SHEARON HARRIS NUCLEAR' POWER PIANT.

DOCKET N04-50 400/ LICENSE NO. NPF-63 REQUEST FOR LICENSE AMENDMENT g,

-AREA TEMPERATURE MONITORING TECHNICAL SPECIFICATION PAGES 4

9

.)'.'

-t l-Ol

/

.s' E.

i-1 l~

l-1

-w' 8912220011.891218

- PDR -- ADOCK-05000400

.p PDC

.1 i

7 A

+

I

TABLE 3.7-6 P

AREA TEMPERATURE MJNITORING MAXIMUM TEMPERATURE

' AREA

' LIMIT (*F)

REACTOR AUXILIARY. BUILDING L

1.

Control Room Envelope, (El 305')

ES 2.

Process I&C, Room (El 305')

85 3.

Rod Control Cabinets Area (El 3t5')

104 4

A&B Battery Rooms (El 2S6')

85

5.. A&E Switchgear Rooms (El 286')

90 6.

Main Steam, Feedwater Pipe Tunnel (El 286' & 261')

116 7.

SA&SB Electrical Penetration Areas (El 261' & 286')

104 8.

Area with MCC 1A35SA and 1B355B (El 261')

104 9.

HVAC Chill'ars, Auxiliary FW Piping & Valve Area (El 261')

104 10.

CCW Pumps, CCW Hx, Auxilia y FW Pumps Area (El 236')

104 11.

lA-SA, 15-SB, and IC-SAB Charging Pump Rooms (El 236')

104 12.

Service Water Booster Pump 13-SB (El 236')

104 13.

Mechanical and Electrical Penetration Areas (El 236')

10t.

14 Containment Spray Additive Tank, and H&V Equipment Area (El 216')

104

15. Trains A&B Containment Scray Pump, RHR Pump, H&V Equipment Areas (El 190')

104 i

FUEL HANDLING BUILDING t

16.

Trains A&B Emergency Exhaust System Areas (El 261')

104

17. A :1 P::1 Cri t; P r,.
nd,;;;; !.,,; Mag;r fra:

(El 225')

Sc/rf//

104 WASTE PROCESSING BUILDING

18..H&V Equipment Rcom (El 236')

104 MISCELLANEOUS

19.. Tank Area (El 236')

-ter / o f 20.

Diesel. Fuel 011 Storage Building (El 242')

122 21.

Emergency Service Water Electrical Equipment Room 104 22.

Emergency Service Water Pump Room 122 23.

DELETED 24.

lA-SA & 18-58 H&V Equipment Rooms (El 292')

122

25. lA-SA & 18-53 H&V Equipment Rooms (El 280')

118 26.

lA-SA & IB-53 Electrical Rooms (El 261').

116 27.

lA-SA & 13-SB Diesel Generator Rooms (El 261')

120 SHEARON HARRIS - UNIT 1 3/4 7-29

!