05000416/LER-1983-060-03, /03L-0:on 830329,during Cold Shutdown,Load Shedding & Div I LSS Sequencing Panel Failure Alarm Actuated.Caused by Failure of 15-volt Dc Power Supply Used to Power Solid State Electronics for Sys Logic

From kanterella
(Redirected from ML20023B554)
Jump to navigation Jump to search
/03L-0:on 830329,during Cold Shutdown,Load Shedding & Div I LSS Sequencing Panel Failure Alarm Actuated.Caused by Failure of 15-volt Dc Power Supply Used to Power Solid State Electronics for Sys Logic
ML20023B554
Person / Time
Site: Grand Gulf 
Issue date: 04/28/1983
From: Byrd R
MISSISSIPPI POWER & LIGHT CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
Shared Package
ML20023B542 List:
References
LER-83-060-03L, LER-83-60-3L, NUDOCS 8305050178
Download: ML20023B554 (2)


LER-1983-060, /03L-0:on 830329,during Cold Shutdown,Load Shedding & Div I LSS Sequencing Panel Failure Alarm Actuated.Caused by Failure of 15-volt Dc Power Supply Used to Power Solid State Electronics for Sys Logic
Event date:
Report date:
4161983060R03 - NRC Website

text

..

NRC FORM 386 U. S. NUCLEAR CE!ULATORY 'mana**manen

  • 77',

Attachment to AECM-83/0261 LICENSEE EVEDT REPORT Page 1 of 2 CONTROL BLOCK: l l

l l

l l

h IPLEAgE pensT OR TYPE ALL REOUIRED INFORMATIO8N lo li_I l e4 S i al s i d i l@l o l ol -1 ol o l ol o ol-1 ol o @IS41 1111 11 t@l I

l 7

8 9 LICENSEE CODE 14 15 LICENst Nuadel M 3i Lactam Tvyt al - S7CATSB@

CON'T 0 0 @aoI ol 51 o1 olo l 411161@l ol 3 l 2191 sl 31@lol 4121 el e l 31@

o i si ooCasi esummen as a

sveier emiu 74 15 mePanT oATE 8e 7

e EVENT DESCRIPTION AND PROSABLE CONSE0ptseCES h o 2 [On March 29. 1983. while in Cold Shutdown. a Load Sheddino and I

o 3 l Sequencing (LSS) panel failure alarm actuated.

The Division I LSS 1

o 4 l system, the Division I Diesel Generator, LPCI A and LPCS were 1

o s l subsequently declared inoperable.

The Division II Diesel Generator was 1 o s lavailable.

LPCI C was the only operable ECCS system, therefore, an 1

o 7 [LCO was entered pursuant to T.S.3.5.2.

This event is reported j

o 8 l pursuant to T.S.6.9.1.13.b.

1 7

8 9 8D oOE SveCOBE COMPONENT CODE S

DE l ElB l@ W@ @@ l IlN I SlT l R[U Q lF@

Z@

Pl o 9 is n

in i3 i.

LER RO EVENT vf AR O

DE T

neO

@,agg le1 31 L--J l o l6 I o f M

i ol31 p'

M po

,, 21 22 23 24 26 27 28 2

3 K N C

LA T ME Hours 22 S8 i FOmed US.

lutAN pe,a lA J@LZJ@

LZ J@

L2JO I

I I

I I

t'._J@

LN jg

{Ajg lX l 9l9 l 9)g 33_.

34 35 _

38 37 40 41 42 43 en 47 CAUSE DESCRIPTION ANDCORRECTIVE ACTIONS h

[ go-] lThe cause was f ound to be f ailure of the 15V DC power supply used to j

[ power the solid state electronics for system logic and timing functions.j i i gThe LSS cabinet is supplied by Automation Industries, Vitro Laboratoriesj l Division.

The power supply is manufactured by CEA, part no. CEA3B150Y j

, 3 glo3FLP3.

The power supply was replaced on April 9, 1983.

l i 4 7

8 9 l

sTAN

% Poguem oTHER STATUS o fW DesclW GIW 9000mIPTeeII l I i I s I L' J@ l' l' l' l@l "

I l.a J@l ' "'*"

l l

AC TIVI TV C TENT Amount or ACTiv>Tv.@ I LoCATeenermELtAsE@

RetpSE@D or RyEAsEQlE l

(_j i 6 7

9 9 10 ft 44 4

E PERSONNEL EMPosunE5 i e ~gi. gT"'"'"

j j

PERSONNF L INJ IES 3 "

l 0 '[I*'gl jgl l

, y r

ee n

i2 8305050178 830428 LOSS OF OR DAMAGE TO FActLITv 43 PDR ADOCK 05o00416 l

T }"

y "'"'m S

PDR i 9 k

j 7

8 9 to 80 PUB L ICITY 98AC UE ONLY CU9 [U@I" 1

11111'lillill:

7

' 1 10 M 66 80 3 on h d NAME OF PREPARER PHONE:

. _,,,,... _,, _.. _.. - _ _ _ _ _ _ _ _.,. ~.. _ _ _ _...

4*'

Attachmsnt to AECM-83/0261 Page 2 of 2 SUPPLEMENTARY INFORMATION TO LER 83-060/03 L-0 Mississippi Power & Light Company.

Grand Gulf Nuclear Station - Unit 1 Docket No. 50-416 Technical Specification involvtd: 3.5.2

- Reported Under Technical Specification: 6.9.1.13.b Event Narrative:

On March 29, 1983, while in Cold Shutdown, a Division I Load Shedding and Sequencing panel failure alarm actuated. Upon investigation'it was determined that power was available.to the panel, however, some indicating lights were off. A subsequent maintenance investigation found the internal 15V DC power supply failed. The power supply powers solid state circuits for system logic and timing functions. The power supply was replaced and LSS Division I was restored on April 9, 1983.

During the event, an LCO was entered under T.S.3.5.2 due to LPCI C being the only operable ECCS system. Division I (D/G 11, LPCI A, and LPCS) was declared inoperable due to inoperability of LSS Division I.

HPCS was inoperable due to maintenance being performed on the HPCS and D/G 13 systems. LPCI B was inoperable due to the SSW B system being down for maintenance. This is submitted as a final report.

I i

_, ~...

~

.m