TABLE 3.3-10 FIRE DETECTION INSTRUMENTS Instrument Location Minimum Instruments Operable Smoke
. Heat
- 1. -
Control ~ Room 4
N/A 2.
Cable Spreading Mezzanine 20 4
-3.
West Cable Vault 3
3 4.
East Cable Vault 3
3 5.
Computer Room 1
N/A 6.
Normal Switchgear Room 8
N/A 7.
A/E Emergency Switchgear Room 3
N/A 8.
D/F Emergency Switchgear Room 3
N/A 9.
Remote Shutdown Panel 1
N/A (Process Instrument Room
- 10. Station Battery Rooms (each)
N/A 1
11.
Relay Room 1
N/A
- 12. No. 1 Diesel Generator 2
1 13.
No. 2 Diesel-Generator 2
1
- 14. Upper Charcoal Filters N/A 6
15.
Lower Charcoal Filter N/A 6
16.
Control Room Air Conditioning Room 2
N/A 17.
Reactor Trip Breaker Room 3
N/A 18.
Unit II Control Room Zone 7 4
N/A Zone 8 1
N/A Zone 9 1
N/A 19.
Charging Pump Cubicle 1/ cubicle N/A BEAVER VALLEY - UNIT-1 3/4 3-48 PROPOSED WORDING 8202190127 820211 PDR ADOCK 05000334 P
o-TABLE 3.3-10 (continued)
FIRE: DETECTION INSTRUMENTS Instrument : Location.
Minimum Instruments 0perable Smoke Heat
- 20. Cable Vault 3'
-4 N/A
-(Eley. 720'-on side of
- Unit 2: Control Room) 21.
Intake Structure 6/ cubicle N/A-(A, B and C Cubicle)
' NOTE: D CUBICLE
~ N/A_
1-
- 22..CCR Pump Area 4
N/A
- 23. Auxiliary Feedwater Pump Area 4
~N/A
- 24. Cable Penetration Area U 2 N/A
- 25. RHR Pump Area 2
~
-N/A
,s BEAVER VALLEY - UNIT 1 3/4 3-48a PROPOSED WORDING
-