n f

g'; -

Il

~

SOUTH CAR 0tlNA EttcTRic a GAS COMPANY eost ornce so n.

CotursiA, south CARoWNA 29288 T. C. NicMots, J n.

w. en...... o.oa c ne=

June 25,'1981 naan onu,a.e Mr. Harold R. Denton, Director Office of Nuclear Reactor Regulation U. S. Nuclear Regulatory Commission Washington, D. C.

20555

Subject:

Virgil C. Summer Nuclear Station Docket No. 50/395 Offsite Dose Calculation Manual

Dear Mr. Denton:

In our letter dated June 4, 1981, the NRC staff was provided the Offsite Dose Calculation Manual (ODCM) for the Virgil C. Summer Nuclear Station.

Page 2.0-10 contained an error which is corrected by the attached page 2.0-10 of this letter. The attached page should be inserted in place of the page presently in the ODCM. Since you were provided ten copies of the ODCM, we are providing you with ten copies of page 2.0-10.

1 If you have any questions, please let us know.

p Very truly yours, 1

T. C. Nichols, Jr.

RBC:TCN:lkb cc:

11. R. Denton w/ attach. (10)

V. C. Summer w/o attach.

H. N. Cyrus w/o attach.

T. C. Nichols, Jr. w/o attach.

D. A. Nauman w/o attach.

W. A. Williams, Jr. w/ attach.

R. B. Clary w/o attach.

O. S. Bradham w/ attach. (2)

A. R. Koon w/ attach.

M. N. Browne w/o attach.

B. A. Bursey w/ attach.

Dr. J. Ruoff w/ attach.

J. L. Skolds w/o attach.

J. B. Knotts, Jr. w/ attach.

J. Cox w/ attach.

W. R. Baehr w/ attach.

G. E. Higginbotham w/ attach.

9 J. H. Barker w/o attach.

d O i

NPCF File g

enesnosso g

,g

I

. r' dose parameter for radionuclide i, (mrem /yr pe, P

I 9

3 2

uCi/m ) for inhalation and (m -mrem /yr per uCi/sec) for other pathways. from Table 2.2-1 I

h average release rate of radionuclide i (required by Qj' Technical Specification 3.11.2.1.b) in the current year (uCi/sec).

2.2.2 Unrestricted Area Dose to Individual I

2.2.2.a For the purpose of sections 3.11.2.2 and 3.11.2.4 of the Technical Specifications, the air dose in unrestricted areas shall be determined as follows:

air dose due to gamma emissions from noble gas D

y radionuclide i (mrad) 3.17 x 10-8 M YT(i' Qj (26)

=

j I

where, 3.17 x 10 the fraction of one year per one second X3' relative concentration for unrestricted areas for long term releases 5.3 x 10-6 sec/m in the SE sector
  • 3 cumulative release of noble gas radionuclide i over Q

I j

the period of interest (uCi).

I air dose due to beta emissions from noble gas D,

radionuclide i (mrad).

  • Values based on Reference 4, Table 2.3-119; Reference 5, Table 6.1-10.

g 8106 290 Yo3 ODCM, V C Summer, SOUTil CAROLINA ELECTRIC AND GAS C0.