAND GULF-UNIT 1 3/4 3-81 Amendment No. f2, 68
-I 1..
~
I r
TABLE 3.3.7.9-1 (Continued)
-FIRE DETECTION INSTRUMENTATION-MINIMUM INSTRUMENTS OPERABLE
- ROOM-ELEV ROOM NAME HEAT
' FLAME (1)
SMOKE (1)
(X/Y)-
(X/Y)
(X/Y) 7.
Zone 2-8 27/0
+
1A4011 166
Northeast Corridor 1A402-166' Steam Tunnel Roof 1A403
-166' Southeast Corridor 1A404 166
Unassigned Area 1A405 166' Containment-Vent.
' Equip.1 Room
- 1A406
'166' Containment Exhaust Filter Rm.
~1A407-166' MCC Area
_ 0/2(C0 )
2 1A410 166 -MCC-Area 0/2(CO )
2
-1A417
'166'
-North Corridor (Partial) 11A420:
166' South Corridor ~(Partial)'
1A424 166' Set Down Area (Partial)
-4
- 8.. Zone 2-9 12/0 1A519 185' Storage Area-1A519A 185' Snubber Test Room-1A519B-185' Snubber-Test Control Room 1A524 195' Platform 1A527 185' Load' Center Area
-1A529 185' FPC & CU'Rm.
1Ab38 185' Platform l
- 9. -Zone 2-13 31/0 1A602 208' Storage Area 1A603 208' Passage 1A604 208' Fuel Handling Area 1A606 245' HVAC Equip. Area
- 10. Zone 2-14 17/0 i
'1A114 93' Fan Coil Area-(Partial) 1A115 93' Piping Penetration Rm.
I 1A116 93' Piping Penetration Rm.
E 1A117 93' Misc. Equip.: Area i-(Partial) 1A118 93' RHR "C" Pump Room-1A119 93' LPCS Pump Room-4 1A120 93' CCW Pump & Heat Ex. Rm.
L 1A122 103' South Corridor (Partial).
l 1A123 103' North Corridor (Partial)
- 11. Zone 2-15 1/0 1A539 185' Cable Chase 3
GRAND GULF-UNIT 1 3/4 3 Amendment No. #2,68