ML20041B152

From kanterella
Jump to navigation Jump to search
Proposed Changes to Tech Spec 4.6.1.5 Re Surveillance Requirements for Containment Air Temp
ML20041B152
Person / Time
Site: Davis Besse 
Issue date: 02/17/1982
From:
TOLEDO EDISON CO.
To:
Shared Package
ML20041B147 List:
References
NUDOCS 8202230331
Download: ML20041B152 (1)


Text

-

,9 j

x CONTAINMENT SYSTEMS AIR TEMPERATURE LIMITING CONDITION FOR OPERATION 3.6.1.5 Primary containment average air temperature shall not exceed 120*F.

APPLICABILITY:

MODES 1, 2, 3 and 4.

ACTION:'

With the containment average air temperature. > 120*F, reduce' the average air temperature to within the limit within 8 nours, or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

SURVEILLANCE REQUIREMENTS a t lea st two of 4.6.1.5 The primary co aininent, average air teinperat'ure shall be the arithmetical. average of the temperatures at the following locations and shall be determined at least once per 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />s:

Location a.

Containm'ent air cooler 1-1 inlet.

b.

Containment air cooler 1-2 inlet.

c.

Containment air cooler 1-3 inlet.

l l

i I

l i

DAVIS-BESSE, UNIT 1 3/4 6-8 e202230331jo8$N6 PDR ADOCK o PDR c

j P

g

!