.... _.

4

?

i UNIT SHUTDOWNS AND POWER REDUCTIONS DOCKET No.

50-425 l

DATE:

APRIL 25, 1990**

l UNIT NAME:

VEGP UNIT 2 COMPLETED BY: J. C. WILLIAMS TELEPHONE:

(404) 826-4279

^

REPORT MONTH NARCH 90 i

R R.

5 E

E

-Y T

A T

LICENSEE S C-Y-

S H

EVENT T0 COMPONENT CAUSE & CORRECTIVE

+

P DURATION 0

0 REPORT

~ED CODE ACTION TO NO.

DATE E

(HOURS)

N D

NUMBER ME (SUBC00E)

PREVENT RECURRENCE 90-2 03/20 F

45.2**

A 3

2-90-002 EL-87 SEE.BELOW t

I F: FORCED REASON:

METHOD: -

EVENTS REPORTED INVOLVE 5: SCHEDULED -A-EQUIPMENT FAILURE EXPLAIN) I - MANUAL A GREATER THAN 20%

B-MAINTENANCE OR TES' 2 - MANUAL SCRAM REDUCTION IN AVERAGE-C-REFUELING 3 - AUT0.. SCRAM DAILY POWER LEVEL FOR D-REGULATORY RESTRICTION 4 - CONTINUATIONS-

-THE PRECEDING 24 HOURS..

1 E-OPERATOR TRAINING & LICENSE LOAD REDUCTION F-ADMINISTRATIVE 9.OTHER (EXPLAIN)'

G-0PERATIONAL' ERROR (EXPLAIN)~

H-0THER (EXPLAIN) l EVENT 90-2

-CAUSE:

GENERATOR TRIP / TURBINE TRIP DIFFERENTIAL RELAY ACTUATION../ REACTOR TRIP CAUSED BY THE RELAY ACTUATED WHEN AN ELECTRICAL f

FAULT OCCURRED IN THE UNIT I LOW V0LTAGE SWITCHYARD.' INCORRECTLY SET CURRENT TRANFORMER TAPS CAUSED THE RELAY TO BE OVERLY SENSITIVE TO SYSTEM IMBALANCES.

I CORRECTIVE ACTION: THE CURRENT TRANSFORMER TAPS WERE RESET-IN ACCORDANCE WITH L

ORIG'INAL DESIGN. DETAILS WILL BE LOCATED-IN LER 2-90-002.

    • -REVISION I TO V2-4 V2-4 00 Oo!kbOO g4

+

s ENCLOSURE 4 l

V0GTLE ELECTRIC GENERATING PLANT - UNIT 2 MONTHLY OPERATING REPORT FOR MARCH, 1990 TABLE OF CONTENTS l

UNIT SHUTDOWNS AND POWER REDUCTIONS Page V2-4.