-_

8 JAN su I

Docket No. 50-334 File No. lAL 81-14 Duquesne Light Company t

ATTN: Mr. J. J. Carey Q., ' '

Vice President

[a-Nuclear Division S

P. O. Box 4 o/

I-Shippingport, PA 15077 f,/, 4 ',:,,

q

.J

.s o, Gentlemen:

~2 x..

'Q2

/-

('. s

Subject:

Imediate Action Letter 81-14 a

N Q N.._ d This refers to your letter of January 6,1982, in response to%r Immedla)e Action Letter 81-14 of March 9,1981 and to a telephone conversatWbetween Mr. K. Grada of your staff and Mr. D. Beckman of this office on January 7 1982.

Imediate Action Letter 81-14 listed the actions you took to prevent recurrent losses of Residual Heat Removal (RHR) System flow when the Reactor Coolant System (RCS) is drained below the range of Control Room pressurizer level indication.

Your January 6 letter proposed changes to those actions.

]

The following proposed modifications were provided by Mr. Grada during the telephone conversation:

l

)

a.

The RCS level standpipe will be continuously monitored anytime the remote level indications disagree with each other or the standpipe by more than 20%.

b.

The RCS level standpipe will be monitored continuously and personnel will be posted at the RHR pumps for imediate venting if indicated RCS level decreases below 50% loop span.

c.

During periods of loss or degradation of RHR flow, two incore thermocouples percore quadrant will be logged every ten minutes until flow is restored fully or all actions required by your Abnomal Procedure " Loss of RHR with RCS drained to Midspan of Loops", are complete.

Your proposed modification appears' acceptable.

Implementation of these actions will be reviewed during our routine inspections.

We understand that you will obtain our concurrence for any additional modifications to these actions prior to implementation.

?D0}00153820:00 G

05000334 PDR h

(

-SGC /

e,em, n:m.....

..aaet. 4 r Dae..............aaer.M....

..... f......

Kei Starostecki

/'

sunme, Be,,m. an..:.e..l. l.....G r.e e..n..ma n,.

...... v...Y.#...........

..h....M....... 1,

...........Q

.4//de.................

f..........

.m, NRC FORM 318 (10-80) NRCM 024a OFF1CIAL RECORD COPY usomen-sas*o

8 JAN 1982 Duquesne Light Company

.2-If our understanding of your planned actions is incorrect, please contact this office by telephone and in writing within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

Sincerely.

Original Signed By:

R. W. Starostecki, Director Division of Resident and Project Inspection cc:

F. Bissert, Manager, Nuclear Support Services R. Washabaugh, QA Manager H. P. Williams, Station Superintendent W. S. Lacey, Chief Engineer R. Martin, Nuclear Engineer J. Sieber, Manager, Nuclear Safety and Licensing T. D. Jones, Manager, Nuclear Operations R. M. Mafrice, Nuclear Engineer N. R. Tonet, Manager, Nuclear Engineering Public Document Room (PDR)