05000316/LER-1981-037-03, /03L-0:on 810728 & 29,containment Pressure hi-hi Bistable Found to Trip Outside Tech Spec Requirements.Caused by Instrument Drift.Bistable Recalibr.During Retest,Bistable Actuation Point Found Excessive.Bistable Replaced

From kanterella
(Redirected from ML20010E257)
Jump to navigation Jump to search
/03L-0:on 810728 & 29,containment Pressure hi-hi Bistable Found to Trip Outside Tech Spec Requirements.Caused by Instrument Drift.Bistable Recalibr.During Retest,Bistable Actuation Point Found Excessive.Bistable Replaced
ML20010E257
Person / Time
Site: Cook 
Issue date: 08/25/1981
From: Rischling J
INDIANA MICHIGAN POWER CO. (FORMERLY INDIANA & MICHIG
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
Shared Package
ML20010E254 List:
References
LER-81-037-03L, LER-81-37-3L, NUDOCS 8109030245
Download: ML20010E257 (2)


LER-1981-037, /03L-0:on 810728 & 29,containment Pressure hi-hi Bistable Found to Trip Outside Tech Spec Requirements.Caused by Instrument Drift.Bistable Recalibr.During Retest,Bistable Actuation Point Found Excessive.Bistable Replaced
Event date:
Report date:
3161981037R03 - NRC Website

text

-

LICENSEE EVENT REPORT CONTRot BLOCK:

l l

l

}

l lh (PLEASE PRINT OR TYPE ALL REQUIREO INFORMATION)

Wlil l M! Il DI C l Cl 2 !@l 0 l 0 l o l o l o l o 101010 lo 10 l@l4 Il 11 Il 11 l@l I

l@

d 9 LICENSE E CODE 14 55 LIC ENSt NLYtsER h

ib L4 CENSE Ti PE 30 St LAT bd CON'T IoIiI

'C" l L l@l 0 l 5 l 0 l 0 l 013 l 1 l 6 l@l 0 l 7 ! 2 I 8 I 8 l1 l@l0 l8 12 l5 18 Il l@

s EVENT DESCRIPTION AND PROB AB C NS ' ENCES to; ;j DURING NORilAL OPERATION, WHILE PERFORMING A SURVEILLANCE TEST, A CONTAINMENT PRESSURE 1 HIGH-HIGH BISTABLE WAS FOUND TO TRIP AT A VALUE EQUIVALENT TO 3.1 PSIG ON TWO OCCAS-l g,,,

,g,,,, SIONS, 07-28-81 and 07-29-81.

THIS IS NON-CONSERVATIVE IN RESPECT TO T.S. TABLE I

3.3-4 ITEM 2.C. (3.0 PSIG).

THE APPROPRIATE ACTION REQUIREMENTS WERE FULFILLED.

J

,njsj,

j, g j l PREVIOUS OCCURRENCES OF A SIMILAR NATURE INCLUDE: 050-316/80-31; 79-07 AND 22.

I f o lil l I

loisi i I

so s,

OE CODE SLB E

COYPONENT CODE SLBC DE S

CE loloi i I l B l@ I E l@ l El@ l I l N I S l T l R l u l@ I S l@ [Z_j @

SE QUENTI AL OCCLA A[.CE EPOHT REVISION tg y q3 EVENT

  • EAR REPOHT NO CCDE TYPE N O.

@.g.g 18 l 11 l-l l 013171 l/l 1013I IL l

[-j l0 l JJ 24 lb 21 23 23 30 31 32 hu B-S PPLIE YAN FA TUREH TA k*

A Tf O PL

'T THQ HQLRS 22 S B IT D F R$

l E l@l Z l@

l Z l@

lZ l@

l 0l 0l Ol 0]

l Yl@

lYl@

lNI@

lFl1l810l@

IJ 4

Jo J/

40 41 42 43 44 47 CAUSE DESCPIPTION AND CORRECTIVE ACTIONS h l i j o l l AFTER RECALIBRATING THE BISTABLE ON 07-28-81, A RETEST ON 07-29-81 ALSO FOUND THE I

g ;,j l BISTABLE ACTUATION POINT TO EXCEED THE L.C.0. VALUE.

THE BISTABLE (FOXBOR0 63U-BC-I

,,,,,;OHEA-F) WAS EXERCISED, RECALIBRATED AND RETURNED TO SERVICE. ADDITIONAL CHECKS WERE I

,,,,,; PERFORMED ON 07-30-81 AND 07-31-81 WITH NO INSTRUMENT DRIFT INDICATED. ANOTHER CHECK l

,,,,,;WAS PERFORMED ON 08-19-81, THE BISTABLE ACTUATION (SEE ATTACHED SUPPLEMENT) 1

-)

80 ST 3

> PO/.E H OTHER ST A TUS bSCO RV DISCOVFHY DESCRIPTION It l' I l E l@ l ll 010l@l NA l

lBl@lSURVEILLANCETEST l

8 d drm ry Cob N T nELEA;fD OF RE L E A' E AYOUNT OF ACTIVITY LOC ATION OF REL EASE li 16 l l Z l @ lZ l@[NA j

l NA l

4 6

10 11 44 4S 80 P!H30P Ntt[mrarcuts

  • .UYPfH TYPf DE SCRIP TtON l'l II010lO_j@lZl@l NA l

' n R.. d'r., L m smP rm. @

~

l' l i101010181 NA l

1 1

11

-)

?

i,c s W IZl@l ng l

1, 80 P: li t n:I r v NRC USE ONLY N

NA

[

((((;[j;;;;;lj m,U t o DE M D PriqN "s

" g109030245 810825 J. L. R1schlin9 616-465-5901 g

gDRADOCK05000

B e

.O ATTACHMENT TO LER#81-037/03L-0 SUPPLEMENT TO CAUSE DESCRIPTION SETPOINT DRIFTED IN A CONSERVATIVE DIRECTION AND THE BISTABLE WAS DECLARED IN0PERABLE. THE APPROPRIATE ACTION REQUIREMENTS WERE COMPLETED AND THE BISTABLE WAS REPLACED. AFTER BEING CALIBRATED THE NEW BISTABLE WAS PLACED IN SERVICE.