05000280/LER-1982-097-32, /03L-0:on 821014,auxiliary Feed Pumps Prevented from Automatically Starting on Loss of Both Normal Feed Pump Motors.Caused by Incomplete Design Change W/Improper Documentation.Jumpers Installed in Control Circuitry

From kanterella
(Redirected from ML20028A486)
Jump to navigation Jump to search
/03L-0:on 821014,auxiliary Feed Pumps Prevented from Automatically Starting on Loss of Both Normal Feed Pump Motors.Caused by Incomplete Design Change W/Improper Documentation.Jumpers Installed in Control Circuitry
ML20028A486
Person / Time
Site: Surry 
Issue date: 11/12/1982
From: Joshua Wilson
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
Shared Package
ML20028A478 List:
References
LER-82-097-032, LER-82-97-32, NUDOCS 8211220222
Download: ML20028A486 (2)


LER-1982-097, /03L-0:on 821014,auxiliary Feed Pumps Prevented from Automatically Starting on Loss of Both Normal Feed Pump Motors.Caused by Incomplete Design Change W/Improper Documentation.Jumpers Installed in Control Circuitry
Event date:
Report date:
2801982097R32 - NRC Website

text

NRC 802M 366 U. S. NUCLE AR REGULATO:lY COMMISSION LICENSEE EVENT REPORT 4

0*.fNTROL BLOOK; l

\\

l l

l l

(PLEASE PRINT OR TYPE ALL REculRED INPORMATIONI 6

i O n In In l In in l @l4 Ill ll ll 1l @ l ;At 6e @

l l

l

c 'il I v!A IS IP I S 1 1l 0 1 0l l O l 5 9 UCEN54100;E 14 5

uCENSE NWMSER 2$

26 u;ENSE Tvet JO El

or-3j'*,d IL }@l 015101010 l 2 I R I o l@l1 1011 14 I 8 I 2 hl11Il112I 81 21@

O!iI 6

66 61 000KETNUM9ta 68 6e IVENT DATE la

?S RE*QRT DATE so EVENT OESCRIPTION ANO *sOBABLE OCNSEQUENCES h i: i: ; 1 With the unit at cold shutdown. control relava fynm tha nuxiliary steam genernenr 1

,3, i feed pump auto start circuitry were removed. While still at cold shutanun. ir un. 1

;,, ; ; discovered that the control relays removed prevented the auxiliarv feed numns frnm 1 j o i s ; l automatically starting on the loss of bbth normal feed pumo motors.

Thin evene i= 1 I c is i I contrary to Administrative Procedure 39 and reportable oer T. S.6.6. 2.b. (1).

sinco I lci7!Ithe unit was at cold shut dokn and the auxiliary feed pumps remained available for I io ea I i the opposite unit, the health and safety of the out,lic were not affected.

I so e

SYSTEM CAust

CAUSE

COMP.

VALvt CCD3 CooE SUSCCDE COMPONENT CCDE susCcQE sus:Cof to19l l Cl Hl h lX l @ [Z_l h i PI UlM IP lYl Xl h W h d h 7

8 9

10 11 12 13 18 19 20 SEQUENTIAL OCOUR R ENCE RipoRT REvtsion Lamind tvtNTvt4R REPORT No.

CODE Tvet No.

@,arg 18 12 I l-l 10 19 17 l l/l 10 l 1 l W

[--J W

_ 21 22 23 24 26 27 3

3 30 at 32 K N A

QN ON T u

MOURS 5t i PCR 3.

36 u

  • MA U RER l.!Lj@lc l@

L1J@

L.2J@

10 Io Io Io I Ly_1@

Lu.]@ U@

l 110 I 7 I s l@

22 24 ss as 32

.o ai 42 as 4,

CAUSE DESCRIPTION AND CC,RRECTIVE ACTIONS Ii i o i IThe event was caused by an incomplete desien chnngo uich imnennor anrumaneme<nn I

I g lin the 1972/73 time frame. Jumpers were installed in the ennern1 riven 4evo en 6 21 lallow automatic starting of the motor driven auxiliarv feed purnon.

I liial !

I i

il t.i l

.0 t

A

% DOWER QTWER STATUS Dt O RY DIS 00vERY 3g30miPTioN Soocial Tn anoc ri nn.

I is j lG lh 10 10 10 \\ @ l N/A l

(_CJhl 11 22 n

44 as as 30 s 4,

eggy,,,

v RELEASto CFRELtASE AMOUNT QP ACT1viTV LOCATION QP RELEA3(

It isI(3]@ [zj@l N/A l

l N/A l

7 4 9 to 11 44 45 30 8t*50NNEL Ex*0SURES Nt: Mete Tvrt Ots:mieTION

! 171101010 l@l z l@l N/A l

.t.se~NeiNJ2,si NLette Ots:R i ++i O N

[ i s i lo l o l o l@l N/A l

to I 9 11 12 LO13 0s em OAuacg Tc sac;g-v

- vet ers:=i. Tion I1 191 lz lhl N/A l

euus.,

8211220222 821112 NRC USE ONLY

[: ; o j Whj :=i* ion @

PDR ADOCK 05000280

,ssL t:

ess S

PDR l

l1 iiii!Iii Iilj 68 $9 80 3 3 9

'O (804) 157-1184 2

J. L. Wilson

....E ave::.=g :,=

i

.g.

hTTACHMENT l-

- SURRY POWER STATION, UNIT NO. 1
- DOCKET NO:

50-280 REPORT NO:

82-097/03L-0 EVENT.DATE:

10-14-82 TITLE OF THE EVENT: LOSS OF ADMINISTRATIVE CONTROL l

j 1.

Description of the Event:

l' With unit one at cold shutdown, an unscheduled review of electrical drawings

. by the on shift training coordinator prompted the testing of the auxiliary j

feed pump automatic start circuitry. The automatic start feature of the motor driven auxiliary feedwater pumps on loss of normal feedwater pumps was found to be inoperable.

Failure of the automatic pump start was caused by scheduled electrical maintenance removing unpowered control relays from the auxiliary feed pump cubicles for 1-FW-P-3A and 3B.

This work was performed due to an incomplete design change with improper documentation in the 1972/73 time frame.

This event is contrary to Administrative Procedure 39 and reportable per T.S.

6. 6. 2. b. (3).

2.

Probable Consequences and Status of Redundant Equipment:

1 The automatic start feature of motor driven auxiliary feedwater pumps on loss of normal feedwater pumps is designed in anticipation of low steam generator level.

Pump auto start for all other functions remained operable during this event.

Since the anticipatory auto-start of the auxiliary feed pumps is de-signed for at power feed' pump trips and the unit remained at cold shutdown, the i

health and safety of the public would not have been affected.

3.

Cause

The event was caused by an incomplete design change with improper documentation.

4 4

4.

Immediate Corrective Action

The immediate corrective action was to install Jumpers in the Auxiliary Feed Pump control circuitry to allow auto-start upon loss of normal feed pumps.

5.

Subsequent Corrective Action:

i The circuit will be permanently returned to the original design.

Station drawings FE8BD, 8BQ and ESK 5K will be changed to indicate the original design.

6.

Action Taken to Prevent Recurrence:

None.

7.

Generic Implications:

This event is not Generic to unit two since the feature that allows both normal feed pumps to be in pull to lock without auto-start of the auxiliary feed pumps' was never installed.