ML20009D059
ML20009D059 | |
Person / Time | |
---|---|
Site: | Oyster Creek |
Issue date: | 07/10/1981 |
From: | Sklar J GENERAL PUBLIC UTILITIES CORP. |
To: | |
Shared Package | |
ML20009D058 | List: |
References | |
NUDOCS 8107230075 | |
Download: ML20009D059 (11) | |
Text
. ._ __ _ _.
MCNIELY OPERATICES SulEARY JUNE 1981 At the beginning of the reporting period, the Oyster Creek Nuclear Generating Station was in the process of startup. 'Ihe startup was lengthened considerably by Main condenser tube leak problems, condensate pmp availability, and the unavailahility of #2 Traversing Incore Probe (TIP) . Full core thamal power was attained on June 11 at a generator output of 635 IWe.
On June 23, load was rarhM to 70% when "B" Feedwater String was taken cut of service to correct a seal water leak. Beginning on June 18, degrading condenser vacum forced overall plant output to be rachM to approximately -
470 IWe over a period of a week. A-reactor SCRAM due to low condenser vacum occurrrA on June 26. After maintenance on the steam traps for the Stesa Jet Air Ejectors, preparations for startup were anderway on June 28 wham water was discovered in the turbine luba oil systen. Changing out the oil. delayed startup until June 30. The rer.ctor was brought critical at 0637 on June 30 and at the end of the reprting period power was being increased as plant paraneters allowed.
The following Reportable occurrerres were identified during the month Jof June:
R.O. 81-21 -was identified on June 3 when Reactor High Pressure Scram switches RE03P, C, and D were found to have settings less conservative ':.han Technical Specificaticn requirenents.
R.O. 81-23 w ered on June 3 when the dry wil was vented to reduce the oxygen concentration and Drywell to Torus differential pressure was not maintained.
- R.O. 81-24 occurred on June 15 when two Dnergency Service Water Pmps failed to meet surveillance acceptarre criteria and were elac1= red inoperable.
Also a Tachnical Speification violation occurred when the required surveillance test was not perfornxi within the = pacified time frame.
R.O. 81-25 occurred on June 17 when both doors to the Reactor Bni1rling Railroad Airlock were found open as a result of reactor ventilation system misoperation.
R.O. 81-26 was identified on June 27 when the setpoint for the Isolation Condenser Reactor High Pressure Switch was found to be less conservative than Technical Specifica-tion requirements.
8107230075 810715 -
t PDR ADOCK 05000219 ;
R PDR
OPERATING DATA REPORT i
OPERATING STATLE l l
LNIT N N .. . . . . . .
........... OYSTER CREEK j 14CKEP NINBER . . . . . . . . ,....... 50-219 UFILITY DATA PREPARED BY .... ...... J.B. SIGAR 609-693-6013 REPOMNG PERICO . . ............ JLNE 1981
~ LICENSED THERMAL PONEROWI) ......... 1930 NMPIME RATING (GRDSS M) ........ 650 IESIG ELEC.TRICAL RATING (NET M) . . . . .. 650 MAXDEM DEPENDABIE CAPACITY (GROSS 14fE) ... 650 MAXDEN DEPENDABIE CAPACITY (NETE M) ... 620 IF CHANGES OOCUR IN CAPACITY RATING SINCE IAST REPORP, . GIVE REASN ....... NONE PCMER IEVEL TO NHICH RESTRICIED, IF
. ANY (NEff M) .....: ... ....... 450 REASCE FOR RESPRICTICE, IF ANY ....... DEGRADING CDNDENSER VACULM KNTH YEAR CLMLATIVE t
IOURS IN PERIOD' 720.0 4343.0 100991.0 IOURS RX CRITICAL 621.1 3223.1 75653.7 l - RX RESERVE SHJ1DONN HRS. 0.0 0.0 468.2 l HRS. GEN CE LINE 603.7 3028.4 73997.4 L Uf RESERVE SHU1DOWN HRS. 0.0 0.0 0.0 GOSS THERMAL ENERGY 965800.0 5031640.0 125178120.5 GROSS EIEC. ENERGY 311230.0 1652420.0 42580665.0 L
NEff EIEC. ENERGY 297480.0 1579420.0 41018078.0
! Uf SERVICE FACIOR 83.8 69.7 73.3 l Uf AVAIIABILITY FACIOR 83.8 69.7 73.3 l
Uf CAPACITY FACIOR FOC 66.6 58.7 66.9 Uf CAPACITY FACIOR DER- 63.6 55.9 62.5 EORCED OUTAGE FACIOR 16.2 9.3 6.7 THE NEXT SCHEDUIED OUTAGE IS TO BEGIN ON NOVEMBER 31, 1981 1
AVERAGE DAILY POWER IEVEL DOCIET f . . . . . 50-219 LNIT . . . . . . . O . C . 9.1 REPORP DATE . . . July 14, 1981 COMPIETED BY . . . J.B. Sklar TEIEPIDE . . . . 609-693-6013 KNDI: June 1981
-DAY g DAY g
- 1. 379. 17. 544.
