ML20012B178

From kanterella
Jump to navigation Jump to search

Forwards Topical Rept Evaluation of GE Rept NEDO-31558, Position on NRC Reg Guide 1.97,Rev 3 Requirements for Post- Accident Neutron Monitoring Sys. BWR Owners Group Position Unacceptable
ML20012B178
Person / Time
Site: Oyster Creek
Issue date: 02/26/1990
From: Dromerick A
Office of Nuclear Reactor Regulation
To: Fitzpatrick E
GENERAL PUBLIC UTILITIES CORP.
Shared Package
ML20012B179 List:
References
RTR-REGGD-01.097, RTR-REGGD-1.097 TAC-51115, NUDOCS 9003130730
Download: ML20012B178 (2)


Text

9; 7 F:.[ ((

~ February 26, 1990'-

l'!

-t

( 4,fbociet No. 50-219'

.Mr. E. E. Fitzpstrick' Vice President and Director 1

Oyster Creek Nuclear-. Generating Station J

o P.O. Box 388-Forked River, New Jersey 08731

Dear Mr. Fitzpatrick:

1 e

SUBJECT:

POST.ACCIDENTNUETRONFLEXMONITORINGFORBWRS(TACNO.51115)

Reference:

BWR Owners; Group letter (R. F. Janeak) to NRC (T. E. Murley), BWR j

Owners Group Licensing Topical Report _" Position on NRC Regulatory l

Guide 1.97, Revision 3 Requirements for Post-Accident Neutron MonitoringSystem"(GeneralElectricReportNEDO-31558), April 1,_1988 s

Regulatory Guide-(R.G.)- 1.97 and-10 CFR 50.49 require that neutron flux be a

monitored by Category 1 instrumentation. The staff has allowed BWRs to operate with' existing instrumentation until instrumentation was developed that conforms to the requirements of R.G. 1.97 and 10'CFR 50.49.-- Instrumentation that meets the requirements of R.G. l.97'and 10 CFR'50.49 is now available.

The Boiling Water Reactor Owners Group (BWROG) submitted the above Reference for. review. : The staff has. completed its-evaluation of' the topical report. ' As a result of our evaluation the staff finds the BWROG position unacceptable.

Enclosed.is a letter to the BWROG and our Safety Evaluation.regarding this matter.-

tTherefore, you are required to install neutron flux monitoring' instrumentation

+

that conforms to the requirements of R.G. 1.97 and 10 CFR 50.49...We request that.you respond within 30 days of receipt of this letter indicating your stent to comply with this requirement and advise us of the schedule for-

.s iuplementation of. neutron flux monitoring instrumentation that meets the.

requirements of R.G.1.97 and 10 CFR 50.49.

w Sincerely, 4

/s/

Alexander W. Dromerick, Senior Project Manager So Project Directorate I-4

'o u Division of Reactor Projects. I/II j'

Office of Nuclear Reactor Regulation N

Enclosure:

'I iox

~As Stated R8 g

cc w/ enclosure:

g See-next page T N h[N$!@ NRC & Local PDRs

'.M DISTRIBUTION Plant File S. Varga (14E4)

'B. Boer (ITA2)

S. Norris A. Dromerick OGC E. Jordan (MNBB3302)

ACRS 10)-

0FC :LA:PDI.4-

PM:PDI-4

~iPD:PDI-4 ~

..... :...........,h:...y :..... :......

3:...........:............:...........:........

NAME;:Sl691L ~

defick :JStolz I

l:............::............::............::........

fD(

DATE 4 /$/90 g/jf/90

g 90 Jg

~

0FFICIAL: RECURD'TUPY

\\

Do m nt'N C r LTR:T0 EEFITZ DN S0 219

f 1

7 Mr. E. E. Fitzpat' rick '

Oyster Creek Nuclear-s

- Dyster Creek Nuclear l Generating Station Generating Station cc:

Ernest L. Blake, Jr.

Resident Inspector Shaw, Pittman, Potts and Trowbridge c/o U.S.-NRC 2300 N Street, NW Post Office Box 445 Washington, D.C. '20037 Forked River, New Jersey 08731 J.B. Liberman, Esquire.

Commissioner Bishop. Liberman, Cook, et al.

New Jersey Department of Energy 1155 Avenue of the Americas 101. Commerce Street

~

New York, New York-10036' Newark, New Jersey 07102 Kent Tosch, Chief Regional Administrator, Region I New Jersey Department of Environmental' r

U.S.- Nuclear Regulatory Commission Protection 475 Allendale Road-Bureau of Nuclear Engineering.

King of-Prussia, Pennsylvania 19406 CN 415:

Trenton, New Jersey 08625 BWR Licensing Manager-GPU Nuclear Corporation

-1 Upper Pono Road Parsippany, New Jersey 07054

- Deputy Attorney General State of:New Jersey _

Department'of Law and Public Safety 3

36 West State Street'- CN 112 Trenton, New Jersey 08625 Mayor Lacey Township 818 West-Lacey Road-Forked River, New Jersey 08731 1-Licensing Manager Oyster Creek Nuclear Generating Station Mail Stop: Site Emergency Bldg.

P. 0. Box 388 forked River, New Jersey 08731 i

't

+