h

.l Oconee Technical. Specifications - 3.10 3.10.1.c Change to read the same. as 3.9.1.c.

3.10.2 Replace the words' "the end of the quarter" with " incurring I

the reporting requirecent."

s 3.10. 5. a Change to read "The gaseous waste tanks shall be main-tained and operated for the purpose of keeping releases within the objective of these specifications and shall process all radioactive gases fron the vent ;as header prior to their release when the activity released.during any calendar quarter exceeds one fourth the annual release quantities as determined by the objectives of this specification."

3.10.5.c Add "As far as practicable, release of radioactive gas will be coordinated with favorable meteorological con ditions."

Page 3.10.3 Bases, second paragraph, first sentence - change "5 mrem" to "10 mren '

.Page 3.10-4 Bases, paragraph beginning "The I'-131" - add the sentence, "A survey will be conducted once per year to verify the absence of milk producing ccws within. a five nile radius of the plant."

l Page 4.1-9 Table 4.1 Include sensitivity of analysis in this table. Make this table consistent with the. reporting requirenents given in Table 6.6-1, page 6.6-10 3

0 D

vv O

h w db A l a a

O Dg 31 t

gO f

ATTACME'TT Oconee Technical Specifications - 3.9

3. 9.1. c Change to read

" Describe these acticns in a report to the Con =ission within 30 days after incurring the reporting

- obligation."

3.9.4 Change to read "The equipnent installed in the liquid radio-active vaste system shall be naintained and operated for the purposes of keeping releases within the objectives of these specifications and shall process all liquids prior to their discharge when the activity, excluding tritiun and dissolved noble gases, released during any calendar quarter exceeds 1.25 curies. "

e S