- 2. -457. 18. 564.
- 3. 416.- 19. 545.
- 4. 453. 20. 524.
- 5. 518. 21. 510.
- 6. 497. 22. 430.
- 7. .496. 23, 427.
- 8. 308. 24. 444.
- 9. 445. 25. 408.
- 10. 459. 26. 53.
- 11. 578. - 27. O.
- . 12. 595. 28. O.
13.- 594. 29. O.
- 14. 594. 30. O.
- 15. 602.
- 16. 583.
- _ .. . ~ . . _ _ _ _ _ . , _ . _ . . . .__. __. - . . _ _ _ _ _ . _ _ _ - - - _ - _ _ . _ _- _ - - _
' DOCKET NO.
50-219 ,
UNITSilUTDOWNS AND PosVER REDUC 110NS UNIT NAME Oyster Creek #1 DATE July 10, 1981 COMPLETED BY J. B. Skl ar-REPORT MONTil JWE 1981 TELEPHONE 609-693-6n11 g
"L a c
- ,E g "g gI3 Licensce Eg Cause & Corrective No. Date k Eg = 3sE Event p mo Eu
^' **
F jE E jigg Report # g Prevent Recurrence 3
i.
i 17 6-26-81 F 116:20 A 3' N/A ZZ ZZZZZ Autanatic Scram due to low condenser vacuun. Corrective action consisted of maintenance on the steam traps for the Steam Jet Air Ejectors.
i i
i l
i
! 2 3 4 F: Forced Reason: Method: Exhibit G Instructions S: Scheduled A Equipment Failure (Explain) 1 Manual for Preparation of Data i
i B-Maintenance of Test 2-Manual Scram. Entry Sheels for Licensee C Refueling 3-Automatic Scram. Event Report (LER) File (NUREG-
- D Regulatory Restriction 4 Other(Explain) 0161)
E-Operator Training & IJcense Examination j F-Administrative 5
< G-Operational Error (Explain) Exhibit I - Same Source (9/77) II-Other (Explain)
JUNE
SUMMARY
OF QASL' MECHANICAL' MAINTENANCE, EQUIPMENT NALFUNCTION ,. ' CORRECTIVE ACTION
!- t Torus Ventilation Valve Position indication Switch actuating arm adjusted V-28-18 .not working and tightened-Emergency Service Nater Degraded performance B and C pumps ' removed, cleaned Pumps . suction, checked impeller clearance, ~
flow rates verified on al1 pumps Railroad Airlock Doors Locking top plate Top plate assembly repaired (Inner) allowing leakage B CRD Pump Degraded performanca . Rebuilt pump, replaced rotor and coupling V-20-40 (Core Spray s Packing leak Adjusted packing to stop leak System I)
Shutdown Cooling System Closed Cooling Water Replaced union with a new one "A" Pump leak to pump Oil Cooler
JUNE
SUMMARY
@F QASL ELECTRICAL MAINTENANCE ~ -
EQUIPMENT MALFUNCTION CORRECTIVE ACTION Emergency Service Water. Pump Out of calibration Calibrated ammeter B-Motor Ammeter Emergency Service Water Pump Out of calibration Replaced ammeter A-Motor Ammeter Containment Spray Valve Flex-conduit loose Reconnected conduit V-21-11 Railroad Airlock Doors Must be operated from Replaced limit switches relays CRD "B" Pump Motor Abnormal noise Replaced inboard and outboard bearings Emergency Service Water No local position Removed broken light socket Valve V-3-88 indication when closed MSIV Drain Valve V-1-ll Torque switches needs Reset switches resetting C Bus Under Voltage Requires relamping Relamped Indication CRD Notch Override Switch Stop plate worn Replaced detent stop plate
rag ,1 JUNE
SUMMARY
'F QASL INSTRUMENT MAINTENANCE ,
EQUIPMENT MALFUNCTION CORRECTIVE ACTION ,
V-15-61 Install Vent Cap Vent Cap installed
- 2 TIP Machine TIP retracted into Drive Replaced TIP, adjusted limit switches, cabinet ' reset logic and calibrated system Rndweste overboard dischsrge High alarm in contiruously Alarm circuit not wired correctly.
monitor Repaired and testad sateifactory.
A0G System "B" Recombiner H2 Analyzer drifting Removed moisture from units and calibrated DW Humidity Recorder Stuck on point 4 Repaired, cleaned and calibrated MSL Rad. Monitors #3 and 4 Surveillance discrepancy corrected discrepancies by adjusting trip points according.to procedure A0G System Exhaust Alarming continuously Calibrated monitor, adjusted set Rad Monitor points in accordance with Standing Orders i
Radwaste effulent monitor Recorder out of calibration j Calibrated Recorder Radwaste effulent monitor Leak at Detector Welding req. referred to Mechanical Maintenance l
Shutdown Cooling Flow Control Jumper "A" Loop ; Installed Jumper on "A" Loop IRM CH. #17 Surveillance discrepancy Corrected discrepancy by adjustment Electronics according to procedure IRM CH. #11 Not fully inserted Manually assisted to full insert.
