j - * ** ,9 x

CONTAINMENT SYSTEMS AIR TEMPERATURE .

LIMITING CONDITION FOR OPERATION 3.6.1.5 Primary containment average air temperature shall not exceed 120*F. .

APPLICABILITY: MODES 1, 2, 3 and 4.

ACTION:'

With the containment average air temperature. > 120*F, reduce' the average air temperature to within the limit within 8 nours, or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />. ,

SURVEILLANCE REQUIREMENTS a t lea st two of 4.6.1.5 The primary co aininent, average air teinperat'ure shall be the arithmetical . average of the temperatures at the following locations and shall be determined at least once per 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />s:

Location

a. Containm'ent air cooler 1-1 inlet. -
b. Containment air cooler 1-2 inlet.

Containment air cooler 1-3 inlet.

c.

l .

l .

i I

l

  • i DAVIS-BESSE, UNIT 1 3/4 6-8 e202230331jo8$N6 PDR ADOCK o PDR c j P g  !