_ ___ - ____ _

S.

APPENDIX A NOTICE OF VIOLATION Tennessee Valley Authority Docket Nos. 50-438 & 50-439 Bellefonte Units 1 and 2 License Nos. CPPR-122 & CPFR-123 l

As a result of the inspection conducted on July 13-16, 1982, and in accordance with the NRC Enforcement Policy, 47 FR 9987 (March 9, 1982), the following violation was identified.

10 CFR 50, Appendix B, Criterion V as implemented by PSAR Section 17.1.5 requires that activities af fecting quality be accomplished in accordance with documented instructions, procedures, or drawings. General Construction Specification G-38 paragraph 3.2.1.2 identifies cables which have a minimum bend radius in excess of 12 inches.

Contrary to the above, cable identified as having a minimum bend radius exceeding 12 inches was installed in vertical cable tray fittings which have a 12 inch radius.

This installation causes the cable bend radius to be violated.

This is a Severity Level IV Violation (Supplement II).

Pursuant to the provisions of 10 CFR 2.201, you are hereby required to submit to this office within thirty days of the date of this Notice, a written statement or explanation in reply, including: (1) admission or denial of the alleged viola-tion; (2) the reasons for the violation if admitted; (3) the corrective steps which have been taken and the resultc achieved; (4) corrective steps which will be taken to avoid further violations; anc (5) the date when full compliance will be achieved. Consideration may be given to extending your response time for good cause shown.

Date: Agust 12, 1982 l

8210150195 820923 PDR ADOCK 05000438 G

PDR u