Modification pending approval by Engineering to repair this problem
~
JUNE
SUMMARY
i F QASL INSTRUMENT MAINTENANCE ' cont'd P:g; 2
~
MALFUNCTION ' CORRECTIVE ACTION EQUIPMENT .
DW Humidity-Recorder Out of calibration Performed calibration ARM R014C-4 Spiking Performed calibration MSL Rad Monitor #4 Trip point discrepancy Adjusted to correct trip point A R:cire Pump Limit switch calibration Calibrated limit switch required DW/ Torus D/P Inst. Erratic operation Replaced with new unit A Isol. Condenser Erratic Indication Refilled reference leg.
02 Analyzer Indication climbing for Removed moisture from System and no apparent reason performed complete calibration ARM R014C-7 Downscale Replaced sensor and calibrated Recirc Pump Bearning Reading high Cleaned Rotary switch and calibrated Temp. Rec.
IRM Front Panel Tests Surveillance discrepancy Made necessary adjustment per procedure APRM CH. #6 Recorder Not responding Cleaned, adjusted and calibrated Off Gas Line Flow Recorder Gears not driving Replaced bushings and calibrated A Recirc Pump Winding Temp high Installed spare RTD and calibrated monitor SRM CH. #23 Mode switch alignment Aligned switch and tested satisfactory
JUNE 'SLDMARY f F QASL INSTRUMENT MAINTENA E cont'd- P g) 3 MALFUNCTION CORRECTIVE ACTION EQUIPMENT l In-shield switch not Adjusted switch and tested satisfactory' TIP Machine #2 working properly Downscale Replaced sensor and calibrated ARM RO14A-5 i
Cannot zero i Replaced Flux Pumps and calibrated LPRM 1217D and'2009D i
Out of Servica' Cleaned Rotary switch and calibrated-Racirc Pumps suction T:mp. Recorder ,
I Malfunctioning Repaired broken Thermocouple Cicen up System Temp c!cment Zero level indication Calibrated water removal system A0G moisture removal train Remove Jumper on Completed A SDC Pump "A" Loop Calibrate Scraia Calibrated Syste- oy Surveillance Condenser Lov Vacuum Function procedure Surveillance discrepancies Corrected discrepancies by adjustment APRMs according to procedure Pen hanging up Cleaned, adjusted and calibrated pen Off Gas Line Flow Recorder mechanism Chart not taking up Could not substantiate problem A0G Exhaust monitor Surveillance discrepancies Corrected discrepancies by recorder MSL P.ad monitor calibration
' JUNE
SUMMARY
TF QASL INSTRUMENT MAINTF. NANCE cont'd Pc_ g : 4
.EOUIPMENT MALFUNCTION . CORRECTIVE ACTION
- AOG Hydrogen Analyzer System full'of water Removed water and calibrated monitor 9
Ev:nt Recorder (Scram) Paper not taking up Tightened drive gear on chart take up Fira Alarm in 4160 Room Alarming - no apparent Replaced resistor in detector string cause S
~'
..- Oyster Creek Station il i Docket No. 50-219 RE:FmrTNG INFORMATICN Nane of Facility: Oyster Creek Station #1 i:
ScbMn1M date for next refueling shutdown: November 28, 1981 Sctwhi1M date for restart following refueling: May 31, 1982
.Will refueling or remmption of operation thereafter require a Technical spacification chruge 'or other license i=Y=A=nt?
- A Tech Spec Omnge Request to incorporate G.E. fuel agm=nblies will be sutznitted by August 15, 1981.
Sdwhi1M date(s) . for subnitting proposed licensing action and supporting infrw = +1e=1:
- March 9,1981 - Ccaplete NEDO W= ant #24195 (G.E. Beload
-Fuel Applicaticm for Oyster Creek) was subnitted.
Inportant licensing considerations aaanciated with refueling, e.g., new or different fuel design or supplier, unreviewed design or performance analysis methods, significant changes in fuel design, new operating pwcalures:
-1) General Electric Fuel Assenblies . fuel design and perfonnance analysis methods have been approved by the NBC. New operating g M.nes, if naca==ary, will be subnitted at a later date.
2)' Exxon Fuel Assemblies - No major changes have been made nor are there any anticipated.
The nih of fuel'assenblies (a) in the core -
560 (b) in the spent fuel storage pool - 781 The present '.ioensed spent fuel pool storage capacity and the v e of any increar= in licensed storage capacity that has been requested oz. is planned, in numb r of fuel assemblies:
Present: L 1,800 Planned: 2,600 The projected date of the last refueling that can be discharged to the spent fuel pool assuning the-present lixnsed capacity:
The Spring 1987 Outage.*
- Note: This'is for a normal refueling. Full core off-load, however, can only be mu-mdated through about 1983 or 1984 with 1800 licensed locations.
--. .-. . - - -